HomeMy WebLinkAboutMechanical_Wed_Jan_4_2023_08-40-33ENERGY DESIGN CRITERIA:GENERAL NOTES:1. FURNISH ALL LABOR, MATERIAL, EQUIPMENT AND TOOLS REQUIRED TO COMPLETE INSTALLATION OF THE MECHANICAL SYSTEM INCLUDING BUT NOT LIMITED TO DUCTWORK, PIPING, INSULATION, AIR DISTRIBUTION DEVICES, EQUIPMENT, CONTROLS, AND ALL OTHER WORK INDICATED ON THE DRAWINGS OR AS SPECIFIED HEREIN.2. OBTAIN ALL PERMITS, INSPECTIONS, AND APPROVALS AS REQUIRED BY LOCAL AUTHORITIES HAVING JURISDICTION AND DELIVER CERTIFICATE OF APPROVAL TO THE GENERAL CONTRACTOR. ALL ASSOCIATED FEES SHALL BE PAID BY THE CONTRACTOR.3. CONTRACTOR SHALL COMPLY WITH OSHA REQUIREMENTS.4. ALL MATERIALS AND EQUIPMENT OF THE MECHANICAL SYSTEMS NECESSARY TO ITS PROPER OPERATION, BUT NOT SPECIFICALLY MENTIONED OR SHOWN ON THE DRAWINGS, SHALL BE FURNISHED AND INSTALLED WITHOUT ADDITIONAL CHARGE.5. THE CONTRACTOR SHALL FULFILL ALL REQUIREMENTS OF THE CONTRACT DOCUMENTS AND SHALL COMPLETE THE IMPROVEMENTS SHOWN ON THE DRAWINGS AND INDICATED IN THE GENERAL NOTES AND SPECIFICATIONS. ALL SYSTEMS SHALL BE FINISHED AND PROVEN TO BE FULLY OPERATIONAL AND USEABLE. PROVIDE TESTING, ADJUSTING, AND BALANCING FOR THE MECHANICAL AIR SYSTEMS BY AN AGENCY CERTIFIED BY "AABC" OR "NEBB".6. VISIT SITE AND CAREFULLY EXAMINE EXISTING SITE CONDITIONS PRIOR TO SUBMITTING BID. NO ALLOWANCE WILL BE MADE FOR LACK OF KNOWLEDGE OF EXISTING SITE CONDITIONS. ANY ADJUSTMENTS IN DUCTWORK ROUTING SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE OWNER.7. THESE DRAWINGS ARE SCHEMATIC IN NATURE AND ARE NOT INTENDED TO INDICATE ALL POSSIBLE CONDITIONS. IT IS INTENDED THAT A COMPLETE MECHANICAL SYSTEM BE PROVIDED WITH ALL NECESSARY EQUIPMENT, APPURTENANCES, AND CONTROLS COMPLETELY COORDINATED WITH ALL DISCIPLINES AND CONNECTED TO THE MECHANICAL SYSTEMS. ALL PARAMETERS INDICATED IN THESE CONTRACT DOCUMENTS SHALL BE STRICTLY CONFORMED TO AS SPECIFIED. ANY ITEMS AND LABOR REQUIRED FOR A COMPLETE MECHANICAL SYSTEM IN ACCORDANCE WITH ALL APPLICABLE CODES, STANDARDS, AND THESE CONTRACT DOCUMENTS, SHALL BE FURNISHED AND INSTALLED WITHOUT INCURRING ANY ADDITIONAL COST TO THE OWNER. CAREFULLY REVIEW ALL CONTRACT DOCUMENTS AND WORK OF OTHER TRADES PRIOR TO THE PREPARATION OF SHOP DRAWING SUBMITTALS.8. COORDINATE ALL WORK WITH ALL TRADES. