HomeMy WebLinkAbout107 PINE KNOB DR APPLICATION FOR HVAC PERMIT
DEPARTMENT DECISION TOWN OF SOUTH WINDSOR PERMIT#
Application is hereby: BUILDING DEPARTMENT 1-10 o2'51
APPROVED 1540 SULLIVAN AVENUE
644-2511 ext. 230 Bldg.Permit#
Date Building Inspector
Application must be printed or typed
FEE SCHEDULE Location of Job:
$041,000=$15.00 l D 7 yam �•70Zi
Over$1,000= Street No. Street Lot No.
$15.00 per$1,000
or any fraction thereof Tenant Designation Apt..No.
APPLICANT rZy G''-l�1 SfL✓i S�
APPLICANT ADDRESS
APPLICANT'S PHONE#
OW N $� OWNER
A & OWNER ADDRESS -;x
(107 OWNER PHONE
CO ] ESTIMATED COST$ ��C>
U IS THIS A CONTRACT COST? � Yes No
� FEE ENCLOSED$ �
TYPE OF JOB:
OR•COS New Installation
XAlteration/Addition/Repair
2-6 [7 6
Revised 03/05/10
APPLICATION FOR HVAC PERMIT(Continued from feverse side)
TYPE OF SYSTEM: TYPE OF BUILDING:
❑ HEATING OrRESIDENTIAL
R4V'C ❑ COMMERCIAL
❑ VENTILATION ❑ INDUSTRIAL
HEATING
❑ STEAM LOW PRESSURE LIMIT LBS. HIGH PRESSURE LM41t LBS.
❑ HYDRONIC ❑ WARM AIR ❑ UNIT RADIANT HEATER
EXISTING RADIATION ADDITIONAL RADIATION TOTAL RADIATION
DESIGN TEMP.OUTSIDE OF INSIDE OF DIFFERENCE OF
TOTAL HEAT LOSS(BTUH) OF(BEAT LOSS SHEET MUST ACCOMPANY APPLICATION)
DESCRIBE ALL HEATING EQUIPMENT(INCLUDING MAKE&MODELLNO.)
5 tA� 141G �a� /- 6 c�S;e 62 7�
� s 60.f4-cam
GROSS HEATING CAPACITY(INPUT-BTUH) �.��GNET RATING(OUTPUT-BTUH)
TYPE OF FUEL
❑ OIL-GPM OIL TANK LOCATION: ❑ INSIDE ❑ OUTSIDE CAPACITY
❑ GAS-INPUT LPG TANK CAPACITY ELECTRIC-KW
AIR CONDITIONING
DESIGN TEMP: OUTSIDE YS�-F INSIDE °F DIFFERENCE OF
TOTAL HEAT GAIN(BTUH) 2 AYIJEAT GAIN SHEET MUST ACCOMPANY APPLICATION)
DESCRIBE ALL COOLING EQUIPMENT(INCLUDING MAKE&MODEL NO.)
TONNAGE ` COOLING CAPACITY(BTUH)
VENTILATION
DESCRIBE ALL AIR HANDLING EQUIPMENT(INCLUDING KITCHEN EXHAUST EQUIPMENT)
TOTAL SIZE OF SYSTEM(CFM) FRESH AIR INTAKE(CFM)
(PLANS MUST ACCOMPANY APPLICATION) -
FURTHER DESCRIPTION OF WORK
THE UNDERSIGNED HEREBY APPLIES FOR A PERMIT TO PERFORM THE WORK DESCRIBED AND IS TO
COMPLY WITH ALL LOCAL ORDINANCES AND STATE OF CONNECTICUT BUILDING CODES IN THE
PERFORMANCE OF SUCH WORK.
CONTRACT RS LICENSE NO. TYPE STATE
SIGNATURE OF APPLICANT i '�`� DATE
NXA6
HIGH EFFICIENCY UP TO 16 SEER AIR CONDITIONER
ENVIRONMENTALLY SOUND R-410A REFRIGERANT
1%THRU 5 TONS SPLIT SYSTEM
208/230 Volt, 1-phase, 60 Hz
c
REFRIGERATION CIRCUIT
• Scroll compressors on all models
• Filter-drier supplied with every unit for field installation
• Copper tube/aluminum fin coil
•48 and 60 models for higher SEER. lower capacity
•49 and 61 models for higher capacity, lower SEER
EASY TO INSTALL AND SERVICE
• Easy access service valves on all models
• External high and low refrigerant service ports Use of the AHRI Certified TM Mark
• Only two screws to access control panel indicates a manufacturer's participation in
the program.For verification of certification
• Factory charged with R-410A refrigerant for individual products go to
BUILT TO LAST wwa.ahndiredory.org.
