190 BUCKLAND ROAD
SECTION ONE: GENERAL 1.1 SCOPE OF THIS DOCUMENT THIS SPECIFICATION DOCUMENT PROVIDES THE REQUIREMENTS TO PROVIDE A TEMPORAL 3 MANUAL AND AUTOMATIC FIRE ALARM SYSTEM PURSUANT TO SECTION 907.2 OF THE 2018 BUILDING CODE OF CONNECTICUT AND LOCAL CODE REGULATIONS. THE SYSTEM SHALL BE MANUFACTURED BY EDWARDS AND SHALL BE AN EST-3X ANALOG ADDRESSABLE MICROPROCESSOR BASED FIRE ALARM CONTROL PANEL, OR EQUAL. THIS CONTROL PANEL SHALL INCLUDE, BUT NOT BE LIMITED TO, SYSTEM CABINET, DOIAICD QI IDDI V I WIT CVCTGAA I"MITRQI I WIT WITH ANAInr InnP IrINIT ANn I rn f VYVLl1 VVII LI Vltll I, VIV(LIYf VVfYI DISPLAY UNIT ASSOCIATED PERIPHERAL DEVICES, PROGRAMMING, WIRING, AND OTHER RELEVANT COMPONENTS. 1.2 WORK INCLUDED 1.2.1 GENERAL REQUIREMENTS THE CONTRACTOR SHALL FURNISH AND INSTALL A COMPLETE 24VDC ANALOG ADDRESSABLE MULTIPROCESSOR -BASED FIRE ALARM CONTROL PANEL AS SPECIFIED HEREIN. THE CONTROL PANEL SHALL INCLUDE BUT NOT BE LIMITED TO ALL CONTROL EQUIPMENT, POWER SUPPLY, INITIATING DEVICES, AUDIBLE AND VISUAL NOTIFICATION APPLIANCES AS APPROPRIATE, E, CONDUIT, WIRING, FI 11 1 INGS, AND ALL OTHER ACCESSORIES NECESSARY TO PROVIDE A COMPLETE AND OPERABLE SYSTEM. 1.2.2 LABELING ALL CONTROL PANEL EQUIPMENT SHALL BE LABELED WITH THE MANUFACTURER'S NAME AND LOGO TYPE TO ASSURE THE INTEGRITY OF THE COMPLETE SYSTEM. "HYBRIDIZED" SYSTEMS (CONTAINING EQUIPMENT FROM SEVERAL DIFFERENT MANUFACTURERS) SHALL NOT BE CONSIDERED ACCEPTABLE. 1.2.3 AGENCY APPROVALS ALL EQUIPMENT SHALL BE LISTED BY UNDERWRITERS LABORATORIES, INC., APPROVED BY FACTORY MUTUAL OR AS ACCEPTED BY THE AUTHORITY HAVING JURISDICTION (AHJ). THE FIRE ALARM SYSTEM IN ITS ENTIRETY SHALL BE IN COMPLIANCE WITH ALL APPLICABLE FIRE AND ELECTRICAL CODES AND COMPLY WITH THE REQUIREMENTS OF THE LOCAL AUTHORITY HAVING JURISDICTION OVER SAID SYSTEMS. ACCESSORY COMPONENTS AS REQUIRED SHALL BE CATALOGUED BY THE MANUFACTURER AND U.L. LISTED TO OPERATE WITH THE MANUFACTURER'S CONTROL PANEL. 1.2.4 SPECIFIC U.L. PROVISIONS THE SYSTEM SHALL COMPLY WITH THE APPLICABLE PROVISIONS OF THE FOLLOWING U.L. STANDARDS AND CLASSIFICATIONS: • UL STANDARD # 864, CONTROL UNITS, FIRE PROTECTIVE SIGNALING SYSTEMS • UOJZ, CONTROL UNITS, SYSTEM • UOXX, CONTROL UNIT ACCESSORIES, SYSTEM 1.2.5 SPECIFIC NFPA S I ANDARDS THE SYSTEM SHALL COMPLY WITH THE APPLICABLE PROVISIONS OF THE FOLLOWING CURRENT NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) STANDARDS: • NFPA 72 OF 2013 • NFPA 90A, INSTALLATION OF AIR CONDITIONING AND VENTILATING SYSTEMS • LIFE SAFETY CODE # 101, SAFETY TO LIFE FROM FIRE IN BUILDINGS AND STRUCTURES 1.2.6 WIRING FOR FIRE ALARM USE, WIRE AND CABLE SHALL BE U.L. LISTED AND A MINIMUM OF 16 AWG OR AS REQUIRED BY LOCAL CODES AND AUTHORITY HAVING JURISDICTION. RACEWAYS CONTAINING CONDUCTORS IDENTIFIED AS "FIRE PROTECTIVE CONTROL PANEL" CONDUCTORS SHALL NOT CONTAIN ANY OTHER CONDUCTORS. NO AC CURRENT CARRYING CONDUCTORS SHALL BE ALLOWED IN THE SAME RACEWAY WITH THE DC FIRE ALARM DETECTION AND SIGNALING CONDUCTORS. 1.3 SUBMITTALS THE OWNER OR HIS DESIGNATED REPRESENTATIVE SHALL APPROVE ALL EQUIPMENT SUBMITTAL. 1.3.1 GENERAL REQUIREMENTS MANUFACTURERS ORIGINAL CATALOG DATA AND DESCRIPTIVE INFORMATION SHALL BE SUPPLIED FOR ALL MAJOR COMPONENTS OF THE EQUIPMENT TO BE SUPPLIED. SUPPLIERS QUALIFICATIONS SHALL INDICATE YEARS IN BUSINESS, SERVICE POLICIES, WARRANTY DEFINITIONS, AND A LIST OF SIMILAR INSTALLATIONS. CONTRACTOR QUALIFICATIONS SHALL BE SUPPLIED INDICATING YEARS IN BUSINESS AND PRIOR EXPERIENCE WITH INSTALLATIONS THAT INCLUDE THE TYPE OF EQUIPMENT THAT IS TO BE SUPPLIED. ALL PERTINENT INFORMATION SHALL BE SUPPLIED REGARDING THE RELIABILITY AND OPERATION OF THE EQUIPMENT TO BE SUPPLIED. DELIVERY DATES OF THE EQUIPMENT TO BE SUPPLIED SHALL BE FURNISHED. INSTALLATION AND FINAL TEST/ACCEPTANCE DATES OF THE EQUIPMENT SHALL BE SUPPLIED. SUFFICIENT INFORMATION SHALL BE SUPPLIED SO THAT THE EXACT FUNCTION OF EACH INSTALLED DEVICE IS KNOWN. NOTE: DOCUMENTATION SUBMITTAL OF SHOP DRAWINGS SHALL CONTAIN AT LEAST ONE (1) BOOKLET OF ORIGINAL MANUFACTURER SPECIFICATION AND INSTALLATION INSTRUCTION SHEETS. SUBSEQUENT BOOKLETS MAY BE COPIES. ALL EQUIPMENT AND DEVICES ON THE SHOP DRAWINGS TO BE FURNISHED UNDER THIS CONTRACT SHALL BE CLEARLY MARKED IN THE SPECIFICATION SHEETS. 1.3.2 OTHER THAN SPECIFIED EQUIPMENT EQUIPMENT OTHER THAN SPECIFIED SHALL BE CONSIDERED FOR APPROVAL PROVIDED THE FOLLOWING IS SUBMITTED IN WRITING BY THE ELECTRICAL CONTRACTOR TO THE ENGINEER TEN (10) DAYS BEFORE THE BID DATE: rn 1P" 1 1f❑TVIAIP A1I1 ❑❑AIAfIAfl�f? 11C AAATC❑IAI O Tn QC A. COMPLETE LIS 10, UMOUI[Ir 1 IVIVJ HIVU UIvMVVIIVVJ OF Ivlfi I CrMtki-0 I V oL USED. B. A COMPLETE LIST OF CURRENT DRAWING REQUIREMENTS DURING NORMAL SUPERVISORY CONDITIONS, TROUBLE CONDITIONS, AND ALARM CONDITIONS. C. BATTERY STANDBY CALCULATIONS SHOWING TOTAL STANDBY POWER NEEDED TO MEET THE SYSTEM REQUIREMENTS AS SPECIFIED. 1.3.3 SUBSTITUTED EQUIPMENT IF EQUIPMENT OTHER THAN THAT SPECIFIED IS SUPPLIED, IT SHALL BE THE LUJU J MAl.. J UM0 UBLIGATIUJV TO SUBIVII I T E: APPRUPRIA T E DULiUIV9ENTATiOiv AivD ALLOW THE SPECIFYING ENGINEER SUFFICIENT TIME TO CONSIDER THE EQUALITY OF THE SUBSTITUTED ITEMS. 1.3.4 SATISFYING THE ENTIRE INTENT OF THESE SPECIFICATIONS IT IS THE CONTRACTOR'S RESPONSIBILITY TO MEET THE ENTIRE INTENT OF THESE SPECIFICATIONS. DEVIATIONS FROM THE SPECIFIED ITEMS SHALL BE AT THE RISK OF THE CONTRACTOR UNTIL *THE DATE OF FINAL ACCEPTANCE BY THE ARCHITECT, ENGINEER, AND OWNER'S REPRESENTATIVE. ALL COSTS FOR REMOVAL, RELOCATION, OR REPLACEMENT OF A SUBSTITUTED ITEM SHALL BE AT THE RISK OF THE ELECTRICAL CONTRACTOR. 1.4 CODES AND STANDARDS THE SYSTEM SHALL COMPLY WITH ALL LOCAL AND STATE CODES WITH NO EXCEPTIONS. SECTION TWO: SYSTEM OPERATION 2.1 MULTIPROCESSOR -BASED THE SYSTEM SHALL BE OF MULTIPROCESSOR DESIGN TO ALLOW EACH 1/0 FUNCTIONAL MODULE TO HOLD AND EXECUTE ITS OWN MICROPROCESSOR AND SOFTWARE PROGRAM UNDER THE CONTROL OF THE MAIN SYSTEM MICROPROCESSOR. 2.2 FIELD PROGRAMMABLE THE SYSTEM SHALL BE CAPABLE OF FIELD PROGRAMMING IN TWO MODES: 1. FRONT PANEL PROGRAMMED THROUGH THE USE OF THE ON -BOARD LCD DISPLAY AND THE USE OF THE PROGRAMMING SWITCHES ON THE SYSTEM CONTROL UNIT AND THE INDIVIDUAL INPUT AND OUTPUT CIRCUITS INCLUDING ZONES, NOTIFICATION CIRCUITS, AND RELAYS. WHILE IN THE PROGRAMMING MODE, THE CONTROL PANEL SHALL PROVIDE A FIRE ALARM OVER -RIDE TO ASSURE THAT NO ALARMS WILL BE MISSED OR LOST. PROGRAMMING SHALL BE PASSWORD PROTECTED AND SHALL NOT REQUIRE THE USE OF AN ADDITIONAL PROGRAMMING APPLIANCE OR TOOL. 2. COMPUTER PROGRAMMED THROUGH THE USE OF AN FCP (FIELD CONFIGURATION PROGRAM) DEDICATED SOFTWARE PACKAGE. THE SYSTEM CONFIGURATION SHALL BE SAVED TO 3" OR 5" DISK FOR EASY ACCESS AND FIELD PRvUr%mIVf IIVIvUIFICATION VYII II t IQUT THE ADDITIUINI OF I INW 1-VIII- HARDWARE. WHILE IN THE PROGRAMMING MODE, THE CONTROL PANEL SHALL PROVIDE A FIRE ALARM OVER -RIDE TO ASSURE THAT NO ALARMS WILL BE MISSED OR LOST. SYSTEMS WHICH MUST COME "OFF-LINE" TO BE PROGRAMMED WILL NOT BE ACCEPTABLE. A HARD -COPY OF THE FINAL SYSTEM CONFIGURATION SHOWING ALL INPUTS, OUTPUTS,DESCRIPTIONS, ADDRESSES, PROGRAMMING MATRIXES, ETC. SHALL BE SUPPLIED AT NO EXTRA COST. 2.3 RS-232C SERIAL OUTPUT A SUPERVISED RS 232C SERIAL POET SI IALL BE PROVIDED TO OPEP J_ DE - I E PRINTERS TO PROVIDE AN 80 COLUMN READOUT OF ALL ALARMS, TROUBLES, LOCATION DESCRIPTIONS, TIME, DATE, ETC. THE COMMUNICATION SHALL BE STANDARD ASCII CODE OPERATING AT 1200 BAUD. 2.4 CONTROL -BY -EVENT (CBE) PROGRAM OPERATION OR AUTOMATIC ACTIVATION OF ANY MANUAL PULL STATION, SMOKE DETECTOR, HEAT DETECTOR, OR WATERFLOW ZONE SHALL ACTIVATE THE SYSTEM'S CONTROL -BY -EVENT PROGRAM TO CAUSE: 1. THE APPROPRIATE SIGNAL TO BE SENT TO A CENTRAL STATION. 2. SHUT DOWN ALL AIR HANDLING UNITS AS SPECIFIED HEREIN. 3. THE "SYSTEM ALARM" LED SHALL ALSO FLASH AND THE PANEL BUZZER SHALL PULSE RAPIDLY. 4. INDICATE ON THE LCD DISPLAY UNIT. THE DESCRIPTION OF THE SPECIFIC ANALOG/ADDRESSABLE DEVICE IN ALARM VIA AN 80-CHARACTER ALPHA -NUMERIC DISPLAY. THE "SYSTEM ALARM" LED SHALL ALSO FLASH AND THE SCUTS SYSTEM AUDIBLE SIGNAL SHALL PULSE. THE DISPLAYS SHALL BE OF THE LIQUID CRYSTAL TYPE (LCD), CLEARLY VISIBLE IN POOR LIGHT CONDITIONS. 5. CLOSE ALL MAGNETICALLY HELD DOORS AUTOMATICALLY. U. PERFORM AIVY ADDITIONAL FUK TIC 1 UIJ no SPECIFIED H1_1%"IN OR nS SHOWN ON THE PLANS. 2.5 GENERAL SYSTEM OPERATION 1. WHEN AN ALARM OCCURS ON A ZONE THE CONTROL PANEL INDICATES THE ALARM CONDITION UNTIL MANUALLY RESET. 2. AN ALARM MAY BE ACKNOWLEDGED BY ACTUATING THE "ACKNOWLEDGE" SWITCH. THIS SHALL SILENCE THE PANEL BUZZER, AND CHANGE THE "SYSTEM ALARM" LED AND THE INDIVIDUAL ZONE LED FROM FLASHING TO STEADILY LIT. 3. ALL ALARM SIGNALS MAY BE SILENCED BY ACTUATING THE "SILENCE" SWITCH. THIS SHALL STEADILY ILLUMINATE THE "SIGNAL SILENCE" LED. IF A SUBSEQUENT ALARM IS ACTIVATED, THE ALARM SIGNAL SHALL "RESOUND" UNTIL AGAIN SILENCED. ONCE SILENCED, ALL ALARM SIGNALS MAY BE RESTORED AGAIN BY ACTIVATING THE "SILENCE" SWITCH. WATERFLOW ZONES SHALL BE NOWSILENCEABLE. 2.6 GREEN "POWER ON" LED A GREEN "POWER ON" LED SHALL NORMALLY BE LIT, INDICATING THAT THE SYSTEM IS RECEIVING NORMAL 120 VAC ELECTRICAL POWER. A FAILURE OF NORMAL CONTROL PANEL POWER SHALL CAUSE THIS LED TO EXTINGUISH. 2.7 AMBER "SYSTEM TROUBLE" LED 1. AN AMBER "SYSTEM TROUBLE" LED SHALL LIGHT AND THE SYSTEM AUDIBLE SIGNAL SHALL STEADILY SOUND WHEN ANY TROUBLE IS DETECTED IN THE SYSTEM. FAILURE OF NORMAL POWER, OPENS OR SHORT CIRCUITS ON THE INDICATING OR ZONE CIRCUITS, DISARRANGEMENTS IN SYSTEM WIRING, FAILURE OF THE MICROPROCESSOR OR ANY IDENTIFICATION MODULE, OR SYSTEM GROUND FAULTS SHALL ACTIVATE THIS TROUBLE CIRCUIT. 2. A TROUBLE SIGNAL MAY BE ACKNOWLEDGED BY ACTUATING THE "ACKNOWLEDGE" SWITCH. THIS SHALL SILENCE THE PANEL TROUBLE BUZZER. IF ADDITIONAL TROUBLE CONDITIONS OCCUR, THE TROUBLE CIRCUITRY WILL RESOUND. 3. DURING AN "ALARM" CONDITION, ALL "TROUBLE" SIGNALS SHALL BE SUPPRESSED WITH THE EXCEPTION OF LIGHTING THE AMBER "COMMON TROUBLE" LED STEADILY. 2.8 ALARM SIGNALS ALL ALARM SIGNALS SHALL BE AUTOMATICALLY "LOCKED IN" AT THE CONTROL PANEL UNTIL THE OPERATED DEVICE IS RETURNED TO ITS NORMAL CONDITION AND THE CONTROL PANEL IS MANUALLY RESET. WHEN USED FOR WATERFLOW, THE SILENCE SWITCH SHALL BE BYPASSED. 2.9 ALARM OR TROUBLE ACTIVATION OF INITIATING ZONES ALARM OR TROUBLE ACTIVATION OF INITIATING ZONES SHALL BE INDICATED BY ZONE ALARM AND TROUBLE LED'S. 2.10 ELECTRICALLY SUPERVISED 1. EACH INITIATING AND SIGNAL CIRCUIT SHALL BE ELECTRICALLY SUPERVISED FOR OPENS, SHORTS, AND GROUND FAULTS IN THE WIRING. 2. THE OCCURRENCE OF ANY FAULT SHALL ACTIVATE THE SYSTEM TROUBLE CIRCUITRY BUT SHALL NOT INTERFERE WITH THE PROPER OPERATION OF A AIv nI❑/1I LIT TLf AT Mn ETC' AInT UAI/C A CAI II T rIn Kit'NITInhI AIVJ VJ[UUII IllHl UVCJIVVI I"1MVCMFtAUL1 VVIVUIIIVIM. 3. EACH INITIATING CIRCUIT SHALL BE CAPABLE OF BEING WIRED USING CLASS "A" (STYLE D) SUPERVISED CIRCUITS (A GROUND FAULT ON EITHER CONDUCTOR OR A BREAK SHALL NOT PREVENT A DEVICE FROM OPERATING ON EITHER SIDE OF THE BREAK) OR CLASS "B" (STYLE B) SUPERVISED CIRCUITS (A BREAK OR GROUND FAULT IN ANY CONDUCTOR SHALL BE REPORTED AS A TROUBLE CONDITION) AT NO EXTRA COST. 2.11 DRIFT COMPENSATION - ANALOG SMOKE SENSORS 1. SYSTEM SOFTWARE SHALL AUTOMATICALLY ADJUST EACH ANALOG SMOKE nCAlon❑ A❑❑❑nVInAATCI V nnfr`c CAe1U IAICCV COD i"WAAir]CQ IAI CCnICIT1X1ITV JCIVJVr1 Hrrnt/m Yfm t CLt Vt VI,LL uIf YYLLf1f WIN. -f rvt -vf-V IIvII I DUE TO THE EFFECTS OF COMPONENT AGING OR ENVIRONMENT (I.E.: DUST). EACH SMOKE SENSOR SHALL MAINTAIN ITS ACTUAL SENSITIVITY UNDER ADVERSE CONDITIONS TO RESPOND TO ACTUAL ALARM CONDITIONS WHILE IGNORING THE FACTORS WHICH GENERALLY CONTRIBUTE TO NUISANCE ALARMS. 2. THE SYSTEM TROUBLE CIRCUITRY SHALL ACTIVATE, DISPLAY "DIRTY DETECTOR" AND "VERY DIRTY DETECTOR" INDICATIONS AND IDENTIFY THE INDIVIDUAL SENSOR WHEN A SMOKE SENSOR HAS BEEN COMPENSATED BEYOND ITS ACCEPTABLE LIMITS. 2.12 DUAL - MODE WALK TEST THE CONTROL UNIT SHALL PROVIDE A DUAL - MODE ZONED WALK TEST ALARMISUPERVISION STATUS OF EACH INITIATING DEVICE CONNECTED TO THE SYSTEM. DURING WALK TEST, THE CONTROL UNIT SHALL AUTOMATICALLY RESET AFTER AN ALARM CONDITION ENABLING THE TESTING TECHNICIAN TO CONTINUE TESTING THE SYSTEM WITHOUT REQUIRING A RETURN TO THE CONTROL. 1. A SILENT WALK TEST WILL RECORD ALL TESTS TO A PRINTER FOR HISTORICAL REFERENCE WHILE NOT ACTIVATING THE NOTIFICATION APPLIANCE CIRCUITS. 2.13 PRINTED CIRCUIT BOARDS, CONTROL PANEL COMPONENTS 1. ALL CONTROL PANELS SHALL BE CONTAINED IN A 16-GAUGE STEEL. 2. ALL GROUPS OF CIRCUITS OR COMMON EQUIPMENT SHALL BE CLEARLY MARKED AND SHALL BE EXPANDABLE BY INSERTING INTERCHANGEABLE UNITS. 3. CIRCUITRY SHALL BE PROVIDED IN THE CONTROL PANEL TO PERMIT TRANSMISSION OF TROUBLE AND ALARM SIGNALS OVER LEASED OR PRIVATELY OWNED TELEPHONE CABLES TO A REMOTE RECEIVING PANEL. A REVERSE POLARITY OR A MASTERBOX CIRCUIT AS REQUIRED SHALL BE PROVIDED IN THE CONTROL PANEL. THERE SHALL BE A REMOTE DISCONNECT SWITCH TO ALLOW TESTING OF THE FIRE ALARM SIGNAL WITHOUT TRANSMITTING AN ALARM SIGNAL TO THE CENTRAL STATION. 4. THE CONTROL UNIT SHALL BE RED IN COLOR AND SHALL INCLUDE THE FOLLOWING FEATURES: 2.14 CITY CONNECTION THE ENTIRE FIRE ALARM SYSTEM SHALL BE CONNECTED VIA LEASED TELEPHONE I IMPQ Tn_ A c1=AITRA! cTATnII IN ACr-nQnANN= WITH THE PP IIRFIIAFNTS nF THE FIPF DEPARTMENT. A. THE FIRE DEPARTMENT SHALL BE CONSULTED AS TO THE AUTHORIZED CENTRAL STATION COMPANIES SERVING THE CITY/i OWN. B. THE FIRE ALARM SYSTEM SHALL TRANSMIT BOTH ALARM AND TROUBLE CONDITIONS WITH THE ALARM SIGNAL HAVING PRIORITY OVER THE TROUBLE SIGNAL AS FOLLOWS: 1. COMMON TROUBLE 2. MANUAL ALARM ACTIVATION 3. SMOKE/AUTOMATIC ACTIVATION A. CI IPFP\1./ICQPV Ar.TNATm C. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL INSTALLATION CHARGES. D. THE OWNER SHALL BE RESPONSIBLE FOR TELEPHONE COMPANY LEASE CHARGES. SECTION THREE: SYSTEM COMPONENTS THE ANALOG ADDRESSABLE SYSTEM SHALL CONSIST OF THE FOLLOWING MODULES, COMPONENTS, AND PERIPHERAL DEVICES, EACH OF WHICH IS DESCRIBED IN DETAIL IN THIS SECTION: • SYSTEM CABINET • POWER SUPPLY UNIT • SYSTEM CONTROL UNIT • KEYBOARD DISPLAY UNI T • PERIPHERAL DEVICES (MANUAL STATIONS, SMOKE DETECTORS, HEAT DETECTORS, ETC.) 3.1 SYSTEM CABINET 1. THE SYSTEM CABINET SHALL BE EITHER SURFACE OR SEMI -FLUSH WITH A TEXTURE FINISH AND SHALL BE MADE OF THESE PARTS: BACKBOX, INNER nnnR AMII nI ITFR nnnR -IHP SYCTPM CARINFT Hnl ISPS THP MICROPROCESSOR AND RELATED SYSTEM CIRCUITRY. 2. THE CABINET SHALL BE OF DEAD -FRONT CONSTRUCTION AND 16-GAUGE COLD ROLLED (CR) STEEL. THE DOOR SHALL BE RED. 3.2 POWER SUPPLY UNIT A. THE 120 VAC MAIN POWER SHALL BE TRANSFORMER CONVERTED TO LOW VOLTAGE, RECTIFIED AND FILTERED 24 VDC NOMINAL FOR SYSTEM OPERATION AND TO ELIMINATE THE POSSIBILITY OF LINE VOLTAGE BEING PRESENT ON ANY INTERNAL PANEL COMPONENTS. B. THE SYSTEM SHALL CONTAIN AN INTEGRAL, FILTERED, NOMINAL 24 VDC AT 6AMPS POWER SUPPLY, WHICH SHALL COMPLY WITH U.L. S T ANDARD # 864 FOR POWER LIMITED OPERATION. 3.2.1 BATTERY CHARGER A. THE POWER SUPPLY SHALL CONTAIN A BATTERY CHARGER WITH A MAXIMUM AVERAGE CHARGING CURRENT OF 1.0 AMP (THIS CURRENT SHALL BE SUFFICIENT TO MAINTAIN THE SYSTEM BATTERIES AT FULL CHARGE). B. IF THE SYSTEM LOSES AC POWER, A SYSTEM TROUBLE SHALL OCCUR. C. THE CHARGER OUTPUT SHALL BE SUPERVISED AND FUSED. 3.2.2 BATTERIES BATTERIES SHALL BE OF SUFFICIENT CAPACITY TO PROVIDE POv.'ED FOD THE ENTIRE SYSTEM UPON LOSS OF NORMAL 120 VAC POWER FOR A PERIOD OF TWENTY FOUR (24) HOURS WITH FIFTEEN (15) MINUTES OF ALARM SIGNALING AT THE END OF THIS TWENTY FOUR HOUR (24) PERIOD AS REQUIRED BY NEC CODE, ARTICLE 760. 3.2.3 NOTIFICATION APPLIANCE CIRCUITS TWO (2) INDEPENDENT NOTIFICATION APPLIANCE CIRCUITS SHALL BE PROVIDED ON THE SYSTEM POWER SUPPLY, EACH POLARIZED AND RATED AT 3.2 AMPS @24VDC, INDIVIDUALLY FUSED AND SUPERVISED FOR OPENS, GROUNDS, AND SHORT CIRCUITS. 3.3 SYSTEM CONTROL UNIT ENCLOSED WITHIN THE SYSTEM CABINET, SHALL CONTAIN THE MICROPROCESSOR, MEMORY, SYSTEM OPERATING SOFTWARE STORED ON A NON-VOLATILE EPROM, SYSTEM CONFIGURATION MEMORY STORED ON A NON-VOLATILE EEPROM, AND THE CIRCUITS NECESSARY TO SUPPORT A FIRE CONTROL SYSTEM. THE SYSTEM CONTROL UNIT SHALL FUNCTION AS THE SYSTEM'S INFORMATION AND CONTROL CENTER, PROCESSING ALL MESSAGES FROM THE FIELD DEVICES (SUPERVISORY, TROUBLE, ALARM). 3.3.1 MICROPROCESSOR A. THE MICROPROCESSOR SHALL EXECUTE ALL SUPERVISORY PROGRAMMING TO DETECT AND REPORT THE FAILURE OR DISCONNECTION OF ANY MODULE OR PERIPHERAL DEVICE. AN ISOLATED "WATCHDOG" CIRCUIT SHALL MONITOR THE MICROPROCESSOR AND UPON FAILURE SHALL ACTIVATE THE SYSTEM TROUBLE CIRCUITS. B. THE MICROPROCESSOR SHALL ACCESS THE SYSTEM PROGRAM, WHICH IS STORED IN NON-VOLATILE EEPROM MEMORY, FOR ALL CONTROL -BY -EVENT (CBE) FUNCTIONS. THE SYSTEM PROGRAM SHALL NOT BE LOST UPON FAILURE OF BOTH PRIMARY AND SECONDARY POWER. VOLATILE MEMORY SHALL NOT BE ACCEPTABLE. C. A COMMON PSS-485 COMMUNICATION RI IS NFTWnRK SHAI I TIP THE MICROPROCESSOR ON-LINE WITH ALL OTHER MICROPROCESSORS WITHIN THE MULTIPROCESSOR NETWORK TO AFFORD RAPID RESPONSE TO ALL ALARM OR TROUBLE CONDITIONS WITHIN THE SYSTEM. 3.3.2 REAL-TIME CLOCK THE MODULE SHALL HAVE A REAL-TIME CLOCK CAPABLE OF MONITORING ALL REAL-TIME PROGRAMMING AND ALL TIME CONTROL FUNCTIONS. 3.4 KEYBOARD DISPLAY UNIT THE KEYBOARD AND DISPLAY MODULE SHALL BE OF MEMBRANE STYLE CONSTRUCTION WITH A 4 LINE BY 20 CHARACTER LIQUID CRYSTAL DISPLAY. IN THE NORMAL MODE IT SHALL DISPLAY THE TIME, THE TOTAL NUMBER OF ACTIVE EVENTS AND THE TOTAL NUMBER OF DISABLED POINTS. IN ALARM MODE IT SHALL DISPLAY THE TOTAL NUMBER OF EVENTS AND THE TYPE OF EVENT ON DISPLAY. THE MODULE SHALL HAVE VISUAL INDICATORS FOR THE FOLLOWING COMMON CONTROL FUNCTIONS; AC POWER, ALARM, SUPERVISORY, MONITOR, TROUBLE, DISABLE, GROUND FAULT, CPU FAIL AND TEST. THERE SHALL BE COMMON CONTROL KEYS AND VISUAL INDICATORS FOR; RESET, ALARM SILENCE, TROUBLE SILENCE, DRILL AND ONE CUSTOM PROGRAMMABLE KEYANDICATOR. 3.5 PERIPHERAL DEVICES: 3.5.1 ANALOG IONIZATION SMOKE SENSOR - SIGA-IS A. ANALOG IONIZATION SENSORS SHALL HAVE A DUAL CHAMBER IONIZATION SENSOR OF THE DUAL UNIPOLAR TYPE. EACH IONIZATION SENSOR SHALL BE CAPABLE OF BEING SET FOR SEVEN SENSITIVITY SETTING RANGING FROM 3.0 TO 1.0 %/FT EQUIVALENT OBSCURATION, WITH A PREDEFINED SETTING OF 3.0%. B. AUTOMATIC AND MANUAL FUNCTIONAL SENSITIVITY AND PERFORMANCE TESTS SHALL BE POSSIBLE ON ALL PHOTOELECTRONIC SENSORS WITHOUT THE NEED OF GENERATING SMOKE. THIS TEST METHOD SHALL TEST ALL SENSOR CIRCUITRY AND A "FAILED TEST" INDICATION SHALL BE PROVIDED ON THE KDU UPON ANY FAILED TEST. C. TWO LED VISUAL INDICATORS PROVIDING LOCAL 360 DEGREE VISIBILITY OF OPERATING STATUS AND ALARM INDICATION SHALL BE PROVIDED ON EACH SENSOR. THE LED'S SHALL PULSE PERIODICALLY INDICATING THAT THE SENSOR IS RECEIVING POWER AND COMMUNICATION IS BEING SUPPLIED. THIS FEATURE SHALL BE FIELD PROGRAMMABLE. UPON ALARM THESE TWO LED'S SHALL LIGHT CONTINUOUSLY. A VISIBLE ALARM SIGNAL SHALL BE CAPABLE OF BEING REMOTELY ANNUNCIATED. D. THE SYSTEM SHALL CHECK THE SENSITIVITY OF EACH SENSOR PERIODICALLY. IF A SENSOR ALARM THRESHOLD SENSITIVITY HAS CHANGED, DUE TO AGING AND/OR DUST ACCUMULATION, THE SYSTEM SHALL AUTOMATICALLY COMPENSATE FOR THIS SENSITIVITY CHANGE (DRIFT COMPENSATION). F THE SPNSOR SCREEN AND COVER ASSEMBLY MUST BE EASILY REMOVABLE FOR FIELD CLEANING. WIRE CONNECTION SHALL BE MADE BY CLAMPING PLATE AND SCREW. 3.5.2 ADDRESSABLE MONITOR MODULE - SIGA-CT1, SIGA-CT2, SIGA-MM1 AN ADDRESSABLE MONITOR MODULE WIRED AS STYLE B (CLASS "B") SHALL BE FURNISHED TO PROVIDE AN ADDRESS FOR NORMALLY OPEN (N.O.) CONTACT DEVICES. A. AN ADDRESSABLE MONITOR MODULE CAPABLE OF BEING CONFIGURED STYLE D (CLASS"A") OR STYLE B (CLASS "B") SHALL BE FURNISHED TO PROVIDE AN ADDRESS FOR NORMALLY OPEN (N.O.) CONTACT DEVICES. B. THE ADDRESSABLE MONITOR MODULE SHALL CONTAIN A YELLOW STATUS LED WHICH SHALL FLASH WHEN IN A QUIESCENT MODE AND LIGHT CONTINUOUSLY WHEN ACTIVATED. THE STATUS LED SHALL BE FIELD PROGRAMMABLE NOT TO PROVIDE QUIESCENT STATUS INDICATION, IS SO DESIRED.ADDRESSABLE OUTPUT MODULE. 3.5.3 ADDRESSABLE OUTPUT MODULE - SIGA-CR A. THE ADDRESSABLE OUTPUT MODULE SHALL BE CONNECTED TO THE SAME LOOP AS THE ANALOG/ADDRESSABLE MONITOR DEVICES AND SHALL PROVIDE A RELAY OUTPUT (FORM "C" 2 AMP @ 24 VDC, RESISTIVE ONLY), A NOTIFICATION APPLIANCE CIRCUIT OUTPUT (1 AMP @ 24 VDC, REQUIRING SEPARATE POWER INPUT), OR AN AUDIO NOTIFICATION APPLIANCE CIRCUIT OUTPUT (43.75 wvr%I 10 @ 70.1 VRIv1S, REQUIRING SI-I rvj ,I"n-w lilt m I). B. THE ADDRESSABLE OUTPUT MODULE SHALL CONTAIN A YELLOW STATUS LED WHICH SHALL BE FIELD PROGRAMMABLE NOT TO PROVIDE QUIESCENT STATUS INDICATION, IF SO DESIRED. SECTION FOUR: FAN SHUTDOWN 4.1 HVAC CONTROL DESIGNATED HVAC UNITS SHALL BE SHUT DOWN THROUGH THE AUXILIARY ZONE CONTACTS OF THE CONTROL PANEL AFTER AN ALARM HAS BEEN INITIATED FROM THE PARTICULAR ZONE THAT IS DESIGNATED TO CONTROL THE HVAC AS SHOWN ON THE PLANS. THE DISCONNECT SWITCH SHALL BE SUPERVISED. FAN RESTART SHALL BE BY A SECONDARY MEANS OF RESET. SECTION FIVE- WIRING 5.1 INSTALLERS RESPONSIBILITIES HE FIRE ALARM 00 D 1. THE INSTALLER SHALL C OF HATE THE INSTALLATION T COORDINATE EQUIPMENT WITH THE MANUFACTURER OR HIS AUTHORIZED DISTRIBUTOR. 2. ALL CONDUCTORS AND WIRING SHALL BE INSTALLED ACCORDING TO THE MANUFACTURER'S RECOMMENDATIONS. 3. IT SHALL BE THE INSTALLERS RESPONSIBILITY TO COORDINATE WITH THE SUPPLIER, REGARDING THE CORRECT WIRING PROCEDURES BEFORE INSTALLING ANY CONDUITS OR CONDUCTORS. 4. WIRING SHALL BE INSTALLED PER THE REQUIREMENTS OF NEC. A. CONDUIT SHALL BE PROVIDED AS REQUIRED BY LOCAL AUTHORITIES. SECTION SEVEN: WARRANTY AND FINAL TEST 7.1 GENERAL THE CnIITPA TnP CHAT I WAPPAAIT Al I FnI IIPIIAFNT ANTI IIIIIPING FPFF FPnM INHERENT MECHANICAL AND ELECTRICAL DEFECTS FOR ONE YEAR (365 DAYS) FROM THE DATE: OF FINAL ACCEPTANCE. 7.2 FINAL TEST BEFORE THE INSTALLATION SHALL BE CONSIDERED COMPLETED AND ACCEPTABLE BY THE AWARDING AUTHORITY, A TEST OF THE SYSTEM SHALL BE PERFORMED AS FOLLOWS: 1. THE CONTRACTOR'S JOB FOREMAN, IN THE PRESENCE OF A REPRESENTATIVE OF THE MANUFACTURER, A REPRESENTATIVE OF THE OWNER, AND THE FIRE DEPARTMENT SHALL OPERATE EVERY BUILDING FIRE ALARM DEVICE TO ENSURE PROPER OPERATION AND CORRECT ANNUNCIATION AT THE CONTROL PANEL. 2. AT LEAST ONE HALF OF ALL TESTS SHALL BE PERFORMED ON BATTERY STANDBY POWER. 3. WHERE APPLICATION OF HEAT WOULD DESTROY ANY DETECTOR, IT MAY BE MANUALLY ACTIVATED. 4. THE COMMUNICATION LOOPS AND THE INDICATING APPLIANCE CIRCUITS SHALL BE OPENED IN AT LEAST TWO (2) LOCATIONS PER ZONE TO CHECK FOR THE PRESENCE OF CORRECT SUPERVISORY CIRCUITRY. 5. WHEN THE TESTING HAS BEEN COMPLETED TO THE SATISFACTION OF BOTH THE CONTRACTOR'S JOB FOREMAN AND THE REPRESENTATIVES OF THE MANUFACTURER AND OWNER, A NOTARIZED LETTER CO -SIGNED BY EACH ATTESTING TO THE SATISFACTORY COMPLETION OF SAID TESTING SHALL BE FORWARDED TO THE OWNER AND THE FIRE DEPARTMENT. 6. THE CONTRACTOR SHALL LEAVE THE FIRE ALARM SYSTEM IN PROPER WORKING ORDER, AND, WITHOUT ADDITIONAL EXPENSE TO THE OWNER, SHALL REPLACE ANY DEFECTIVE MATERIALS OR EQUIPMENT PROVIDED BY HIM UNDER THIS CONTRACT WITHIN ONE YEAR (365 DAYS) FROM THE DATE OF FINAL ACCEPTANCE BY THE AWARDING AUTHORITY. 7. PRIOR TO FINAL TEST THE FIRE DEPARTMENT MUST BE NOTIFIED IN ACCORDANCE WITH LOCAL REQUIREMENTS. 7.3 AS BUILT DRAWINGS, TESTING, AND MAINTENANCE INSTRUCTIONS 7.3.1 AS BUILT DRAWINGS A COMPLETE SET OF REPRODUCIBLE "AS-BUIL I " DRAWINGS SHOWING INS T ALLED WIRING, COLOR CODING, AND WIRE TAG NOTATIONS FOR EXACT LOCATIONS OF ALL INSTALLED EQUIPMENT, SPECIFIC INTERCONNECTIONS BETWEEN ALL EQUIPMENT, AND INTERNAL_ WIRING OF THE EQUIPMENT SHALL BE DELIVERED TO THE OWNER UPON COMPLETION OF SYSTEM. 7.3.2 OPERATING AND INSTRUCTION MANUALS OPERATING AND INSTRUCTION MANUALS SHALL BE SUBMITTED PRIOR TO TESTING OF THE SYSTEM. FOUR (4) COMPLETE SETS OF OPERATING AND INSTRUCTION MANUALS SHALL BE DELIVERED TO THE OWNER UPON COMPLETION. 7.3.3 TESTING FREQUENCY INSTRUCTIONS A. COMPLETE, ACCURATE, STEP-BY-STEP TESTING INSTRUCTIONS GIVING RECOMMENDED AND REQUIRED TESTING FREQUENCY OF ALL EQUIPMENT, METHODS FOR TESTING EACH INDIVIDUAL PIECE OF EQUIPMENT, AND A COMPLETE TROUBLE SHOOTING MANUAL EXPLAINING HOW TO TEST THE PRIMARY INTERNAL PARTS OF EACH PIECE OF EQUIPMENT SHALL BE DELIVERED TO THE OWNER UPON COMPLETION OF THE SYSTEM. B. MAINTENANCE INSTRUCTIONS SHALL BE COMPLETE, EASY TO READ, UNDERSTANDABLE, AND SHALL PROVIDE THE FOLLOWING INFORMATION: • INSTRUCTION ON REPLACING ANY COMPONENTS OF THE SYSTEM, INCLUDING INTERNAL PARTS. • INSTRUCTIONS ON PERIODIC CLEANING AND ADJUSTMENT OF EQUIPMENT WITH A SCHEDULE OF THESE FUNCTIONS. • A COMPLETE LIST OF ALL EQUIPMENT AND COMPONENTS WITH INFORMATION AS TO THE ADDRESS AND TELEPHONE NUMBER OF BOTH THE MANUFACTURER AND LOCAL SUPPLIER OF EACH ITEM. C. USER OPERATING INSTRUCTIONS SHALL BE PROVIDED PROMINENTLY DISPLAYED ON A SEPARATE SHEET LOCATED NEXT TO THE CONTROL UNIT IN ACCORDANCE WITH U.L. STANDARD 864. CHASE Cp M �GE IMEnaineerina D.P.C.I we enameer success 116 West 32nd Street,12th Floor, New York, N.Y. 10001 P 212.643.9055 F 212.643.0503 www.mgedpc.net MG ENGINEERING, P.C. 116 W 32ND STREET,12TH FLOOR, NEW YORK, NY 10001 T. 212.643.9055 1 WWW.MGEDPC.NET Steverud Associates SEVERUD ASSOCIATES CONSULTING ENGINEERS, LAC 469 SEVENTH AVENUE - SUITE 900, NEW YORK, NY 10018 T.212.986.37001 WWW.SEVERUD.COM I # I ISSUANCE I DATE 1 ISSUED FOR BID 06-28-2019 - ISSUED FOR BID 08-15 2019 TPG\rchitecture TPG ARCHITECTURE, LLP 31 PENN PLAZA 132 WEST 31ST STREET, STH FLOOR, NEW YORK, NY 10001 212.768.0800 1 TPGARCHITECTURE.COM IN CONSIDERATION OF RECEIVING DRAWINGS FROM TPG ARCHITECTURE LLP IN AN ELECTRONIC FORM, THE RECIPIENT AGREES, TO THE FULLEST EXTENT PERMITTED BY LAW, TO HOLD HARMLESS AND INDEMNIFY TPG ARCHITECTURE LLP FROM AND AGAINST ALL CLAIMS, LIABILITIES, LOSSES, DAMAGES, AND COSTS, INCLUDING BUT NOT LIMITED TO ATTORNEY'S FEES, ARISING OUT OF, OR IN ANYWAY CONNECTED WITH THE USE, RE -USE, MIS -USE, MODIFICATION, OR MISINTERPRETATION OF THE MACHINE-READABLE INFORMATION PROVIDED BY TPG ARCHITECTURE LLP UNDER THIS AGREEMENT. PROJECT SOUTH WINDSOR BUCKLAND 190 S U C KLAN D ROAD SOUTH WINDSOR, CT 06074 DRAWING NAME FIRE ALARM K1^ I-n O ^MI l^fI lI^ATI^XIn IVU I tJ & brtull-IUA I IUM SEAL I DATE 06.13.2019 PROJECT Nn /.