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE ACTUAL LOCATION OF EQUIPMENT, CONDUIT, PANELS, DUCTWORK, EQUIPMENT SUPPORTS, PIPING, ETC. AND COORDINATE THE INSTALLATION ACCORDINGLY. EXACT LOCATIONS FOR CONNECTIONS TO THE MECHANICAL SYSTEM SHALL BE FIELD VERIFIED.9. ALL MATERIAL SHALL FIT THE SPACE AVAILABLE. VERIFY DIMENSIONS AND CLEARANCES AT BUILDING BEFORE COMMENCING WORK.10. TRANSITION RECTANGULAR DUCTWORK ON BOTTOM AND SIDES. INSTALL DUCT AS HIGH AS POSSIBLE AND MAINTAIN TOP OF DUCTWORK LEVEL.11. FLEXIBLE DUCT RUNOUTS TO CEILING DIFFUSERS SHALL BE AS STRAIGHT AS POSSIBLE AND FREE OF SAGS AND KINKS WITH PROPER STRAP SUPPORTS CONNECTED TO THE STRUCTURE. MAXIMUM FLEXIBLE DUCT LENGTH SHALL BE 6 FT.12. DUCT DIMENSIONS SHOWN ARE INSIDE CLEAR DIMENSIONS.13. PORTIONS OF DUCTWORK VISIBLE THROUGH GRILLES AND REGISTERS IN FINISHED AREAS SHALL BE PAINTED FLAT BLACK.14. ALL FANS, DAMPERS, AND OTHER MECHANICAL ITEMS ABOVE CEILING SHALL BE ACCESSIBLE. CONTRACTOR SHALL COORDINATE ALL ACCESS PANELS IN CEILINGS OR WALLS AS REQUIRED, REFER TO THE PROJECT SPECIFICATIONS FOR ACCESS PANEL REQUIREMENTS.15. CONTRACTORS SHALL COORDINATE VOLTAGE AND PHASE OF EACH PIECE OF EQUIPMENT WITH THE ELECTRICAL CONTRACTOR PRIOR TO ORDERING.16. INSTALL THERMOSTATS AND TEMPERATURE SENSORS AT PROPER ELEVATIONS AS REQUIRED TO COORDINATE WITH LATEST ADA REQUIREMENTS WITH ASSOCIATED CONTROL WIRING AND CONDUIT AS REQUIRED, REFER TO SPECIFICATIONS.17. COORDINATE DUCTWORK INSTALLATION WITH PLUMBING, FIRE PROTECTION AND ELECTRICAL SYSTEMS. MAKE OFFSETS AND TRANSITIONS TO COORDINATE WITH OTHER TRADES WITHOUT ADDITIONAL CHARGE.18. INSTALL HVAC EQUIPMENT AS INDICATED IN THE CONTRACT DOCUMENTS AND IN ACCORDANCE TO MANUFACTURER'S RECOMMENDATIONS.19. GUARANTEE ALL HVAC EQUIPMENT AND SYSTEMS FOR ONE YEAR AFTER OWNER ACCEPTANCE. ALL HVAC EQUIPMENT WITH COMPRESSORS SHALL INCLUDE EXTENDED PARTS WARRANTY TO COVER COMPRESSORS FOR 5 YEARS AFTER OWNER ACCEPTANCE.20. AIR MOVING EQUIPMENT SHALL NOT BE OPERATED UNTIL 2” THICK TEMPORARY AIR FILTERS ARE IN PLACE. IF ANY EQUIPMENT IS OPERATED DURING ANY PART OF CONSTRUCTION, NEW CLEAN FILTERS SHALL BE PROVIDED AT LEAST WEEKLY. PROVIDE AN EXTRA SET OF CLEAN FILTERS AT THE TIME OF FINAL INSPECTION BY THE ENGINEER.21. INSTALL RESTRAINTS AND FASTENERS AS REQUIRED TO MEET LOCAL SEISMIC AND WIND LOAD CRITERIA. PROVIDE EQUIPMENT AND CONSTRUCTION THAT MEET THESE REQUIREMENTS; INSTALL