HomeMy WebLinkAbout1 LIPMAN DR 2 OCT 22104Te;2t .3 7 (Nkwur Ar L`Specializing in Underground Fuel Tanks t 360 East Center Street / p Manchester, CT 06040 U m Important Documents Inv. i i Y i Tankworks October 11, 2004 Mr. Stuart Lipman One Lipman Drive South Windsor, CT 06074 Re: Removal and Disposal of(1)-1000 Gallon Underground Oil Tank At: 1 Lipman Drive, South Windsor, CT 06074 Thank you for the opportunity to service the removal of one (1)-1000 Gallon Underground Oil tank at the above referenced address. The soil in the tank grave showed no signs of contamination and the grave was backfilled. Before backfilling one(1) final confirmation soil sample was taken from the 1000 Gallon Underground Oil tank grave and tested at an independent laboratory for TPH(total petroleum hydrocarbons)by IR (Method 418.1). The soil sample results for the Bottom tank grave indicated BDL(Below Detection Limits). The recommended TPH limit in a GA Classification is 500 parts per million. This letter,along with the attached soil sample results, should be stored safely with all legal documents pertaining to this property. This information, along with your Tankworks invoice and cancelled check(s), will serve as verification for future reference. Please feel free to call us if you have any further questions. It has been a pleasure working with you. We hope that you are pleased with our services and that you will recommend us to others. Very truly yours, TANKWORKS REMOVAL & REPLACEMENT LLC Rosemary Viola Rainville Owner cc: Town of South Windsor,Fire Marshal's Office, 1540 Sullivan Avenue, South Windsor,CT 06074 1-800-653-3140 Main Office 360 East Center St. Manchester CT 0.040 LIPMA1VFINALDO 0 ,\tt ACpp9O PHOENH : e `N Environmental Laboratories, Inc. 587 East Middle Turnpike,P.O.Box 370,Manchester,CT 06040 Tel.(860)645-1102 Fax(860)645-0823 Analysis Report FOR: Attn: Mrs.Rose Rainville Y Tankworks, Inc. October 11, 2004 360 East Center Street Manchester, CT 06040 Sample Information Custodv Information Date Time Matrix: SOIL Collected by: DO 10/07/04 11:00 Location Code: TANKWKS Received by: SW 10/07/04 15:10 Rush Request: RUSH24HR Analyzed by: see "By" below P.O.#: SDG I.D.: GAF92185 Laboratory Data Phoenix I.D.: AF92185 Client ID: 1 LIPMAN RD BOTTOM Parameter Result RL Units Date Time By Reference Percent Solid 95 % 10/08/04 K/E E160.3 Tot.Petroleum HC BDL 21 mg/Kg 10/08/04 PJ E418.1 Comments: ND=Not detected BDL =Below Detection Limit R.L=Reporting Limit If there are any questions regarding this data,please call Phoenix Client Services at extension 200. Phyllis hiller,Laboratory Director October 11,2004 Page 1 of 1 �O �N ACCOgoH t- as a= Environmental Laboratories, Inc. 587 East Middle Turnpike,P.O.Bog 370,Manchester,CT 06040 Tel.(860)645-1102 Fax(860)645-0823 QA/QC Report October 11, 2004 QA/QC Data SDG I.D.: GAF92185 Parameter Blank LCS Rec % MS Rec % RPD QA/QC Batch Sample No:AF91325 (AF92185) Tot.Petroleum HC BDL 97 91 NR If there are any questions regarding this data,please call Phoenix Client Services at extension 200. LCS -Laboratory Control Sample AOL MS -Matrix Spike RPD -Relative Percent Difference Between Sample and Sample Duplicate Phyllis hiller,Laboratory Director October 11,2004 Page 1 of 1 LOT 3/ 42 N 99. 