• Baked-on powder coat finish over galvanized steel
• Post-painted (black) coil fins C@US
• Coated, weather-resistant cabinet screws LISTED
• Coated inlet grille with 3/8"(10mm) spacing for extra protection (hail guard)
WARRANTY*
NER
�:°w�.��•a ��.�
,•i,•nq•r• Nrpo• x bw
5 year compressor limited warranty •• „ °°"�=��e'•°^°°'" „°°
obw nuM1e •lrpon cn.rpvq• •bw�
n wn*m poprcNrp••M•Mow ry
• 5 year parts limited warranty (including compressor and coil) •°�•••w•• •� •n•• �•
-With timely registration, an additional 5 year parts limited warranty(including compressor and coil)
* For owner occupied, residential applications only. See warranty certificate for complete details and restrictions.
including warranty coverage for other applications
UNIT PERFORMANCE DATA
Model Size Nominal Min. Circuit Max. Fuse Operating Dimensions Ship/Operating Notes
Number (tons) Btu/hr Ampacity or Breaker height x width x depth in.(mm) Weight lbs. (kg)
NXA618GKA 1'/2 18,000 11.8 20 28-11/16 x 25-3/4 x 25-3/4 154/ 125 (70/57)
729 x 654 x 654
NXA624GKA 2 24,000 17.7 25 28-5/16 x x 792 x 792 x 31-3/16
719 x 92 x 147/ 183(83/67)
NXA630GKA 2'/z 30,000 16.8 25 32-5/16 821 x 792 x 792 x 31-3/16 188/ 153(85/69)
x 92 x
NXA636GKA 3 36,000 18.1 30 28-5/16 x 35 x 35 204/ 165(93/75)
719 x 889 x 889
NXA642GKA 3'/2 42,000 23.6 40 39-1/8 x 35 x 35 254/213 (115/96)
994 x 889 x 889
NXA648GKA 4 48,000 26.1 40 39-1/8 x 35 x 35 317/264(144/ 120)
994 x 889 x 889
NXA649GKA 4 48,000 28.4 40 39-1/8 x 35 x 35 269/231 (122/ 105)
994 x 889 x 889
NXA660GKA 5 60,000 28 40 45-15/16 x 35 x 35 310/272 (141 / 123)
1167 x 889 x 889
NXA661 GKA 5 60,000 32.5 50 45-15/16 x 35 x 35 310/272 (141 / 123)
1167 x 889 x 889
Specifications subject to change without notice.
END4X
VERTICAL EVAPORATOR COILS
CASED WCOILS
1'/s THRU 5 TONS
ENVIRONMENTALLY SOUND R-410A SYSTEMS
• Bolt-on TXV metering device factory installed on all models
(equalizer tube brazed in)
•Two condensate drain connections
• Cabinet widths match flush with ICP 14-3/16", 17-1/2",21"
and 24-1/2"gas furnace cabinets
(field fabricated transitions required to match other ICP furnace models)
• Removable front access panel
• Hemmed flanges for safer handling .,
• Foil faced insulation
• Non-sweat cabinet, even at extreme conditions
• Cabinets meet or exceed 2%air leakage codes
• Sturdy, pre-painted steel cabinet
• Upflow or downflow installation
• Compact design, shorter than comparable A-coils
•Aluminum main tubing and aluminum fins(copper stubs for field connection) C@US
WARRANTY*
• 5 year parts limited warranty LISTED
-With timely registration, an additional 5 year parts limited warranty
' For owner occupied, residential applications only. See warranty certificate for
complete details and restrictions, including warranty coverage
for other applications
Use of the AHRI Certified TM Mark indicates
a manufacturer's participation in the program.
For verification of certification for individual
products,go to www.ahndirectory.org.
UNIT PERFORMANCE DATA UNIT PERFORMANCE DATA
Model Size Dimensions Model Size Dimensions
Number (tons) H x W x D inches (mm) Notes Number (tons) H x W x D inches(mm) Notes
END4X18L14A 12-5/8 x 14-3/16 x 21 END4X37L17A 3 27-3/16 x 17-1/2 x 21
1-1/2 321 x 360 x 533 691 x 445 x 533
17 x 17-1/2 x 21 21-1/8 x 17-1/2 x 21
END4X19L17A (432 x 445 x 533) END4X42L17A 537 x 445 x 533
END4X24L14A 14-5/8 x 14-3/16 x 21 END4X42L21A 3-1/2 19 x 21 x 21
2 (372 x 360 x 533 483 x 533 x 533
14-5/8 x 17-1/2 x 21 26-5/16 x 24-1/2 x 21
END4X24L17A (372 x 445 x 533 END4X43L24A 669 x 622 x 533
17 x 14-3/16 x 21 22-1/16 x 21 x 21
END4X30L14A (432 x 360 x 533) END4X48L21A 560 x 533 x 533
END4X30L17A 2-1/2 17 x 17-1/2 x 21 END4X48L24A 4 22-1/16 x 24-1/2 x 21
(432 x 445 x 533) (560 x 622 x 533
23-1/4 x 17-1/2 x 21 26-7/8 x 24-1/2 x 21
END4X31 L17A 591 x 445 x 533 END4X60L24A 5 683 x 622 x 533
END4X36L17A 17 x 17-1/2 x 21 END4X61L24A P
2-7/16 x 24-1/2 x 21
3 432 x 445 x 533 824 x 622 x 533
END4X36L21A 17 x 21 x 21
432 x 533 x 533
Specifications subject to change without notice.