ADDITIONAL SUPPORTS, VIBRATION ISOLATION, SPECIALTY CONNECTIONS/FITTINGS, AND ATTACH ROOF CURBS TO STRUCTURE AS NECESSARY. PROVIDE RATIONAL ANALYSIS CALCULATIONS IF REQUIRED. COORDINATE WITH ARCHITECT AND STRUCTURAL ENGINEER.22. WHERE CODE MANDATES AND/OR LOCAL JURISDICTION DICTATES THE COMMISSIONING OF BUILDING SYSTEMS, OR IF THE PROJECT IS TO BE LEED CERTIFIED, THEN THE PROJECT MUST BE COMMISSIONED. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO COORDINATE WITH THE COMMISSIONING AGENT, ARCHITECT, ENGINEERS AND SUBCONTRACTORS, TO PLAN INSTALLATION REVIEWS, EQUIPMENT/SYSTEM TESTING, AND TO PROVIDE ADEQUATE NOTICE FOR ALL TESTING EVENTS. CONTRACTOR SHALL BE REQUIRED TO PROVIDE ADDITIONAL DOCUMENTATION DURING THE PROJECT CONSTRUCTION. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION AND REQUIREMENTS.23. UNLESS NOTED OTHERWISE, ALL HVAC THERMOSTATS SHALL BE 7-DAY PROGRAMMABLE TYPE WITH THE FOLLOWING FEATURES: OCCUPIED/UNOCCUPIED SETPOINTS; HEATING/COOLING CROSSOVER PROTECTION; BATTERY BACKUP; OVERRIDE BUTTON (2 HR DURATION). PROGRAM EQUIPMENT SETPOINTS IN ACCORDANCE WITH CODE REQUIREMENTS, 75 DEGREES F (COOLING) AND 70 DEGREES F (HEATING) FOR OCCUPIED MODE; 85 DEGREES F (COOLING) AND 55 DEGREES F (HEATING) FOR UNOCCUPIED MODE.LOCATIONCLIMATE ZONE 5ENVELOPE PROPERTIESROOF INSULATION: R-25ciWALL INSULATION: R-13 + R-3.8C OR R-20GLASS U-VALUE: 0.38GLASS SHGC: 0.40OPAQUE DOOR U-VALUE: 0.37SLAB INSULATION: R-10 (24" BELOW)INDOOR SPACE CONDITIONSINDOOR POOL: 86 DEGREES F (DB) / 50% RHALL OTHERS (OCCUPIED): 75 DEGREES F (DB) / 50% RH COOLING 70 DEGREES F (DB) HEATINGALL OTHERS (UNOCCUPIED): 85 DEGREES F (DB) COOLING 55 DEGREES F (DB) HEATINGAPPLICABLE CODES -2016 CONNECTICUT BUILDING CODE2016 CONNECTICUT MECHANICAL CODE2012 INTERNATIONAL ENERGY CONSERVATION CODEMOTOR OPERATED VALVEMOVN.I.C.NOT IN CONTRACTTHROUGHTHRUSQUARE FEETSFFEET PER MINUTEFPMBELOWBELABOVE CEILINGA/CEXHAUSTEXHELECTRICALELECCFCUBIC FEETADADJAFFARCHBDB/FBTUHCCAPCDCFMCLGCOCONCCONNCONTDDBDGDIFFDNDWGSEAEATEGENGERESPEWTFDFLRFODFSDFTGALGPMGRHPINLWTMBHMDMINMODNOMNPSHAOAOBDOCOPNGPHPIUPLBGPRVPSIAPSIGRARAGRARREGRLRPMRSSASDSGSPSQSRSTRTETGTRANST'STATTYPUCUNOVAVVELW/WBWCWGFNCACCESS DOORADJUSTABLEABOVE FINISHED FLOORARCHITECTBACKDRAFT DAMPERBELOW FLOORCONVECTORCAPACITYCEILING DIFFUSERCUBIC FEET PER MINUTECEILINGCLEANOUTCONCRETECONNECTIONCONTINUATIONDRAINDRY