HomeMy WebLinkAbout200 deming st code mod. 20141.-ENT OFADMINISTRATIVE sERVICEs STATE OF cONNEcrlcur
DIVISION OF CONSTRUCTION SERVICES
OFFICE OF THE STATE BUILDING INSPECTOR
May 15,2014
Mr.Donald Havener,PECosentiniAssociates1KendallSquare,Suite 82204
Cambridge,MA 02139
RE:M-411-14 The Residence at South Windsor Farms200-Deming Street
South Windsor,Connecticut
Dear Mr.Havener:
i have reviewed the referenced request for modification of Section 334.10(3)ofthe2005NationalElectricalCodeportionofthe2005StateBuildingCode,whichstatesthatTypeNM,NMC and NMS cables are allowed to be used in structures
permitted to be of Types lll,lV,and V construction.
It is my decision that a modification is not required to allow NM cable within a
portion of a building of Type ll construction.This decision is based on the factthatalthoughthebuildingisofTypellconstruction,the design professional hasdemonstratedthatthebuildingcanbeconstructedofTypelllAconstructionthuscomplyingwiththeabovementionedcoderequirement.
lf you have any questions,please contact me at (860)713-5900.
Very truly yours,
Daniel Tierney
Deputy State Building Inspector
DT:jlc
c:Christopher Dougan,South Windsor Building Official
165 Capitol Avenue,Room 265
Hartford,CT 06106
Phone:(860)713-5900 Fax:(860)713-7410 www.ct.gov/dcs
An Affirmative Action/Equa/Opportunity Employer
n
STATE OF CONNECTICUT.
DEPARTMENT OF PUBLIC SAFETYDIVISIONOFFIRE,EMERGENCY &BUILDING SERVICESOFFICEOFTHESTATEBUILDINGINSPECTOR
April 7,2004
_Mr.Joseph ChamberlainChamberlainRemodeling LLC2OWhitonStreetWindsorLocks,CT 06096
RE:.M486~04 349 Clark'Stree‘t ..South Winds‘o’r,Connecticut
Dear Mr.'Chambeflain;
l have reviewed the referenced request'for modification to utilize Section 310.1.0f the 2003 International Residential .COde.‘
It is my decision to approve this modificatiOn,as requested,to utiliZe the'approved language of the referenced section of the2003 InternationalResidentialCode;in lieu of-the requirements-of the 1999 Staten Building Code.This decision is based On the approved language of the model document.
If you have any(-questions,please contact Daniel Tierney,Deputy State BuildingInspector,at (860)685-831 0.‘I
Christopher R.Laux',AIAStateBuildingInspector
CRL:DT:p‘mcc:Christopher Dougah,south Windsor Buildingbfhciai
.v ‘a _‘,:Telephone (860)685-83 101111CounttyClub'Ro’ad P.O.Bo'x 2794MiddletoWn,CT 06457-9294http://www.state.ct.us/dps/dfebsAnEqualOppoxtunity Employer
STATE OF CONNECTICUT
DEPARTMENT OF PUBLIC SAFETYDIVISIONOFFIRE,EMERGENCY &BUILDTNG SERVICESOFFICEOFTHESTATEBUILDINGINSPECTOR
December 28,2004
Ted Montana Grill
500 Evergreen Way,Suite 500SouthWindsor,CT 06074
RE:M-1 787-04 %§ulldlgg600-EvergreenWaySouthWindsor,Connecticut
Dear Sir or Madam:
l have reviewed the referenced request for modification to utilize Sections 419.1and425.1,ofthe 2003 International Plumbing Code.
It is my decision to approve this modification,as requested,to utilize theapprovedlanguageofthereferencedsectionofthe2003InternationalPlumbing ‘Code,in lieu of the requirements of the 1999 State Building Code.This decisionisbasedontheapprovedlanguageofthemodeldocument.
lf you have any questions,please contact Daniel Tierney,Deputy State Building
‘ris op er R.Laux,AIAStateBuildingInspector
CRL:DT:pm ,cc:Christopher Dougan,South Windsor Building Official
r Telephone (860)685-83 101'1 ll Country Club Road P.O.Box 2794Middletown,CT 06457-9294http://wwwstatectus/dps/dfebsAnEqualOpportunity Employer
i ’
TATE OF CONNEG
DIVISION OF CONSTRUCTION SERVICES
OFFICE OF THE STATE BUILDING INSPECTOR
N T OF ADMINISTRATIVE SERVICE S
September 12,2014
Mr.Donald Havener
Consentini Associates
1 Kendall Square,Suite 82204
Cambridge,MA 02139
RE:M-713-14 The Residence at South Windsor Farms
200 Deming Street
South Windsor,Connecticut
Dear Mr.Havener:
i have reviewed the referenced request for modification of Section 711.4,of the
2003 lnternationai Building Code portion of the 2005 State Building Code,which
states in part that horizontai assemblies shall be continuous without openings,
penetrations or joins except as permitted.
iit is my decision to approve this modification,as requested,and allow the
penetration of horizontal assemblies as submitted within the September 10,
2014,revised request for modification,with the stipulation that the submitted
corrections be inspected and approved by a special inspector whose
qualifications shall be’r%iewed an by the South Windsor Building
Official,Mr.Christopher Dougan.This decision is based on the alternative
means and methods provided that result in equivalent fire safety.
lf you have any questions,please contact me at (860)71 3—5900.
Very truly yours,
r ,W
Daniel Tierney
Deputy State Building inspector
DTzjlc
c:Christopher Dougan,South Windsor Building Official
Terry Brouwer,OSFM
165 Capitol Avenue,Room 265
Hartford,CT 06106
Phone:(860)713-5900 Fax:(860)713—7410 www.ct.gov/dcs