107 Pine Knob Drive South Windsor
HVAC Load Calculations
for
Joel Benitez
107 Pine Knob Drive
South Windsor Ct. 06074
it
ftsiDxwffmL.
R H VAC WAC LOAos
Prepared By:
Robert Starvish
Quality Heating&Cooling DBA Airesery
148 Prospect Hill Rd.
East Windsor Ct. 06088
860.627.9455
Tuesday,June 13,2017
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
Rhvac•Residential&Light Commercial HVAC Loads Ellie software Development,Inc.
Quality Heatinq&Coolinq 107 Pine Knob Drive South Windsor
East Windsor. T 08 Page 2
[Project Rport - - - - - -
General Poct Information _
Project Title: 107 Pine Knob Drive South Windsor
Designed By: Robert Starvish
Project Date: Wednesday, May 10, 2017
Client Name: Joel Benitez
Client Address: 107 Pine Knob Drive
Client City: South Windsor Ct. 06074
Client Phone: 860-970-2069
Client E-Mail Address: jbsupr94@gmail.com
Company Name: Quality Heating & Cooling DBA Airesery
Company Representative: Robert Starvish
Company Address: 148 Prospect Hill Rd.
Company City: East Windsor Ct. 06088
Company Phone: 860.627.9455
Company Fax: 860.292.6325
Company E-Mail Address: AireservNCC@gmail.com
Company Website: AireServ.com/North-Central-CT
Design Data --_ _ -
Reference City: Windsor Locks Bradley Field, Connecticut
Building Orientation: Front door faces South
Daily Temperature Range: Medium
Latitude: 42 Degrees
Elevation: 197 ft.
Altitude Factor: 0.993
Outdoor Outdoor Outdoor Indoor Indoor Grains
Dry Bulb Wet Bulb Rel.Hum Rel.Hum Di)( Bulb Difference
Winter: 8 7.07 n/a n/a 70 n/a
Summer: 88 71 44% 50% 75 22
Check Figures _-- -- -
Total Building Supply CFM: 763 CFM Per Square ft.: 0.862
Square ft. of Room Area: 886 Square ft. Per Ton: 483
Volume (ft'): 6,643
BuildingLoads
Total Heating Required Including Ventilation Air: 31,850 Btuh 31.850 MBH
Total Sensible Gain: 16.671 Btuh 76 %
Total Latent Gain: 5,334 Btuh 24 %
Total Cooling Required Including Ventilation Air: 22,005 Btuh 1.83 Tons (Based On Sensible +
Latent)
Notes -- - -- - — - - - - -- -- -- -- -- -
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition. Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data
at your design conditions.
CA...\107 Pine Knob Drive South Windsor.rh9 Tuesday, June 13, 2017, 11:24 AM
Rhvac-Residential&Light Commercial HVAC Load* Elko Software Development,Ine.
Quality Heating&Cooling 107 Pine Knob Drive South Windsor
East Windsor.CT 06088 Page 3
Load Preview Report
Net, ft.' Sen Let Net San Sys
C sI Sys Duct
Scope To /Ton Area Gain Gain Gain Loss � Size
i _ CFM CFM CFM
Building 1.83 483 886 16,671 5,334 22,005 31,850 399 763 763
System 1 1.83 483 886 16,671 5,334 22,005 31,850 399 763 763 20x8
Supply Duct Latent 148 148
Return Duct 0 252 252 1,318
Zone 1 886 16,671 4,934 21,605 30,532 399 763 763 20x8
1-Kitchen 224 5,183 1,262 6,445 7,573 99 237 237 3-5
2-Bath 1 38 371 21 392 1,243 16 17 17 1-5
3-Master Bedroom 180 3,129 1,207 4,336 6,220 81 143 143 2-5
4-Livinq 224 3,246 130 3,376 7,857 103 149 149 2-5
5-Bedroom#2 93 1,781 1,128 2.909 2,641 35 82 82 1-5
6-Bedroom#3 127 2,962 1,186 4,148 4.998 65 136 136 2-5
C:\ ...\107 Pine Knob Drive South Windsor.rh9 Tuesday, June 13, 2017, 11:24 AM
Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development,Inc.