BULBDOOR GRILLEDIFFUSERDOWNDRAWINGSEACHENTERING AIR TEMPERATUREEXHAUST GRILLEENGINEEREXHAUST REGISTEREXTERNAL STATIC PRESSURE (IN WG)ENTERING WATER TEMPERATUREFIRE DAMPERFLOORFACE OPERATED DAMPERFIRE/SMOKE DAMPERFEETGALLONS PER MINUTEGRILLEHORSEPOWERINCHESLEAVING WATER TEMPERATUREMAXIMUMMANUAL DAMPERMINIMUMMOTOR OPERATED DAMPERMOUNTEDNOISE CRITERIANORMALLY CLOSEDNORMALLY OPENNUMBER OR DESIGNATIONNOMINALNET POSITIVE SUCTION HEAD AVAILOUTSIDE AIROPPOSED BLADE DAMPERON CENTERSOPENINGELECTRICAL PHASEPOWERED INDUCTION UNITPLUMBINGPRESSURE REDUCING VALVEPOUNDS PER SQ. IN. ABSOLUTEPOUNDS PER SQ. IN. GAUGERETURN AIRRETURN AIR GRILLERETURN AIR REGISTERREGISTERRELATIVE HUMIDITYREFRIGERANT LIQUIDROTATIONS PER MINUTEREFRIGERANT SUCTIONSUPPLY AIRSMOKE DAMPERSUPPLY GRILLESQUARESUPPLY REGISTERSTRUCTURALTOILET EXHAUSTTRANSFER GRILLETRANSITIONTHERMOSTATTYPICALUNDERCUTUNLESS NOTED OTHERWISEVARIABLE AIR VOLUME UNITVELOCITYWITHWET BULBWATER COLUMNWATER GAUGEDEGREES FAHRENHEITMTDABBREVIATION/DEFINITION ABBREVIATION/DEFINITIONLINEAR FEETLINEAR SLOT DIFFUSERPOUNDSLINEAR BAR GRILLELEAVING AIR TEMPERATURELOUVER & SCREENLFLSDLBS.LBGLATL&SBRITISH THERMAL UNIT/HOURMAX1000 BTU/HOURN/ANOT APPLICABLESSSTAINLESS STEELHR HOURHD HEAD (FT WC)FLEX FLEXIBLEFADIA DIAMETER ( )KWKILOWATTN.C.N.O.NO.R/HSTATIC PRESSURE (IN. W.G.)GALLON(S)FREE AREANOTE: THESE ARE STANDARD ABBREVIATIONS. ALL ITEMS MAY NOT APPEAR ON DRAWINGS.PRESSURE DROPPFLANGETEST WELLTHERMOMETERPRESSURE GAUGEGAUGE COCKSTRAINERPRESSURE REDUCING VALVENON-SLAM CHECK VALVE (CV)3-WAY CONTROL VALVEGATE VALVE (GV)BUTTERFLY VALVE (BV)BALL VALVEREFRIGERANT LINE (SUCTION/LIQUID)THERMOSTAT/SENSOR/HUMIDISTATMOTOR OPERATED DAMPERMOTOR OPERATED FIRE SMOKE DAMPERFIRE DAMPER (HORIZONTAL/VERTICAL)MANUAL DAMPERDUCT DROPDUCT RISEEND CAP (PIPE OR DUCT)EXISTING EQUIPMENT TO BE REMOVEDFLEXIBLE DUCT CONNECTIONLINED DUCTWORKRETURN/EXHAUST AIR DEVICESUPPLY AIR DEVICENOTE: THIS IS A STANDARD LEGEND. ALL ITEMS MAY NOT APPEAR ON DRAWINGS.PUMPUNIONORM.D.RSDSFDRDRLMDRAINFDSYMBOLSDESCRIPTIONSDEXISTING EQUIPMENT TO REMAINFSDTHSMOKE DETECTORCONDENSER WATER SUPPLY/CONDENSER WATER RETURNCWS CWRCHILLED WATER SUPPLY/CHILLED WATER RETURNCHWS CHWRHEATING WATER SUPPLY/HEATING WATER RETURNHWS HWREXISTING EQUIPMENT RELOCATEDFSDHVAC ABBREVIATIONSHVAC LEGENDREVISIONSPROJECT #:DATE:phonefaxmpg-architects.com330.666.5770330.666.88123660 