HomeMy WebLinkAbout03-02P_DEE ZEE ICE_SANDRA DRIVEGENERAL SITE PLAN NOTES: THE DEVELOPER SHALL NOTIFY THE TOWN ENGINEER'S OFFICE 24 HOURS IN ADVANCE TO SCHEDULE INSPECTION OF SUB -BASE, GRAVEL, PAVEMENT, SIDEWALKS, DRAINAGE STRUCTURES AND PIPES, SANITARY SEWERS AND MANHOLES. ALL SITE WORK SHALL BE CONSTRUCTED IN ACCORDANCE WITH TOWN OF SOUTH WINDSOR STANDARDS AND CONNECTICUT D.O.T. FORM 814,AS AMENDED EROSION AND SEDIMENTATION CONTROLS SHALL BE INSTALLED IN ACCORDANCE WITH THE " EROSION AND SEDIMENTATION CONTROL HANDBOOK" PREPARED BY THE SOIL CONSERVATION SERVICE 1688. NO SITE IMPROVEMENTS SUCH AS DRAINAGE, SANITARY SEWER, SIDEWALKS, EXCAVATIONS, FILLING, PAVEMENT OPERATIONS, ECT. SHALL COMMENCE UNTIL THE SITE ENGINEERING BOND AS REQUIRED BY THE PLANNING AND ZONING COMMISSION, IS POSTED WITH THE TOWN OF SOUTH WINDSOR. NO STUMPS TO BE BURIED ON SITE AN AS -BUILT PLAN SHALL BE SUBMITTED FOR REVIEW AND APPROVAL PRIOR TO THE REQUEST FOR A CERTIFICATE OF OCCUPANCY. ANY ADDITIONAL SEDIMENT/EROSION CONTROL MEASURES DEEMED NECESSARY BY STAFF DURING CONSTRUCTION OF ANY SITE IMPROVEMENTS SHALL BE IMPLEMENTED BY THE DEVELOPER. IN ADDITION, THE DEVELOPER SHALL BE RESPONSIBLE FOR MAINTENANCE, REPAIR, REPLACEMENT OF ALL REQUIRED CONTROL MEASURES UNTIL ALL DISTURBED ARES HAVE BEEN STABILIZED TO THE SATISFACTION OF STAFF. THE USE,STORAGE, OR DISPOSAL OF ANY MATERIALS NOT IN ACCORDANCE WITH WHAT IS SHOWN ON THE APPROVED PLANS, OR REQUIRED BY ANY REGULATORY AGENCY, MAY RESULT IN THE IMMEDIATED REVOCATION OF ANY PERMIT/APPROVAL GRANTED BY THE COMMISSION. ALL FRONT LOT CORNERS ARE TO BE PINNED/STAKED AT THE TIME OF SUBMITTAL OF A REQUEST FOR A BUILDING PERMIT. WHEN A CERTIFICATE OF OCCUPANCY IS REQUESTED, ALL LOT CORNERS MUST BE PINNED. ANY SIGNS TO BE INSTALLED ON THE PROPERTY SHALL BE SUBJECT TO STAFF AND/OR COMMISSION REVIEW. ANY EXCESS EXCAVATED MATERIAL MUST BE DISPOSED OF IN A SUITABLE MANNER AND LOCATION ACCEPTABLE TO TOWN STAFF. ANY APPROVED LANDSCAPING WILL BE SUBJECT TO FINAL REVIEW BY THE TOWN PLANNER FOR ADEQUACY AND SUITABILITY OF SPECIES IN THE LOCATIONS PROPOSED. ANY APPROVED EXTERIOR LIGHTING SHALL NOT BE DIRECTED ONTO ABUTTING PROPERTIES OR ROADWAYS HANDICAP PARKING STALLS SHALL BE MARKED IN ACCORDANCE WITH STATE AND TOWN REGULATIONS HORIZONTAL DATUM BASED ON N.A.D. 1927 THERE ARE NO WETLANDS ON PARCEL PARCEL IS NOT AFFECTED BY 100 YEAR FLOOD PLAIN ALL ROOF LEADERS SHALL BE TIED INTO STORM DRAINAGE SYSTEM ALL UTILITIES TO BE INSTALLED UNDERGROUND THERE SHALL BE NO OUTSIDE STORAGE ON SITE A DRAIN LAYERS PERMIT WILL BE REQUIRED FOR THE INSTALLATION OF THE SANITARY SEWER LINE IN THE STREET A STREET CUT PERMIT WITH A PERMANENT PATCH FEE WILL BE REQUIRED FOR THE INSTALLATION OF THE SANITARY SEWER LINE IN THE STREET THE WATER USE TO MAKE ICE THAT IS NOT DISCHARGED TO THE SANITARY SEWER MUST BE MONITORED. A SEPERATE WATER METER MAY BE NEEDED FOR THIS PURPOSE. EROSION CONTROL NOTES LAND DISTURBANCE WILL BE KEPT TO A MINIMUM_ RESTABILIZATION WILL BE SCHEDULED AS SOON AS POSSIBLE. TEMPORARY SEEDING OR PERMANENT HYDROSEEDING SHOULD TAKE PLACE IMMEDIATELY UPON COMPLETION OF GRADING. PERMINATED SEEDING WILL BE SCHEDULED DURING THE PERIOD OF APRIL 1 - JUNE 15; AUGUST 15 - SEPTEMBER 15. EROSION AND SEDIMENT CONTROL MEASURES WILL BE INSTALLED PRIOR TO CONSTRUCTION WHENEVER POSSILBLE AND WILL BE MAINTAINED IN EFFECTIVE CONDITION THROUGHOUT THE CONSTRUCTION PERIOD. HAYBALE AND SILT FENCE FILTERS WILL BE INSTALLED AS SHOWN ON THIS PLAN AS WELL AS AT ALL CULVERT OUTLETS. ADDITIONAL CONTROL MEASURES WILL BE INSTALLED DURING CONSTRUCTION PERIOD IF NECESSARY AS REQUIRED. ALL EROSION AND SEDIMENTATION CONTROL MEASURES WILL BE CONSTRUCTED IN ACCORDANCE WITH THE STANDARDS AND SPECIFICATIONS OF THE "CONNECTICUT GUIDELINES FOR SOIL EROSION AND SEDIMENTATION CONTROL", CONNECTICUT CONCIL ON SOIL AND WATER CONSERVATION,JANUARY 1985. SEEDING DATES: APRIL THROUGH JUNE 15 AND AUGUST 15 THROUGH SEPTEMBER 15. IF SEEDING CANNOT BE DONE WITHIN SEEDING DATES, USE MULCHING MEASURES TO PROTECT SITE AND DELAY SEEDING UNTIL THE NEXT RECOMMENDED SEEDING PERIOD. FERTILIZE WITH 10-10-10 @ 7.5 LBS./1000 SF. LIME (50 PLUS MAGNESIUM OXCIDE) 100 LBS./1000 SF. MULCH ( ALL SLOPES 3 USE STRAW OR HAY (70-90 LBS./1000 SF) FREE OF WEEDS OR COURSE MATTER. CHEMICAL BINDERS SUCH AS PETROSET TERRATRACK HYDOR MULCH AND AEROSPRAY WILL BE USED AS RECOMMENDED BY MANUFACTURER TO ANCHOR MULCH. MULCH MUST BE INSPECTED PERIODICALLY, IN PARTICULAR, AFTER A RAINSTORM TO CHECK FOR FILL EROSION. WHERE EROSION IS SEVERE, ADDITIONAL MULCH SHOULD BE APPLIED. GRASSES SHALL NOT BE CONSIDERED ESTABLISHED UNTIL A GROUND COVER IS ACHEIVED , WHICH IS MATURE ENOUGH TO CONTROL SOIL EROSION TO SURVIVE SEVERE WEATHER CONDITIONS. CONSTRUCTION NARRATIVE: 1. INSTALL SILT FENCE EROSION CONTROL IN AREAS SHOWN ON PLAN 2. CLEAR AND GRUB TREES AND VEGETATION TO LIMITS SHOWN. 