Quality Heatinq 8 Coolinq 107 Pine Knob Drive South Windsor
East Windsor, - - - - Page 4
Duct Size Preview
Room or l Velocity � SP Velocity Length lg Clg Act. Duct
Duct H
Duct Name Souroe ' minimum Max'locm Factor', Design100' Loss, Duct, Flow Flow Flow Size
System 1
Supply Runouts
Zone 1
1-Kitchen Built-In 450 750 0.01 0.1 580.1 99_ 237 3-5
2-Bath 1 Built-In 450 750 0.01 0.1 124.4 16 17 1-5
3-Master Bedroom Built-In 450 750 0.01 0.1 525.3 81 143 2-5
4-Living Built-In 450 750 0.01 0.1 544.9 103 149 2-5
5-Bedroom#2 Built-In 450 750 0.01 0.1 597.8 35 82 1-5
6-Bedroom#3 Built-In 450 750 0.01 0.1 497.2 65_� 136 2-5
Other Ducts in System 1
Supply Main Trunk Built-In 650 900 0.003 0.1 686.9 399 763 20x8
Summary
System 1
Heating Flow: 399
Cooling Flow: 763
CA...\107 Pine Knob Drive South Windsor.rh9 Tuesday, June 13, 2017, 11:24 AM
Rhvac-Residential&Light Conworcial 14VAC Loads Elite Software Development,Ina
Qualitv Heating&Cooling 107 Pine Knob Drive South Windsor
East Windsor,CT 06088 Pag
Total Building Summary Loads I
Component Area Sen Lat Sen Total.
jDesc_r-iption- Quan _ _ .Loss Gain Gain _ _ Gain)
1D-cv-o: Glazing-Double pane, operable window, clear, 107.6 3,803 0 3,838 3,838
vinyl frame, u-value 0.57, SHGC 0.56
1 E-cv: Glazing-Double pane window, fixed sash, clear, 7.2 249 0 258 258
vinyl frame, u-value 0.56, SHGC 0.66
11 D: Door-Wood - Solid Core 18 435 0 91 91
11 F: Door-Wood - Solid Core With Metal Storm 20.2 352 0 136 136
12B-Osw: Wall-Frame, R-11 insulation in 2 x 4 stud 712.5 4,285 0 1,526 1,526
cavity, no board insulation, siding finish, wood studs
12B-Osw: Part-Frame, R-11 insulation in 2 x 4 stud cavity, 72 433 0 82 82
I no board insulation, siding finish, wood studs
166-19: Roof/Ceiling-Under Attic with Insulation on Attic 885.8 2,693 0 2,085 2,085
Floor (also use for Knee Walls and Partition Ceilings),
Vented Attic, No Radiant Barrier, Dark Asphalt
Shingles or Dark Metal, Tar and Gravel or Membrane,
R-19 insulation
19A-Ocp: Floor-Over enclosed crawl space, No insulation 885.8 6,086 0 1,276 1,276
on exposed walls, sealed or vented space, passive,
no floor insulation, carpet or hardwood
Subtotals for structure: 18,336 0 9,292 9,292
People: 3 3,270 2,130 5,400
Equipment: 1,131 2,784 3,915
Lighting: 0 0 0
Ductwork: 8,941 400 1,962 2,362
Infiltration: Winter CFM: 68, Summer CFM: 35 4,573 533 503 1,036
Ventilation: Winter CFM: 0, Summer CFM: 0 _ _ 0 0 _ 0 0_
Total Building Load Totals: 31,850 5,334 16,671 22,005
Leheck Figures _ _ _ . ..
Total Building Supply CFM: 763 CFM Per Square ft.: 0.862
Square ft. of Room Area: 886 Square ft. Per Ton: 483
Volume (ft3): 6,643
Building Loads
Total Heating Required Including Ventilation Air: 31,850 Btuh 31.850 MBH
Total Sensible Gain: 16,671 Btuh 76 %
Total Latent Gain: 5,334 Btuh 24 %
Total Cooling Required Including Ventilation Air: 22,005 Btuh 1.83 Tons (Based On Sensible +
Latent)
Notes___
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data
at your design conditions.
C:\ ...\107 Pine Knob Drive South Windsor.rh9 Tuesday, June 13, 2017, 11:24 AM
Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development,Inc.
Quality Heating&Cooling 107 Pine Knob Drive South Windsor
Windsor.East T 06088 Page 6
s stem 1 Summary_ Loads---____ _ -
Component Area Son Lat Son Total
DOSCrbtlon Quan loss Gain Gain Gain
1 D-cv-o: Glazing-Double pane, operable window, clear, 107.6 3,803 0 3,838 3,838
vinyl frame, u-value 0.57, SHGC 0.56
1 E-cv: Glazing-Double pane window, fixed sash, clear, 7.2 249 0 258 258
vinyl frame, u-value 0.56, SHGC 0.66
11 D: Door-Wood -Solid Core 18 435 0 91 91
11 F: Door-Wood -Solid Core With Metal Storm 20.2 352 0 136 136
126-0sw: Wall-Frame, R-11 insulation in 2 x 4 stud 712.5 4,285 0 1,526 1,526
cavity, no board insulation, siding finish, wood studs
1213-0sw: Part-Frame, R-11 insulation in 2 x 4 stud cavity, 72 433 0 82 82
no board insulation, siding finish, wood studs
1613-19: Roof/Ceiling-Under Attic with Insulation on Attic 885.8 2,693 0 2,085 2,085
Floor(also use for Knee Walls and Partition Ceilings),
Vented Attic, No Radiant Barrier, Dark Asphalt
Shingles or Dark Metal, Tar and Gravel or Membrane,
R-19 insulation
19A-Ocp: Floor-Over enclosed crawl space, No insulation 885.8 6,086 0 1,276 1,276
on exposed walls, sealed or vented space, passive,
no floor insulation,_carpet or hardwood
Subtotals for structure: 18,336 0 9,292 9,292
People: 3 3,270 2,130 5,400
Equipment: 1,131 2,784 3,915
Lighting: 0 0 0
Ductwork: 8,941 400 1,962 2,362
Infiltration: Winter CFM: 68, Summer CFM: 35 4,573 533 503 1,036
Ventilation: Winter CFM: 0, Summer CFM: 0 0 0 0 0
System 1 Load Totals: 31,850 5,334 16,671 22,005
-Foures
Supply CFM: 763 CFM Per Square ft.: 0.862
Square ft. of Room Area: 886 Square ft. Per Ton: 483
Volume(ft3): 6,643
Loacis
Total Heating Required Including Ventilation Air: 31,850 Btuh 31.850 MBH
Total Sensible Gain: 16,671 Btuh 76 %
Total Latent Gain: 5,334 Btuh 24 %
Total Cooling Required Including Ventilation Air: 22,005 Btuh 1.83 Tons(Based On Sensible+
Latent)
Notes
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data
at your design conditions.
