HomeMy WebLinkAbout250 NUTMEG ROAD SOUTH_1.,� NORTH
4' 6' . 8' 19 12' 14' 16' 18'
. 4-WAY SEISMIC BRACE (IF REQUIRED) =
• S
3
FIRE SPRINKLER LEGEND:
tY RECESSED TYPE PEi�4DENT FIRE SPRINKLER, (TOTAL OF 19)
NPT. -36 "E�;RFI=, K=5.6, CHPOME FINISN)
3ENERAL NOTES:
1. OCCUPANCY - ORDINARY HAZARD GROUP 1 PER NFPA #13.
2. THERE IS AN EXISTING FIRE SPRINKLER SYSTEM INSTALLED IN THIS BUILDING. THE I
EXTENT OF THIS CONTRACT IS TO RELOCATE AND ADD FIRE SPRINKLERS TO
ACCOMMODATE FOR NEW PARTITIONS AND CEILING PLAN IN THE SPACE THAT IS BEING
RENOVATED.
3. THE EXISTING FIRE SPRINKLER SYSTEM IS A HYDRAULIC CALCULATED SYSTEM. 1
4. ALL THE EXISTING PIPING 2" AND SMALLER IS SCHEDULE 40 "BLACK" STEEL PIPING WITH I
BLACK CAST IRON THREADED FITTINGS. PIPING 2 %" AND LARGER IS SCHEDULE 10
"BLACK" STEEL LIGHTWALL PIPING WITH GROOVED FITTINGS.
5. ALL NEW HANGERS TO BE LOCATED AND SIZED IN ACCORDANCE WITH NFPA 413.
6. STRUCTURAL LOAD BEARING ANALYSIS OF THE FIRE SPRINKLER SYSTEM AND ITS
RELATED COMPONENTS HAS NOT BEEN INCLUDED AS PART OF THIS FIRE SPRINKLER
CONTRACT.
7. THIS AREA TO BE ADEQUATELY HEATED (ABOVE 40 DEGREES): PIPE IS FILLED WITH
WATER AND MUST BE KEPT FROM FREEZING.
8. PENDENT FIRE SPRINKLERS TO BE INSTALLED VISUALLY STRAIGHT BUT NOT NECESSARILY
LOCATED IN THE CENTER OF TILE.
9. ELECTRICAL OR ALARM WIRING IS NOT INCLUDED IN THE FIRE SPRINKLER CONTRACT. )
I
reKjj-A0r.
REV.# DATE REVISION
RED HAWK
FIRE & SECURITY RI SCr15864, CT FA#S-,-/C C• i
55 ROBINSON BOULEVARD RI FPMll374,1,1A FAY37%; I
ORANGE, CT 064.77 " RI FA119065, CT FLCOO ! r-;.
TEL 203-672-9699 FAX 203-891-8858
OPM
t
(SHOP ROOM) t`
0 250 NUTMEG ROAD SOUTH
���� SOUTH WINDSOR, CT.
' FIRE SPRINKLER RENOVATION -- -
DRAWN By.. ' . QHECKED III': UNDERWRITER: JOB
T22 , �o To
SCALE: 1 DATE: SHEETI,,� , t .
FIRE SPRINKLER LEGEND:
RU FsSFf) TYPF PENDENT FIRE SPRINKLER, (TOTAL OF 19) i