3. STRIP TOPSOIL TO STOCKPILING AREAS 4. EXCAVATED FOR BUILDING FOUNDATION 5. INSTALL SITE UTILITIES AND DRAINAGE SHOWN 6. INSTALL HAYBALE E&S CONTROL AT CATCH BASINS 7. BACKFILL FOUNDATION AND FINE GRADE FOR CONCRETE SLAB 8. GRADE AREA AROUND BUILDING AND GRADE FOR PAVEMENT 9. INSTALL BINDER COURSE OF PAVEMENT 8t CURBING 10. BACKFILL CURBS, TOPSOIL AND SEED ALL DISTURBED AREAS TO STABILIZE SOIL, LANDSCAPE PER PLAN. 11. REMOVE SILT FENCE EROSION CONTROL AFTER DISTURBED AREAS @ ADDITION ARE STABILIZED TO THE SATISFACTION OF TOWN STAFF STORM SYSTEM MAINTENANCE SCHEDULE: 1. INSPECT ALL CATCH BASIN SUMPS EVERY SIX MONTHS FOR ANY REQUIRED REMOVAL OF EXCESS DEBRIS. 2. ALL CATCH BASINS TO BE CLEANED ANNUALLY TO PREVENT BUILD UP OF SILT AND/OR EXCESS DEBRIS. CONTACT PERSON: DAVE ZYLBERMEN 860-528-3500 CIV °cue :K a NO.1342 �cccc41, Sri RV �`% I HEREBY CERTIFY THAT THIS MAP IS SUBSTANTIALLY CORRECT TO MY KNOWLEDGE AND BELIEF AND WAS PREPARED IN ACCORDANCE WITH THE STANDARDS OF A CLASS A-2 DEPENDENT RESURVEY AS DEFINED IN SECTIONS 20-30OB-1 THRU 20-30OB-20 OF THE REGULATIONS OF CONNECTICUT STATE AGENCIES " MINIMUM STANDARDS FOR SURVEYS AND MAPS IN THE STATE OF CONNECTICUT" EFFECTIVE 6-21-96 AS ADOM'ED 0 THE CONNECTICUT ASSOCIATION OF LAND SURVEYORS, O SEPT.26 , 1996. / BORA SKI , L.S. # 13422 DATE 26°52'17"E -� 4t15' EXISTING CONTOURS PROPOSED CONTOUR EXISTING SPOT ELEVATION PROPOSED SPOT ELEVATION SILT FENCE EROSION CONTROL PROPOSED CATCH BASIN EXISTING CATCH BASIN 175 w METAL HALIDE EXTERIOR WALL PACK ZONING DATA TABLE ZONE: I (INDUSTRIAL) REQUIRED PROVIDED LOT AREA 20,000 SF 40,733.20 SF LOT WIDTH 100 FT. 100.02 FT. LOT DEPTH 150 FT. 260.60 FT. FRONT YARD 35 FT. 72.98 FT. SIDE YARD 10 FT. 11.22 FT. REAR YARD 25 FT. 26.00 FT. MAX.BUILDING COVER 50% 16% (INCL.FUTURE) IMPERVIOUS COVER 65% 41% ( INCL.FUTURE) "' NO WETLANDS OR WATERCOURSES ON PROPERTY"' STAKED HAYBALE @ CATCH BASIN REQUIRED PARKING CALCULATION: L±j ( EROSION CONTROL) OFFICE = 650 SF A 000 (4.5) = 3 / TP TEST PIT LOCATION MANUFACTURING = 5200 SF / 700 = 8 / TOTAL REQUIRED =11 (1 HANDICAP) ANDRE C. & ANDRE K. CHARBONEAU TOTAL PROVIDED = 11 ( 1 HANDICAP) 75 , ANDRE C. & ANDRE K. CHARBONEAU--_ \ CONCRETE DUMPSiER PAD \ w/ CFWN UW FENCE - _jT3ALL SLAM IN FENCE SITE PLAN \ \ 1 "=20' \ TEST PIT INFORMATION DATE: JANUARY 23,2003 FOREST HUMUS / TOPSOIL FINE TO MEDIUM SAND, GROUND WATER SEEPAGE AT 71" NO INDICATION OF MOTTLING FOREST HUMUS / TOPSOIL FINE TO MEDIUM SAND, GROUND WATER SEEPAGE AT 68" NO INDICATION OF MOTTLING 75.33 \ \ r/ \ ' F MYb TE 6(�FFF � R 75 1540 SULLIVAN AVENUE • SOUTH WINDSOR, CT 06074 i.y� sE 1540 SULLIVAN AVENUE • SOUTH WINDSOR, CT 06074 °soe.<o•'� TELEPHONE (860) 644.2511 -+Oa�cOs'� TELEPHONE (860) 644.251l March 6, 2003 January 23, 2003 Certified #70001670000775520368 PDS Engineering Attm Chris Eseppi 107 Old Windsor Road Bloomfield, Cr 06002 RE: AppL #03-02P -Dee Zee lee Site- westerly of Sandra Drive, I zone Dear Mr. Eseppi: At the January A 2003 regular meeting, the Inland Wetlands Agency/Conservation Commission approved application #03-02P - Dee Zee lee Site- Sandra Drive -Inland Wetland/Conservation Commission application for the construction of a 6200 sq. ft. industrial building, pang, stormwater structures and associated improvements on property located westerly of Sandra Drive, I, Industrial zone, This approval is subject to the following conditions: 1. One blueprint Copy of the entire set of plans and this letter reproduced thereon, must be submitted to this Commission. This must be completed within 65 days of approval prior to any Construction activity on the site. Plans submitted to Planning & Zoning Commission shall be Considered having met this requirement 2. The application shall indemnify and hold harmless the Town of South Windsor against any liability, which might result from the proposed operation or use, 3. The permit is valid for five yeas and "I expire on January 22, 2008. It is the landown er(s)1applicant(s) responsibility to track expiration dates and notify the Commission of a renewal request at least 65 days prior to expiration. 