28 I \ O 2050� 36.00 '4z. EXISTING GARAGE - z LOT 30 LOT 29 38, 687.88 sq ft o � m N O 2/.O CDN /000 GAL EPTIC R !1 TA N1( ,O 0 �J cp 23. N a o � 50 B G LINE Is O� Q 9 0 I P, /5 .56 to .Srocr<ROE�cE ELLINGTON ROAD BEING LOT 29 ON MAP ENT/TLE SAND HILL ESTATES MAY 2 , 1970 FOUNDATION CERTIFIED AS SHOWN MAY I3, 1972 PLOT PLAN FOR " L / P M A N EL L ING TON ROAD-SOUTH WINDSOR, CONN. SCALE /" = 4p MARCH 2 8, /972 ✓AMES E. SHEEHY LS.7034 CERTIFIED MAY 13, 1972 SEPTIC SYSTEM � LOT 3/ 42- L:^dE+L FEE?` OF'TILE PER 99.28 o� � ru �� ,r;:;�r� 12 FEET C.O.C. rntv.: ol - 20.0 36.00 N Cl N PROPOSED GARAGE LOT . 30 J LOT 29 38,68788 sq ft o 0 VO . 2. Q�0 yQ p o •¢ � � - . 210 \ N IOOANA L EPT/C, o ° -- 50 8L 00 ONE I 1 I 90 000 - D',,2g2'I ( I 15756 P''3 El—l—INGTO/V ROAD :v • BE/NG LOT 29 ON MAP ENT/TLE tSAND HILL ESTAYES " MAY 21 1970 -.-_r •11 •,safe r 'V ,r. PLOT PLAN FOR ,`�`' •_" - ~' L A N ,. . ELL/NGTON ROAD—SOUTH !�Y/NDSOR CONN. - = Y • s 3 CAL E �„ = 40 MARCH 2 8, /972 » •�°� ✓ANES E. SHEEHY LS.7034 r f APPLICATION FOR HVAC PERMIT DEPARTMENT DECISION TOWN OF SOUTH WINDSOR PERMIT# Applic by: BUILDING DEPARTMENT I V) l� r APPROVED 1540 SULLIVAN AVENUE Bldg.Permit# .l 644-2511 ext. 230 Date lding Inspector -- Application must be printed or typed FEE SCHEDULE Location of Job: $0-$1,000=$15.00 w , Over$1,000= Street No. Street Lot No. $15.00 per$1,000 or any fraction thereof Tenant Designation Apt.No. APPLICANT APPLICANT ADDRESS W ,�6 CJUCbD Q� APPLICANT'S PHONE# <I�`'�"—1;d9 —S2 l I OWNER UA(�� WN S .�Or F4< OWNER ADDRESS L �� OWNER PHONE O ? ESTIMATED COST$ C IS THIS A CONTRACT COST? 4/"'Yes No FEE ENCLOSED$ J�C) TYPE OF JOB: �$0 CQ� New Installation old U U S(o ✓ Alteration/Addition/Repair Revised 03/05/10 WcaC L(L-5 /(S A)U wixl o z,0 r APPLICATION FOR HVAC PERMIT(Continued from reverse side) TYPE OF SYSTEM: TYPE OF BUILDING: YHEATING ❑ RESIDENTIAL YA/C ❑ COMMERCIAL ❑ VENTILATION ❑ INDUSTRIAL HEATING ❑ STEAM LOW PRESSURE LIMIT LBS. HIGH PRESSURE LIMIT LBS. LVHYDRONIC ❑ WARM AIR ❑ UNIT RADIANT HEATER EXISTING RADIATION ADDITIONAL RADIATION TOTAL RADIATION DESIGN TEMP.OUTSIDE OF INSIDE OF DIFFERENCE OF TOTAL HEAT LOSS(BTUH) OF(HEAT LOSS SHEET MUST ACCOMPANY APPLICATION) DESCRIBE ALL HEATING EQUIPMENT(INCLUDING MAKE&MODEL NO.)-Ul'tJ P(JkjTG0 ho GROSS HEATING CAPACITY(INPUT-BTUH) 149" NET RATING(OUTPUT BTUH) TYPE OF FUEL ��' li(OIL-GPM OIL TANK LOCATION: dINSIDE ❑ OUTSIDE CAPACITY ❑ GAS-INPUT LPG TANK CAPACITY ELECTRIC-KW AIR CONDITIONING DESIGN TEMP: OUTSIDE 'I °F INSIDE OF DIFFERENCE I OF TOTAL HEAT GAIN(BTUH)a o K (HEAT GAIN SHEET MUST ACCOMPANY APPLICATION) DESCRIBE ALL COOLING EQUIPMENT(INCLUDING MAKE& MODEL NO.) CD v 't ►J ai o1�`d TONNAGE _ COOLING CAPACITY(BTUH) VENTILATION DESCRIBE ALL AIR HANDLING EQUIPMENT(INCLUDING KITCHEN EXHAUST EQUIPMENT) TOTAL SIZE OF SYSTEM(CFM) FRESH AIR INTAKE(CFM) (PLANS MUST ACCOMPANY APPLICATION) FURTHER DESCRIPTION OF WORK THE