^MnS r-n OJU3.30 SCALE N.T.S. DRAWN BY XXX DOB PAGE l rHFr:KFn RY XX l 3 OF 3 DWG NO. FA-602.00 DOB NO. a Cem New n v ,lapping o h ❑ ❑ Cem (soi _ Wapping `*'� 7 � rFOfi OF• a EURNNAM"Sr Sp. t 71F Wetherell. Pond . r � Saint Johns Cem j ` - .. i--✓oNN 0 LI)s �lFk qo4�� Pond /. SOURCE: UNITES STATES GEOLOGICAL SURVEY, 7.5 MINUTE SERIES MAPS, MANCHESTER, CT; DATED 2018 LOCATION / KEY MAP SCALE: I " = 2000'± CONSTRUCTION DOCUMENTS PROPOSED BANK AND DRIVEmTHRU FACILITIES MAP 27, LOT 8 190 BUCKLAND ROAD TOWN OF SOUTH WINDSOR, HARTFORD COUNTY, CONNECTICUT I_ ` l 7 r ♦ • • `• Oall 40 ♦�•• =4 Q PROJECT SITE MAP 27 V LOTS 8 3 4 & 5 ft v Air, AW Ah. a 10 4,111 h . �� f ,a41 te SOURCE GOOGLE EARTH PRO SATELLITE IMAGERY, DATE RETRIEVED 09/1 1/2018 AERIAL MAP Know what's below Call before you dig. SCALE: I " = 200'± PLANS PREPARED BY: TONEFIELD engineering & design Rutherford, NJ • New York, NY Princeton, NJ • Tampa, FL • Detroit, MI www.stonefieldeng.com 584 Broadway, Suite 310, New York, NY 10012 Phone 718.606.8305 PLAN REFERENCE MATERIALS: I. THIS PLAN SET REFERENCES THE FOLLOWING DOCUMENTS INCLUDING, BUT NOT LIMITED TO: • PROPERTY AND TOPOGRAPHIC 190 & 240 BUCKLAND ROAD SOUTH WINDSOR, CONNECTICUT SURVEY, PERFORMED BY DESIGN PROFESSIONALS, INC., DATED 10115/2018 • ARCHITECTURAL PLANS PREPARED BY TPG ARCHITECTURE, DATED 12/0712018 • LANDLORD PLANS PREPARED BY DESIGN PROFESSIONALS, INC., DATED 05/08/2019 • PERMITTING PLANS PREPARED BY DESIGN PROFESSIONALS, INC., DATED 01/U4/2019 • GOOGLE EARTH PRO SATELLITE IMAGERY, DATE RETRIEVED 0911 H2018 2. ALL REFERENCE MATERIAL LISTED ABOVE SHALL BE CONSIDERED A PART OF THIS PLAN SET AND ALL INFORMATION CONTAINED WITHIN THESE MATERIALS SHALL BE UTILIZED IN CONJUNCTION WITH THIS PLAN SET. THE CONTRACTOR IS RESPONSIBLE TO OBTAIN A COPY OF EACH REFERENCE AND REVIEW IT THOROUGHLY PRIOR TO THE START OF CONSTRUCTION. APPLICANT 190 BUCKLAND ROAD, LLC 6 EXECUTIVE DRIVE, SUITE 100 FARMINGTON, CT 06032 860-6674-5624 OWNER EARL & BARBARA REICHLE 247 ABBE ROAD SOUTH WINDSOR, CT 06074 LEXxMrlAR REAL 1 Y IL 158 CHERRY STREET MILFORD, CT 06460 ROBIN BOND 94 WEST ROAD SOUTH WINDSOR, CT 06074 ROUNSEVILLE MARRION & ROY TRUSTEES 206 BUCKLAND ROAD SOUTH WINDSOR CT, 06074 TENANT JP MORGAN CHASE i C9 i o �D rill -,�P cs + jlfthe that tt I" PJa !?'l py,.,,n" "acted w. PrePosan h Ghd sn.-_,_. "F"`£.+am -ry balldtn8 °r altertlaas are true __ ` O atloos to be ther .itdd vlth Pj th •'nd m`n stste� 3rni•iin _i,-,� an, rlsthis apP1i� e ,i� Cil�ij;S gO rC s-1, rP ygal/t2pni^if ee, Uerrnit. tion -a :r t -. rs as oil 'rBned and final issu once `of a Pen e^t build his PlIvil 'rid a rs Is irn, 'r'r' Plr, sod "roi,„ Sr'bh•�t dr`E:ul to ih� co .:onditionally Approved atrnb b ril,ingdishaU tion tI6la . _ These filed suit;I with 6 Inspector A �t� crag. ho. � �— SS� �o RECEIVED MAY 0 7 2020 South Windsor Building Dept I SHEET INDEX I DRAWING TITLE SHEET # COVER SHEET C-1 SITE PLAN C-2 GRADING PLAN C-3 STORMWATER MANAGEMENT PLAN C-4 UTILITY PLAN C-5 LIGHTING PLAN C-6 LANDSCAPING PLAN C-7 - C-8 CONSTRUCTION DETAILS C-9 - C-1 I LO i a V Q F Z W U me G W U) Y m O� o W Q O o � W _N 4n v N LU �.� LL Z o z a o E 0 Ln o UjOf cc) :2 z� zC Z aW Le �+ r O �� . co r o 1�Sf r 0 cc O L d CO CO Ln W W F'- i V U O Z Q U W Q IL o Z Z O m ' °z0 0 W <;r VW = 01P5 U) abo p ~ z °boIL�oOu o>V _N o C °_U a ETZ ZACHARY E. CHAPLIN, P.E. CONNECTICUT LICENSE No. 33026 LICENSED PROFESSIONAL ENGINEER —— --- STONEFIELD engineering & design SCALE: AS SHOWN PROJECT ID: K-18044 TITLE: COVER SHEET DRAWING: Cm I LIGHT FIXTURE SCHEDULE TYPE VVLTAVE It1AX VYF171 P1vG Ur-OW-IPI IVIV AL-1 120 60W SPECIAL'eColor GRAZE QLX POWERCORE' 4' SURFACE -MOUNT BLUE LED FIXTURE w/ 30x60 BEAM SPREAD AND INTEGRAL DRIVER - 4' eColor GRAZE GLARE SHIELD - FOR END -TO -END CONNECTIONS; ORDER 5' LEADER #108-0000039-02 PER CONTIN. RUN L-2 UNV 34VV 2x2 REC. LENSED 34W 3500K LED TROFFER L-3 120 (2)12W (2)19" LED UNDERCAB. LIGHT WITH OCCUPANCY SENSOR L-6A UNV 110W EXTERIOR SEMI -RECESSED 11 OW 4000K LED DOWNLIGHT I I L-/ Ann ILU A AIAI 14VV An - IAIn AAIRI 4 KUUIVU 14VV O5nn/ LrU LENSrnU nUIVVAILrIGH T -WET RATED ED L-11 120 14W 4" ROUND 14W 3500K LED LENSED DOWNLIGHT- WET RATED L-20 120 < 5W PER FACE SINGLE -FACE LED EXIT SIGN WITH 90-MIN. BATTERY L-21A 1205RW -- -- EXTERIOR WALL -MOUNT 58W 4000K LED FULL -CUTOFF FIXTURE FOR GENERAL LIGHTING WITH PHOTOCELL AND AND 50% DIMMING MOTION SENSOR CONTROL L-21B 120 58W EXTERIOR WALL -MOUNT 58W 4000K LED FULL -CUTOFF FIXTURE FOR GENERAL LIGHTING WITH PHOTOCELL AND AND 50% DIMMING MOTION SENSOR CONTROL AND 90-MINUTE BACKUP BATTERY L-22 120 18W 2' 18W 3500K LED LENSED UTILITY LIGHT w/ OCCUPANCY SENSOR L-301 120 6W LED STRIP LIGHT L-308 120 6W 12"'eW Cove QLX Powercore' RIGID BLUE 120V LED STRIP, WHERE MOUNTED ABOVE ACT-3, USE MOUNTING TRACK MODEL #120-000125-00 OR EQ. TO MINIMIZE LIGHT BLEEDING THROUGH TILE L-402 120 8W LED ALINA PENDANT- STEEL BLUE AND WHITE GRADIENT GLASS GLOBE, 7" H X 4"DIA, OPTIONAL LED DIMMABLE, SILVER COLOR CABLE L404 120 5W LED BLUE GLASS PENDANT FOR BOOTH L405 120 (3) 40W LAMPS 3-PENDANT BLUE GLASS GLOBES, CANOPY FIXTURE WITH INCLUDED LED LAMPS SIMULATING INCANDESCENT LAMPS- SET CORD LENGTHS TO POSITION 5.5" DIAM. SHADE AT 80" AFF, 7.5" DIAM. SHADE AT 84" AFF, AND 3.5' SHADE AT 89" AFF, 120 V,13" ROUND BLACK CANOPY, BLACK CORDS 1 cnn L L-DUU I IAII/ I UIV V InrT-I' 1 6VV/r I I IAIr All I rn An IAitmIr nrT IAI nMIM ni IAAIAIri n ni AAIAIIAAI IAA I rAl/"I I LIIVCNK LCU, 4 VVIDC, or -I IN GRID CHANNCLJ, L MINIMUM LCIVG I n 1 1. SEE LIGHTING FIXTURE SCHEDULES AND DETAILS ON THIS DRAWING E-002 AND E-500 SERIES DRAWINGS. 2. FOR EXACT LOCATION AND MOUNTING HEIGHTS OF ALL LIGHTING FIXTURES, QWITr HFC awn .II INrTIr)N Rr1XFCBOXES CFF SEEAPr.HITPrTI IRAI PI IPNITI IRF 1411 ANSI I Ir, HTINr DRAWINGS.. 3. FINAL CONNECTIONS -10 ALL LIGHTING FIXTURES, LIGHTING TRANSFORMERS AND DRIVERS SHALL BE MADE WITH WIRING HAVING 90°C RATED INSULATION. 4. LIGHTING FIXTURES DESIGNATED AS EMERGENCY, "NIGHT LIGHT" AND EXIT LIGHTS SHALL BE UN -SWITCHED, UON. 5. FOR LIGHTING FIXTURE SPECIFICATIONS REFER TO ARCHITECTURAL & LIGHTING CONSULTANT LIGHTING FIXTURE SCHEDULES, CUT -SHEETS. 6. FOR ADDITIONAL LIGHTING REQUIREMENTS SEE ARCHITECTURAL, LIGHTING, TECHNOLOGY, LIGHTING CONTROLS, AND EQUIPMENT MANUFACTURER'S DOCUMENTATION. 7. ELECTRONIC ENERGY SAVING BALLASTS SHALL BE USED AND SHALL MEET OR EXCEED BOTH THE MINIMUM BALLAST EFFICIENCY FACTOR (B.E.F.) AS SPECIFIED BY UTILITY COMPANY. 8. ALL BALLASTS SHALL BE RATED FOR AND SUPPLY A TOTAL HARMONIC DISTORTION (T.H.D.) OF 10% OR LESS. 9. ALL FLUORESCENT LIGHT FIXTURES SHALL HAVE ENERGY SAVING LAMPS AND SHALL BE EQUIPPED WITH ELECTRONIC ENERGY SAVING BALLASTS. 10. HYBRID & UNIVERSAL BALLASTS SHALL NOT BE USED AND WILL NOT BE ACCEPTED. LIGHTING ZONE CON ROL SCHEDULE ZONE LOCATION / ROOM / FUNCTION CONTROL FUNCTION REMARKS ON OFF OVERRIDE TYPE OVERRIDE LOCATION 1 UKIVt-UP CANOPY UUIIVNLIUH I S PHU I UCELL I I INIEK 1 UN % UFF BANK LOBBY( 3 2a, 2b BUILDING AND POLE -MOUNT EXTERIOR FIXTURES PHOTOCELL TIMER ON/OFF BANK LOBBY 3 3a, 3b EXTERIOR ENTRANCE DOWNLIGHTS AND SITE MONUMENT / PYLON SIGNS PHOTOCELL PHOTOCELL ON/OFF BANK LOBBY 3 4 EXTERIOR BUILDING SIGNAGE PHOTOCELL TIMER ON/OFF BANK LOBBY 3 5 INTERIOR SIGNAGE TIMER TIMER ON/OFF BANK LOBBY 3 6 DECORATIVE TOWER UPLIGHTS PHOTOCELL TIMER ON/OFF BANK LOBBY 3 1 7 VESTIBULE (ALWAYS ON) - - - - - 8 DESK PENDANTS (ALWAYS ON) - - _ _ _ 9 LOBBY GRID STRIP TROFFERS TIMER TIMER WALL DIMMER AT OR NEAR TELLER LINE 1, 2, 3 10 LOBBY RECESSED CANS TIMER TIMER WALL DIMMER AT OR NEAR TELLER LINE 2, 3 11a, 11b LOBBY STRIP FIXTURES TIMER TIMER WALL DIMMER AT OR NEAR TELLER LINE 2, 3 12 BRIM RECESSED CANS TIMER TIMER WALL DIMMER AT OR NEAR TELLER LINE 2, 3 13a, 13b,... OFFICE AND CONFERENCE GRID STRIP TROFFERS MANUAL ON OCCUPANCY SENSOR WALL DIMMER ROOM WALL 4 14 SERVICE HALLWAY OCCUPANCY SENSOR OCCUPANCY SENSOR ON / OFF ROOM WALL 4 15a,15b FILE / PRINT ROOM AND LOUNGE MANUAL ON OCCUPANCY SENSOR WALL DIMMER ROOM WALL 4 16 JANITOR CLOSET MANUAL ON OCCUPANCY SENSOR ON / OFF ROOM WALL 4 17 TELLER LINE MANUAL ON OCCUPANCY SENSOR WALL DIMMER ROOM WALL 4 18a,18b RESTROOMS OCCUPANCY SENSOR OCCUPANCY SENSOR ON / OFF ROOM WALL 4 19a, 19b EQUIP / CASH ROOM MANUAL ON OCCUPANCY SENSOR WALL DIMMER ROOM WALL 4 20 DATA ROOM MANUAL ON OCCUPANCY SENSOR ON/OFF ROOM WALL 4 REMARKS: 1 PROVIDE DAYLIGHT RESPONSIVE CONTROLS ONLY WHERE SHOWN ON PLANS. 2 PROVIDE PILOT LIGHT SWITCH WHERE FIXTURES ARE NOT VISIBLE FROM SWITCH LOCATION. 3 LIGHTING CONTROL ZONES SHALL BE CONNECTED TO RELAY CONTROL PANEL WITH BUILT-IN ASTRONOMICAL TIME CLOCK AND PROGRAMMABLE CONFIGURATIONS. 4 LIGHTING CONTROL ZONES SHALL BE CONNECTED TO STAND-ALONE ROOM CONTROLLERS AND/OR POWER PACKS. RELAY CONTROL PANEL SCHEDULE RELAY CIRCUIT ZONE AREA SERVED 1 PP3#1 z1 DRIVE -UP CANOPY DOWNLIGHTS 2 PP3#3 z2a POLE -MOUNT EXTERIOR FIXTURES 3 PP3#3 z2c BUILDING MOUNT EXTERIOR FIXTURES 4 PP3#17 z3a EXTERIOR ENTRANCE DOWNLIGHTS 5 PP3#11 z3b ILLUMINATED MONUMENT SIGN 6 PP3#17 z4 EXTERIOR BUILDING SIGNAGE 7 PP3#5 z5 INTERIOR SIGNAGE 8 PP3#15 z6 DECORATIVE TOWER UPLIGHTS 9 PP3#7 Z9 LOBBY LINEAR TROFFERS 10 PP3#7 z10 LOBBY RECESSED CANS 11 PP3#7 z1la, z1lb LOBBY STRIP FIXTURES 12 PP3#7 z12 BRIM RECESSED CANS 13 - - - 14 - - - 15 - - - 16 - - - �0C�ill � R M0 7 E73 1. FOR EXACT LOCATION AND MOUNTING HEIGHT OF ALL POWER, TEU/DATA OUTLETS AND MECHANICAL EQUIPMENTS COORDINATE WITH ALL TRADES AND ARCHITECTURAL DRAWINGS. 2. ALL BRANCH CIRC_ I WIRING SHALL BE RUN CO^:SEALED IN WALLS AId- ABOVE HUNG CEILING. UNLESS OTHERWISE NOTED. 3. No. 12 AWG (THHN) SHALL BE THE MINIMUM SIZE AND SHALL BE USED FOR ALL 15A & 20A BRANCH CIRCUIT WIRING, UNLESS OTHERWISE NOTED. CONTRACTOR SHALL ADJUST SIZE FOR VOLTAGE DROP AND OTHER DE -RATING FACTORS AS PER CODE REQUIREMENTS. 4. 3/4" CONDUIT SHALL BE THE MINIMUM TRADE SIZE OF CONDUIT. 5. CIRCUITS ARE DESIGNATED BY THE NUMBER SHOWN ADJACENT TO EACH RECEPTACLE, ETC. WIRING IS SHOWN ONLY FOR UNDER SPECIAL CIRCUMSTANCES. PROVIDE CONDUITS, WIRES, ARMORED CABLES AND BOXES REQUIRED TO ENERGIZE THE EQUIPMENT AS SHOWN. 6. ALL COMMUNICATIONS, SECURITY WORKS ARE A SEPARATE CONTRACT, DON. EC TO PROVIDE ALL CONDUIT, RACEWAY, BACK -BOXES. i?. FOR ADDITIONAL NOTES REFER TO ARCHITECTURAL DRAWINGS. 8. CONDUIT RUNS THAT ARE SHOWN ARE DIAGRAMMATICAL AND SHOW POTENTIAL ROUTING OF CONDUITS. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE RUNS WITH ALL TRADES. MECHANICAL/PLUMBING EQUIPMENT NOTES 1. INTENT OF DRAWING IS TO SHOW LAYOUT OF MECHANICAUPLUMBING EQUIPMENT AND RESPECTIVE ELECTRICAL CONNECTIONS WITH ASSOCIATED DEVICES. FOR EXACT LOCATIONS AND MOUNTING HEIGHTS OF ALL MECHANICAL/PLUMBING EQUIPMENT AND RESPECTIVE CONTROLS REFER TO MECHANICALIPLUMBING DRAWINGS. USE THIS DRAWING FOR CIRCUITING PURPOSES ONLY. 2. CONSTRUCTION MANAGER (CM) SHALL DETERMINE WHICH CONTRACTOR'S SCOPE IT IS TO PROVIDE DISCONNECT SWITCHES AND/OR CONTROL PANELS FOR MECHANICALIPLUMBING EQUIPMENT. COORDINATE WITH CM PRIOR TO INCLUDING COSTS FOR SAME IN BID. DISCONNECT SWITCHES AND CONTROL PANELS SHALL BE INSTALLEDNVIRED BY ELECTRICAL CONTRACTOR U.O.N. COORDINATE WITH MECHANICALIPLUMBING CONTRACTORS FOR ADDITIONAL REQUIREMENTS. 3. CONTRACTOR TO INSTALL & WIRE THERMOSTATS AND ASSOCIATED BACKBOXES FOR ALL EQUIPMENT INCLUDING INDIVIDUAL HEATPUMPS. THERMOSTATS PROVIDED BY MECHANICAL CONTRACTOR. REFER TO MECHANICAL SCHEDULES & SPECS FOR A LIST OF EQUIPMENT AND ASSOCIATED THERMOSTATS. COORDINATE LOCATION OF ALL THERMOSTATS WITH ARCHITECT. VOLTAGE DROP REQUIREMENTS NOTE: FEEDERS ARE SIZED TO MEET 3% MAXIMUM VOLTAGE DROP. CONTRACTOR MUST PROVIDE FEEDERS AS SIZED HERE AS A MINIMUM. IF CONTRACTOR FEEDER ROUTING INCREASES THEIR LENGTH, OR INCREASES VOLTAGE DROP FOR ANY OTHER REASON, CONTRACTOR SHALL INCREASE FEEDER SIZE AND/OR QUANTITY TO MEET 3% MAXIMUM. MAXIMUM BRANCH CIRCUIT VOLTAGE DROP IS 2%. ANY CHANGE REQUESTS SHALL BE SUBMITTED TO ENGINEER FOR APPROVAL IN WRITING. CONTRACTOR SHALL MEASURE FEEDER LENGTHS AS FEEDERS ARE INSTALLED AND SUBMIT THIS DATA TO ENGINEER. INCLUDE TABLE OF FEEDER LENGTHS IN CONTRACTOR'S AS -BUILT DRAWINGS. 7EL7PF10M77d COMMMMrA, 71CM5 77CUP-47Y ('�211 L [E R�, L 0161I's-CIO I i1 CC a Va 71 =M 0, 7 'IEa 1. PROVIDE TELEPHONE, COMMUNICATION, SECURITY AND OTHER LOW -VOLTAGE EQUIPMENT BACK -BOXES & EMPTY CONDUIT SYSTEMS FOR LOW -VOLTAGE WIRING AND CABLING. (LION, WIRING & CABLING IS UNDER SEPARATE CONTRACT.) LOCATION AND SIZE OF CONDUIT SHALL BE AS SPECIFIED ON THE DRAWINGS OR AS REQUIRED. THE MANNER OF INSTALLING CONDUIT SHALL BE THE SAME AS SPECIFIED HEREIN FOR LIGHT AND POWER WIRING SYSTEM AND IN ACCORDANCE WITH THE REQUIREMENTS OF THE TELECOM COMPANY AND OTHER COMMUNICATION SYSTEMS VENDORS. 2. THE TELEPHONE COMMUNICATION, SECURITY AND OTHER LOW -VOLTAGE SYSTEMS SHALL CONSIST OF EMPTY RACEWAYS, JUNCTION BOXES, PULL BOXES, ETC., LEFT IN READINESS FOR WIRING TO BE PROVIDED UNDER SEPARATE CONTRACT, DON. PROVIDE DRAG LINE IN ALL EMPTY CONDUITS. 3. ALL TELEPHONE/DATA/SECURITY/LOW VOLTAGE INSTALLATIONS SHALL BE COORDINATED WITH THE RESPECTIVE VENDORS. it. CONDUITS & BOXES SHALL BE AS SPECIFIED IN ELECTRICAL SPECIFICATIONS. RACEWAYS SHALL HAVE NO MORE THAN THE EQUIVALENT OF TWO 90 DEGREE BENDS WITHOUT INTERMEDIATE PULL BOXES OR ACCESS POINTS. 5. REFER TO ARCHITECTURAL, TELECOM, INFORMATION TECHNOLOGY, SECURITY AND OTHER DRAWINGS FOR ADDITIONAL REQUIREMENTS. 11=2 uU 7RzK 7 UJ EEG RaM O CONTROLS ROLS IN ADDITION TO THE WORK SHOWN IN THESE ELECTRICAL DRAWINGS, THE ELECTRICAL CONTRACTOR IS RESPONSIBLE TO PROVIDE, FURNISH AND INSTALL ALL WORK, LABOR, MATERIALS, FIXTURES, HARDWARE, CABLING AND OTHER COMPONENTS AS SHOWN ON THE ARCHITECTURAL LIGHTING DRAWINGS, INCLUDING ALL LIGHT FIXTURES. SEE ARCHITECTURAL LIGHTING DRAWINGS FOR THESE REQUIREMENTS AND WORK. ELECTRICAL CONTRACTOR IS ALSO RESPONSIBLE TO PROVIDE, FURNISH AND INSTALL ALL CONDUIT, RACEWAY, BACKBOXES AND ASSOCIATED LABOR, HARDWARE AND MATERIALS NECESSARY FOR THE INSTALLATION OF SAME, AND FOR THE INSTALLATION OF DIMMING & OTHER LIGHTING CONTROLS. REFER TO THE ELECTRICAL SPECIFICATIONS AND DRAWINGS OF OTHER TRADES FOR ADDITIONAL WORK, SUCH AS RELATED TO MECHANICAL, PLUMBING AND FIRE ALARM SYSTEMS, AND NOTES REGARDING SEPARATION OF TRADES. GE VRE F,,InL, L H, 0 7 E 8 1. ELECTRICAL CONTRACTOR SHALL VERIFY ELECTRICAL AND GROUNDING REQUIREMENTS OF ALL NEW EQUIPMENT TO BE USED. ALL SPECIAL PURPOSE RECEPTACLES INDICATED ON PLAN SHALL BE VERIFIED WITH EQUIPMENT MANUFACTURER TO INSURE PROPER WIRING. 2. CIRCUIT NUMBERS ARE FOR GUIDANCE ONLY. CONTRACTOR SHALL BE RESPONSIBLE TO BALANCE PHASES. REFER TO PANEL SCHEDULES FOR BRANCH CIRCUIT REQUIREMENTS. 