C:\...\107 Pine Knob Drive South Windsor.rh9 Tuesday, June 13, 2017, 11:24 AM
Rhvac-Residential&Light Commercial HVAC Loads Ellie Software Development,Inc.
Quality Heating&Cooling * 107 Pine Knob Drive South Windsor
East Windsor,CT 06088 Page 7
S stem 1 Room Load Summary
vp in lwwgwoRww Clg Clg Min Act
Room Area Sens Htg Duct Duct Sens Lat Clg Sys
No Name SF Btuh CFM Size Vel Btuh Btuh CFM CFM
---Zone 1---
1 Kitchen 224 7,573 99 3-5 580 5,183 1,262 237 237
2 Bath 1 38 1,243 16 1-5 124 371 21 17 17
3 Master Bedroom 180 6,220 81 2-5 525 3,129 1,207 143 143
4 Living 224 7,857 103 2-5 545 3,246 130 149 149
5 Bedroom#2 93 2,641 35 1-5 598 1,781 1,128 82 82
6 Bedroom#3 127 4,998 65 2-5 497 2,962 1,186 136 136
Duct Latent 148
Return Duct 1,318 0 252
System 1 total 886 31.850 399 16,671 5,334 763 763
System 1 Main Trunk Size: 20x8 in.
Velocity: 687 ft./min
Loss per 100 ft.: 0.089 in.wg
Cooling System Summary_____
Cooling Sensible/Latent Sensible Latent Total
Tons Split Btuh Btuh Btuh
Net Required: 1.83 76%/24% 16,671 5,334 22,005
Equipment Data
Heating System Cooling System
Type: Natural Gas Furnace Standard Air Conditioner
Model:
Indoor Model:
Brand:
Efficiency: 0 AFUE 0 SEER
Sound: 0 0
Capacity: 0 Btuh 0 Btuh
Sensible Capacity: n/a 0 Btuh
Latent Capacity: n/a 0 Btuh
C:\...\107 Pine Knob Drive South Windsor.rh9 Tuesday, June 13, 2017, 11:24 AM
,
' -" .. -J: ...► ,Y'•.,Y.. _.-:y,;.,y ,.cNas �C-y.•r-:_ •„/�,•t•, �;...Z. �.. :Y�.. a.R.-t •sue. .r -_ -..:f' -• ;,;4 ^"�'..
Lot Number; r ±f e r to 11.iap Entitl'�c:
"Subuivision Map, Fine K.no4 Hill Sectiort.i
Av,2ry Street, South Wi:iasor• Connecticut
1'r•operty of I. R Stich Asso( iatrs J.-I Scale
-5t)' April 20, 1959,-Revised April'25, 1959
Liwk:ing i.�7�. ;Lt,'(1 As S'ttoWn
Hrrrc.•n OIAO�2)c• 31 1951 ropcjaeri Layout
i
I StAc;- Ast)oc:iates, Inl.