UNDERSIGNED HEREBY APPLIES FOR A PERMIT TO PERFORM THE WORK DESCRIBED AND IS TO COMPLY WITH ALL LOCAL ORDINANCES AND STATE OF CONNECTICUT BUILDING CODES IN THE PERFORMANCE OF SUCH WORK. 3a67b1 __ j CONTRACTORS LICENSE TYPE STATE SIGNATURE OF APPLICANT /hki& DATE QS�/ a I l 6 Lipman 1 Lipman Dr OSouth VVindsor Main & 2nd F-Ir HVAC Load Calculations for Stuart Lipman I Lipman Drive South Windsor,CT 06074 AUT E.W.Irkll zv,77 ri rT- erN- RESID9NMAL � H VA C L oADs Prepared By: Chris Miller BBT Mechanical Services, LLC 22 Wapping Wood Rd Ellington,Connecticut 06029 860-209-9917 Wednesday, May 12,2010 Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition,Version 2,and ACCA Manual D. Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development,Inc. „ BBT Mechanical Services Lipman 1 Lipman Dr South Windsor Main&2nd Fir Ellington,CT 06029 Page 2 Proiect Report General Project Information Project Title: Lipman 1 Lipman Dr South Windsor Main&2nd Fir Designed By: Chris Miller Project Date: Friday May 04,2007 Client Name: Stuart Lipman Client Address: 1 Lipman Drive Client City: South Windsor,CT 06074 Client Phone: 860-436-1234 Company Name: BBT Mechanical Services,LLC Company Representative: Chris Miller Company Address: 22 Wapping Wood Rd Company City: Ellington,Connecticut 06029 Company Phone: 860-209-9917 Company Fax: 860-871-9422 Company E-Mail Address: bbtmechanical@snet.net EDesign Data Reference City: Hartford, Connecticut Building Orientation: Front door faces North Daily Temperature Range: Medium Latitude: 41 Degrees Elevation: 19 ft. Altitude Factor: 0.999 Elevation Sensible Adj.Factor: 1.000 Elevation Total Adj.Factor: 1.000 Elevation Heating Adj.Factor: 1.000 Elevation Heating Adj. Factor: 1.000 Outdoor Outdoor Outdoor Indoor Indoor Grains Dry Bulb Wet Bulb Rel.Hum Rel.Hum Dry Bulb Difference Winter. -10 -10.4 81% n/a 72 n/a Summer: 93 73 39% 50% 75 25 Check Figures Total Building Supply CFM: 1,468 CFM Per Square ft.. 0.577 Square ft. of Room Area: 2,544 Square ft. Per Ton: 694 Volume(ft')of Cond.Space: 19,347 Building Loads Total Heating Required Including Ventilation Air: 63,740 Btuh 63.740 MBH Total Sensible Gain: 32,999 Btuh 91 % Total Latent Gain: 3,439 Btuh 9 % Total Cooling Required Including Ventilation Air: 36,437 Btuh 3.04 Tons(Based On Sensible+ Latent) 3.67 Tons(Based On 75%Sensible Capacity) Notes Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition,Version 2,and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads. y J w Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development,Inc. BBT Mechanical Services Lipman 1 Lipman Dr South Windsor Main&2nd Fir Effiroon.CT 06M Page 4 Load Preview Report Net, ft2: Sen Lat Net! Seni Sys, Sys Sys pact i Htg' Clg'. Act; Scope Ton JTon Area: Gain' Gain Gain; Loss" Size CFM, CFM; CFM, Building 3.04 838 2,544 32,999 3,439 36,437 63,740 785 1,468 1,468 System 1 3.04 838 2,544 32,999 3,439 36,437 63,740 785 1,468 1,468 14x17 VerClation 732 635 1,367 3,335 Duct Latent 163 163 Zone 1 1,578 24,680 2,128 26,803 37,226 484 1,123 1,123 12x16 1-Green Bed Room 2nd F1 103 2,211 