4. All approvals required must be obtained and submitted prior to any activity on the site. 5. A contact person shall be identified on the plans. 6. incorporate the rooftanoffinto subsurface infiltrators subject to the test pits and discussion with Town staff. 7. We recommend a bond in the amount of $3,000 be submitted to the Planning & Zoning . Commission to ensure compliance with the Erosion and Sedimentation Control Measures. Very truly yours, WLAND WETLANDS AGENCY/ CONSERVATION COMMISSION idr Philip Forzley, Vice Chairperson PF:dr cc: CbiefBuilding Official Town Engineer N/F EARL D. & JANET MORRIS PDS Engineering & Construction, Inc. 107 Old Windsor Road Bloomfield, Cr 06002 Atm: Chris Eseppi RE: Dec Zee loe Sande Drive, South Windsor, Cr Dcar Mr. Eseppi: The South Windsor Water Pollution Control Authority, at its regular meeting of March 4,200, gave approval for the connection to the Tower's sewerage system ofa commercial buildinglocued at Lot #9, Saudis Drive, South Windsor, Cr, as more specifically shown on plans emitted "Site Plan, Dee Zee Ice" prepared by PDS Engineering & Construction, Inc., Bloomfield, Cr, Drawing Nola) C- 101 dated 10-10- 02,raised 10-23-02, 10-2&02,12-12-02,1-9.03, 1.28.03, 2-18-03, sad subject to the following conditions 1. This approval isfm the specified use and sizeofthe building as above on current plane 2. Technical approval ofthe Tom Engineering Depacmnnt. 3. Final Authority approval and somptana ofibe aanitarysewerage contraction will be givenonce the sewer line has been installed and inspected by the Town staff, and based upon the written verification ofthe To" stafftlntaid sanitary server line, was installedfit substantial conformance with the design plan previously approved by the Authority, and mee sing all Town regulations and appropriate technical specifications rela ftto sanitary awer construction. This approval letter mot be superimposed on the final approval plans. very truly youes, Jo h J. Carina, Chahmn Water Pollution Control Authority JJC:dd Cc: Matthew Colligan, Town Manager Michael J. (antick, Dbectoc of Public Works Jetrpoolhtle, Town Engineer Mania BamA DirectorofPlsnning John Collins, Chief Building Inspector David Zylbcrnrn 7. a_aics 2v 1540 SULLIVAN AVENUE • SOUTH WINDSOR, CT 06074 TELEPHONE (860) 644-2511 Mr. Christopher Escppi PDS Engineering & Construction, Inc. 10-23-02 REV.LAYOUT 10-28-02 REV. LAYOUT 12-12-02 P&Z APPLICATION 1-9-03 MOVE DUMP.,ADD BERM 1-28-03 ADD NOTES&TEST PIT DATA 2-18-03 DELETE REAR DRIVE 3-27-03 FINAL TOWN APPROVAL PDS ENGINEERING & CONSTRUCTION, INC. 107 Old Windsor Road Bloomfield, Connecticut.06002 Telephone: (860) 242-8586 FAX (860) 242-8587 SITE ENGINEERING : (APPLICANT) PDS ENGINEERING & CONSTRUCTION 107 OLD WINDSOR ROAD BLOOM FIELD,CONNECTICUT 06002 860-242-8586 SURVEYOR : PDS ENGINEERING & CONSTRUCTION 107 OLD WINDSOR ROAD BLOOM FIELD,CONNECTICUT 06002 860-242-8586 OWNER DAVE ZYLBERMAN 350 CHAPEL ROAD SOUTH WINDSOR,CONNECTICUT 06074 860-528-3500 107 Old Windsor Road Bloomfield, CT 06002 Re: Appl #03-02P, Dec Zee ice, Site Plan (� Dear Mr. Eseppi: U We are pleased to advise you that the Planning & Zoning Commission voted on February 18, 2003, to approve LIJ with modifications the above referenced application for a Site Plan of Development. This approval is for the z construction ofa 6,200 square foot industrial building on property located on the westerly end of Sandra Drive, z I Zone as shown on plans prepared by PDS Engineering & Construction, Job No. C-100, dated December 12, 2003, as revised. This approval is subject to the following modifications: O C)1. Prior to commencement of any site work, a meeting must be held with Town Staff. 