3. U.O.N ALL BRANCH CIRCUIT WIRING SIZES ARE 2#12 t 1#12G IN A 3/4" CONDUIT. ALL CIRCUIT S AND FEEDERS SHALL HAVE A FULL SIZE INSULATED GREEN GROUND CONDUCTOR AND BE CONNECTED TO GROUND BUS IN RESPECTIVE PANEL. MINIMUM SIZE CONDUCTOR AND CONDUIT IS #12 THHN CU, 3/4"C (EMT). 4. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING AND PROVIDING THE ACTUAL NUMBER OF CONDUCTORS REQUIRED FOR ALL BRANCH CIRCUIT WIRING TO SERVE THE INTENDED FUNCTION. 5. ALL DEVICE PLATE FINISHES/COLORS SHALL BE AS INDICATED BY ARCHITECT REFER TO ARCHITECTS TELECOM AND ELECTRIC PLANS FOR ADDITIONAL ELECTRICAL INFORMATION. 6. FOR EXACT LOCATION AND QUANTITY OF RECEPTACLES, TELEPHONE AND OTHER OUTLETS, REFER TO THE ARCHITECT'S DRAWINGS. 7. ELECTRONIC AS -BUILT DRAWINGS, SHOWING CONDUIT RUNS AND CIRCUITING MUST BE GIVEN TO ARCHITECT, ENGINEER AND OWNER FOR RECORD AT THE COMPLETION OF THE JOB. 8. PANEL DIRECTORIES SHALL BE COMPLETELY FILLED IN AT COMPLETION OF JOB. 9. ALL NEW VOICE AND DATA WIRING IN CEILING PLENUM SHALL BE RUN IN EMT CONDUIT. NEW WALL OUTLETS SHALL RECEIVE 3141' EMPTY CONDUIT STUB -UP WITH DRAG WIRE AND JUNCTION BOX. 10. EACH COMBINATION DATA/TELEPHONE AND DATA OUTLET SHALL UTILIZE 1" E.M.T. STUBBED UP TO HUNG CEILING FROM JUNCTION BOX. 11. CONTRACTOR SHALL COORDINATE ALL NEW TELEPHONE CONDUIT RUNS WITH TELECOM COMPANY REPRESENTATIVE BEFORE STARTING WORK. 12. CONTRACTOR TO PROVIDE AN EMPTY CONDUIT SYSTEM AND OUTLET BOXES FOR INSTALLATION OF NEW SECURITY SYSTEM. VERIFY EXACT REQUIREMENTS WITH StuuKl I Y 1/ENDUK. 13. ALL HOLES IN SLABS OR WALLS SHALL BE FIRE STOPPED VIA LISTED FIRE -STOPPING ASSEMBLIES. SUBMIT TO ENGINEER FOR APPROVAL. 14. PROVIDE A GROUND BUS IN NEW PANELS. 15. CONTRACTOR TO DE -RATE CONDUCTORS IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE WHEN INSTALLING MORE THAN THREE (3)120VAC CIRCUITS IN A 3/4"C HOMERUN AND OTHERWISE REQUIRED. 16. REFER TO PROJECT SPECIFICATIONS FOR ADDITIONAL, IMPORTANT REQUIREMENTS. 17. ALL LINE AND LOW VOLTAGE WIRING SHALL BE INSTALLED IN CONDUIT SYSTEMS CONFORMING TO PROJECT SPECIFICATIONS. ARMORED AND METAL -SHEATHED CABLES, TYPES AC AND MC, AND NON-METALLIC SHEATHED CABLES, TYPES NM, NMC, AND NMS, ARE NOT PERMITTED. 18. ALL ENDS OF CONDUIT SYSTEM SHALL HAVE A BUSHING OR A COUPLING INSTALLED FOR THE PURPOSE OF PROVIDING PROTECTION OF CONDUCTORS. IN NO CASE ARE CONDUIT ENDS PERMITTED TO REMAIN OPEN. 19. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL WIRING, INCLUDING LOW -VOLTAGE, TO OWNER -PROVIDED SIGNAGE. ALL JUNCTION BOXES FOR SIGNAGE SHALL BE PLACED AS REQUIRED TO INSTALL THE SIGNAGE AS INDICATED IN THE ARCHITECTURAL ELEVATIONS. COORDINATE WITH OWNER'S SIGNAGE VENDOR AND REFER TO MANUFACTURER'S WIRING DIAGRAMS. 20. ALL LOW VOLTAGE WIRING IN INACCESSIBLE AREAS SHALL BE INSTALLED IN METALLIC CONDUIT. 21. CONDUIT SYSTEMS INSTALLED ON THE ROOF SHALL BE SUPPORTED AT MAXIMUM INTERVALS OF FIVE FEET WITH HARDWARE SECURED TO THE BUILDING SURFACE. 22. EMERGENCY LIGHTING AND EXIT SIGN CIRCUIT BREAKERS SHALL BE LOCATED IN THE BOTTOM RIGHT OF THE ELECTRICAL PANEL. 23. ALL WIRING FOR THE PURPOSE OF EMERGENCY SYSTEMS SHALL BE INSTALLED IN A SEPARATE CONDUIT SYSTEM INDEPENDENT OF OTHER SYSTEMS. 24. THERE SHALL BE A SEPARATE IDENTIFIED NEUTRAL INSTALLED FOR EACH EMERGENCY LIGHTING CIRCUIT AND/OR EXIT LIGHTING CIRCUIT. 25. SECURELY FASTEN EACH RECESSED GRID LIGHT FIXTURE TO THE CEILING SYSTEM WITH APPROPRIATE SUPPORT BRACKETS AND CLIPS PER INDUSTRY STANDARDS. AT LEAST TWO CORNERS OF EACH FIXTURE SHALL BE SUPPORTED INDEPENDENTLY FROM ANY OTHER SUPPORTING SYSTEM. 26. ALL BRANCH CIRCUIT CONDUCTORS SHALL BE CONNECTED BY MEANS OF A SCREW TERMINAL. 27. THE CONTINUITY OF ANY BRANCH CIRCUIT CONDUCTOR INCLUDING ANY IDENTIFIED GROUNDED CONDUCTOR SHALL NOT DEPEND UPON DEVICE CONNECTIONS, SUCH AS LAMPHOLDERS, RECEPTACLES, ETC., WHERE THE REMOVAL OF SUCH DEVICES WOULD INTERRUPT THE CONTINUITY. 28. DE -RATING OF NEUTRALS IS PROHIBITED. 29. THE USE OF AUXILIARY GUTTERS, WIREWAYS, RACEWAYS AS ENCLOSURES FOR SERVICE ENTRANCE OR TAPPING OF SERVICE ENTRANCE CONDUCTORS IS STRICTLY PROHIBITED. 30. METAL IDENTIFICATION TAGS SHALL BE INSTALLED WHERE THE GROUNDING CONDUCTOR IS CONNECTED TO THE GROUNDING ELECTRODE. 31. PENETRATIONS OF FLOORS, ROOF, WALLS, AND WALL MEMBRANES REQUIRED TO HAVE FIRE -RESISTANCE RATINGS SHALL BE PROTECTED WITH THROUGH -PENETRATION FIRE STOPS SUITABLE FOR THE METHOD OF PENETRATION. MAINTAIN ALL FIRE RATINGS. THROUGH -PENETRATIONS FIRE STOPS SHALL BE TESTED IN ACCORDANCE WITH UL AND BUILDING CODE REQUIREMENTS. CHASE Cp ��AdnF = v hVEngineering D.P.C./we engineer success 116 West 32nd Street, 12th Floor, New York, N.Y. 10001 P 212.643.9055 F 212.643.0503 www.mgedpc.net MG ENGINEERING, P.C. 116 W 32ND STREET,12TH FLOOR, NEW YORK, NY 10001 T. 212.643.9055 1 WWW.MGEDPC.NET Severud Assoda-%tes SEVERUD ASSOCIATES CONSULTING ENGINEERS, PC 469 SEVENTH AVENUE - SUITE 900, NEW YORK, NY 10018 T.212.986.37001 WWW.SEVERUD.COM # I ISSUANCE I DATE I ISSUED FOR BID 06-28-2019 ISSUED FOR BID 08-15-2019 oil n :7 TPG ARCHITECTURE, LLP 31 PENN PLAZA 132 WEST 31ST STREET, 5TH FLOOR, NEW YORK, NY 10001 212.768.0800 1 TPGARCHITECTURE.COM IN CONSIDERATION OF RECEIVING DRAWINGS FROM TPG ARCHITECTURE LLP IN AN ELECTRONIC FORM, THE RECIPIENT AGREES, TO THE FULLEST EXTENT PERMITTED BY LAW, TO HOLD HARMLESS AND INDEMNIFY TPG ARCHITECTURE LLP FROM AND AGAINST ALL CLAIMS, LIABILITIES, LOSSES, DAMAGES, AND COSTS, INCLUDING BUT NOT LIMITED TO ATTORNEY'S FEES, ARISING OUT OF, OR IN ANY WAY CONNECTED WITH THE USE, RE -USE, MIS -USE, MODIFICATION, OR MISINTERPRETATION OF THE MACHINE-READABLE INFORMATION PROVIDED BY TPG ARCHITECTURE LLP UNDER THIS AGREEMENT. PROJECT SOUTH WINDSOR BUCKLAND 190 BUCKLAND ROAD SOUTH WINDSOR, CT 06074 DRAWING NAME ELECTRICAL GENERAL NOTES AND LIGHTING SCHEDULES SEAL DATE 06.13.2019 PROJECT N0. 8303.58 SCALE N.T.S. DRAWN BY MDM DOB PAGE CHECKED BY XX -OF- NO. E-002.00 L----j j B#27 1 I 1 1 J g B#27 I 1 I 0 1 1 1 1 1 e fB#2 - 5 - T 7 J B#27 J B#27 y� T C#17 z3a J B#27 L-70 z13f 1 z13f —i--- ----- ----- C#2 L-500 L-500 zl3g z13 z13h u, DL D� z13h C#2 ��i Os )�� C#2 oS )�) L410NL z13f z13g C#2 C#7 (; zg O ® 0O L-11 L-11 L-11 O ® L-11 L-11 C#9 os )) C#2z13h O C#2 z10 zl3g L-412 L-412 z13h z13f z13f z13f C#9 C#9 ll L-500 L-500 z8 z8 —j C#2 C#2 z10 EM L-11 C#7 C#7 0 EM C#7 () L-11 L-11 z10 z10 z10 D z13e7+ - — i — — — ~� I 1 A L-307 z9 00 z13e L-307 j� EM z11 L-500 z11 C#7 L-500 C#7 z9 C#7 L-500 C#7 EM QI z9 1 L-41ONL zl3e \ C#7 EM L-500 C#9 O OS ))) EM L-500 L-500 zg Q z13e C#7 z9 C#7 C#7 L-500 L-500 C#2 z9 C#7 " L-500 z9 q I C#7 EM L-408A z12 L-500 0 z13d L-500 C#7 C#7 z9 L-500 C#7 L-500 EM z13d \ z9 z81n 1� 1 C#7 EM L_5nn C#9 U �'71 z9 C#7 L-500 EM z9 -500 C#7/L-500 EM C#2 z9 L-500 z13d C#7 z9 _ C#7 -500 ((cI o z13d MD C#7 u 7140 Qz13n 4IOU 1.-ouv IN L-aw 1 �) z13a I #3c L-500 z3 1 z1C#2c L-500 L-41ONL OS )) I z13b ` C#g 0 III!i! L-41ONL / r(c© oS )) f z8 TII C#9 p0 13c \\�I� / L-41ONL z))� z13c z8 L-500 C#9 O C#2 z8 C#2 L-500 C#2 C#2�� z13b z13a z13c L-500 z13c L-500 1T_T yl ----------- -- ---- B#31 -------------------- _ (i J1-- - - - - - - - - - - - - - - J L-7 6#31 C#17 5 B#31 5 LOG M u � H G CCM 7 PR C_ Lr2�c0IEMi 0 TAG AREA CONTROL DESCRIPTION NARRATIVE 0 PRIVATE CONSULTATION SPACE LOCAL MANUAL CONTROL TO FULL ON / FULL OFF AND CONTINUOUS DIMMING FUNCTIONALITY. (PCS) / BOOTH AUTOMATIC FULL OFF WITHIN 30 MINUTES AFTER LAST OCCUPANT LEAVES VIA OCCUPANCY SENSOR. �2 CASUAL MEETING SPACE (CMS) LOCAL MANUAL CONTROL TO FULL ON / FULL OFF AND CONTINUOUS DIMMING FUNCTIONALITY. AUTOMATIC FULL OFF WITHIN 30 MINUTES AFTER LAST OCCUPANT LEAVES VIA OCCUPANCY SENSOR. LOCAL MANUAL CONTROL TO FULL ON / FULL OFF AND CONTINUOUS DIMMING FUNCTIONALITY. 3� PRINTIFILE & LOUNGE AUTOMATIC FULL OFF WITHIN 30 MINUTES AFTER LAST OCCUPANT LEAVES VIA OCCUPANCY SENSOR. RESTROOMS / SERVICE HALLWAY AUTOMATIC OCCUPANCY SENSOR TO FULL POWER ON & TURN-OFF WITHIN 30 MINUTES AFTER LAST OCCUPANT LEAVES & MANUAL CONTROL TO TURN LIGHTS OFF. 5 VESTIBULE NO CONTROLS - LIGHTS ON 2417 FOR EGRESS, SAFETY PURPOSES. LOCAL MANUAL CONTROL TO FULL ON / FULL OFF AND CONTINUOUS DIMMING FUNCTIONALITY. © TELLER AREA AUTOMATIC FULL OFF WITHIN 30 MINUTES AFTER LAST OCCUPANT LEAVES VIA OCCUPANCY SENSOR. Q7 EQUIP / CASH ROOM LOCAL MANUAL CONTROL TO FULL ON / FULL OFF AND CONTINUOUS DIMMING FUNCTIONALITY. AUTOMATIC FULL OFF WITHIN 30 MINUTES AFTER LAST OCCUPANT LEAVES VIA OCCUPANCY SENSOR. LOCAL MANUAL CONTROL TO FULL ON / FULL OFF. AUTOMATIC FULL OFF WITHIN 30 MINUTES AFTER ® DATA ROOM LAST OCCUPANT LEAVES VIA OCCUPANCY SENSOR. OJANITOR'S CLOSET / SPRINKLER LOCAL MANUAL CONTROL TO FULL ON / FULL OFF. AUTOMATIC FULL OFF WITHIN 30 MINUTES AFTER ROOM LAST OCCUPANT LEAVES VIA OCCUPANCY SENSOR. 10 BANKING LOBBY / LIVING ROOM AUTOMATIC ON/OFF VIA TIME -SWITCH CONTROLS; MANUAL LIGHT -REDUCTION CONTROLS VIA WALL DIMMER TO CONTROL ALL LUMINAIRES BY AT LEAST 50%. 11 EXTERIOR ENTRANCE AUTOMATIC ON/OFF VIA PHOTOCELL CONTROLS. 12 MECHANICAL ROOM / BACK AUTOMATIC ON VIA PHOTOCELL CONTROLS & AUTOMATIC OFF VIA TIME SWITCH CONTROLS. ENTRANCE rjz4 C#17 C#17 C#17 � � z3a z3a I �`M - � L-7� L-7® B#27 - J #27 C#3 z2a -- COI;f lu' R '19 EM C#7 0 C#7 IV - - L-11 L-11 z10 z10 (0) C#9 L-405-NL z8 C#7 E L-11 z10 _._.T L-307 z11 C#7 A CZ#7 EM C#9 00 z9 L-500 z7 CI EM/NL El L-500 z7 C#9 EM/NL L-500 C#9 z7 EM/NL 41 L-7 C#17 z3a EM C#17 J z4 6 EM -- — �-_M C I >.. L-20 4 C#4 zl8a L2 z18a ti �- ---- z18a) j -� �) C#4 3 � z18a L2 z15a L-500 EM 3❑ os )) z14� ;! )\ zl5a L2 L2 1#4 2 C#4 /) z15a = - EM C#4` ( �' T � EM L k L2 z16 [� C#4 C#4 �)) C#4 os )) L-22 OS z1 z18b z18bEM j T C#5 z16 ^ L-500 z16 C#4�D os ))) z18b J z18b z5 z14 ® EM 7 L-500 C#4 L-500 ® z15b z9 L-20 �'!r C#7 C#4 EM C#7 z14 z14� o n z15b D L-500 z9 DFF z17 C#4 ��� 1 [• C#7 11 z15b of it z17 © ® C#4 °S )) ! C#7 L-11 -11 L-500 C#4 EM T z9 z17 C#7 os) C#4 - �_ � 1 G I II )) C#4 z15b a Z9 z17 1z17 EM z9 EM O C#4 C#4 C#4 C#7 L z15b -11 T, z9 -i- L-500 9 o L2 i 8 �((OS) (joC job �© z20 I El oS ))) EM D� L-500 z19a C#4 in z7 L2 z19a EMC#9 EM/NL EMz19aC#4 z20 ! jl L-500 o OS ))� z7 C#4 C#4 z19b C#9 z19b z19b ❑7 z1919a )) z20 L2 L-500 EM/NL C#4 —; rC z19a OS L2 z7 EM/NL '.. ,I ----{� r 7. T- -- �- z19a - - - - z20 . . r a L-7 z3a I VST FLOOD ELECTRICAL LMHTMG FLA, H SCALE: 1 /4" = 1'-O" LIGHTING Off Y -RI0L H o l] LP_:: BASIS OF LIGHTING CONTROL DESIGN IS LEVITON. IF ALTERNATE MANUFACTURER IS PROPOSED, THE CONTRACTOR SHALL SUBMIT A FLOOR PLAN INDICATING THE DEVICE LAYOUT WITH SENSOR RANGES INDICATED, AS WELL AS, ALL ASSOCIATED EQUIPMENT CUT SHEETS AND WIRING DIAGRAMS FOR REVIEW. LIGHTING NOTES: 1. LIGHT FIXTURES DESIGNATED WITH 'EM' INDICATES EMERGENCY FIXTURE. PROVIDE 90 MINUTE EMERGENCY BATTERY PACK (CONSTANT POWER SUPPLY). 2. LIGHT FIXTURES DESIGNATED WITH WL' INDICATES UNSWITCHED NIGHT LIGHT FIXTURE. (CONSTANT POWER SUPPLY WITH LOCK -ON CIRCUIT BREAKER). 3. LIGHTING ZONES ARE SHOWN BY THE LOWER CASE LETTER NEXT TO THE LIGHT FIXTURE. REFER TO LIGHTING ZONE CONTROL SCHEDULE ON SHEET E-002 FOR ADDITIONAL INFORMATION. 4. ALL PENETRATIONS AND OPENINGS SHALL BE FIRE STOPPED WITH UL LISTED FIRE STOPPING ASSEMBLY. 5. COORDINATE EXACT CEILING MOUNTED AND WALL MOUNTED SENSOR PLACEMENT WITH LIGHTING CONTROLS MANUFACTURER FOR OPTIMAL USE. 6. ELECTRICAL CONTRACTOR TO ENSURE WALL MOUNTED SWITCHES ARE NOT BLOCKED BY DOOR OPENING. COORDINATE WITH ARCHITECTURAL DOOR SCHEDULES. 7. REFER TO SHEET E-002 AND E-500 SERIES DRAWINGS FOR ADDITIONAL LIGHTING CONTROL DETAILS AND SCHEDULES. 8. ELECTRICAL CONTRACTOR SHALL PROVIDE AN UNSWITCHED HOT LEG TO LIGHTING FIXTURES WITH INTEGRAL OCCUPANCY SENSORS. CONTRACTOR TO ENSURE FUNCTIONALITY OF LIGHTING FIXTURE. 9. CONTRACTOR SHALL PROVIDE AN UNSWITCHED HOT LEG FROM NEAREST CIRCUIT TO FEED ALL "EM" LIGHT FIXTURES AND EXIT SIGNS. A.1 ' (B.1� a � C#13 10 J C#1 L-6A L-6A z1 ®®®® z1 ®� C#1 00 1 f G® ® L-6A ® ® L-6A z1 z1 C#1 C#1 3.1 10 PANELBOARD'PP1'. 20 PANELBOARD'PP2'. O PANELBOARD'PPT. ® FLUSH MOUNTED RELAY CONTROL PANEL,'RCP'. O MOTORIZED SHADE MOTOR CONNECTIONS. COORDINATE SHADE CONTROL LOCATIONS WITH ARCHITECT. © PROVIDE WEATHERPROOF JUNCTION BOX FOR EXTERIOR ILLUMINATED BANK SIGNAGE. COORDINATE EXACT LOCATION WITH ARCHITECT AND SIGNAGE VENDOR. 70 PROVIDE JUNCTION BOX FOR INTERIOR ILLUMINATED BANK SIGNAGE. COORDINATE EXACT LOCATION WITH ARCHITECT AND SIGNAGE VENDOR. ® PROVIDE MANUAL -ON ONLY OVERRIDE SWITCHES FOR TIME SWITCHED CONTROL ZONES AS NOTED BELOW: (1) ONE SWITCH SHALL OVERRIDE ALL EXTERIOR LIGHT FIXTURES (1) ONE SWITCH SHALL OVERRIDE ALL INTERIOR TIME SWITCHED LIGHT FIXTURES (1) ONE SWITCH SHALL OVERRIDE ALL BANK SIGNAGE 90 MANUAL LIGHT REDUCTION SWITCHES FOR LOBBY LIGHT FIXTURES AS FOLLOWS: (1) ONE SWITCH SHALL CONTROL ZONE'z9' (1) ONE SWITCH SHALL CONTROL Z0NE'z10' (1) ONE SWITCH SHALL CONTROL ZONE'z1 V (1) ONE SWITCH SHALL CONTROL ZONE'z12' 10 PROVIDE WEATHERPROOF JUNCTION BOX FOR EXTERIOR ILLUMINATED DRIVE -UP E N O 0 D T T C 0 IT IT T D N R. 11 NEW UNDERCABINET LIGHTING, FLEX CONDUIT THROUGH WALL TO J-BOX BELOW. 