Embassy ParkwayFairlawn, OH 44333MECHANICAL GENERAL NOTESM000CAMBRIA SUITES HOTEL1000 LONGLEAF LANE,SOUTH WINDSOR, CT 060741 OF 2215815JUNE 24, 2016BID ALTERNATES #3 - WIRED THERMOSTATS: CONTRACTOR IS TO PROVIDE A DEDUCT ALTERNATE TO HVAC BID WHICH REMOVES ALL WIRELESS THERMOSTATS AND ALL SUPPORTING CONTROL SYSTEMS. WIRED THERMOSTAT, TYPE ISLANDAIRE 6040927, OR EQUAL, IS TO BE USED IN LIEU OF THE REMOVED WIRELESS THERMOSTATS. COORDINATE ELECTRICAL ROUG-IN AND CONTROL WIRING W/ ELECTRICAL CONTRACTOR.44 6/25/2018 BULLETIN #1 21345665431254312777VERTICAL TERMINAL AIR CONDITIONING UNIT SCHEDULEQUANTITYUNITNUMBERVTAC-AWBEAT (°F)DIRECT EXPANSION COOLING COILCAPACITYSENSIBLE(MBH)CAPACITYTOTAL(MBH)DBELECTRICALSELECTIONBASED ONREMARKSEERSEE PLANSVTAC-B(KW)HEATELECTRICCOPSEE PLANSREVERSE CYCLE(MBH)HTG (MTSH)FCU-1-1LOCATIONNUMBERUNITCFMFAN DATA(IN. W.G.)EXTERNALS.P.EAT (°F)(MBH)CAPACITYSENSIBLE(MBH)CAPACITYTOTALDBD.X. COOLING COILFAN COIL UNITWBREVERSE CYCLE(MBH)ROOFLOCATIONBASED ONSELECTIONNUMBERUNITAIR COOLED CONDENSING UNITCOND.(°F)EATCOMPRESSOR DATATYPENO.CARRIER 25HCB560BASED ONSELECTIONREMARKSSEERFANHP (W)MOTOR(KW)HEATELECTRICCU-1-1ELECTRICALELECTRICALHTG (MTSH)HSPFLAUNDRY [151]FCU-1-2FCU-1-3FCU-1-4FCU-1-5FCU-1-6FCU-1-7FCU-1-8FCU-1-9FCU-1-12FCU-1-13FCU-1-14BOH CORR. [144]MEETING [155]PREFUNCT. [137]KITCHEN [138]FITNESS [114]ELEV. EQ. RM [117]IT ROOM [125]WORK [122]MARKET [134]HANGOUT [133]MEETING [155]PREFUNCT. [137]PUB [135]ROOFROOFROOFROOFROOFROOFROOFROOFROOFROOFROOFCU-1-2CU-1-3CU-1-4CU-1-5CU-1-6CU-1-7CU-1-8CU-1-9CU-1-10CU-1-11CU-1-12CU-1-13CU-1-14CARRIER FX4DNF6145.0 60.02,0000.43/40.40.40.40.4N/A67 60.015.0 (20.0)3.8 (5.0)18.067806.0 (8.0)30.0678015.0 (20.0)60.0678025.0 (27.7)87.067803.8 (5.0)18.0678011.3 (15.0)48.06780N/A6780N/A29.867806.0 (8.0)24.06780678011.3 (15.0)42.067806001/313.518.01,0001/222.530.02,0003/445.060.03,0002.467.590.06001/313.518.01,6001/236.048.0490-13.518.0860-22.530.08001/318.024.08001/318.024.01,4001/231.542.0N/A15.0978.5CARRIER FX4DNF19CARRIER FX4DNF31CARRIER FX4DNF61CARRIER 40RUAA08CARRIER FX4DNF19CARRIER FX4DNF49CARRIER RAV-SP180KRTCARRIER RAV-SP300CTCARRIER FX4DNF25CARRIER FX4DNF25CARRIER FX4DNF43CARRIER 25HCB518CARRIER 25HCB530CARRIER 25HCB560(3.3)SCROLL1(11.0)CARRIER 38AUQA08CARRIER 25HCB518CARRIER 25HCB54811.519.5CARRIER RAV-SP180AT28.520.6CARRIER RAV-SP300AT2CARRIER 