2. No building permit will be issued until the final mylars have been filed in the Town Clerk's office. � LU ^ 3. This application ie subject to the conditions of approve of the inland Wetlands Agency/Conservation [i Commission, including a bond in the amount of $3,000.00. Q C)4. An as -built plan is required prior to issuance ofa Certificate of Occupancy per Section 8.1.10 of the Zoning LU Q Regulations. LU az a 5. Footing drains are required if the building has a basement. Q IY 6. A landscape bond in the amount of $5,000.00 is required and must be submitted prior to filing of mylars. z z I- LU 7. All plans used in the field by the developer must bear the stamp and authorized signature of the Town of F- W Q = tit South Windsor. 0 z S. WPCA approval is required. 9. Ilia State Traffic Commission certificate is required, no building pemnits will be issued until the certificate bi bi � O Q O 0 Q ■ d 1 has been issued (per CGS V4-310. I0. The building street number must be included on the final plan. fl 11. Engineering comments of February 11, 2003 must be addressed to the Town Engineer's satisfaction. 12. All mechanical units to be located in the front of the building to mitigate sound. SEAL i 13. The rear loading door and drive must be eliminated. 14. The wall Pak lighting must be eliminated. ?� Black and white transparent mylars of Sheet #2 with the above modifications, together with three blueprint copies of the entire set of plans must be submitted to this Commission within 30 days to be stamped and signed. 0 1 The letters of approval of this Commission as well as the Wand Wetlands Agency/Conservation Commission must be reproduced on the mylars. = 0.1 After the mylars have been signal by the Commission, they will be returned to you for filing in the Office of the o ( Town Click. After filing these plans, a copy of the receipt must be submitted to the Planning Department sincerely, ei.t k 0 N A r011E11731 U110b��, Kevin McCann, Chairman Planning and Zoning Continuation ENGINEER: FB KMcCAmh ARCHITECT: BS cc` Town fItuil inn Chief Building Official PROJECT M G R : Assessor Superintendent of Pollution Control Fire Marshal nDA=C-n DV• DC cmi 01 PLANTING NOTE PLACE TOPSOIL MIXTURE IN BOTTOM OF HOLE AND SATURATE. AFTER PLACING PLANT, WORK TOPSOIL MIXTURE CAREFULLY AROUND ROOT BALL AND THEN SATURATE. WHEN HOLE IS ONE HALF FULL OF MIXTURE, SATURATE AGAIN. FILL HOLE COMPLETELY WITH TOPSOIL MIXTURE AND SATURATE AGAIN. DECIDUOUS TREES WITH LESS THAN 2 1/2" CAL. AND EVERGREEN TREES LESS THAN 4' HT. SHALL BE STAKED WITH 2 EQUALLY SPACED STAKES AROUND THE TREE. Dwiduouw STAKES SHALL BE UNIFORM IN H AND FASTENED TO EACH TREE AT ABOUT 5' BY MEANS OF TWO STRANDS OF TWISTED #10 GUAGE IRON WIRE. REMOVE BURLAP FROM TOP 1/3 FOF-� (SEE PLANTING NOTES) SELECTIVELY PRUNE ALL TREES AND M11 SHRUBS OF DEAD AND TQPSOIL AND M DYING BRANCHES N PLANTING DETAILS N.T.S. TREES 12` DECIDUOUS TREES WITH A 2 1 2" CAL. gAgN HT EATER AND EVERGREENBETREES Q GUYE[� WITH 3 KE STAS gEQUALLY SPACED AROUND THE TREE, EACH STAKE WIRED �7- AROUND THE TREE THROUGH RUBBER HOSE.^` RUBBER HOSE (ONE PER STAKE) BURLAP OR WATERPROOF WRAPPING MATERIAL TO SECOND BRANCHING (DECIDUOUS TREES). CROWN SET 2" BELOW THAT OF NURSERY SETTING. 18" WOODEN STAKE - PAINT OR FLAG TOP. r—FINISH GRADE Time List Sym. Quan. Botanical Name Common Name Size Root MS 2 MALUS SNOWDRIFT SNOWDRIFT FLOWERING CRABAPPLE 1 1/2in. 2in. Cal. B&B PAN 3 PICEA ABIES NORWAY SPRUCE 8ft.-1011. Ht. B&B PM 9 PSEUDOTSUGA MENZIESII DOUGLAS FIR 8ft.-10ft. Ht. B&B PO 8 PICEA QMORIKA SERBIAN SPRUCE 8ft: 10ft. Ht. B&B POS 1 4 1 PICEA OMORIKA I SERBIAN SPRUCE Eft.-7ft. Ht. B&B QR 1 4 1 QUERCUS RUBRA I RED OAK I 21/2in.-3in. Cal. B&B Shrvl---) List Sym. Quan. Botanical Name Common Name Size Root DVW 12 RHODODENDRON SP. 'DELAWARE VALLEY DELAWARE VALLEY WHITE AZALEA 18in.-24in. Spd. CONT. FIF 5 FORS. X INT.'FIESTA FIESTA FORSYTHIA 18in.-24in. 5 d. CONT. ICC 2 ILEX CRENATA'COMPACTN COMPACT JAPANESE HOLLY 18in.-24in. S d. CONT. JSG 14 JUNIPERUS CHIN. SARGENTII'GLAUCN BLUE SARGENTS JUNIPER 18in.-24in. Sod. CONT. PJM 22 RHODODENDRON'PJM' PJM' RHODODENDRON 18in.-24in. S d. CONT. RCA 4 RHODODENDRON CATAWB.'ALBN WHITE CATAWBA RHODODENDRON 18in.-24in. S d. CONT. RM 7 RHODODENDRON MAXIMUM ROSEBAY RHODODENDRON 24in.-30in. Ht. B&B TH 6 TAXUS MEDIA'HATFIELDII' HATFIELD YEW 21/2ft: aft. Ht. CONT. VD 7 VIBURNUM DENTATUM ARROWWOOD VIBURNUM 18in.