249 2,460 2,504 33 101 101 1_6 2-Myra's Office 2nd FI 104 2,158 251 2,409 2,143 28 98 98 1--6 3-Exercise Room 2nd Fl 119 2,547 319 2,866 3,665 48 116 116 1--6 4-Stuart's Bedroom 2nd Fir 228 2,289 565 2,854 5,304 69 104 104 1--6 5-Stuart§Bath&Closets 2nd Fir 135 1,745 83 1,828 Z758 36 79 79 1--5 6-2nd Fir Bath 44 120 0 120 177 2 5 5 1--5 7-2nd Fir Interior Hail 05' 176 0 176 261 3 a 8 1--5 8-Living Room Main Fi 275 5,922 389 6,311 6,959 90 269 269 2--7 9-tiring Room Again Fir 181 1,360 67 1,427 3,265 42 62 62 1--5 10-Kitchen Main Fir 159 428 0 428 638 8 19 19 1--5 11-Sun Room t.ain F6 165 5,725 205 5,930 9,552 124 -260 260 2--7 Zone 2 966 12,169 512 12,681 23,179 301 554 554 9x13 12-aua!'s0M.ce 181 1583 67 1,650 3,396 44 72 72 1--5 13-Front Entry 109 2,101 40 2,141 3,252 42 96 96 1-6 14-Family Room 1 311 0 0 0 871 11 0 0 0_0 15-Family Room 2 255 7,643 240 7,883 9,122 119 348 348 3 6 16-Back Room 110 842. 165 1,007 6,538 85 38 38 1--5 Sum of room airflows may be greater than system airflow because system has multiple zones. I + AW Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development,Inc. . BBT Mechanical Services Lipman 1 Lipman Dr South Windsor Main&2nd Fir Elfi CT 06M Page 6 Total Building Summary Loads Component Area Sen Lat Sen Total Description Quan Loss Gain Gain Gain 1 D-cv-o:Glazing-Double pane,operable window,clear, 280.2 13,093 0 13,602 13,602 vinyl frame,u-value 0.57,SHGC 0.56 1E-cw:Glazing-Double pane window,fixed sash,clear, 28.9 1,328 0 1,468 1,468 wood frame,u-value 0.56, SHGC 0.66 1E-cv:Glazing-Double pane window,fixed sash,clear, 17.6 808 0 894 894 vinyl frame, u-value 0.56,SHGC 0.66 1OB-b:Glazing-French door,double pane clear glass, 38.1 2,342 0 858 858 metal frame with break, u-value 0.75, SHGC 0.47 1E-cv:Glazing-Double pane window,fixed sash,clear, 17.9 820 0 1,116 1,116 vinyl frame, u-value 0.56,SHGC 0.66 11 G:Door-Wood-Panel 21 930 0 329 329 12B-Osw:Wall-Frame, R-11 insulation in 2 x 4 stud cavity, 1655.6 13,170 0 4,353 4,353 no board insulation,siding finish,wood studs 1613-19:Roof/Ceiling-Under Attic with Insulation on Attic 1833.6 7,367 0 4,762 4,762 Floor(also use for Knee Walls and Partition Ceilings), Vented Attic, No Radiant Barrier, Dark Asphalt Shingles or Dark Metal,Tar and Gravel or Membrane, R-19 insulation 20P-19:Floor-Over open crawl space or garage,Passive, 103.2 423 0 67 67 R-19 blanket insulation,any cover 19A-19p:Floor-Over enclosed unconditioned crawl 546.2 1,720 0 378 378 space,No insulation on exposed walls,sealed or vented space, passive, R-19 blanket 22A-pm:Floor-Slab on grade,No edge insulation, no 40 3,871 0 0 0 insulation below floor,any floor cover, passive, heavy dry or light wet soil Subtotals for structure: 45,872 0 27,827 27,827 People: 6 1,200 1,380 2,580 Equipment: 0 0 0 Lighting: 0 0 0 Ductwork: 0 163 1,400 1,563 Infiltration:Winter CFM:161,Summer CFM:84 14,533 1,440 1,660 3,100 Ventilation:Winter CFM_37,Summer CFM:37 3,335 635 732 1,367 Total Building Load Totals: 63,740 3,439 32,999 36,437 Check Figures - --- Total Building Supply CFM: 1,468 CFM Per Square ft.. 0.577 