25HCB524CARRIER 25HCB524CARRIER 25HCB542FCU-2-1 7,500208V/1PH340MMK-AP0073H2UL80 67 8,5000DUCTLESSCU-R-1MARK TYPECOOLINGCAPACITY(BTUH)CFM O.A.SUPPLY FAN EAT (°F)DB WBHEATINGCAPACITY(BTUH)ELECTRICALSELECTION BASEDON CARRIER MODEL #CONDENSINGUNITREMARKSDUCTLESS 0 13,500678035012,000FCU-2-2DUCTED 0 17,0006780MMD-AP0154BH2UL63515,400FCU-2-3DUCTLESS 0 6780FCU-3-1DUCTLESS 0 6780FCU-3-2FCU-3-3DUCTLESS 0 8,50067803407,500FCU-4-1FCU-4-2 12,000 350 80 67 13,5000DUCTLESSMMK-AP0123H2ULMMK-AP0073H2ULMMK-AP0123H2ULCU-R-1CU-R-1CU-R-1CU-R-1CU-R-1CU-R-1CU-R-1 144.0 208V/3PH 97MMY-AP1444FT6UL11.5MARKCOOLINGCAPACITY(MBH)ELECTRICALSELECTION BASEDON CARRIER MODEL #REMARKSEERAMBIENTTEMPERATURE(°F)UNITNUMBEREF-1-1SERVICE LOCATION CFMFAN TYPESTATICPRESSURE(IN. W.G.)SELECTIONBASED ONFAN MOTORDRIVEFANRPMELECTRICALHPREMARKSELEC. [148]GREENHECK MODEL CSP-A700BREAK [141]POOL ROOFROOFEF-1-2EF-2-1EF-R-1KEF-1ROOFGREENHECK MODEL CSP-A250120V/1PHGREENHECK MODEL G-070-VGGREENHECK MODEL SWB-210-15EXHAUSTKITCHEN EXHAUSTEXHAUSTEXHAUSTEXHAUSTDOWNBLASTDOWNBLAST450 0.40 849 DIRECT (350)(83)DIRECT9930.40200120V/1PH1/4DIRECT13750.25200208V/1PH1/2DIRECT15101.0012101-1/2BELT28171.501935BI UTILITYVENTINLINEINLINEGREENHECK MODEL G-123-VGDUCTEDCU-R-1DUCTED 0 24,000678079021,000FCU-4-3CU-R-1MMK-AP0243H2ULDUCTLESS 0 27,000678060024,000FCU-4-4MMD-AP0214BH2UL162.0 3.4HEATINGCAPACITY(MBH)COP208V/1PH208V/3PH208V/3PH(COP)97979797979797979797971SCROLL1SCROLL1SCROLL1SCROLL1SCROLL1SCROLL1HERMETIC11SCROLL1SCROLL1SCROLL208V/1PH(EER)19.024.0POOL ROOFEF-2-2GREENHECK MODEL G-123-VGEXHAUSTDOWNBLAST1/4DIRECT8600.25970FCU-1-10FCU-1-11DUCTLESS 0 8,5006780MMK-AP0073H2UL3407,500FCU-2-4CU-R-106780FCU-3-4CU-R-1DUCTLESS7,500 34035012,0003407,5008,50013,5008,500MMK-AP0073H2ULMMK-AP0123H2ULMMK-AP0073H2UL80(W)OACFM14015050554055055105425N/AN/A115630280505HERMETIC0 17,0006780MMD-AP0154BH2UL63515,400CU-R-1FUNCT. STOR. [140]DWEF-1GREENHECK MODEL CSP-A700DISHWASHER EXHAUST0.75525120V/1PHINLINE 1024 DIRECT (350)15.38.515.38.515.28.515.08.515.08.515.38.715.08.515.38.70.40.40.40.40.4208V/1PH208V/1PH208V/1PH208V/1PH208V/1PH208V/1PH208V/1PH208V/1PH208V/1PH208V/1PH208V/1PH208V/1PH208V/1PH208V/1PH208V/1PH208V/1PH208V/1PH208V/1PH208V/1PH208V/1PH208V/1PH208V/1PH208V/1PH208V/1PH208V/1PH208V/1PH208V/1PH208V/1PH208V/1PH208V/1PH208V/1PH208V/1PH208V/1PH208V/3PH2PROVIDE WALL-MOUNTED, DIGITAL PROGRAMMABLE