12 DIMMER SWITCH SHALL HAVE AN LED ON/OFF INDICATOR AND BE ENGRAVED WITH THE FOLLOWING: "OPEN AREA LIGHTING" a SCALE:: 1 /4" = 1'-0" CfjCUF DESG_V%IALMON LEGEND PREFIX PANEL DESIGNATION VOLTAGE A PP1 120/208 B PP2 1201208 C PP3 120/208 CHASE ! j A AA j lGE MEngineedng D.P.C./we engineer success 116 West 32nd Street,12th Floor, New York, N.Y. 10001 P 212.643.9055 F 212.643.0503 www.mgedpc.net NIG ENGINEERING, P.C. 116 W 32ND STREET, 12TH FLOOR, NEW YORK, NY 10001 T.212.643.9055 1 WWW.MGEDPC.NET Slrzwerud Associates SEVERUD ASSOCIATES CONSULTING ENGINEERS, GEC 469 SEVENTH AVENUE - SUITE 900, NEW YORK, NY 10018 T.212.986.37001 WWW.SEVERUD.COM # I ISSUANCE I DATE ISSUED FOR BID 06-28-2019 ISSUED FORBID 08-15-2019 11\ ADDENDUM #1 09-09-2019 BULLETIN #2 03-30-2020 TPG\rch'Itecture TPG ARCHITECTURE, LLP 31 PENN PLAZA 132 WEST 31ST STREET, STH FLOOR, NEW YORK, NY 10001 212.768.0800 1 TPGARCHITECTURE.COM IN CONSIDERATION OF RECEIVING DRAWINGS FROM TPG ARCHITECTURE LLP IN AN ELECTRONIC FORM, THE RECIPIENT AGREES, TO THE FULLEST EXTENT PERMITTED BY LAW, TO HOLD HARMLESS AND INDEMNIFY TPG ARCHITECTURE LLP FROM AND AGAINST ALL CLAIMS, LIABILITIES, LOSSES, DAMAGES, AND COSTS, INCLUDING BUT NOT LIMITED TO ATTORNEY'S FEES, ARISING OUT OF, OR IN ANY WAY CONNECTED WITH THE USE, RE -USE, MIS -USE, MODIFICATION, OR MISINTERPRETATION OF THE MACHINE-READABLE INFORMATION PROVIDED BY TPG ARCHITECTURE LLP UNDER THIS AGREEMENT. PROJECT SOUTH WINDSOR BUCKLAND 100 �� U CKLAN D ROAD SOUTH WINDSOR, CT 06074 DRAWING NAME 1 S T FLOOR ELECTRICAL LIGHTING PLAN SEAL DATE 06.13.2019 I PROJECT NO. 8303.58 SCALE AS INDICATED DRAWN BY MDM DOB PAGE CHECKED BY XX 4 OF 13 i DWG NO. -101.0® 1 2 0 18"t218" 26" B``#1�9ff'' `L B#9 B#9 18" I I I'II B#9 18" pI 2 B#7 18" 18" =4D=26" B#7 B#7 -- 0=4v 26" 18" 42 B#7 18" 18" 0 B#5 8" G N !42 88 B#11 18" =@= B#5 CIRCUIT DESIGNATION LEGEND PREFIX PANEL DESIGNATION VOLTAGE A PP1 120/208 B PP2 120/208 C PP3 1201208 24'`H' 24" B#9 24" 24" B#9 18" B#3 18" 2 18" 26" B#5 ® 18" B#3 B#3 ?�OWER NOTES: PROPOSED ROUTE FC CONDUIT TRENCHIN 6 ` I J — — — - —-- — — TB#30 22 �2/\1 -ii B B#6 UA U &,__ li� i � 18" B#6 18" 8" 181118" 18" F. 3 20 18" I 1 / B#2 B#4 B#6 E.P.2 J 44" 21 B#30 — 12 GFI SHADE CONTROL — P. =o_ 13#10 44" T B#8 B#10 4" J 8#30 Ir 42" (TEL) THERMOSTATS 44"0— 11 TT` GFI B#1 38" 44" T� FEC 1 — 1 4" J B#30 II 2GFI =--& 'B#10 J B#6 18„ Bo-; 30 I 44 44" B#10 I GFI 21 � GFI10 j ` 18 B#21 42 _ _I B#18 4 GFI �\C J B#21 8" 2 8" GFCI B#20 3 GFCI 42" B#12 (TEL) Lj_ n2 B ® 44' 64" 84" NGE i J 1; E S ICi� I �lo ' 18" 3 B#14 B#16 4" o��, 18" B#28 c /1� rnu DJS7A 'fl I ti" Du %V LAWL`t GFCI ,I 50" ► 2 3 GFCI B#16 B#26 it D E s 50" �"J JK38" 50 ► 1�g , B#12 18" 3 B#14 18": B#28 , 18° s 18" ►4" 7 44" T 18" J B#30 DC� �DC 18" 0--- 4B#25 38" ST 18" 18" 24" 1' B#29 J 66" C#9 15 72" 0 7 38 72 B#3 �--.�-� J 44" B#1 ES K DC 0C DB 38" J — n '— o 44" 1ST FLOOR ELECTRICAL POWER PLAN SCALE: 1 /4" = 1'-O" 1. TRENCH FLOOR FOR ALL FLOOR MOUNTED POWER/DATA OUTLETS. COORDINATE WITH STRUCTURAL ENGINEER. TYPE, QUANTITIES AND LOCATIONS SHALL BE DESIGNED AND EVALUATED FOR FLOOR STRUCTURAL EXPOSURE AND FIRE RATING OF THE FLOOR BEFORE CONSTRUCTION BEGINS. 2. CONTRACTOR SHALL COORDINATE WITH BUILDING MANAGEMENT AND STRUCTURAL ENGINEER ALL CEILING AND WALL PENETRATIONS PRIOR TO ANY INSTALLATION OF ANY WORKS. B#28 N 42" B#1618" ► I. (TEL) Tirl -_- 80" B#41 42141#42 9 ST T 18" ®DC 44" 64„ 84„2 441$� �K - a 0 104" 2 42 (TEL)► B#23 36 " ®\ B#37 18 84 ► B#32 44 84" B#38 B#39 60, 18" B#36 B#33 B#34 B#23 B#23 �\ J 18" 18" 38" VI" IV, 10 ' LL_ L J 17 U PROVIDE LEGRAND EFB45 FLOOR -RECESSED BOX WITH (2)120V DUPLEX RECEPTACLES, (1) PLATE WITH (2) DATA JACKS, AND (1) BLANK PLATE. 2O PROVIDE JUNCTION BOX FOR MOTORIZED SCRIM DOOR IN SOFFIT. COORDINATE EXACT REQUIREMENTS WITH SCRIM DOOR VENDOR. COORDINATE EXACT LOCATION OF SCRIM DOOR CONTROLS WITH ARCHITECT. 30 PROVIDE 3/4"C DOWN THE WALL AND INTO WIREWAY FOR POWER. PROVIDE 1-1/411C DOWN THE WALL INTO A JUNCTION BOX UNDER THE TELLER COUNTER FOR VOICE/DATA CABLING. USE G5000 WIREMOLD. PROVIDE VC DOWN THE WALL INTO A JUNCTION BOX UNDER THE TELLER COUNTER FOR SECURITY CABLING. RUN CIRCUITRY AS INDICATED IN PLAN FOR THE RECEPTACLES. ® AT eATM LOCATIONS, PROVIDE (1) DUPLEX RECEPTACLE, (1) SINGLE GANG TELECOMMUNICATIONS OUTLET, AND (1) SECURITY STUB UP. PROVIDE (3) 3/4"C HOMERUN TO ELECTRICAL PANELBOARDS AND DATA ROOM. 50 PROVIDE POWER AND DATA/AUDIOVISUAL PROVISIONS FOR DISPLAY SCREEN. HOMERUN CONDUITS TO ELECTRICAL PANELBOARDS AND DATA ROOM WITH DRAG LINE. © PROVIDE SINGLE GANG STAMPED STEEL FLOOR BOX WITH ONE (1) DUPLEX RECEPTACLE. COORDINATE EXACT LOCATION WITH ARCHITECT. 70 ELECTRICALLY POWERED LOW ENERGY POWER OPERATOR WITH CONCEALED ON/OFF POWER SWITCH. PROVIDE CIRCUIT AS SHOWN. ELECTRICAL CONTRACTOR (E.C) SHALL PROVIDE A RACEWAY TO THE FRONT OUTER VESTIBULE DOOR FRAMES FOR THE PURPOSE OF RUNNING WIRES FOR THE ELECTRIC DOOR LOCKING DEVICES, OVER -RIDE KEY SWITCH AND ASSOCIATED EQUIPMENT. THE ELECTRICAL CONTRACTOR (E.C) IS TO FURNISH & INSTALL ALL CONDUIT & JUNCTION BOXES INCLUDING FLEXIBLE CONDUIT, IF AND AS REQUIRED. A DRAG LINE //Q�\\ MUST BE INCLUDED IN THIS RACEWAY FOR LOW VOLTAGE/SECURITY WIRING. O FIRE ALARIVI °iVN I RVL PANEL. REFER TV FIRL ALARIVI DRAYYIIVUJ FVR FURTHLR �/ INFORMATION. O PROPOSED LOCATION OF MANUAL TRANSFER SWITCH AND UTILITY METER / CT CABINET. REFER TO SHEET E-003 FOR ADDITIONAL INFORMATION. 10 PANELBOARD'PP1'. 11 PANELBOARD'PP2'. 12 PANELBOARD'PPT. 13 RELAY CONTROL PANEL,'RCP'. 14 (2) 1" PVC CONDUITS BELOW GRADE WITH PULL WIRE FOR FUTURE DRIVE -UP ATM TELECOMMUNICATIONS WIRING. CONDUIT AND PULL WIRE SHALL TERMINATE INSIDE AN UNDERGROUND TRAFFIC RATED PULL BOX. COORDINATE ALL WORK WITH CIVIL ENGINEER. 15 (1)1-1/4" PVC CONDUIT BELOW GRADE WITH PULL WIRE FOR FUTURE DRIVE -UP ATM. CONDUIT AND PULL WIRE SHALL TERMINATE INSIDE AN UNDERGROUND TRAFFIC RATED PULL BOX. COORDINATE ALL WORK WITH CIVIL ENGINEER. 16 PROVIDE JUNCTION BOX FOR ATM SURROUND LIGHTING. 17 PROVIDE (2) NEMA L5-20R TWIST LOCK RECEPTACLES. 18 PROVIDE (2) 4" CONDUITS FOR TELECOMMUNICATION SERVICE DEMARC. COORDINATE EXACT LOCATION WITH TELECOMMUNICATIONS SERVICE UTILITY. 19 PROVIDE A COMPLETE EMERGENCY CALL SYSTEM THAT ACTUATES A VISIBLE AND AUDIBLE ALARM IN A NORMALLY OCCUPIED AREA, EDWARDS SIGNALING 7008B-N5 OR APPROVED EQUAL. SEE DETAIL 7 ON SHEET E-503 FOR WIRING INFORMATION. 20 BUZZER/STROBE FOR EMERGENCY CALL SYSTEM. 21 PULL CORD FOR EMERGENCX CALL SYSTEM. 2 22 FOR SECURITY DOOR. DRIVE -UP ATM I B#28 ' 0 0 0 0 C#13 - 0 0 GFI@ — WP r PULL BOX FOR LOW VOLTAGE CABLING I o0 0 0 O NOTE: PULL ALL REAQUIRED CONDUITS TO CONCRETE ISLAND AND CAP, FOR FUTURE USE. CHASE:p AC � AIGE MEngineering D.P.C./ we engineer success 116 West 32nd Street,12th Floor, New York, N.Y.10001 P 212.643.9055 F 212.643.0503 www.mgedpc.net _ MG ENGINEERING, P.C. 116 W 32ND STREET, 12TH FLOOR, NEW YORK, NY 1,0001 T. 212.643.9055 1 WWW.MGEDPC.NET Severed Assodatt,vs SEVERUD ASSOCIATES CONSULTING ENGINEERS, PCB 469 SEVENTH AVENUE - SUITE 900, NEW YORK, NY 10018 T.212.986.37001 WWW.SEVERUD.COM # I ISSUANCE DATE ISSUED FOR BID 06-28-2019 ISSUED FOR BID 08-15-2019 ADDENDUM #1 09-09-2019 1A2 BULLETIN #2 03-30-2020 1 TPG�rchitecture TPG ARCHITFCTIIRF- I LP 31 PENN PLAZA 132 WEST 31ST STREET, 5TH FLOOR, NEW YORK, NY 10001 212.768.0800 1 TPGARCHITECTURE.COM IN CONSIDERATION OF RECEIVING DRAWINGS FROM TPG ARCHITECTURE LLP IN AN ELECTRONIC FORM, THE RECIPIENT AGREES, TO THE FULLEST EXTENT PERMITTED BY LAW, TO HOLD HARMLESS AND INDEMNIFY TPG ARCHITECTURE LLP FROM AND AGAINST ALL CLAIMS, LIABILITIES, LOSSES, DAMAGES, AND COSTS, INCLUDING BUT NOT LIMITED TO ATTORNEY'S FEES, ARISING OUT OF, OR IN ANY WAY CONNECTED WITH THE USE, RE -USE, MIS -USE, MODIFICATION, OR MISINTERPRETATION OF THE MACHINE-READABLE INFORMATION PROVIDED BY TPG ARCHITECTURE LLP UNDER THIS AGREEMENT. PROJECT SOUTH WINDSOR BUCKLAND 190 BUCKLAND ROAD SOUTH WINDSOR, CT 06074 DRAWING NAME 1 ST FLOOR ELECTRICAL POWER PLAN SEAL DATE 06.13.2019 PROJECT ivO. 8303.58 SCALE 1 /8"=V-0" III DRAWN BY " MDM I DOB PAGE CHECKED BY M I O Vr IJ i DWG NO. E-201.00 DOB NO. CHASE ! j C#36 ,j T EBH-1 �r _ I EBH-1 III Bu_)TH1 I I C#42 J T EBH-1 MECHANICAL POWER NOTES: 1. CIRCUITS ARE DESIGNATED BY THE NUMBER SHOWN ADJACENT TO EACH MECHANICAL EQUIPMENT. WIRING IS SHOWN ONLY UNDER SPECIAL CIRCUMSTANCES. PROVIDE ALL CONDUITS, WIRES AND BOXES REQUIRED TO ENERGIZED THE EQUIPMENT AS SHOWN. 2. INSTALL AND WIRE ALL CONDENSATE PUMPS, LEAK DETECTION/PANELS AND VARIOUS SENSORS SHOWN ON HVAC DRAWINGS OR SPECIFICATIONS. 3. CONTRACTOR SHALL COORDINATE THE QUANTITY AND LOCATION OF ALL FIRE SMOKE DAMPERS, DUCT SMOKE DETECTORS, SMOKE AND MOTORIZED DAMPERS WITH HVAC/MECHANICAL DRAWINGS. PROVIDE 120V, 20A, 10 CIRCUITS FOR ALL SMOKE DAMPERS, FIRE SMOKE DAMPERS AND MOTORIZED DAMPERS. CONNECT SIX (6) DAMPER MOTORS MAXIMUM PER 20A CIRCUIT. ALL DUCT SMOKE DETECTORS SHALL BE TIED -IN WITH FIRE ALARM SYSTEM. FIRE SMOKE DAMPERS SHALL BE CONNECTED TO THE FA SYSTEM. CONFIRM WITH BUILDING ENGINEER. PROVIDE CONTROL RELAYS AT ORIGIN OF CIRCUIT. ALL RELAYS AND WIRING PROVIDED BY ELECTRICAL CONTRACTOR. COORDINATE WITH MECHANICAL CONTRACTOR AND FIRE ALARM SYSTEM MAINTENANCE VENDOR PRIOR TO INSTALLATION. REFER TO ELECTRICAL AND HVAC DRAWINGS FOR QUANTITY AND LOCATION. 4. COORDINATE EXACT LOCATION AND REQUIREMENTS OF HOT WATER MAINTENANCE CABLING AND HEAT TRACE CABLING WITH PLUMBING CONTRACTOR. EBI-1-1 JT C#32 i� - _ C,"A - T 'I JT EBH-1 �t EBI-1-1 r J C#32 F1 BHA JT < C#30 , HEAT TRACF A#(23,25,27) 7 lid EDH-1 VESTIBULE L - 1 I KEY NOTES: O PANELBOARD'PP1'. 20 PANELBOARD'PP2'. 30 PANELBOARD'PP3'. ® RELAY CONTROL PANEL, 'RCP'. 50 PROVIDE 30A, 240V, 2P NON -FUSIBLE SAFETY SWITCH IN NEMA TYPE 1 ENCLOSURE. 6 PROVIDE 30A, 240V, 2P NON -FUSIBLE SAFETY SWITCH IN NEMA TYPE 3R ENCLOSURE. 0 PROVIDE 30A, 240V, 3P NON -FUSIBLE SAFETY SWITCH IN NEMA TYPE 1 ENCLOSURE. H CORRIC _ — PRI'vT FI --- 2 A#24 WATER HEATER 5 1 A#18,20 A#26 #19,21 ECP -11 LD A#26 CP A#26 LD A#26 ,d A#2,4 A#6,8 ' 5 dI A#26 CP - A#26 i EUI-1-1 C}(29,31) EF-1 c; �T A#22 II I I 11 II EF-2 RESTRC T - At' 22 k-- i C#(29,31) 2 m �I .�-P s � ,.I �U N G E t1I r iI A#22 %T A#14,16 E� 33 _ BSB-1 I FC-P-1 A#26 . — LD A#26 A#10,12 JOS U ,11 5 11G r. 0 C�RICUF D E&IGNATION LEGEND PREFIX PANEL DESIGNATION VOLTAGE A PP1 120/208 B PP2 120/208 C PP3 120/208 �MGE MEngineering D.P.C./we engineer success 116 West 32nd Street,12th Floor, New York, N.Y. 10001 P 212.643.9055 F 212.643.0503 www.mgedIp met MG ENGINEERING, P.C. 116 W 32ND STREET,12TH FLOOR, NEW YORK, NY 10001 T. 212.643.9055 1 WWW.MGEDPC.NET iqgpIpipi .�'Omo' 04 NAM F40- 11 =Aw SEVERUD ASSOCIATES CONSULTING ENGINEERS, PC 469 SEVENTH AVENUE - SUITE 900, NEW YORK, NY 10018 T. 212.986.37001 WWW.SEVERUD.COM # JISSUANCE DATE ISSUED FOR BID 06-28-2019 ISSUED FOR BID 08-15-2019 ADDENDUM #1 09-09-2019 Qz BULLETIN #2 03-30-2020 TPG\rch'1tectuv1K^; TPG ARCHITECTURE, LLP 31 PENN PLAZA 132 WEST 31ST STREET, 5TH FLOOR, NEW YORK, NY 10001 212.768.0800 1 TPGARCHITECTURE.COM IN CONSIDERATION OF RECEIVING DRAWINGS FROM TPG ARCHITECTURE LLP IN AN ELECTRONIC FORM, THE RECIPIENT AGREES, TO THE FULLEST EXTENT PERMITTED BY LAW, TO HOLD HARMLESS AND INDEMNIFY TPG ARCHITECTURE LLP FROM AND AGAINST ALL CLAIMS, LIABILITIES, LOSSES, DAMAGES, AND COSTS, INCLUDING BUT NOT LIMITED TO ATTORNEY'S FEES, ARISING OUT OF, OR IN ANY WAY CONNECTED WITH THE USE, RE -USE, MIS -USE, MODIFICATION, OR MISINTERPRETATION OF THE MACHINE-READABLE INFORMATION PROVIDED BY TPG ARCHITECTURE LLP UNDER THIS AGREEMENT. PROJECT SOUTH WINDSOR BUCKLAND 190 BUCKLAND ROAD SOUTH WINDSOR, CT 06074 I DRAWING NAME 1 ST FLOOR MECHANICAL POWER PLAN SEAL DATE 06.13.2019 i PROJECT NO. 8303.58 I i SCALE 11411 = 1'-0" I' DRAWN BY MDM DOB PAGE i j CHECKED BY XX j 6 OF 13 DWG NO. E-30i.00 AW n rs$ac L CHASE Co 1. CIRCUITS ARE DESIGNATED BY THE NUMBER SHOWN ADJACENT TO EACH MECHANICAL EQUIPMENT. WIRING IS SHOWN ONLY UNDER SPECIAL CIRCUMSTANCES. PROVIDE ALL CONDUITS, WIRES AND BOXES REQUIRED TO ENERGIZED THE EQUIPMENT AS SHOWN. AL-1 z6 AL-1 z6 AL-1 z6 AL-1 z6 -0 — AL-1- - z6 -AL-1 - z6--- -AL 1— z6 AL-1 z6 ROOF ELECTRICAL PLAN SCALE: 1 /4" = V-0" FBI__\\7 H, 00 Fa U PROVIDE 60A, 240V, 3P NON -FUSIBLE SAFETY SWITCH IN NEMA TYPE 3R ENCLOSURE. C#15 20 PROVIDE INTERIOR SURFACE -MOUNTED JUNCTION BOX WITH DISCONNECT SWITCH FOR AL-1 STRIP UPLIGHTS. CONCEAL ABOVE FINISH CEILING. REFER TO ARCHITECTURAL DRAWINGS FOR ADDITIONAL INFORMATION. 30 PROVIDE WEATHERPROOF FLOOD FIXTURE, PHILIPS LPF3-C-4K-FL-S-X-1-BZ SERIES OR APPROVED EQUAL. i F+/x, + + + ,4 + + + I` Q \ B#41 --- �` WP I RTU-1 _ 1 /� [tI+ + + I+ + i+ + + + GFI 1 +fit + �+ + + + + B#41 WP A#13,15 17 a B#41 (DA WP A#7,9,11 GFI B#41 WP a 3 (TYPICAL OF 3) a 8#41 WP C#10 C#10 J® Y L�A0VE-UPc' 'R OOF F®V4EF% Pig nL, Mi SCALE: 1 /4" = 1 `-0" CIRCUIT DESIGNATION LEGEND PREFIX PANEL DESIGNATION VOLTAGE A PP1 120/208 B PP2 1201208 C PP3 120/208 / 7 / rr MEngineenng D.P.C./ we engineer success 116 West 32nd Street,12th Floor, New York, N.Y. 10001 P 212.643.9055 F 212.643.0503 www.mgedpc.net MG ENGINEERING, P.C. 116 W 32ND STREET, 12TH FLOOR, NEW YORK, NY 10001 7.212.643.9055 1 WWW.MGEDPC.NET Severud Associates SEVERUD ASSOCIATES CONSULTING ENGINEERS, PC 469 SEVENTH AVENUE - SUITE 900, NEW YORK, NY 10018 u . 212.986.37001 WWW.SEVERUD.COM 1 # 1 ISSUANCE I DATE Il ISSUED FOR BID 06-28-2019 ISSUED FORBID 08-15-2019 TPG\rchitecture TPG ARCHITECTURE, LLP 31 PENN PLAZA 132 WEST 31ST STREET, 5TH FLOOR, NEW YORK, NY 10001 212.768.0800 1 TPGARCHITECTURE.COM 41 IN CONSIDERATION OF RECEIVING DRAWINGS FROM TPG ARCHITECTURE LLP IN AN ELECTRONIC FORM, THE RECIPIENT AGREES, TO THE FULLEST EXTENT PERMITTED BY LAW, TO HOLD HARMLESS AND INDEMNIFY TPG ARCHITECTURE LLP FROM AND AGAINST ALL CLAIMS, LIABILITIES, LOSSES, DAMAGES, AND COSTS, INCLUDING BUT NOT LIMITED TO ATTORNEY'S FEES, ARISING OUT OF, OR IN ANY WAY CONNECTED WITH THE USE, RE -USE, MIS -USE, MODIFICATION, OR MISINTERPRETATION OF THE MACHINE-READABLE INFORMATION PROVIDED BY TPG ARCHITECTURE LLP UNDER THIS AGREEMENT. PROJECT SOUTH WINDSOR BUCKLAND 190 BUCKLAND ROAD SOUTH WINDSOR, CT 06074 DRAWING NAME ROOF ELECTRICAL PLAN SEAL DATE 06.13.2019 PROJECT NO. 8303.58 SCALE 1 ,ll = 1 1-011 DRAWN BY MDM DOB PAGE . CHECKED BY XX - OF - DWG NO. E -31 0 2`,00 DOB NO. CHASE � PANEL'PP1' GROUND BUS Not to Scale BUS A/B/C NOTES 1, CONNECT SPD TO BREAKER AS FOLLOWS: 2P30 FOR 1 PHASE 3P30 FOR 3 PHASE 2. RELOCATE BREAKER IN PANEL AS NECESSARY TO PROVIDE THE SHORTEST WIRE LENGTH TO SPD. 3. DIRECT CONNECTION TO BUS IS NOT PERMITTED. 