Square ft.of Room Area: 2,544 Square ft. Per Ton: 694 Volume(ft?)of Cond.Space: 19,347 B�filding Leads - - Total Heating Required Including Ventilation Air: 63,740 Btuh 63.740 MBH Total Sensible Gain: 32,999 Btuh 91 % Total Latent Gain: 3,439 Btuh 9 % Total Cooling Required Including Ventilation Air: 36,437 Btuh 3.04 Tons(Based On Sensible+ Latent) 3.67 Tons(Based On 75% Sensible Capacity) Notes Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition,Version 2,and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads. Rhvac.Residential&Light Commercial HVAC Loads Elite Software Development,Inc. BBT Mechanical Services CLipman 1 Lipman Dr South Windsor Main&2nd Fir Eifi on,CT OW29 Rage 32 System 1 Room Load Summary (cont'd) Equipment Data Brand: WTGO SERIES 3 RUUD UAND SERIES Description: Oil Boiler Efficiency: 85 AFUE 13 SEER Sound: Capacity: 145,000 Btuh 34,800 Btuh Sensible Capacity: n/a 26,100 Btuh Latent Capacity: n/a 8,700 Btuh AHRI Reference No.. n/a 3176027 i I Rhvac-Residential&Light Comrnorclal HVAC loads ,"; Elite Software Devebpment,lnc. . i 2nd Fir BBT Mechanical SenServices Lipman 1 Lipman Dr South Windsor Main 8� (�}FEtFr n,CT 06029 ti _ a `� S1J 4 System 9 Room Load Summary _ � W Htg Htg RU F Run C g Clg CI9 Air Roorn't Area Sens Rad Duct Duct Sens Lat Nom Sys No Name S1= Btuh Len Size Vel Btuh Btuh CFM CFNt, -Zone 1- 1 Green Bed Room 103 2,504 4.4 1-6 512 2,211 249 101 101 2nd FI 2 Myra's Office 2nd 104 2,143 3.8 1-6 500 2,158 251 98 98 FI 3 Exercise Room 119 3,665 6.5 1-6 590 2,547 319 116 116 2nd FI 4 Stuarts Bedroom 228 5,304 9.3 1-6 530 2,289 565 104 104 2nd Fir 5 Stuart's Bath & 135 2,758 4.9 1-5 582 1,745 83 79 79 Closets 2nd Fir 6 2nd Fir Bath 44 177 0.3 1-5 40 120 0 5 5 7 2nd Fir Interior 65 261 0.5 1-5 59 176 0 8 8 Hall 8 Living Room Main 275 6,959 12.3 2-7 504 5,922 389 269 269 FI 9 Dining Room 181 3,265 5.7 1-5 454 1,360 67 62 62 Main Fir 10 Kitchen Main Fir 159 638 1.1 1-5 143 428 0 19 19 11 Sun Room Main 165 9,552 16.8 2-7 487 5,725 205 260 260 Fir Zone 1 subtotal 1,578 37,226 65.5 24,680 2,128 1,123 ---Zone 2- 12 Stuart's Office 181 3,396 6.0 1-5 528 1,583 67 72 72 1 13 Front Entry 109 3,252 5.7 1-6 487 2,101 40 96 96 14 Family Room 1 311 871 1.5 0-0 0 0 0 0 0 15 Family Room 2 255 9,122 16.1 3-6 590 7,643 240 348 348 16 Back Room 110 6,538 11.5 1-5 281 842 165 38 38 Zone 2 subtotal 966 23,179 40.8 12,169 512 554 Ventilation 3,335 732 635 Duct Latent 163 _ System 1 total 2,544 63,740 106.3 32,999 3,439 1,468 11468 System 1 Main Trunk Size: 14x17 in. Velocity: 888 ft./min Loss per 100 ft.: 0.101 in.wg Note: Since the system is multizone,the Peak Fenestration Gain Procedure was used to determine glass sensible gains at the room and zone levels,so the sums of the zone sensible gains and airflows for cooling shown above are not intended to equal the totals at the system level. Room and zone sensible gains and cooling CFM values are for the hour in which the glass sensible gain for the zone is at its peak. Sensible gains at the system level are based on the"Average Load Procedure + Excursion" method. I