-24in. Sod. CONT. ALL LANSCAPE BEDS TO RECEIVE PINE BARK MULCH N Q3 P 8 oo� O O OV 00�0 Q o MS 1 P 6 JSG 0 7 Q Do JSG 7 TH q6 POS 4 1 CONCRETE DUMPSTER PAD w/ CHAIN LINK FENCE INSTALL SLATS IN FENCE LANDSCAPE PLAN 1 "=30' M 6Q 00• FUTURE ADDITION 1800 SF FIN.FLR.74.00 PROPOSED BUILDING 4400 SF FIN.FLR.74.00 \00' FIF 5 • �I/fit + PJM 4 3 7 PM 5 LOT AREA = .94 ACRE 40,733.20 SF LADA, P.C. Land Planners lada2.tif 104 West Street Simsbury, CT 06070 (860) 651-4971 2050 Route 22 (Suite 106) Brewster, NY 10509 (845) 278-7424 'FINAL TOWN APPROVAL d PDS ENGINEERING & CONSTRUCTION, INC. 107 Old Windsor Road Bloomfield, Connecticut.06002 Telephone: (860) 242-8586 FAX (860) 242-8587 SITE ENGINEERING : (APPLICANT) PDS ENGINEERING & CONSTRUCTION 107 OLD WINDSOR ROAD BLOOM FIELD,CONNECTICUT 06002 860-242-8586 SURVEYOR : PDS ENGINEERING & CONSTRUCTION 107 OLD WINDSOR ROAD BLOOM FIELD,CONNECTICUT 06002 860-242-8586 OWNER : DAVE ZYLBERMAN 350 CHAPEL ROAD SOUTH WINDSOR,CONNECTICUT 06074 860-528-3500 Z a w J z a v Z O0 W LLB >� a a w o � c.� w Q w N nz o n � . � 0 Z W co z Z IQ o L'] Q J � o SEAL SHS MGR: Q_ C=1 02 N 0 1-28-03 OILSEPAR.,RET.WALL & C7 2" %t 1'-6t/e%2" 2^ �0 „ �'� " 1. SET POSTS ANO EXCAVATE DUMP PAD DETAILS >' 2" 2" A 6" X 6" TRENCH, 2-18-03 RET.WALL DIMENSION > O I 2-#4x4'-0" LONG---� SET POST OQWNSLOPE. , 2. STAPLE THE WIRE MESH { 70P OF FRAME APPLIES WIRE F£NctivG—J FENCING To THE POSTS. 3-27-03 FINAL TOWN APPROVAL y 2's/re" FLOW 100 ---► r ,!'' ----PRECAST CONCRETE UNIT LAWN/ STREETS/ \\ ADJUST FRAME ELEVPTION ° CROSS-COUNTRY PAVED AREAS WITH BRICKS 6"toi2 OPOSED GRADE TRENCH CUT ` • 6" TO 8" DEEP 2" 8%- 1 " �j 2 -Ae" TOPSOIL Bt SOD OR SEED SEE PERMANENT --^- SAW CUT AND SEAL JOINT s" TO s" WIDE cn PAVEMENT PATCHING DETAIL Ix " 2"X4"X5' STAKES DRIVEN P'! Ts/ e Q > Is AV£MENT SECTION OR 4"MIN' 1 (COMPACTED) CLASS2 BITUMINOUS « > 3 - CONCRETE SURFACE COURSE (OR INTO GRADE 12" MIN., LANdSCAPING (SEE PLANS) <?: ;U;Q,; t�' "(�Q'pp: EXISTING SET 8' TO 10' APART, AND s ti. ....- APPROVED GRANULAR NON- MArcN.EXISTING, IF GREATER) M,04 v d: • d b PAVEMENT CANTED 10' INTO SLOPE Ci I "_•p,-.K', ORGANIC BACKFILL MATERIAL --- 2"(COMPACTED) CLASS I BITUMINOUS 12 fj ,0y PLACED AND COMPACTED IN '-'-"'-"' "' _-"- RECAST CONCRETE OR „4• Q• .. ONE FOOT (1'} (MAX.) LIFTS. MATCNEEXE.STINNG,RiF GaafR) M,oa ('} CONCRETE MASONRY UNITS � j�'. f A:d"px �~ G"(COMPACTED) PROCESSED TRAPROCK 0 1. ' + 2 WARNING TAPE PER CONK. �~ ��••' 70 ! -{ t ? 3 MINIMUM 1':I 1 A Ab WARNING TAPE - MIN. 12" GENERAL STATUTE SECTION iL' BASE.- M,05,01 4RICA TACH FILTER FABRIC THE PARE FENCING A. BACKFILL THE TRENCH n N MAX. 24" ABOVE PIPE 16 (MIN. AS AMENDED, PLACED �'a p 1 E1ah PA FILTER FAD EXTEND IT INTO AND COMPACT THE 12"(MIN.) T024°(MAX.)ABOVE D s'•t c7q';E TRENCH 8". &:,'ti: •' d �• "n!A EXCAVATED SOIL. '1.;,1.„•:;,t,.:: ':1'.:-'. !.:.'. �", I:.;,i ;•/.1;.: 6" - I TOP OFPIPE. t71:V'4} I 6a(COMPACTED)PROCESSED GRAVEL � POURED CONCRETE OR - ,.. PRECAST SUMP z 0: ': ' •-• o• Do.l: I APPROVED BACKFlLI PLACED PQ� I :o (TRENCH BACKFILL) M.02-GRAO,'8 .. b0 DoSUBASEOVER COMPCTED SUSGRADE AND COMPACTED IN 12' LAYERS "(OR AS OTHERIWSE APPROVED)I COMPACTED BACKFILL 11 NO STONE LARGER THAN 3"\ 6" OF 3/4" CRUSHED STONE SAND BLA NOTESi _ NKET-MIN.TRENCH' NOTESFOLD FA RI \` ! B CUP 5'-4" 4'_4» t' 12 MIN. -' :. is I - , PIPE,AS SPECIFIED + wJDTH I BEDDING ON SUITABLE NATIVE MATERIAL SAND BOOING PLACED AND I VARIES I I. ALL SAW CUT AND SEALED JOINTS TO I.MINIh1UM COVER OVER TOP OR COMPACTED IN 6' LAYERS 1/20.0. , " I' -+! BE EITHER PARALLEL WITH, OR PERPEN- ' OF PIPE SHALL BE 2'-0". NO STONE LARGER THAN `.: :: see x FRONT ELEVATION SIDE ELEVATION • 3/4" CRUSHED STONE BEDDING MATERIAL PIPE ; .;.:ter,' M 1 ` DICULAR TO, THE CENTER -LINE OF « IN ROCK EXCAVA71ON OR IN UNSUITABLE 1 1/2 MATERIAL SHALL ,a;.,.,: 1 TYPICAL THE PIPE. PDS ENGINEERING & 2.WALL THICKNESS FOR ' MATERIAL -AS DIRECTED BY THE ENGINEER MEET D.O.T.D0TM2.05 a ,.o TRENCH a 1/20.0. 8 •eo ` 3/4" BROKEN TRAPROCK I SECTION I 2. ALL MATERIALS ARE 7C MEET " PRECAST UNITS LESS THAN MATERIAL SHALL MEET D.O.T. M,02,01.1 �O P ( FORM 814, AS AMENDED I, FOR 3/4-STONE. PIPE o 0o f I 10 HIGH IS 6 . / f�. 