4. USE A CHASE NIPPLE CONNECTION VIA KNOCKOUT. 5. USE #10 AWG OR LARGER CONDUCTORS. 6. LIMIT WIRE LENGTH TO 18" OR LESS. 7. KEEP WIRE FREE OF ANY SHARP BENDS. 8. SPD TO BE MODULAR, UL 1449 3RD EDITION LISTED. 9. 100 KA PER PHASE, 600V CLAMPING. 10. SPD TO BE AS MANUFACTURED BY SURGE SUPPRESSION INC, OR APPROVED EQUAL. MODEL NUMBER AS FOLLOWS: 120/208V, 3 PHASE-#SKLB-3Y1-87 277/480V, 3 PHASE - #SKLB-3Y2-87 120/208V,1 PHASE - #SKLB-1 S1 -87 CARD READER CONTROLLER POWER DOOR OPERATOR DOORACTIVATION LOCK STRIKE INPUT POWER OUTPUT DPDT ^(+) RELAY OUTPUT RELAY a_ _, ( ) F CARD j I SPLICE I READER I 1 I I I I ELECTRIC iLUI STRIKE I cU I j ENTER EXIT I I i PUSH PLATE PUSH PLATE 1 iI t l I I I I I I I I I I I i I I I I I I I I j I DAYTIME CARD I j I I READER OVER -RIDE i I j KEY SWITCH I I i I IL------------ ------------------� i ---------------------------------� 7 SYSTEM OPERATION 1. POWER DOOR OPERATOR PROVIDES POWER TO ELECTRIC STRIKE TO ENSURE STRIKE IS UNLOCKED PRIOR TO DOOR OPERATION. 2. STRIKE IS POWERED BY BOTH CARD READER AND DOOR OPERATOR TO RETRACT STRIKE FOR MANUAL OR AUTOMATIC DOOR OPERATION. 3. FOR AFTER-HOURS PUSH PLATE ENTRY, THE PUSH PLATE MUST BE ACTIVATED DURING THE CARD READER DELAY TIME PERIOD (4-5 SECONDS). 4. DURING BUSINESS HOURS, THE KEY SWITCH IS TURNED TO "UNLOCKED"/GREEN, CLOSING THE CIRCUIT AND BYPASSING THE CARD READER, ALLOWING POWER OPERATOR TO BE USED WITH PUSH PLATE ONLY. AFTER HOURS, KEY SWITCH IS TURNED TO "LOCKED`YRED (AS SHOWN), OPENING THE CIRCUIT AND REQUIRING USE OF THE CARD READER TO ACTIVATE THE DOOR. 5. THE EXIT PUSH PLATE OPENS THE DOOR FOR EXITING, REGARDLESS OF CARD READER USE OR KEY SWITCH POSITION. 1'- - n r� \ 1 I ' n _ I a , '� I' I I 1 - J' ► L t I � GROUNDING ELECTRODE (BUILDING STEEL) GROUNDING ELECTRODE (U.G. METAL PIPE) Not BONDING JUMPER "ER WITH JUMPER SERVICE EQUIPMENT ENCLOSURE 0 0�.O.On o.O'a on.0 o,•nY0 O _ -... �` vo u. _,"° GROUNDING ELECTRODE (RE -BARS) BOND TO ENCLOSURE GROUNDING ELECTRODE CONDUCTOR NEUTRALBUS 2 POWER DOOR OPERATOR DOOR ACTIVATION LOCK STRIKE TERMINALS POWER OUTPUT RELAY 21 (+)O--O (-)� o o� T6 0019 ENTER EXIT PUSH PLATE PUSH PLATE AFTER-HOURS HOLD OPEN OPERATOR �� CONTROL REMOTE AUTO® KEY SWITCH O OUTER DOOR INNER DOOR PANEL LOCKS KEYED ALIKE F1 ALL PANELS SYSTEM OPERATION 1. POWER DOOR OPERATOR PROVIDES POWER TO ELECTRIC STRIKE TO ENSURE STRIKE IS UNLOCKED PRIOR TO DOOR OPERATION. 2. THE "ENTER" PUSH PLATE AT THE VESTIBULE SIDE OF THE VESTIBULE DOOR AND THE "EXIT" PUSH PLATE IN THE LOBBY ACTIVATE THE VESTIBULE DOOR OPERATOR. 3. DURING BUSINESS HOURS, KEY SWITCH IS TURNED TO "AUTO", CLOSING THE CIRCUIT AND ALLOWING BOTH PUSH PLATES TO TRIGGER THE OPERATOR. 4. AFTER BUSINESS HOURS, KEY SWITCH IS TURNED TO "OFF" (AS SHOWN), OPENING THE CIRCUIT AND DISABLING THE POWER OPERATOR TO PREVENT DAMAGE WHILE THE DOOR IS LOCKED. OIL PANEL IDENTIFICATION LABEL DOOR HINGE (TYP) FASTENING SCREW (TYP FOR ALL) PANEL TRIM F - I1H EL D �ti0' W'F r=i 1j1 O %—]_M-00OR cll 4 ,/i'I 11'' %t�, I KEY NOTES: 1� #8 Cu AWG #1/0 Cu AWG 1/4"X4"X24 (MIN)" COPPER GROUND BAR WITH WALL MOUNTING BRACKETS AND INSULATORS J 0 0 0 0 0 r� 0 ERICO (ERITECH) TMGB-A141-15PT OR EQUAL. TO BE PROVIDED BY ELECTRICAL CONTRACTOR �rR01UJI ADO M2 BU3IOA I0 al, 7AFL i� -Al Not scale BRANCH CIRCUIT BREAKER IN PANEL BOARD. UNSWITCH'HO T LINE' TO MAINTAIN EMERGENCY BATTERY CHARGE'ON' LOCAL LIGHT SWITCH (IF REQUIRED) r--- - - - - - - - - - - \O I I ANY CONTROL EM I OR TIME -CLOCK, SENSOR, RELAY CONTACT. NORMAL LIGHTING FIXTURES SWITCHED EMERGENCY LIGHTING FIXTURE. SWITCHED EMERGENMEM' LIGHTING FIXTURE WIRING DIAGRAM NTS NOTES: 1. FOR SWITCHED EMERGENCY LIGHTING FIXTURES DENOTED BY "EM", ELECTRICAL CONTRACTOR SHALL PROVIDE AN ADDITIONAL UNSWITCHED WIRE FROM SAME CIRCUIT SERVING FIXTURE AND CONNECT IT TO LINE SIDE OF EMERGENCY BALLAST/DRIVER. SW IT CHED REEMCT U MR ��� ���J� ��� 9 Not to Scale DRILLED HOLE 3/8" NUT, BOLT, LOCKWASHER GROUND CABLE 7/16" DIAMET AND CABLE TERMINAL ASSEMBLY 3" 3" 3" I I I I 4" 1 2" I 411- - FASTENER, 3'-O" BAR LENGTH AS REQUIRED; ON CENTER, 1/4" THICK COPPER MIN. TW BOLTED TO STRUCTU STEEL COLUMN L OCz,' L COFFER GROUND BAR 6` of m Scale RIVEngineeiing D.P.C./we engineer success 116 West 32nd Street,12th Floor, New York, N.Y. 10001 P 212.643.9055 F 212.643.0503 www.mgedpc.net MG ENGINEERING, P.C. 116 W 32ND STREET, 12TH FLOOR, NEW YORK, NY 10001 T. 212.643.9055 1 WWW.MGEDPC.NET Severed Azs-sodates SEVERUD ASSOCIATES CONSULTING ENGINEERS, PC 469 SEVENTH AVENUE - SUITE 900, NEW YORK, NY 10018 T.212.986.37001 WWW.SEVERUD.COM II # ISSUANCE DATE l ISSUED FOR BID 06-25-2019 ISSUED FOR BID 06-15-2019 f II �Z3i I I TPG ARCHITECTURE, LLP 31 PENN PLAZA 132 WEST 31ST STREET, 5TH FLOOR, NEW YORK, NY 10001 212.768.0800 1 TPGARCHITECTURE.COM IN CONSIDERATION OF RECEIVING DRAWINGS FROM TPG ARCHITECTURE LLP IN AN ELECTRONIC FORM, THE RECIPIENT AGREES, TO THE FULLEST EXTENT I �1 PERMITTED BY LAW, TO HOLD HARMLESS AND INDEMNIFY TPG ARCHITECTURE 1 LLP FROM AND AGAINST ALL CLAIMS, LIABILITIES, LOSSES, DAMAGES, AND (II COSTS, INCLUDING BUT NOT LIMITED TO ATTORNEY'S FEES, ARISING OUT OF, �I OR IN ANY WAY CONNECTED WITH THE USE, RE -USE, MIS -USE, MODIFICATION, I� OR MISINTERPRETATION OF THE MACHINE-READABLE INFORMATION PROVIDED BY TPG ARCHITECTURE LLP UNDER THIS AGREEMENT. PROJECT SOUTH 10fiNDSOR BUCKLAND 190 DUCKLAND ROAD SOUTH WINDSOR, CT 06074 DRAWING NAME ELECTRICAL DETAILS SHEET 1 SEAL DATE 06.13.2019 PROJECT NO. 8303.58 SCALE N.I.S. I DRAWN BY MDM CHECKED BY XX DOB PAGE -OF- DWG NO. E - 5 1.00 DOB NO. CHASE ! j 4 5" A ;Mnlill _tea ■lk li, ■ I AkVVAKNINU Arc Flash and Shock Hazard 3-1I/2" I Appropriate PPE Required uo not operate controls or open covers without appropriate personal protection equipment. Failure to comply may result in injury or death. Refer to NFPA 70E for minimum PPE requirements. NOTES: 1. PROVIDE GENERIC ARC -FLASH LABELS AS SHOWN ON ALL ELECTRIC LOAD CENTERS, PANELBOARDS, SWITCHBOARDS, SWITCHGEAR, MOTOR CONTROLLERS, VFDS, ATS, ENCLOSED SWITCHES AND CIRCUIT BREAKERS, CONTROL PANELS, SPLICE BOXES AND ALL OTHER ELECTRICAL SERVICE & DISTRIBUTION EQUIPMENT. 2. LABELS TO COMPLY WITH NFPA 70, NFPA 70E, 29 CFR 1910.144, 29 CFR 1910.145 (OSHA) AND ANSI Z535 (COLORS, SYMBOLS, ETC.) 3. LABELS SHALL BE SELF-ADHESIVE, POLYESTER OR VINYL FILM LABELS; PREPRINTED, 6-MIL-THICK, FLEXIBLE LABEL LAMINATED WITH A CLEAR, WEATHERPROOF, UV -RESISTANT, CHEMICAL RESISTANT COATING. MINIMUM LETTER HEIGHT SHALL BE 3/8 INCH. 4. INSTALL IDENTIFICATION MATERIALS AND DEVICES AT LOCATIONS FOR MOST CONVENIENT VIEWING WITHOUT INTERFERENCE WITH OPERATION AND MAINTENANCE OF EQUIPMENT. APPLY TO EXTERIOR OF DOOR, COVER, OR OTHER ACCESS. n rR rr- n n n n n n /A __i7 n -) r-=,, n n ram, F= n Mot io Scale 3/4" CONDUIT STUB W/ 12005A CIRCUIT TO IRRIGATION CONTROLLER SERVICE SWITCHES ABOVE SUSPENDED CEILING FOR CUSTOM PROJECTS WITH MULTIPLE ALARMED DOORS, SIZE POWER SUPPLY TO SERVE ALL DOORS AND INSTALL IN A CENTRAL BACK -OH -HOUSE ROOM J TO POWER DIST. PANEL J DOOR ALARM POWER SUPPLY ABOVE FIN. CEILING OVER DOOR- REFER TO DOOR HARDWARE SCHED.; COORD. W/ DOOR AND \ � � HARDWARE VENDOR(S) 314" CONDUIT TO CENTER DOOR HINGE FOR POWER TRANSFER HINGE CONNECTION BY DOOR HARDWARE INSTALLER- COORDINATE CONDUIT HEIGHT A.F.F. W/ DOOR FRAME INSTALLER POWER TRANSFER HINGE BY DOOR HARDWARE INSTALLER I i Not to Scale -- — _-- 2 (1) 3/4" CONDUIT FOR POWER (1) 1-1/4" CONDUIT FOR TELECOMMUNICATION (1) 1-114" CONDUIT FOR AUDIOVISUAL NOTES: ZS) FLOOR SLAB 1. EXACT LOCATION OF CONDUIT PENETRATIONS TO BE COORDINATED WITH ARCHITECT. ram, /A F�) 117,\ r7an r— n, nnnr_r=' ,r\ r�FP, r\ 1� /I"IV—)nr\n r_'�l, -ten Rn - - j'� r,- v I,� i--r r,.\ 'i/r,' I k:u�llry -•:I i �ii' � L=-' � i UL� h U L=� L) l! i� u ��J �/1J uv G-� li\i U r� L /-'� !J L��a Lv a L) 1� 6'-`;1 U L- Mo€ o Scale + Na m Scale PROJECTS EXCEPT THOSE WITH WOOD LINTELS: FLEX. CONDUIT WHIP THROUGH LINTEL AND FINISHED WINDOW HEAD TO SHADE HOUSING POWER DISCONNECT SWITCH CONCEALED ADnXIC rCn INN FINISH uvwl l ALL CONDUIT CONCEALED BEHIND WALL FINISHES II PROJECTS WITH WOOD LINTELS: FLEX. CONDUIT TO JUNCTION BOX RECESSED ABOVE FINISHED R _ WINDOW HEAD POWER OPERATED WINDOW SHADE - REFER TO PLAN FOR LOCATIONS ALUMINUM AND GLASS STOREFRONT FRAMING SYSTEM WINDOW GYPSUM BOARD INTERIOR FINISH AND WINDOW JAMB SOLID SURFACE STOOL WITH REVEAL BELOW ELECTRICAL SERVICE TO SHADE MOTOR REQUIRED AT RIGHT SIDE OF WINDOW OPENING AS VIEWED FROM THE BUILDING INTERIOR C !+/lwlnl IlT \AriTl 1 1 1/1f1nr1"L 1 %AflP msw T/ r1 rl+ Ml/ P AKfI l (1) 3/4" CONDUIT FOR POWER NOTES: FLOOR SLAB ILEX RECEPTACLE 1. EXACT LOCATION OF CONDUIT PENETRATIONS TO BE COORDINATED WITH ARCHITECT. V n nM.9R[\17-� n�l�f'1:-i F=n NO \� H� I wi y.l t� +"' IJ U' +��,{Iv ,IMF -.> ! :a t;. \; r. li" i`✓'' i�-�� h L JEU\,U L��Jt�t�tl 1 LI-�JLJh� ,DU'II� CONDUI ESISTANCE RATED WALL UL LISTED FIRE -STOPPING ASSEMBLY SLEEVE CONDUIT PENETRATION THRU FIRE RATED WALL Not to Scale =MGE MT� AIDEngineering D.P.C.1 we engineer success 116 West 32nd Street,12th Floor, New York, N.Y. 10001 P 212.643.9055 F 212.643.0503 www.mgedpc.net MG ENGINEERMG, P.C. 116 W 32MID STREET, 12TH FLOOR, NEW YORK, NY 10001 T. 212.643.9055 1 WWW.MGEDPC.NET ./1' J ;f # 4. dti sA VU1 J 11 U. SLVE:C2,CUIU ASSOCIATES CONSULTING ENGENEEE S, GEC 469 SEVENTH AVENUE - SUITE 900, NEW YORK, MY 1001 US T.212.986.37001 WWW.SEVERUD.COM # I ISSUANCE I DATE 1 I ISSUED FORBID 1 06-28-2019 1 I ISSUED FOR DID 1 08-15-2019 1 TPG\rchitecture TPG ARCHITECTURE, LLP 31 PENN PLAZA 132 WEST 31ST STREET, 5TH FLOOR, NEW YORK, NY 10001 212.768.0800 1 TPGARCHITECTURE.COM IN CONSIDERATION OF RECEIVING DRAWINGS FROM TPG ARCHITECTURE LLP IN AN ELECTRONIC FORM, THE RECIPIENT AGREES, TO THE FULLEST EXTENT PERMITTED BY LAW, TO HOLD HARMLESS AND INDEMNIFY TPG ARCHITECTURE LLP FROM AND AGAINST ALL CLAIMS, LIABILITIES, LOSSES, DAMAGES, AND COSTS, INCLUDING BUT NOT LIMITED TO ATTORNEY'S FEES, ARISING OUT OF, OR IN ANY WAY CONNECTED WITH THE USE, RE -USE, MIS -USE, MODIFICATION, OR MISINTERPRETATION OF THE MACHINE-READABLE INFORMATION PROVIDED BY TPG ARCHITECTURE LLP UNDER THIS AGREEMENT. 111 14111xo1I DRAWING NAME I� ELECTRICAL DETAILS SHEET 2 SEAL DATE 06.13.2019 non Ir_rr nun 17 1 IIVJLU 1 IVV. ql dU d.Lc SL IJaJ J aJ IJ I SCALE N.T.S. DRAWN BY MDM DOB PAGE CHECKED BY XX - OF - DING NO. - . 0 0" DOB NO. FIGURE 1: WGA100 (CAN BE USED WITHOUT SENSOR FOR SWITCHING LINE LOAD) FIGURE 4: 15A NON -LIGHTING LOAD CONFIGURATION Binary Input, (DIP Switch 4 or DIP Switch 5 On) Switched Line Voltage Load Relay (Binary Output, DIP Switch 1 On) White Neutral Black Hot 120-277VAC Ir White Neutral Line II I d vvucl9rED Wirin 14A G witched Load 7VAC Low Voltage Wiring �ae;a a.eY w—rn„ y---- °� 22AWG Cap WUA100 o unused ,� w.nx.ow WIreS Digital (binary) Sensor. 24VDC in RED 24 VDC Power Output Leak detection sensor Common BLACK Ground/Common Control Out BLUE Binary Input (active high, enabled with DIP YELLOW Binary Input (active hiah. enabled FIGURE 2: LIGHTING CIRCUIT CONTROL Switching a 20A Branch Circuit, Load limit 15A: This configuration allows the WA100-PM to to provide On/Off Switching Of a brash Circuit. WHITE Neutral DIP Switches Ballast Type: Wired OFF -- BLACK Hot 120-277VAC On/Off+ 0-10V Sensor. a _ON dimming #4 ON None Line Voltage Wires Perform Installation Test Suite 1 01 O Low Voltage FOE C, Wires " ' ,hh,uv.N.Lvorka Na. 5 �OTn" '. Relo, wwc col WA 100- P M Cap Unused OWires Fxnaooru,. o++r ,y,• o..arywauo, � ,w+wtwao J-Box or Equivalent OI l0 Switched Hot Neutral I Brach Circuit FIGURE 3A: MULTI POLE CONTACTOR CONFIGURATION FOR LIGHTING WITH WA100-PM This configuration allows the WA100-PM to provide On/Off switching Control to an external contactor. Driver type: DIP Switches Wired OFF—. On/Off (no dimming) MR Sensor e _ (#4 ON) None ON WHITE Neutral Perform Installation Test Suite 1 BLACK Hot 120-277VAC Low Voltage ® Wires o.uw«r,.t.erp..+ maw 4 Neutral Wg100-PM Cap Unused O Wires Black Hot 120-277VAC \ Li^� V:2��k Low Voltage ®Wiring ? "° 22AWG WntmN. —ft Ca unused °�IVGA100 op�� wires 120-277VAC Hot Switched line voltage Neutral Power Outlet, 7 Pump, Motor, etc. I 15A/1hp maximum I FIGURE 5: WA100-PM DIMMING CONFIGURATION DIP Switches Wired OFF— ® Sensor. �_oN (all OFF) None Perform Installation Test Suite 1 WHITE Neutral BLACK Hot 120-277VAC\ Line Voltage Wires ;;: DaMImN.Iwo.Faa + a+a Low Voltage WA100-PM Wren O F>4tlovW»Onrf 1S4� rr�.Q.,-`a) RED Switched Load 120-277VAC GRAY I(-) GRAY Analog Ground Hot Dimming Ballast Neutral or LED Driver VIOLET + VIOLET 0-10V Analog Output(dimming control (0-10 VDC) Hot Dimming Ballast GRAY (-) Cap Unused Wires or LED Ddver Neutral (0-10 VDC) VIOLET + 0-10v Dimming output SmA available \V Up to 10 LED drivers or fluorescent ballasts typical, the chance of low voltage errors increases with more. FIGURE 6: WA100-PM DIMMING CONFIGURATION FOR EMERGENCY ZONES USING SHUNT RELAY RRU-X-UNV EMERGENCY Hot 120-277VAC `tea I WA100-PM -Vz Line Voltage Supply Hots EMERGENCY Hots Neutral Control Input Control Input JL C EMERGENCY Hot Neutral 3L2 5 3 714 Dimming Ballasts ri11-10 0101 or LED Drivers CONTACTOR (0-10 VDC) (120 or 277VAC Coil Voltage) (19 — 0.n 2T1 4T2 5T3 8T4 Load Outputs (Hot) FIGURE 3B: MULTI POLE CONTACTOR CONFIGURATION FOR RECEPTACLE CONTROL WITH WGA100 This configuration allows the WGA100 to provide On/Off switching control to an external contactor. Driver type: DIP Switches Wired OFF On/Off (no dimming) ffim Sensor. _ON (#4 ON) None WHITE Neutral Perform Installation Test Suite 1 BLACK Hot 120-277VAC ® Low Voltage Wires DaleftwNetworlo: IMe to fty.Y r aF.Y a Neutral .5 w„e 0 Cap Unused WGA100 O Wires mmau..ory +a++ pw.w,so, Control Input Hot CONTACTOR Control Input Neutral Load Outputs (Hot) Line Voltage Supply Hots VIOLET 0-10V Yellow NC Blue COM Brown (-Ao OFF) N/O r EGULAR #2 Neutral RRU-X-UNV Driver Type: DIP Switches Wired y0-1 ® red OFF a —ON dimming 10V Sensor. dimming (all OFF) Perform Installation Test Suite 1 FIGURE 7: WA100-PM WITH EXTERIOR PHOTOCELL REGULAR #1 Hot 120-277VAC Dimming Light Fixture(s), Photosensor configuration: This configuration allows the WA100-PM to provide automatic 0-10V dimming control and to switch light fixtures On/Off. DIP Switches WHITE Neutral Driver. Wired oFF— On/Off+ 0-10V ® Sensor, _ dimming (#g ON) None —ON BLACK Hot 120-277VAC Perform Installation Test Suite 8 Line voltage Low Voltage Wires Q+ C,�,� . Wires "� DaM6eeNelwoltep, � �N+m+n,l ,� ftWY v M1yrbl Cap Unused WA100-PM +z.A w.w+roco,p.. :DKo Wires Fa Ygoor the Q'H 15A+{ r+..