S Pin'c 'Knob Hill
(-r.:•titir.d substantially corr4tct l :tie Knob
No zoning violation South Wiudsor, Connecticut
Sc-ale I "r6U' April '426, 1454
10-7
of ouc (�
Cf2ftC-)
s1�o�a a-
303P - a _3d
77:"
----------- FYI
Lot Numbe.r, r :!fer to Map Entitl.--d
'Subdivision Map, Fine Knob Hii-I Sectiorx.1
Av,:!ry Street, South W-Anasor. Connecticut
1-roperty of I. R StIcIt; Assr.)( iatvs 'file Scale
:'60' April 20, 1959.-Revised April- 25, 1959
Builf:ing ;xt..-d As Shown
0-.toI.)L- 3i 145
Layout
Pine' Knob Hill
szibtstantialiy corr,!.zt P:nob Drive
No --oning vi(.)I;Atiois South 'Niiidsor, Connecticut
Srale I "=60' April 26, 1454
Division of Construction Services
Office of the State Building Inspector
September 1,2021
Joel Benitez
107 Pine Knob Drive
South Windsor,CT 06074
Email:jbsupra94@gmail.com
Request for Modification of the 2018 Connecticut State Building Code
Subject Property: 107 Pine Knob Drive,South Windsor
CASE NUMBER: M-21-0597
Dear Mr.Benitez,
I have reviewed your request for modification of Section R305.1 exception 4 of the 2015 International Residential
Code portion of the 2018 Connecticut State Building Code which states:
Ceiling height in existing basements being converted to habitable space shall not be less than 6 feet 8 inches(2032 m)
clear except under beams,girders,pipes,ducts or other obstructions where the clear height shall be a minimum of 6
feet 4 inches(1931 mm).
Modification requested:
To allow a headroom height of 6'0"under a beam in an existing basement being converted into habitable space.
Decision: APPROVED.
The approval of this modification,to allow a headroom as described, is based on existing conditions that preclude
strict compliance with the requirements for new construction.
This modification is specific to the subject property and the circumstances identified in your application. If you have
any questions,please contact me at 860-713-5900.
Sincerely,
4� V. C�
Joseph V. Cassidy,P.E.
State Building Inspector
C: Darren Hobbs,Director/Deputy State Building Inspector
Kenneth Rich, South Windsor Building Official
450 Columbus Blvd Suite 1303
Hartford,CT 06103
Phone:(860)713-5900 Fax:(860)713-7900 www.ct.gov/dcs
An Affirmative Action/Equal Opportunity Employer
APPLICATION FOR ELECTRICAL PERMIT
DEPARTMENT DECISION TOWN OF SOUTH WINDSOR pgRMTT#
*Applr* oeb BUILDING DEPARTMENT 1(00®5lO
1540 SULLIVAN AVENUE
644-2511 ext. 230Bldg:Permit#
Danspector ,
-14d o y�C�
Application must be printed or typed
FEE SCHEDULE 11 Location of Job:
$041000=$15.00
Over$1,000= Street No. Street Lot No.
$15.00 per$1,000
or any fraction thereof Tenant Designation Apt:No.
1 �
APPLICANT JA —
APPLICANT ADDRESS
t
APPLICANT'S PHONE# — ( 7 S
OW N 3f OWNER
® '� OWNER ADDRESS 10'ir
C OWNER PHONE —
C ESTIMATED COST$ 1000
U IS THIS A CONTRACT COST? Yes No
FEE ENCLOSED$
TYPE OF JOB:
`sOR•C� _ NN w Installation
" Alteration/Addition/Repair
*,ZdfCeofbL4o
Revised 03/05/10
APPLICATION FOR ELECTRICAL PERAUT(Continued from reverse side)
TYPE OF BUILDING IS THIS APPLICATION ASSOC D WITH A
BUILDING PERMIT APPLICATION? YES ❑ NO
W/RESIDENTTAL CURRENT USE AND OCCUPANCY
❑ BUSINESS
❑. ASSEMBLY FUTURE USE AND OCCUPANCY
❑ EDUCATIONAL
❑ INSTITUTIONAL ENGINEER'S NAME PHONE
❑ FACTORY
0. STORAGE ADDRESS
Cl GARAGE .
❑ MIXED USE CITY STATE ZIP
(Other please specify)
TYPE OF INSTALLATION/WIRING METHOD.
SIZE OF SERVICE SIZE OF MAIN CONDUCTORS ..
NUMBERS OF METERS NUMBERS.OF DISCONNECTS AND RATINGS
NUMBERS OF PANELS I NUM BERS.OF DISCONNECTS REQUIRED? ❑ YES ❑ NO
NUMBERS OF LIGHT CIRCUITS NUMBER OF POWER CIRCUITS
NUMBER OF SWITCHES. NUMBER OF OUTLETS 3 .
NUMBER OF`LIGHT FIXTURES NUMBER OYHEAT CIRCUITS
NUMBER`OFA/C CIRCUITS
SEPARATE HEAT LOSS AND A/C CALCULATIONS MUST BE SUBMITTED.
DESCRIPTION OF WORK
(w� �f
0 e
THE UNDERSIGNED HEARBYAPPLIES FOR A PERMIT TO PERFORM THE WORK DESCRIBED AND IS TO
COMPLY WITH ALL LOCAL ORDINANCES AND STATE OF CO
NNECTICUT BUILDING CODES IN THE PERFOR-
MANCE OF SUCH WORK t
CONTRACTORS LICENS O. TYPE STATE
SIGNATURE OF APPLICANT DATE `�
BUILDING PERMIT. J4,416
STATE OF CONNECIICUT
WORKERS'CQOWENSA11ON CONSUSSION
Building Permit Affidavit for Property Owners or Sole Proprietors
(Corm.Caen.Stat.131.286b)
Property looted at_ ( 1=�t`n e k no �r
In the town of
Name of building permit applicant: ( �
Please check one:
I._I,a�the owner of the above property.