4��.J'� . ( 8 A A 6"MIN, goo°o°• ioo;i` g1 BOTTOM OF CONSTRUCTION, INC. BACKFILL TO CENTERLINE OF PIPE +o eSI • cgCC DRAINAGEWAY - WHEN USING POLYETHYLENE OR �% 107 Old Windsor Road p A.B.S. PIPE. 1 0.0• y Z 2" 7y� 1'-6>/s" 1'-6%^ Yi^ 2" 12' PIPE t2" SECTION o A g Bloomfield, Connecticut.06002 Z z a." a iSe" Asa^ N.T. S. Telephone: (860) 242-8586 0 SECTION I FAX (860) 242-8587 { C I ( N.T.S. ELEVATION m S a/ sjd g+�" 3'�Sd• POINTS 'A' SHOULD BE NIGHER THAN POINT 'B' SITE ENGINEERING : (APPLICANT) lr.:.. "'... 1. '� D C7 �.,'; ,:.• %._ . PRECAST CONCRETE UNIT LAN PDS ENGINEERING & CONSTRUCTION r O----ADJUST FRAME ELEVATION TOWN OF SOUTH WINDSOR APPROVED TOWN OF SOUTH WINDSOR TYPICAL SANITARY SEWER APPROVED TOWN OF SOUTH WINDSOR PERMANENT PAVEMENT APPROVED WSTH BRICKS 6"to12" STORM DRAIN TRENCH DETAIL 107 OLD WINDSOR ROAD a ��^ STANDARD DETAIL. "' STA}�IDARD DETAIL TRENCH SECTION .�•� `' STANDARD DETAIL PATCHING DETAIL TYPICAL 2" t oAJANUARY, t s 9 t JANUARY, 1991 JANUARY; 199I BLOOMFIELD CONNECTICUT 06002 ! REVISED: ►VDLI C MO KS 01 RECTOR REVIt[0: tW LlC 1roRKt DIRECTOR REVISED: ►UDLIC WOR s DIRECTOR FILTER FABRIC FENCE ' y FOR EROSION CONTROL 860-242-8586 o W I w rn 77 li 2'-0" n I ACCEss covER Not to ScDle SURVEYOR I I ! SECONDARY ACCESS COVER PRECAST CONCRETE OR CONCRETE MASONRY UNITS AN WLM-MEDIUM WALL LIGHT PDS ENGINEERING & CONSTRUCTION �'�� Metal Halide oa , D � BRlTES �•) _ . 107 OLD WINDSOR ROAD �' .�.: t "/:�:;-.., DIMENSIONS ' �10`�FPG� GRATE ' BLOOM FIELD,CONNECTICUT 06002 _ R:.,::.; ;:;, .:_•'- POURED CONCRETE OR _-,.E.•:::. G J ' 860-242-8586 PRECAST SUMP ` 4��EQ 3' STAKES ANCHOR VATH TWO ................. > r — s' - y I? TO F EACH BALE 1 dui >✓t T31=+� Cn " 4'-O" C OF 3 4" CRUSHED 3'-0" 44' OIA. N.O. (2) LO r y OWNER Z STONE O FOP, WALL MOUNT I rn 1 00 . 1h1�L,cr o NOTES! " 41/47~--I2•K.o. ;� ;� o • I DAVE ZYLBERMAN 5°-4` I,MINIMUM COVER OVER TOP a-4" PS ��F'4 FLow -- -> 1,' — FLow 350 CHAPEL ROAD ® 4" MINIMUM R�- SOUTH WINDSOR,CONNECTICUT 06074 I a FRONT ELEVATION OF PIPE SHALL BE 2' SIDE SIDE ELEVATION I 6 C7 DD7 2" Qj ' ?-.WALL THICKNESS FOR ,a-,/z --! a„— FILTER i'ABRIC , f �• , 1 860-528-3500 a ORECAST UNITS LESS THAN (368.3 mm) (203.2 mm) 1 1 r r 1 1 1 Id HIGH IS 6". t3-0/4" 9'-0" (336.6 mm) CONSTRUCTION ENTRANCE HAY_ BALE INSTALLATION ------------ ---------- - `RACKING PAD AT LfW POINT CATCH BASINS N.T.S. I I I I iI ALL OF BASIN NEENAH TRAP HOOD MODEL NO. R3701 OR CAST EQUAL WITH HOOKS IRON HANDLE TLET PIPE I I ' I l_-----------------------� HANDICAP SIGN SCALE 1/2 =1'-0" z HANDICAPPED PARKING SPACE - 2f: MAX SLOPE' U 1000 GALLON OIL -WATER SEPARATOR STANDARD SIM aT BLUE' BACKGRWND I " CHAMM �A, %T-_ � AND tFt"� INO g� `� ''y` W TRAP HOODS SHALL BE INSTALLED DESIGN NOTES Z IN ALL CATCH BASINS, WHERE T,0,1N• I �•VA!?I�5 1. CONCRETE - 5000 psi 28 days o 0 Uj 0 W W REQUIRED BY TOWN ENGINEER TO 2. Reinforcement- ASTM A-615,Grade 60 d POST SATISFY ENVIRONMENTAL CONCERNS. ' I I 3. Loading- AASHTO HS20-44 N � i • �0 4. Joints sealed with mastic sealant U FINPAV�M�W RNISYED CRAVE 5. Inlet & outlet piping and test not supplied Q O Z 6. Coated inside with epoxy sealer LU Q 12" Coated outside with asphalt sealer LU BAC�CFILL 1Q• 3• Z J J 7. Inlet & outlet pipe connections sealed Q N sT7T/?E7J z � � I— aR. .:;..•,; •. AREA Z ';i 112" SQUARE ULU Z :- CONCRETE' BASE W TOWN OF SOUTH WINDSOR R O • SC-310 END CA � Y:::•'�J%:��:• � - O 1..1 r (%� Q APPROVED ' •' �J ''' ' 5' STANDARD DETAIL TRAP HOOD INSTALLATION FINFAV�WW (8) #- FNM CON) SC-310 CHAMBE a JANUARY , 1 9 9 T WELL GRADED GRANULAR BACKFILL WHICH CONTAIN AN REVISED: rustic x0 Kt 01 RECTOR EVEN DISTRIBUTION OF PARTICLE SIZES WITH NO MORE I'/ 2 INCH WASHED THAN 12Y PASSING THE #200 SIEVE COMPACTED TO A MINIMUM OF 957 OF THE STANDARD PROCTOR DENSITY, C IT it /j/ O S CO CRETE PA l „NG SEAL CRUSHED ANGULAR STONE SEE THE TABLE OF ACCEPTABLE FILL MATERIALS IN L7! !V/V!!tY V�3 CONCRETE {/, BITUMINOUS CONCJRET�" Ct1l�g .. STORMTECH'S DESIGN MANUAL, INSTALLATION MANUAL, Sa4X 112` R'1 �-0` z FILTER FABRICOR WWW,STORMTECH•COM. SCALE: 2- -7 ,,• 1-D • ,_,i• / � ELEV•74.00 i1NISXED GRAD£ I 8" CONC,%A3 w/ 6x6 6/ 6/ wwm (2 LA)U5) • 8" COMPACtP 13ANK.1UN GKAV�I - 1 • v► .• a• # 5 �C3AF @ 2 0 OC M N. • t . `, . _ ♦ •? i ♦ 3 BIT. CQNQRETB 6" MIN. .� .atsa��•••`++ ►*.i�i�'t.�:i,�+ ♦ .�'� 1 _ -� • O O O O O . i. 0 o ao t.• • • •+ . • AROl,Sp AGGREGATE t ELE V 7100 +'+'"• ► •.