+aro.+or+s, tn� +,m+w+wao RED Switched Load 120-277VAC Q Hot GRAY (-) * GRAY Analog Ground Dimming Ballast VIOLET (+) VIOLET 0-10V Analog Output (dimming control) Neutral or LED Driver ,t (0.10 VDC) 24V in RED 24VDC Power Outpul GRAY (-) 24VDC BLACK Digital Ground Hot Dimming Ballast Photosensor Common or LED Drive VIOLET (+) 0-10V Output Control Out ORANGE 0-10V Analog Input Neutral (0.10VDC) * 0-10V Dimming output 5 mA available Up to 10 LED drivers or fluorescent ballasts typical, the chance of low voltage errors increases with more. FIGURE 8: WSA10 FOR TEMPERATURE SENSORS AND CTS 0-10V Sensors Sensor 2 DC Power Thermistor. Supply 1 OK Type 2 (x1) Cable 24VDC :able Shield OV NTC4+�.�°e Thermistm Input Nrc, Thermistor Input NTC 4 - Input 204V ACfDC Current 10 mA NTC 1- '—J 0-10V IN 1 (Matog lnp,a) Min 0.10V IN 2 (Analog Input) GND(Reference Ground) Internal Battery Bacimp: AA 36V U-SOC12 NTC 2+ Temperature: 32 F to 122 F (0 C to 50 C) Triennial" Input VOro Gage: 2418 AWG NTC 2- DO NOT OPEN DEVICE Thorrni r NTC 3+ L—V 24 v AC1DC+ InputPo+nwr Daintree 1npit NTC3- 6 O Drain Wine z4vAcmA Networks Rat 0 O O O CHASE Thermistor. 10K Type 2 (x3) Cable AIGE ` fti�ra,"►t�l±a►7,r Drr(1E;Rt[1tA=hcsiimgaf,gmmAc3 116 West 32nd StreK 121h FbM NOW YOFK N-Y.10001 P 212.643.90M 1F71 08M ulmWMmgsdp=Wt MG ENGINEERING, P.C. Shield & Drain wile 116 W 32ND STREET, 12TH FLOOR, NEW YORK, NY 10001 T. 212.643.9055 1 WWW.MGEDPC.NET FIGURE 9A: WA100-PM WITH POWER PACK FOR RECEPTACLE CONTROL WA100-PM for control of 20A receptacle circuit. DIP Switches Ballast Type: Wired oFF— On/Off + 0-10V ® Sensor. dimming (#2,4 ON) None ON WHITE Neutral _ Perform Installation Test Suite 1 BLACK Hot 120-277VAC Line Voltage Wires O �;eo c 0 0 o Daintm*Netwaft ��^ Low Voltage N,+ele,sAdepler Relay RIodNu, �NA,00 oww.%w.+, WA1(l(1_Pnn Wires .,wFw...o waKratwaq else RED Switched Load wA'ro 120-277VAC O n Powerpack Hot Hot Control Input RED 24VDC Power j Controlled Receptacle Switched Hot T (Common) GREEN Digital Output LSD or Receptacle Circuit Powerpack Neutral BZ200 Cap 24VDC Output (Unused) Power Pack FIGURE 9B: WA100-PM WITH POWER PACK FOR RECEPTACLE CONTROL a+...f ,J Aay. UU SEVERUD ASSOCIATES CONSULTING ENGINEERS, PC 469 SEVENTH AVENUE - SUITE 900, NEW YORK, NY 10018 T.212.986.37001 WWW.SEVERUD.COM WA100-PM for control of 20A receptacle circuit. DIP Switches Ballast Type: ) Wired oFF--6 � — On/Off + 0-10V ® Sensor. dimming (#2,3 ON) None °N WHITE Neutral # ISSUANCE DATE Perform Installation Test Suite 1 BLACK Hot 120-277VA9TO LIGHTING PANEL ISSUED FOR BID 06-28-2019 Line Voltage Wires ® ISSUED FOR BID 08-15-2019 ay.mprnn �'DalntreeNelwgq,• ,a„e1� YMwlaw>wn1 ow Voltage rwwoerwAAio�°`�,wa> WA100-PM Wires era tawm) O i end—w.a 15A+4 rawelaia.+wtm) --..s.+..u..ew eras RED Switched Load — l�nnw.gaoae,aoxzm000 wA,ro a.rabwn ADDENDUM #1 09-09-2019 120-277VAC Q2 BULLETIN #2 03-30-2020 Hot GRAY I(-) GRAY Analog Ground Dimming Ballast VIOLET (+) Neutral or LED Driver (0-10 VDC) Hot Dimming Ballast or LED Driver VIOLET {+) Neutral (o-lovoc) TPG\rchitecture TPG ARCHITECTURE, LLP BLACK Hot 120-277VAC Powerpack Hot 31 PENN PLAZA 132 WEST 31ST STREET, 5TH FLOOR, NEW YORK, NY 10001 TO POWER PANEL Hot 212.768.0800 1 TPGARCHITECTURE.COM Control Input WHITE Neutral C21led Receptacle Switched Hot RED 24VDC Power IN CONSIDERATION OF RECEIVING DRAWINGS FROM TPG ARCHITECTURE LLP IN eptacle circuit (Co"mO") AN ELECTRONIC FORM, THE RECIPIENT AGREES, TO THE FULLEST EXTENT PERMITTED BY LAW, TO HOLD HARMLESS AND INDEMNIFY TPG ARCHITECTURE Powerpack Neutral BZ200 Cap 24VDC output (Unused) GREEN Digital Output LSD LLP FROM AND AGAINST ALL CLAIMS, LIABILITIES, LOSSES, DAMAGES, AND Power Pack COSTS, INCLUDING BUT NOT LIMITED TO ATTORNEY'S FEES, ARISING OUT OF, OR IN ANY WAY CONNECTED WITH THE USE, RE -USE, MIS -USE, MODIFICATION, OR MISINTERPRETATION OF THE MACHINE-READABLE INFORMATION PROVIDED FIGURE 10: ELWMLV/TRIAC DIMMING WITH WA100-PM FOR ON/OFF CONTROL BY TPG ARCHITECTURE LLP UNDER THIS AGREEMENT. PROJECT Driver type: DIP Switches Wired oFF-. SOUTH WINDSOR BUCKLAND This configuration allows the WA100-PM to provide automatic On/Off (no dimming) ® Sensor. a _ON 190 B U C KLAN D ROAD On/Off switching of light fixtures and local line dimmer to provide (#4 ON) None non -networked dimming. SOUTH WINDSOR, CT 06074 Perform Installation Test Suite 1 WHITE Neutral BLACK Hot120-277VAC DRAWING NAME ELECTRICAL DETAILS Line Voltage LOW Voltage wires ® Wires SHEET 4 Dae,tr..N.lwoitat w.""eF, l4M A awaw'0-wew"et°igoo" u.,w a++r a...ww.0 Cap Unused ••�••c••� �wwcow.w DOWires i.........�- xtv. o..P� = 0* tse.. wrm,aq RED Switched Load 120.277VAC SEAL DATE Q6.13.2019 ELV, MLV or other non 0-1OV PROJECT NO. $303.58 manual dimmer SCALE N.T.S. Hot ENonV DRAWN BY MDM DOB PAGE CH KED 11 OF 13 12. 2 DWG NO. E-504.00 DOB NO. CHASE r m GRADE r----- I I I UT TRANS I— L — ---- L------- \: ®' vVVI\VIVIIL-Y V EXTERIOR WALL OF BUILDING ELECTRICAL PANEL AREA N.T.S. DATA ROOM CONTRACTOR SHALL COORDINATE WITH UTILITY COMPANY FOR ACQUIRING AVAILABLE FAULT CURRENT TO BUILDING SERVICE EQUIPMENT AND PROVIDE THIS INFORMATION ALONG WITH ANY OTHER NECESSARY INFORMATION TO ELECTRICAL DISTRIBUTION EQUIPMENT VENDOR. EQUIPMENT VENDOR SHALL SUBMIT WITH EQUIPMENT SUBMITTALS SHORT CIRCUIT CALCULATIONS THAT CONFIRM PANEL AIC RATING IS APPROPRIATE FOR PROJECT LOCATION. 9 r`nNTD AnTnO CJAI I IAInCIV IAIITU 1ITII ITV I"MADANVIQ M Cr%TDIr`AI QCDVIr`C IAIQTAI I ATlnhl G. VVIV I IXM%j 1 UP, ♦ I InLL VVVI\I\ VVI I I IV I ILI I 1 VVIVII n1Y 1 J "[ L" e I INt1 nL JL.1\V II L IIYV 1/1LLn 11 VIV SPECIFICATIONS AND REQUIREMENTS FOR ALL WORK ON LINE SIDE OF ELECTRICAL SERVICE METER. KEY NOTES: 1 INLINE METER SOCKET AND CT CABINET, 400 AMP, 120/208 VOLT, 3 PHASE, 4 WIRE, NEMA 3R. COORDINATE REQUIREMENTS WITH LOCAL UTILITY. INCLUDE ALL COSTS IN BASE BID. PROVIDE NEMA 3R, MANUAL TRANSFER SWITCH WITH LOCKING GENERATOR CONNECTION ENCLOSURE, AND INTEGRAL CABLE CAM -LOCK CONNECTION BAY. ELS STORM SWITCH #SSD4A000400C-208-311-S-S-304089VSCH OR APPROVED EQUAL. SWITCH SHALL BE PROVIDED WITH INTEGRAL 400A CIRCUIT BREAKERS FOR UTILITY AND GENERATOR INPUTS RATED PER UTILITY. SUSE RATED. UL 1008 LISTED. BOND SERVICE N-G WITHIN ENCLOSURE. MOUNT ON H-FRAME SUPPORT STRUCTURE. REFER TO SHEET E-003 FOR PROPOSED LOCATION. INCLUDE ALL COSTS IN BASE BID. ONCE PERMANENT POWER IS CONNECTED, BUT PRIOR TO TURN OVER TO OWNER, GC SHALL COORDINATE WITH CHASE FACILITIES TO TEST FUNCTIONALITY OF MANUAL TRANSFER SWITCH. GC SHALL PROVIDE A GENERATOR TO PERFORM THIS TEST. 3® COORDINATE WITH UTILITY COMPANY FOR EXACT ROUTING, STUB -UP LOCATION, AND DELINEATION OF WORK. STAKE CONDUIT END LOCATION FOR UTILITY COMPANY. ALL UNDERGROUND INSTALLATIONS SHALL COMPLY WITH ARTICLE 300.5 OF THE NEC. &IGE MEnaineerina D.P.C./we enaineersuccess ___ _..V._._-_--_---- 116 West 32nd Street,12th Floor, New York, N.Y.10001 P 212.643.9055 F 212.643.0503 www.mgedpc.net MG ENGINEERING, E.C. 116 W 32ND STREET,12TH FLOOR, NEW YORK, HY 10001 T. 212.643.9055 1 WWW.MGEDPC.NET SE-werud A'Ssociatec-, SEVERUD ASSOCIATES CONSULTING ENGINEERS, PC 469 SEVENTH AVENUE - SUITE 900, NEW YORK, NY 10018 T.212.986.37001 WWW.SEVERUD.COM # ISSUANCE DATE ISSUED FORBID 06-28-2019 ISSUED FOR BID 08-15-2019 f f 1 T P -V h'�'L 'c TPG ARCHITECTURE, LLP 31 PENN PLAZA 132 WEST 31ST STREET, 5TH FLOOR, NEW YORK, NY 10001 212.768.0800 1 TPGARCHITECTURE.COM IN CONSIDERATION OF RECEIVING DRAWINGS FROM TPG ARCHITECTURE LLP IN AN ELECTRONIC FORM, THE RECIPIENT AGREES, TO THE FULLEST EXTENT PERMITTED BY LAW, TO HOLD HARMLESS AND INDEMNIFY TPG ARCHITECTURE LLP FROM AND AGAINST ALL CLAIMS, LIABILITIES, LOSSES, DAMAGES, AND COSTS, INCLUDING BUT NOT LIMITED TO ATTORNEYS FEES, ARISING OUT OF, OR IN ANY WAY CONNECTED WITH THE USE, REUSE, MIS -USE, MODIFICATION, OR MISINTERPRETATION OF THE MACHINE-READABLE INFORMATION PROVIDED BY TPG ARCHITECTURE LLP UNDER THIS AGREEMENT. PROJECT SOUTH WINDSOR BUCKLAND 190 SUCKLAND ROAD SOUTH WINDSOR, CT 06074 DRAWING NAME ELECTRICAL RISER DIAGRAM SEAL DATE 06.13.2019 PROJECT NO. 8303.58 SCALE N.T.S. I� DRAWN BY MDM DOB PAGE CHECKED BY XX -OF- DWG NO. I E-601.uO DOB NO. I i �j C J J4✓ C wu�- �k 5 3 ua.'�.'., 'ua r ?.; U 1. ��L ' o n 2.9 kk Interior Lighting Compliance Certificate `3 Project Information Energy Code: 2015 IECC Project Title: South Windsor Buckland Project Type: New Construction Construction Site: Owner/Agent: Designer/Contractor: 190 Buckland Road MG Engineering D.P.C. South Windsor, CT 06074 116 W 32nd Street New York, NY 10001 Additional Efficiency Package(s) 212-643-9055 High efficiency HVAC. Systems that do not meet the performance requirement will be identified in the mechanical requirements checklist report. Allowed Interior Lighting Power A B C D Area Category Floor Area Allowed Allowed Watts (ft2) Watts / ft2 (B X C) 1-PCS 6 #114 (Common Space Types:Office - Enclosed) 180 1.11 200 2-Main Lobby and Living Room (Bank:Banking Activity Area) 1302 1.01 1315 3-Print/File Room (Common Space Types:Copy/Print Room) 154 0.72 111 4-Janitor's Closet (Common Space Types:Storage <50 sq.ft.) 38 1.24 47 5-Corridor #108 (Common Space Types: Corridor/Tra nsition <8 ft wide) 155 0.66 102 6-Men's Restroom (Common Space Types:Restrooms) 85 0.98 83 7-Women's Restroom (Common Space Types:Restrooms) 79 0.98 77 8-Lounge (Common Space Types:Lounge/Breakroom) 188 0.73 137 9-Data Room (Common Space Types:Computer Room) 86 1.71 147 10-Manual Transaction (Bank:Banking Activity Area) 135 1.01 136 18-Cash Room/LTOS (Bank:Banking Activity Area) 116 1.01 117 11-Equipment Room (Bank:Banking Activity Area) 100 1.01 101 12-Transaction Vestibule (Bank:Banking Activity Area) 196 1.01 198 13-Casual Meeting Space 1 #119 (Common Space 116 1.23 143 Types: Conference/Meeting/Multipu rpose) 14-PCS 2 #118 (Common Space Types:Office - Enclosed) 108 1.11 120 15-PCS 3 #117 (Common Space Types:Office - Enclosed) 180 1.11 200 16-PCS 4 #116 (Common Space Types:Office - Enclosed) 123 1.11 137 17-PCS 5 #115 (Common Space Types:Office - Enclosed) 124 1.11 138 Total Allowed Watts = 3509 Proposed Interior Lighting Power A 8 C D E Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast Lamps/ # of Fixture (C X D) Fixture Fixtures Watt. 1-PCS 6 #114 (Common Space Types:Office - Enclose LED 500: L-500: 6WFT " Linear LED: Other: 1 24 6 144 LED 402: L-402: LED Pendant: Other: 1 1 8 8 Project Title: South Windsor Buckland Report date: 06/28/19 Data filename: M:\8303-58\Calculations\Electrical\8303-58_ComCHECK.cck Page 1 of 10 �r:/IJ"���`u 1f56'a�+�� c'Jaj�Ft�4V lj atl 'Version �;'o.�o�So Exterior Lighting Compliance Certificate Project Information Energy Code: 2015 IECC Project Title: South Windsor Buckland Project Type: New Construction Exterior Lighting Zone 2 (Neighborhood business district) Construction Site: Owner/Agent: Designer/Contractor: 190 Buckland Road MG Engineering D.P.C. South Windsor, CT 06074 116 W 32nd Street New York, NY 10001 212-643-9055 Allowed Exterior Lighting Power A B C D E Area/Surface Category Quantity Allowed Tradable Allowed Watts Watts ! Unit Wattage (B X C) Drive -up Canopy (ATM/Night depository location) (c) 2 machines 90 No 360 Main Entrance (Main entry) 6 ft of door 20 Yes 120 Back Facade Wall (Illuminated area of facade wall or surface) 84 ft2 0.1 No 8 Back Entrance (Other door (not main entry)) 3 ft of door 20 Yes 60 Total Tradable Watts (a) = 180 Total Allowed Watts = 548 Total Allowed Supplemental Watts (b) = 600 (a) Wattage tradeoffs are only allowed between tradable areas/surfaces. (b) A supplemental allowance equal to 600 watts may be applied toward compliance of both non -tradable and tradable areas/surfaces. (c) ATM/Night depository sites have a base allowance of 180 W per site. Proposed Exterior Lighting Power A B C D E Fixture ID : Description / Lamp ! Wattage Per Lamp / Ballast Lamps/ # of Fixture (C X D) Fixture Fixtures Watt. Drive -up Canopy (ATM/Night , depository location 2 machines): Non -tradable Wattage LED 6A: L-6A: Exterior Semi -recessed LED: Other: 1 4 110 440 Main Entrance ( Main entry 6 ft of door width): Tradable Wattage LED 7: L-7: 4" LED Downlight: Other: 1 3 14 42 Back Facade Wall ( Illuminated area of facade wall or surface 84 1`1:2): Non -tradable Wattage LED 7: L-7: 4" LED Downlight: Other: 1 3 14 42 Back Entrance ( Other door (not main entry) 3 ft of door width): Tradable Wattage LED 21 B: L-21 B: Exterior Walt -Mounted LED: Other. 