2._I am the sole proprietor of a business.
2A.Name of business I v �- ,t'1 •z
2B.Federal Employer Ids' ication Number(FBIld)
..................................................................................................:.:.....:..::.....
Pursuant to 131-280,"a.property owner or sole proprietor(who]i;;a m act as a generd
contractor or principal employer"may provide either a certificate of workers'compensation
hommce or a"swam notariaod affidavit...stating that he wM require proof of workers'
compensation inaau=w for all dxW employed on the job site in accordance with this chapter."
Please check one:
1._I do not intend to act as a general contlacor or principal employer.
[sign and stop herel
jSignature of applicant
2..-✓ I iUftd to act as-a gene it contractor or P�employer.' cilicant must either
1� Applicant
IRMA&a oortificate of*Mkers`compensation insurance or sign the affidavit
below:
........................................................................:...........................................
Affidavit
I hereby swear and melt that I will re4uim proof of workers'compensation hmrrmoo for every
contractor,subcentactor,or other wmkw before he/she cnpgw in work on the above property in
accordance with the vorkers' mpensation Act(Chapter 568).
I understand that pursuant to 131-27S CO.S.,offic.irs of a cagocatim and partam in a
_P&t mh*i may dad to ba=AxW firm oaverage Jby a wah ee with the app_s ate_-
_ DistrictOffiW srtddwa Qriet+cr isatreI bodt�=ls eco�ugormieashe
Files his.
Sa4�
Subscrr'bed and sworn to before me fib day of ;204L
(Notary Public/Commissioner of the Superior Court)
DEPARTMENT DECISION APPLICATION FOR PLUMBING PERMIT PERMIT#
Application is hereby: TOWN OF SOUTH WINDSOR
BUILDING DEPARTMENT
APPRM:,,, 1540 SULLIVAN AVENUE
644--2511 EXT.230 l i Bldg. g#
(Date (Building Inspector)
A pplication must be printed or typed
FEE SCHEDULE / Location of Job:
A kt•c&- ti.11
$041,000=$l 5.00 Street No. Street Lot No.
Over$1,000-
$15.00 per$1,000
or any fraction thereof Tenant Designation Apt.No.
APPLICANT
APPLICANT ADDRESS 4e— !Cn 1L 1�
APPLICANT PHONE# raA n)r,
SOW N SFq OWNER
OWNER ADDRESS /,b 4 2,,ti P
0 y 1 a # OWNER PHONE ,l J �� r�0,
�--»
C 1 ESTIMATED COST $ �� O 0
IS THIS A CONTRACT COST? YES ENO
FEE ENCLOSED$ )L
TYPE OF JOB: (� C4
OR-Co New Installation
�lteration/Addition Repair
�o��, oloy6
Revised 12/22/11
APPLICATION FOR PLUMBING PERMIT (Continued from reverse side)
TYPE OF BUILDING IS THIS APPLICATION ASSOCIATED WITH A
RESIDENTIAL BUILDING PERMIT APPLICATION_ ? ❑ YES /'NO
O BUSINESS CURRENT USE AND OCCUPANCY (� �/
O ASSEMBLY
O MERCANTILE FUTURE USE AND OCCUPANCY( { `
O EDUCATIONAL
O FACTORY
O STORAGE ENGINEER'S NAME�� Q PHONE
O GARAGE
O MIXED USE ADDRESS
(Other please specify) CITY STATE ZIP
TYPE OF INSTALLATION I-0 1p r,,, h fd6ij,0Y ke�) SIZE OF MAIN DRAIN
KI)kIleh srvt A
NO. OF TOILETS STYLE NO.URINALS STYLE
NO. OF BATHTUBS NO. OF SHOWERS NO. OF LAVATORIES
NO.OF CONDUCTORS SIZE NO.OF STACKS SIZE
AREA OF ROOF NO.OF CATCH BASINS NO.OF FLOOR DRAINS
NO.OF OTHER FIXTURES KIND
ARE TOILET COMPARTMENTS VENTILATED TO OUTER AIR BY A WINDOW O YES O NO
SIZE OF WINDOW IF NONE C.F.M.OF VENTILATOR
SIZE OF DUCTS SEWER OR SEPTIC TANK
SIZE OF WATER MAIN SIZE OF WATER PIPING&RISER
WATER HEATER: TYPE MANUFACTURER
DESCRIPTION OF WORK
LtA D .� l rrt
THE UNDERSIGNED HEREBY APPLIES FOR A PERMIT TO PERFORM THE WORK DESCRIBED AND IS
TO COMPLY WITH ALL LOCAL ORDINANCES AND STATE OF CONNECTICUT BUILDING CODES IN THE
PERFORMANCE OF SUCH WORK.