►N. Zl' • 00 0 n n O ""^'"• •- • • CANPACiED STABLE �� J P1... . O o O o o 1 SY/B--BASS :. D1 J: CONIiElE i7ERtf P� era 9" 3" PAWNG MATERIAL 6'ELEV.69.67 �(/f�] R {A� + ENGINEER: FB CM NC. \f TE WALK BASE ,t♦XI d a - c c e.. � I r • r 4' DAJG JV7f! ICJclAI. -1 III=1-1 I=1 11=1 I pi= .s�cAc 1/2Sl - o ARCHITECT: B S COMPPCT�n SLI3GI'At?� 3' o„ (2) Tt 5 ��f3A!? coNr, I I II I I I I I I I I I II) I I II WATER TABLE ELEV,68.50 + PROJECT M G R: PIMH 11,r PD? f2" DRAFTED BY: BF 121 MIN. TYP. 34' 12" MIN. TYP. is :•t: •"':•i:• ✓'r:':r •:ir:i, sr , i•:•,•, • i r: � i , •1'YilEr TW 1/ VI�47.4 JG ��1'AINING WALE 5�C110N . ` .. 2" PROCESSED GRAVEL 5�C110N @ CONCP�1F_ Pum51�p PPV N•T,5, STORMTECH SC-310 CHAMBER SYSTEM I I N.T'5' TYPICAL CROSS SECTION DETAIL . COMPACTED STABLE NOT TO SCALE i «WJ3-BA51E 0 12 STANDARD TYPE C CATCH BASIN LET PIPE 15'ADS .65.50 HDPE REDUCER/ADAPTER (SEE DETAIL THIS SHEET) r---- _---------------------� =' ___ IIr= _-=;.==- SEPARATOR UNIT FERNCO COUPLER WITH SHEAR RING SEE DETA] THIS SHEET CONTAMINANT STORAGE MANHOLE PRECAST CONCRETE STRUCTURE WITH WATERTIGHT JOINTS TO THE TOP OF THE MANHOLE PRIMARY SEPARATION CATCH BASIN PRECAST CONCRETE STRUCTURE WITH WATERTIGHT JOINTS TO THE TOP OF THE GRATE INLET PIPE 15-ADS IN V.65.55 B PLAN VIEW 130' HEAVY DUTY MANHOLE ' '—FRAME AND VENTED COVER ANCHORED SECURELY IN PLACE TERTIGHT CONNECTION MEET ASTM C-923 3/4' MINUS STONE FLOWABLE FILL BENEA SEPARATOR U� PRIMARY CATCH BASIN STORAGE MANHOLE SECTI❑N AA BAYSAVER, INC. - Ph: 301-829-6470 Fax: 301-829-3747 1010 DEER HOLLOW DRIVE, MOUNT AIRY, MD 21771 THE BAYSAVER SEPARATION SYSTEM IS PROTECTED BY U.S. PATENT #5746911 A A CORRUGATED HDPE PIPE WATERTIGHT COUPLER WATERTIGHT COUPLER 4 CORRUGATIONS SEPARATOR ID OUTLET PIPE ID Baysaver Baysaver Maximum Maximum Impervious Separator Manhole Sizes Treatment Treatment Area Unit (prim. x stor.) (cfs)*l (gpm)*1 (acres) 1K Baysaver 48x48 2.4 1076 1.2 Separator BAYSAVER MAINTENANCE BAYSAVER SYSTEMS MUST BE INSPECTED AND MAINTAINED PERIODICALLY. INSPECTION IS MADE BY CHECKING THE DEPTH OF SEDIMENT IN EACH MANHOLE WITH A GRADE STICK OR SIMILAR DEVICE. MAINTENANCE IS REQUIRED WHEN THE SEDIMENT DEPTH IN EITHER MANHOLE EXCEEDS 2 FEET. MINIMUM INSPECTI❑N IS REQUIRED TWICE A YEAR TO MAINTAIN ❑PERATION AND FUNCTION OF BAYSAVER. MAINTENANCE C❑NSISTS OF THE F❑LLOWINGi A. C❑NTAMINANT STORAGE MANHOLE 1. REMOVE THE ENTIRE VOLUME OF THE CONTAMINATED WATER BY VACUUM TRUCK, 2, CLEAN THE MANHOLE WALLS AND FLUSH OUT THE MANHOLE USING A HIGH PRESSURE HOSE AND REMOVE FLUSHING WATER BY VACUUM TRUCK, MAKE CERTAIN MANHOLE IS CLEAN, B. PRIMARY SEPARATI❑N CATCH BASIN 1. USING A SUBMERSIBLE PUMP, PUMP THE CLEAN WATER FROM THE CENTER OF THE CATCH BASIN DIRECTLY INTO THE EMPTY STORAGE CATCH BASIN UNTIL THE WATER LEVEL FALLS TO 1 FOOT ABOVE THE SEDIMENT LAYER, 2, REMOVE THE SETTLED SEDIMENT AND REMAINING WATER BY VACUUM TRUCK, 3. CLEAN THE CATCH BASIN WALLS AND FLUSH OUT THE MANHOLE USING A HIGH PRESSURE HOSE AND REMOVE FLUSHING WATER BY VACUUM TRUCK, MAKE CERTAIN CATCH BASIN IS CLEAN, 4. CONTAMINATED MATERIAL REMOVED FROM THE CATCH BASIN MUST BE DISPOSED OF RESPONSIBLY AND LEGALLY BY THE OPERATOR OF THE VACUUM TRUCK, ELEVATION 71,75 NON-SHI B-AYSAVER INSTALLATI❑N INSTRUCTI❑NS 1. CALL UTILITY LOCATOR TO MAKE CERTAIN IT IS SAFE TO EXCAVATE, 2. STAKE OUT THE LOCATION OF THE PRIMARY AND STORAGE STRUCTURES AND EXCAVATE THE HOLE. SLOPES MYST BE LAID BACK OR SHORED AS REQUIRED. EXCAVATION MUST PROVIDE ADEQUATE SPACE TO CONNECT INLET AND OUTLET PIPES TO SEPARATOR MANHOLE AND THE BAYSAVER UNIT. INSTALL STRUCTURES ON SOLID SUBGRADE AS DIRECTED BY A GE❑TECHNICAL ENGINEER, 3. VERIFY THE SUBGRADE ELEVATION AGAINST THE MANHOLE DIMENSIONS AND C❑NNECTING STORM DRAIN INVERTS. ADJUST BASE AGGREGATE IF NECESSARY 4. INSTALL PRIMARY AND STORAGE MANH❑LES, MAKE SURE THE BASES ARE LEVEL AND THE STORAGE MANHOLE ❑PENINGS ARE ALIGNED WITH THE SEPARATOR UNIT. INSTALL RUBBER GASKETS ON BASE UNITS AND COAT WITH LUBRICATING GREASE, INSTALL ADDITI❑NAL MANHOLE SECTIONS AS REQUIRED. 5. SEAL ALL LIFT HOLES ACCORDING TO APPLICABLE REGULATIONS. 6, BACKFILL BASE SECTIONS OF MANHOLES TO INVERT OF STORAGE MANHOLE CONNECTING PIPES. USING APPROVED BACKFILL MATERIAL, BACKFILL AND COMPACT IN LIFTS WHICH ALLOW FOR ACCEPTABLE COMPACTION. BACKFILL AND COMPACTION SHOULD BE SUPERVISED BY A GE❑TECHNICAL ENGINEER, AND IS CRITICAL TO PREVENT FAILURE OF THE SYSTEM. 