1 1 58 58 Total Tradable Proposed Watts = 100 Project Title: South Windsor Buckland Report date: 06/28/19 Data filename: M:\8303-58\Calculations\Electrical\8303-58_ComCHECK.cck Page 4 of 10 A Fixture ID : Description / Lamp / Wattage Per Lamp ! Ballast B Lamps/ Fixture C # of Fixtures D Fixture Wait. E (C X D) 2-Main Lobby and Living Room (Bank:Banking Activity ctivi , Area) LED 500: L-500: 6WFT " Linear LED: Other: 1 75 6 450 LED 405: L-405: Decorative Pendant: Other: 1 3 40 120 LED 308: L-308: Blue Strip LED: Other: 1 66 6 396 LED 11: L-11: 4" LED Downlight: Other: 1 15 14 210 LED 307: L-307: LED Strip: Other: 1 32 6 192 3-Print/File Room (Common Space Types:Copy/Print Room) LED 2: L-2: 2'x2' Recessed Lensed Troffer: Other: 1 2 34 68 4-Janitor's Closet (Common Space Types:Storage <50 sq.ft.) LED 22: L-22: Lensed Utility LED: Other: 1 1 18 18 5-Corridor #108 (Common Space Types: Corridor/Transition <8 ft wide) LED 500: L-500: 6WFT " Linear LED: Other: 1 12 6 72 6-Men's Restroom (Common Space Types:Restrooms) LED 2: L-2: 2'x2' Recessed Lensed Troffer: Other: 1 2 34 68 7-Women's Restroom (Common Space Types:Restrooms) LED 2: L-2: 2'x2' Recessed Lensed Troffer: Other: 1 2 34 68 8-Lounge (Common Space Types: Lounge/Breakroom) LED 22: L-22: Lensed Utility LED: Other: 1 1 18 18 LED 2: L-2: 2'x2' Recessed Lensed Troffer: Other: 1 3 34 102 9-Data Room (Common Space Types:Computer Room) LED 2: L-2: 2'x2' Recessed Lensed Troffer: Other: 1 2 34 68 10-Manual Transaction (Bank:Banking Activity Area) LED 11: L-11: 4" LED Downlight: Other: 1 4 14 56 LED 3: L-3: 15W/FT Undercabinet Linear LED: Other: 1 9 15 135 18-Cash Room/LTOS (Bank:Banking Activity Area) LED 3: L-3: 15W/FT Undercabinet Linear LED: Other: 1 5 15 75 LED 2: L-2: 2'x2' Recessed Lensed Troffer: Other: 1 2 34 68 11-Equipment Room (Bank:Banking Activity Area) LED 2: L-2: 2'x2' Recessed Lensed Troffer: Other: 1 2 34 68 12-Transaction Vestibule (Bank:Banking Activity Area) LED 500: L-500: 6WFT " Linear LED: Other: 1 15 6 90 13-Casual Meeting Space 1 #119 (Common Space Types:Conference/Meeting/q Multipurpose) LED 500: L-500: 6WFT " Linear LED: Other: 1 8 6 48 14-PCS 2 #118 (Common Space Types:Office - Enclosed) LED 500: L-500: 6WFT" Linear LED: Other: 1 8 6 48 LED 402: L-402: LED Pendant: Other: 1 1 8 8 15-PCS 3 #117 (Common Space Types:Office - Enclosed) LED 500: L-500: 6WFT " Linear LED: Other: 1 16 6 96 LED 402: L-402: LED Pendant: Other: 1 1 8 8 16-PCS 4 #116 (Common Space Types:Office - Enclosed) LED 402: L-402: LED Pendant: Other: 1 1 8 8 LED 500: L-500: 6WFT " Linear LED: Other: 1 8 6 48 17-PCS 5 #115 (Common Space Types:Office - Enclosed) LED 402: L-402: LED Pendant: Other: 1 1 8 8 LED 500: L-500: 6WFT " Linear LED: Other: 1 8 6 48 Total Proposed Watts = 2814 Interior Lighting Compliance Statement Compliance Statement,- The proposed interior lighting design represented in this document is consistent with the building plans, specifications, and other calculations submitted with this permit application. The proposed interior lighting systems have been designed to meet the 2015 IECC requirements in COMcheck Version 4.1.1.0 and to comply with any applicable mandatory requirements listed in the Inspection Checklist. Project Title: South Windsor Buckland Report date: 06/28/19 Data filename: M:\8303-58\Calculations\Electrical\8303-58_ComCHECK.cck Page 2 of 10 Exterior Lighting Compliance Statement Compliance Statement: The proposed exterior lighting design represented in this document is consistent with the building plans, specifications, and other calculations submitted with this permit application. The proposed exterior lighting systems have been designed to meet the 2015 IECC requirements in COMcheck Version 4.1.1.0 and to comply with any applicable mandatory requirements listed in the Inspection Checklist. Name - Signature Date Project Title: South Windsor Buckland Report date: 06/28/19 Data filename: M:\8303-58\Calculations\Electrical\8303-58_ComCHECK.cck Page 5 of 10 Name - Title Signature Project Title: South Windsor Buckland Data filename: M:\8303-58\Calculations\Electrical\8303-58_ComCHECK.cck Date Report date: 06/28/19 Page 3 of 10 DRAWING LIST DWG DRAWING TITLE EN-001 ENERGY ANALYSIS COMPLIANCE SHEET 1 EN-002 11 ENERGY ANALYSIS COMPLIANCE SHEET 2 CHASE CP AMEngineering D.P.C./we engineer success 116 West 32nd Street,12th Floor, New York, N.Y. 10001 P 212.643.9055 F 212.643.0503 www.mgedpc.net MG ENGINEERING, P.C. 116 W 32ND STREET, 12TH FLOOR, NEW YORK, NY 10001 T. 212.643.9055 1 WWW.MGEDPC.NET S(3verud Associates SEVERUD ASSOCIATES CONSULTING ENGINEERS, PC 469 SEVENTH AVENUE - SUITE 900, NEW YORK, NY 10018 T.212.986.37001 WWW.SEVERUD.COM # I ISSUANCE I DATE ISSUED FOR BID 06-28-2019 ISSUED FOR BID 08-15-2019 TPG\rchitecturen TPG ARCHITECTURE, LLP 31 PENN PLAZA 132 WEST 31ST STREET, 5TH FLOOR, NEW YORK, NY 10001 212.768.0800 1 TPGARCHITECTURE.COM IN CONSIDERATION OF RECEIVING DRAWINGS FROM TPG ARCHITECTURE LLP IN AN ELECTRONIC FORM, THE RECIPIENT AGREES, TO THE FULLEST EXTENT PERMITTED BY LAW, TO HOLD HARMLESS AND INDEMNIFY TPG ARCHITECTURE LLP FROM AND AGAINST ALL CLAIMS, LIABILITIES, LOSSES, DAMAGES, AND COSTS, INCLUDING BUT NOT LIMITED TO ATTORNEY'S FEES, ARISING OUT OF, OR IN ANY WAY CONNECTED WITH THE USE, RE -USE, MIS -USE, MODIFICATION, OR MISINTERPRETATION OF THE MACHINE-READABLE INFORMATION PROVIDED BY TPG ARCHITECTURE LLP UNDER THIS AGREEMENT. PROJECT SOUTH WINDSOR BUCKLAND 190 BUCKLAND ROAD SOUTH WINDSOR, CT 06074 DRAWING NAME ENERGY ANALYSIS COMPLIANCE SHEET 1 SEAL DATE 06.13.2019 PROJECT N0. 8303.58 SCALE N.T.S. DRAWN BY CDP CHECKED BY XX DOB PAGE 1 OF 2 DWG NO. EN-001.00 DOB NO. CHASE r Inspection Checklist Energy Code: 2015 IECC Requirements: 100.0% were addressed directly in the COMcheck software Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided. Section & R# ID Plan Review I Complies? I Comments/Assumptions - - — — --- C103.2 Plans, specifications, and/or ❑Complies Requirement will be met. [PR4]1 calculations provide all information []Does Not with which compliance can be determined for the interior lighting ❑Not Observable and electrical systems and equipment ❑Not Applicable ^7 document where exceptions to a11U UVI.UII1Clll VVIICIC Chl.epllVlls lV the standard are claimed. Information provided should include interior lighting power calculations, wattage of bulbs and ballasts, transformers and C103.2 [PR8]1 C406 [PR9]1 Plans, specifications, and/or ❑Complies calculations provide all information ❑Does Not with which compliance can be ❑Not Observable determined for the exterior lighting ❑Not Applicable and electrical systems and equipment and document where exceptions to the standard are claimed. Information provided should include exterior lighting power calculations, wattage of bulbs and ballasts, transformers and control devices. Plans, specifications, and/or ❑Complies calculations provide all information ❑Does Not with which compliance can be ❑Not Observable determined for the additional energy ❑Not efficiency packaae options. Applicable Additional Comments/Assumptions: Requirement will be met. Requirement will be met. 1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 13 'Low Impact (Tier 3) Project Title: South Windsor Buckland Data filename: MA8303-58\Calculations\Electrica1\8303-58 ComCHECK.cck Section # Final Inspection Complies? & Req.ID C303.3, Furnished O&M instructions for ❑Complies systems and equipment to the ❑Does Not IC408.2.5. 2 [FI17]3 building owner or designated representative. ❑Not Observable ❑Not Applicable C405.4.1 Interior installed lamp and fixture ❑Complies [FI18]1 lighting power is consistent with what ❑Does Not is shown on the approved lighting ❑Not Observable plans, demonstrating proposed watts ❑Not Applicable are less than or equal to allowed watts. C405.5.1 Exterior lighting power is consistent ❑Complies [FI1911 with what is shown on the approved []Does Not lighting plans, demonstrating proposed watts are less than or equal ❑Not Observable to allowed watts. ❑Not Applicable C408.2.5. Furnished as -built drawings for L-lComplies 1 electric power systems within 90 days ❑Does Not [FI16]' of system acceptance. ❑Not Observable []Not Applicable C408.3 Lighting systems have been tested to ❑Complies [FI3311 ensure proper calibration, adjustment, ❑Does Not programming, and operation. ❑Not Observable ❑Not Applicable Additional Comments/Assumptions: Report date: 06/28/19 Page 6 of 10 Comments/Assumptions Requirement will be met. See the Interior Lighting fixture schedule for values. See the Exterior Lighting fixture schedule for values. Requirement will be met. Requirement will be met. 1J High Impact (Tier 1) 2 Medium Impact (Tier 2) T3TLow Impact (Tier 3) Project Title: South Windsor Buckland Data filename: MA8303-58\Calculations\Electrica1\8303-58_ComCHECK.cck Report date: 06/28/19 Page 9 of 10 aca awn # Rough -in Electrical Inspection Complies? Comments/Assumptions & Re;.ID C405.2.1 Lighting controls installed to uniformly ❑Complies Exception: Areas such as security or emergency areas that [EL15]1 reduce the lighting load by at least []Does Not need continuous lighting. 50%. ❑Not Observable _ ❑Not Applicable ^ C405.2.I Occupancy sensors installed in ❑Complies Exception: Automatic -on controls are allowed in corridors, [EL18]1 required spaces. ❑Does Not stairways, restrooms, primary building entrance areas and ❑Not Observable lobbies, and areas where manual -on controls could impact ❑Not Applicable safety or security. C405.2.1, Independent lighting controls installed []Complies Exception: Areas such as security or emergency areas that C405.2.2, per approved lighting plans and all ❑Does Not need continuous lighting. `3 manual controls readily accessible and ❑Not Observable [EL23]2 visible to occupants. ❑Not Applicable C405.2.2. Automatic controls to shut off all ❑Complies Exception: Areas such as security or emergency areas that I1 building lighting installed in all ❑Does Not need continuous lighting. [Fi 2212 hliiiIriingc, ❑Not Observable ❑Not Applicable C405.2.3 Daylight zones provided with ❑Complies Requirement will be met. [EL16]2 individual controls that control the []Does Not lights independent of general area ❑ Not Observable lighting. ❑Not Applicable C405.2.3, Primary sidelighted areas are ❑Complies Requirement will be met. C405.2.3. equipped with required lighting ❑Does Not 11, C405.2.3. controls. ❑ Not Observable 2 ❑Not Applicable [EL20]1 C405.2.3, Enclosed spaces with daylight area ❑Complies C405.2.3. under skylights and rooftop monitors ❑Does Not 1, are equipped with required lighting C405.2.3. controls. ❑Not Observable 3 ❑Not Applicable I[EL21]1 Exception: Requirement does not apply. C405.2.4 Separate lighting control devices for ❑Complies Requirement will be met [EL4]1 specific uses installed per approved ❑Does Not lighting plans. ❑Not Observable []Not Applicable C405.2.4 Additional interior lighting power ❑Complies Requirement will be met. [EL8]1 allowed for special functions per the ❑Does Not approved lighting plans and is ❑Not Observable automatically controlled and separated from general lighting. ❑Not Applicable C405.2.5 Automatic lighting controls for exterior ❑Complies Requirement will be met. [EL25]na° lighting installed. Controls will be ❑Does Not daylight controlled, set based on ❑Not Observable business operation time -of -day, or ❑Not Applicable reduce connected lighting > 30%. C405.3 Exit signs do not exceed 5 watts per ❑Complies Requirement will be met. [EL6]1 face. ❑Does Not ❑Not Observable []Not Applicable Additional Comments/Assumptions: T 1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3) Project Title: South Windsor Buckland Report date: 06/28/19 Data filename: M:\8303-58\Calculations\Electrical\8303-58_ComCHECK.cck Page 7 of 10 Project Title: South Windsor Buckland Report date: 06/28/19 Data filename: M:\8303-58\Calculations\Electrical\8303-58_ComCHECK.cck Page 10 of 10 1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3) Project Title: South Windsor Buckland Data filename: M:\8303-58\Calculations\Electrical\8303-58_ComCHECK.cck Report date: 06/28/19 Page 8 of 10 ® WING LIST DWG DRAWING TITLE EN-001 ENERGY ANALYSIS COMPLIANCE SHEET 1 EN-002 ENERGY ANALYSIS COMPLIANCE SHEET 2 A ■ ■ Mm.iiyliiVNwiiiiy &R.1 v 1 rvc Ui1&t11GU1 ODUUE707 116 West 32nd Street,12th Floor, New York, N.Y. 10001 P 212.643.9055 F 212.643.0503 www.mgedpc.net MG ENGINEERENIG, P.C. 116 W 32ND STREET, 12TH FLOOR, NEW YORK, NY 10001 T. 212.643.9055 1 WWW.MGEDPC.NET oeverua i-kssocrate SEVERUD ASSOCIATES CONSULTING ENGINEERS, PC 469 SEVENTH AVENUE - SUITE 900, NEW YORK, NY 10018 T.212.986.37001 WWW.SEVERUD.COM # I ISSUANCE I DATE I ISSUED FOR BID 106-28-2019 1 1 I ISSUED FORBID 1 08-15-2019 1 TPG\rchitecture TPG ARCHITECTURE, LLP 31 PENN PLAZA 132 WEST 31ST STREET, 5TH FLOOR, NEW YORK, NY 10001 212.768.0800 1 TPGARCHITECTURE.COM IN CONSIDERATION OF RECEIVING DRAWINGS FROM TPG ARCHITECTURE LLP IN AN ELECTRONIC FORM, THE RECIPIENT AGREES, TO THE FULLEST EXTENT PERMITTED BY LAW, TO HOLD HARMLESS AND INDEMNIFY TPG ARCHITECTURE LLP FROM AND AGAINST ALL CLAIMS, LIABILITIES, LOSSES, DAMAGES, AND COSTS, INCLUDING BUT NOT LIMITED TO ATTORNEY'S FEES, ARISING OUT OF, OR IN ANY WAY CONNECTED WITH THE USE, RE -USE, MIS -USE, MODIFICATION, OR MISINTERPRETATION OF THE MACHINE-READABLE INFORMA T ION PROVIDED BY TPG ARCHITECTURE LLP UNDER THIS AGREEMENT. ,*ROJECT SOUTH , ,. SOUTH•' CT 06074 DRAWING NAME ENERGY ANALYSIS COMPLIANCE SHEET 2 SEAL I DATE 06.13.2019 Di-S NO. PROJECT NO. 8303.58 SCALE N.T.S. DRAWN BY CDP DOB PAGE CHECKED BY XX I 2 OF 2