l_C',IAQ I�
CONTRACTORS LICENSE NO. TYPE STATE
SIGNATURE OF APPLICANT DATE
1600488 TOWN OF SOUTH WINDSOR, CT
PERMIT NUMBER BUILDING PERMIT
DATE: 08/02/2016
GIS ID:72000107 FEE: 30.00
MUMS APPLICATION# 201601040 BUILDING DESCRIPTION:
APPLICANT LOCATION
NAME: BENITEZ JOEL R& ADDRESS: 107 PINE KNOB DRIVE
ADDRESS: 107 PINE KNOB DRIVE OWNER: WELLS FARGO BANK TR
SOUTH WINDSOR,CT 06074 888 EAST WALNUT ST
-PASADENA,CA 91101
DESCRIPTION OF WORK: RELOCATION OF KITCHEN FROM LEFT TO RIGHT.,
SPECIAL CONDITIONS:
ALL WORK TO BE DONE IN ACCORDANCE WITH THE APPLICATION AND PLANS APPROVED BY THE BUILDING DEPARTMENT.
CONSTRUCTION TYPE:
OCCUPANCY GROUP: BUILDING OFFICIAL
8/2/2016 1 1:49 AM THE FEE ABOVE INCLUDES A$0.26 PER THOUSAND CT STATE EDUCATION SURCHARGE
1700231 TOWN OF SOUTH WINDSOR, CT
PERMIT NUMBER HVAC PERMIT
DATE: 06/19/2017
GIS ID: 72000107 FEE: 75.00
MUNIS APPLICATION# 201700716 BUILDING DESCRIPTION:
APPLICANT LOCATION
NAME: QUALITY HEATING AND COOLING. ADDRESS: 107 PINE KNOB DRIVE
ADDRESS: 148 PROSPECT HILL ROAD OWNER: BENITEZ JOEL R&
EAST WINDSOR,CT 06088 107 PINE KNOB DRIVE
SOUTH WINDSOR,CT 06074
DESCRIPTION OF WORK: INSTALL A/C COIL AND CONDENSER TO EXISTING GAS FURNACE.
SPECIAL CONDITIONS:
ALL WORK TO BE DONE IN ACCORDANCE WITH THE APPLICATION AND PLANS APPROVED BY THE BUILDING DEPARTMENT.
CONSTRUCTION TYPE:
OCCUPANCY GROUP: BUILDING OFFICIAL
6/19/201 7 10:18 AM THE FEE ABOVE INCLUDES A$0.26 PER THOUSAND CT STATE EDUCATION SURCHARGE
1600510 TOWN OF SOUTH WINDSOR, CT
PERMIT NUMBER ELECTRICAL PERMIT
DATE: 1 I/01/2016
GIS ID: 72000107 FEE: 15.00
MUNIS APPLICATION# 201601040 BUILDING DESCRIPTION:
APPLICANT LOCATION
NAME: NEW AGE ELECTRICAL`LLC ADDRESS: 107 PINE KNOB DRIVE
ADDRESS: 135 BISSELL STREET OWNER: -WELLS FARGO BANK TR
APT.2 `= 888 EAST WALNUT ST
MANCHESTER,CT 06040, _PASADENA,CA 91101
DESCRIPTION OF WORK: CHANGE OLD PANEL OVER TO 2 NEW GE PANEL'(100 AMP)ADD 2 NEW
COUNTERTOP OUTLETS AND A MICROWAVE OUTLET IN AN UPDATED KITCHEN.
SPECIAL CONDITIONS:
ALL WORK TO BE DONE IN ACCORDANCE WITH THE APPLICATION AND PLANS APPROVED BY THE BUILDING DEPARTMENT.
CONSTRUCTION TYPE:
OCCUPANCY GROUP: BUILDING OFFICIAL
I I/l/2016 3:31 PM THE FEE ABOVE INCLUDES A$0.26 PER THOUSAND CT STATE EDUCATION SURCHARGE
1600315 TOWN OF SOUTH WINDSOR, CT
PERMIT NUMBER PLUMBING PERMIT
DATE: 08/02/2016
GIS ID:72000107 FEE: 30.00
MUNIS APPLICATION 4 201601040 BUILDING DESCRIPTION:
APPLICANT LOCATION
NAME: BENITEZ JOEL R R ADDRESS: 107 PINE KNOB DRIVE
ADDRESS: 107 PINE KNOB DRIVE OWNER: WELLS FARGO BANK TR
SOUTH WINDSOR,CT 06074 888 EAST WALNUT ST
'PASADENA,CA 91101
DESCRIPTION OF WORK: RELOCATE THE WATER TO SINK IN KITCHEN.
SPECIAL CONDITIONS:
ALL WORK TO BE DONE IN ACCORDANCE WITH THE APPLICATION AND PLANS APPROVED BY THE BUILDING DEPARTMENT.
CONSTRUCTION TYPE:
OCCUPANCY GROUP: BUILDING OFFICIAL
8/2/2016 11:50 AM THE FEE ABOVE INCLUDES A$0.26 PER THOUSAND CT STATE EDUCATION SURCHARGE