7. INSTALL BAYSAVER SEPARATOR UNIT AND C❑NNECTING PIPES. SEAL ALL C❑NNECTING JOINTS AND INSTALL REDUCER OR REDUCER/ADAPTER. PR❑VIDE TEMPORARY SUPPORTS AND HOLD-DOWNS AS NECESSARY TO STABILIZE UNIT DURING REMAINING BACKFILL OPERATION. 8. BACKFILL SEPARATOR UNIT AND MANH❑LES, AREAS NOT ACCESSIBLE TO C❑MPACTI❑N EQUIPMENT MUST BE BACKFILLED WITH 3/4' MINUS STONE OR FL❑WABLE FILL. CONCRETE BACKFILL IS NOT ACCEPTABLE, STONE BACKFILL MYST BE PLACED CAREFULLY TO PROVIDE SUITABLE BEDDING FOR THE BASAVER UNIT AND CONNECTION PIPES. BACKFILL C❑MPACTI❑N SHOULD BE SUPERVISED BY A GE❑TECHNICAL ENGINEER. 9. INSTALL AND SET MANHOLE COVER GRADE ADJUSTMENTS AS NECESSARY. 10. INSTALL AND SET MANHOLE FRAME AND COVER UNITS. 11, FILL STRUCTURES WITH WATER. 12, THE SEPARATION MANHOLE AND THE STORAGE MANHOLE SHALL BE CLEANED WHEN SEDIMENT CONTROL MEASURES ARE REMOVED AND THE SITE IS PERMANENTLY STABILIZED. SEDIMENT AND DEBRIS MUST BE DISPOSED OF PROPERLY. PRIMARY CATCH BASIN SECTION BB GENERAL CONSTRUCTION NOTES 1. ALL WORK MUST BE DONE WITH REGARD FOR THE SAFETY OF THE CONSTRUCTION CREW. 2. ALL WORK AND MATERIALS MUST COMPLY WITH APPLICABLE STATE AND LOCAL REGULATIONS. 3. KNOW THE LOCATION AND DEPTH OF ANY UNDERGROUND UTILITIES BEFORE EXCAVATION BEGINS. NOTE: BAYSAVERS ARE TO BE INSTALLED WITH THE STORM DRAIN SYSTEM AND WILL FUNCTION AS SECONDARY SEDIMENT CONTROL DEVICES. UPON COMPLETION OF SITE STABILIZATION, EACH BAYSAVER SYSTEM SHALL BE FLUSHED CLEAN & THE MANHOLES CLEANED OUT AND REFILLED WITH CLEAN WATER. REDUCER/ADAPTER 'YSTEM PIPE DETAIL THIS SHEET) 12 7 AC 6' 0 FERNC❑ FITTING DETAIL (NOT TO SCALE) DISTANCE AC FERNC❑ NO. SHEAR RING 1K 1 7,10' 1 1055-66 SR-27 BAYSAVER SYSTEM DIMENSIONS DESCRIPTI❑N 1K SYSTEM SEPARATOR MANHOLE DIMENSIONS A PRIMARY MANHOLE DIAMETER 48' B MANHOLE DEPTH BELOW OUTLET 8' - V C MINIMUM FLUID DEPTH 8' - 3' STANDARD SEPARATOR UNIT DIMENSI❑NS D SEPARATOR UNIT ID 24' E SEPARATOR UNIT LENGTH 60' F BYPASS PLATE LENGTH 34" G WEIR/BYPASS PLATE THICKNESS 1/2' H ELBOW AND C❑NNECTING PIPE ❑D 7.125" I ELBOW LENGTH 48' J WEIR HEIGHT ABOVE INVERT 3" K BYPASS PLATE HEIGHT ABOVE INVERT 12' L WIDTH OF WEIR AT BASE 3" M OUTLET PIPE DIAMETER M N ELBOW INVERT HEIGHT ABOVE UNIT INVERT 4 1/2' ❑ ELBOW PIPE OVERHANG 12" STORAGE MANHOLE DIMENSIONS P STORAGE MANHOLE DIAMETER 48' Q MANHOLE DEPTH BELOW INLET/❑UTLET 48' R FLUID DEPTH 8' - 0' S TOTAL STORAGE VOLUME 200 CF SYSTEM DIMENSIONS AND ELEVATIONS T SEPARATOR MANHOLE COVER ELEVATION T U STORAGE MANHOLE COVER ELEVATION U V SEPARATOR MANHOLE FLOOR ELEVATION V W STORAGE MANHOLE FLOOR ELEVATION W X INLET PIPE ID AND MATERIAL X1 X2 Y INLET PIPE INVERT Y1 Y2 Z SEPARATOR UNIT INVERT Z AA OUTLET PIPE ID AND MATERIAL AA AB ELBOW INVERT ELEVATION AB AC CONNECTING PIPE INVERT ELEVATION AC AD CONNECTION PIPE SPACING 20' AE STORAGE MANHOLE SIDE OFFSET 72 ± 6" AF STORAGE MANHOLE DOWNSTREAM OFFSET 23' PDS ENGINEERING & CONSTRUCTION, INC. 107 Old Windsor Road Bloomfield, Connecticut.06002 Telephone: (860) 242-8586 FAX (860) 242-8587 SITE ENGINEERING : (APPLICANT) PDS ENGINEERING & CONSTRUCTION 107 OLD WINDSOR ROAD BLOOM FIELD,CONNECTICUT 06002 860-242-8586 SURVEYOR : PDS ENGINEERING & CONSTRUCTION 107 OLD WINDSOR ROAD BLOOM FIELD,CONNECTICUT 06002 860-242-8586 OWNER : DAVE ZYLBER MAN 350 CHAPEL ROAD SOUTH WINDSOR,CONNECTICUT 06074 860-528-3500 U) U_ F- U Q W Z Z W W 0 W > L,J W o� tY a J z W N o o w W W 71 < z W o ® V♦ 0 t1 O S EAL ENGINEER: FB ARCHITECT: BS 8-all C=1 04 I,I I Y� NORTH ELEVATION uiru CAv� Fecrie CHJ 1 CLCV/'-11 IVIV 7A rA QTAniniKif_` cf7gM ROOF ."M SOUTH ELEVATION 1/8"=1'-0" 30'-0" 11 Krr fll r,--rr'n ... / nn%A/1dQ0 nI ITC -T— FUTURE ADDITION WEST ELEVATION 1 /8"=1'-0" :ONCRETE STAIR OVERHEAD DOOR (TYP.) ��. -LER Id a_ PDS ENGINEERING & CONSTRUCTION, INC. 107 Old Windsor Road Bloomfield, Connecticut. 06002 Telephone: (860) 242-8586 FAX (860) 242-8587 SITE ENGINEERING : (APPLICANT) PDS ENGINEERING & CONSTRUCTION 107 OLD WINDSOR ROAD BLOOM FIELD,CONNECTICUT 06002 860-242-8586 SURVEYOR : PDS ENGINEERING & CONSTRUCTION 107 OLD WINDSOR ROAD BLOOM FIELD,CONNECTICUT 06002 860-242-8586 OWNER : DAVE ZYLBERMAN 350 CHAPEL ROAD SOUTH WINDSOR,CONNECTICUT 06074 860-528-3500 Z 0 C U U z W W wZ J W C) ryU 0 - W o 0 Cn O w W z 0 lei f- W z U LU W z ~ 0 0 0® < W n 0 SEAL ENGINEER: FB ARCHITECT: BS PROJECT MGR: DRAFTED BY: BF _ A=200