Cooling System Summary Cooling Sensible/Latent Sensible Latent To _ Tons_ Split Btuh Btuh Btu Net Required: 3.04 91%/9% 32,999 3,439 36,437 1 Recommended: 3.67 75%/25% 32,999 11,000 43,998 I Actual: 2.90 75%/25% 26,100 8,700 34,800 Equipment Data _ _ A Heating System Cooling System Type: Fuel Oil Boiler Standard Air Conditioner Model: P-WTGO-4 UAND-036JAZ Indoor Model: RCFA-H'3617A' Electric# APPLICATION FOR BUILDING PERMIT Mumbing# I Lipman Drive Date: /56'I HVAC # Sprinkler# 30935 FINAL APPROVALS _—_— __--- -- _ - - Estimated Cost $ 7uu Building COMPLETE RED BOXED AREAS Permit Fee $ Engineering Occupancy Fee $ g TYPE OR PRINT ONLY Eng. Insp. Fee $ Affidavit ► SIGN ON REVERSE SIDE Appr. for CO. J Total Fee $ TO THE BUILDING DEPARTMENT,TOWN OF SOUTH WINDSOR, CT (Additional Cost) $ The undersigned hereby applies to do work according to the following: Applicant /-1k Du/% R' Location of Work Dr. (14-n ) Lot No. Applicant's Address 7N &­1-4 ST. Tel.# - 1W-Yiko Town H. cT Zip bb/1-? Lic.# 10/9Y Owner Architect Owner's Address I. Architect's Address Zip Zip Sq. Ft. New Area: 1st FI. 2nd FI. 3rd FI. Total New Area Purpose of this permit Tckr o ; Q?0h-s I (<xe�sg4id T.%ft4/t r« > w<fe s4, -Id City Water❑ Well❑ Septic System❑ Sewer❑ Ins: HO L—AP6'6PZ�ate -65/16 ea Basement Garage Approved byUse Gro onstruction T J(wd / Revised W02 I hereby agree to conform to all the requirements of the Laws of the State of Connecticut and the Ordinances of the Town of , South Windsor and to notify the Building Inspector of any alteration in the plans or specifications of the Building for which this permit is asked.and agree that this building is to be located the proper distance from all street lines,side yard lines,and required distances from all other zones and is located in which this building and its use is allowed. Signedw� 1 hereby apply for a Certificate of Occupancy for the work described in this application for the permit. Signed DO NOT WRITE BELOW THIS LINE INSPECTION COMMENTS Inspection / Approval Date By Appl Code Description Due whom Code Comment ------------------------------------------------------------------------------- •"-30935-8 5,700 B10 FINAL 09/14/04 PJP A B10 FINAL 09/14/04 PJP A CLOSEOUT I, Electric# APPLICATION FOR BUILDING PERMIT Plumbing# 1 Lipman Drive HVAC # Date: � U U Sprinkler# 30878 Estimated Cost $ 7200.0 6 FINAL APPROVALS - -- _— ------- - - --- -, � Permit Fee $ I z a• o e Building COMPLETE RED BOXED AREAS Engineering Occupancy Fee $ TYPE OR PRINT ONLY Affidavit g Eng. Insp. Fee $ Appr. for CO. y SIGN ON REVERSE SIDE Total Fee $ /o20. TO THE BUILDING DEPARTMENT,TOWN OF SOUTH WINDSOR, CT (Additional Cost) $ The undersigned hereby applies to do work according to the following: Applicant M. G. T o S?A R E t_L i .r R Location of Work 1 L i P M A A) D& Lot No. Applicant's Address b a G A R o CA) S T. E . FI A Rs Entz o . c I:. n b i o g Tel.#SSA-t j_s-S `v i i 6 ti i Town EAST H A R T r-a R p C T. zip—0 t.10 b Lic.# .S a 0 Owner cju A RT (-I P MAty Architect Owner's Address i l t Pry A a Op'. Architect's Address SnuiN W(NDSOR L?- Zip O4o,7,-/ Zip Sq. Ft. New Area: 1st Ff. 2nd FI. 3rd FI. Total New Area Purpose of this permit JEPR -OFF t' tSTtNc-. SiPiryc — wot)SE GARAaE (ZE t N S7RL4, Ew S�D//yG Nc lklm A-PPR X 3Goc as t� City Water[:] Well❑ Septic System❑ Sewer❑ Ins: HO rt Area Basement Garage �j Approved by ate d Use Group 'Construction Type.--�'— Revised 6/02 I hereby agree to conform to all the requirements of the Laws of the State of Connecticut and the Ordinances of the Town of South Windsor and to notify the Building Inspector of any alteration in the plans or specifications of the Building for which this permit is asked,and agree that this building is to be located the proper distance from all street lines,side yard lines,and required distances from all other zones and is located in which this building and its use is allowed. Signed M ,b �, oak! I hereby apply for a Certificate of Occupancy for the work described in this application for the permit. Signed DO NOT WRITE BELOW THIS LINE INSPECTION COMMENTS I I Inspection / Approval Date By Appl Code Description Due whom Code Comment ------------------------------------------------------------------------------- **-30878-B 7,200 B10 FINAL 09/14/04 PJP A B10 FINAL 09/14/04 PJP A CLOSEOUT r � F { j� \V�L! ArJ D 1V DC> / �4x� K f�r �-c"� • Imo"r - - "'7 o\ iGE ODL-Ut-" AND HEAGe7P. -- - EX4�. 1tJG- SLICE (z 0 J 2.E L rr A?M_i �ti (�Szt)*�3�'►- l-� t,✓ Ez- A` 1I"' ';-�f TRIM _-•� �,' t-� NE�V � E)CI�TItJ� = X � Pt>r� p,t��r.�• NE1�! \ . .— _ , C�F'�i'�if~ iC � k � �OF L�1.1�• /IGf�' - -� E�.VE To t'It�T"�I �x�T,. _`� . � / _� �Nv t E.iS'.a►(-.i. tl�ica - (1JcaT�1..L �;�`:v' ��'i�'z-• cxQ4T T �zit�JSLDoTt'!�'i7� �� — Q v 1 hJE\\f GOB M, iS IEb.i;)ER 1E..f✓Cock-,lryC7 Q, >C.�- J ' r~.) G �A6E Et -`'r Oc�w) \VI' ► C�, I i - T -.i� I ST1 K c �L(x,� �� .�' T"s U EL F t� I r; 13 +71 f 6c)I�j( R-LTE Ft 7 fts� ce „1xD LPL. u�,�---- --7�'- I� et- !fit L i C,Q L-r.. \`r'/�`,Ct�?';LAWPING 121' 72_. ; 4' _ 2:t E5E LL'�)\V NEw p V F L C�C��. P ice. _ VERTICAL SECTION T _�•� It 3.4 BOW WINDOW DETAILS HORIZONTAL SECTION AN D PP_ ti L J S`' j ,�(!.i - rii�...i� !`.G�� i^•�.�%.r-- I ,.t`r+ i� �tN i ew., �-^ �— _ _ ---- -- - - `t -- j __, . -- _-' - ---- ;f��tjk i i. i.i�':' �!Dt►.�C� To V D'+ E iII Lv;�E7C.7\�/ � ..: I-}�o� O{= �k. � 8E�• �R. ,.}�'jE1'i� P5 T E56 CY - g i � i i N���C�o�� i ! i i ► i � � aU�r� rJ�+;•� `' � I � I �`� ._._. • J i v o I L—E-VAT 10 � o o � C/G BY O�Zi�lh.f �•24 1000170 TOWN OF SOUTH WINDSOR, CT PERMIT NUMBER HVAC PERMIT DATE: 05/13/10 GIS ID:53700001 FEE: 240.00 MUNIS APPLICATION# 201000561 BUILDING DESCRIPTION: APPLICANT LOCATION NAME: BBT MECHANICAL SERVICES,LLC ADDRESS: 1 LIPMAN DRIVE ADDRESS: 22 WAPPING WOOD ROAD OWNER: LIPMAN STUART G ELLINGTON,CT 06029 1 LIPMAN DRIVE SOUTH WINDSOR,CT 06074 DESCRIPTION OF WORK: BOILERAND A/C. SPECIAL CONDITIONS: ALL WORK TO BE DONE IN ACCORDANCE WITH THE APPLICATION AND PLANS APPROVED BY THE BUILDING DEPARTMENT. CONSTRUCTION TYPE: OCCUPANCY GROUP: BUILDING OFFICIAL 5/13/2010 9:18 AM THE FEE ABOVE INCLUDES A$0.22 PER THOUSAND CT STATE EDUCATION SURCHARGE