THERMOSTAT. CONTROLS SHALL HAVE LOCKOUT CAPABILITY SO ADJUSTMENT CAN ONLY BE PERFORMED BY BUILDING PERSONNEL.MOUNT CONDENSING UNIT ON EQUIPMENT CURB RAILS WITH SPRING ISOLATORS.4REFRIGERANT LINES TO BE SIZED PER MANUFACTURER'S RECOMMENDATIONS.HEATER SIZES RATED AT 208V/1PH (230V RATING SHOWN IN PARENTHESIS). PROVIDE SINGLE POINT POWER CONNECTION FOR UNIT AND HEATER.5511112121212112121111212OUTSIDE AIR TO BE CONDITIONED UPSTREAM OF FCU BY OTHER EQUIPMENT (MAUE-1).6INSTALL ADDRESSABLE-TYPE SMOKE DETECTOR IN UNIT RETURN DUCT, UPSTREAM OF FILTERS. IF SMOKE DETECTED, UNIT SHALL SHUT DOWN AND SEND SIGNAL TO FIRE ALARM PANEL.74PROVIDE WALL MOUNTED, DIGITAL PROGRAMMABLE THERMOSTAT.374444474444444472REFRIGERANT LINES TO BE SIZED PER MANUFACTURER'S RECOMMENDATIONS.1INSTALLATION, CONTROLS, AND STARTUP OF VARIABLE REFRIGERANT (VR) SYSTEMS AND COMPONENTS SHALL ONLY BEPERFORMED BY A FACTORY CERTIFIED CONTRACTOR. CONTRACTOR SHALL PROVIDE WRITTEN PROOF OF CERTIFICATIONBY MANUFACTURER WITH BID AND WITH FINAL PROJECT DOCUMENTATION. ALL WORK SHALL BE PERFORMED BY INSTRICT CONFORMANCE WITH THE MANUFACTURER'S RECOMMENDATIONS.12311111111111222222REFRIGERANT LINES TO BE SIZED PER MANUFACTURER'S RECOMMENDATIONS.13INSTALLATION, CONTROLS, AND STARTUP OF VARIABLE REFRIGERANT (VR) SYSTEMS AND COMPONENTS SHALL ONLY BEPERFORMED BY A FACTORY CERTIFIED CONTRACTOR. CONTRACTOR SHALL PROVIDE WRITTEN PROOF OF CERTIFICATIONBY MANUFACTURER WITH BID AND WITH FINAL PROJECT DOCUMENTATION. ALL WORK SHALL BE PERFORMED BY INSTRICT CONFORMANCE WITH THE MANUFACTURER'S RECOMMENDATIONS.MOUNT CONDENSING UNIT ON EQUIPMENT CURB RAILS WITH SPRING ISOLATORS.32132PROVIDE COUNTER-BALANCED BACKDRAFT DAMPER.1FAN SHALL OPERATE CONTINUOUSLY.13PROVIDE WALL MOUNTED, LINE VOLTAGE THERMOSTAT. SET THERMOSTAT TO 75 DEGREES FAHRENHEIT.4FAN SHALL OPERATE ONLY WHEN POOL DEHUMIDIFICATION UNIT (PDUE-1) IS IN ECONOMIZER MODE.7PROVIDE SOLID STATE SPEED CONTROLLER, FOR BALANCING PURPOSES. INSTALL SPEED CONTROLLER AND SWITCH AT UNIT (DO NOT MOUNT ON WALL).3772171211218PROVIDE UNIT MANUFACTURER'S 12" ROOF CURB.889FAN SHALL BE UL LISTED FOR GREASE EXHAUST AND POWER VENTILATOR PURPOSES (U.L. 705 AND U.L. 762).95FAN SHALL OPERATE IN CONJUNCTION WITH THE KITCHEN DISHWASHER.6FAN SHALL OPERATE VIA AUTO/ON SWITCH WITH AUTO FUNCTION CONTROLLED BY GREASE EXHAUST HOOD CONTROLS.56PROVIDE CONDENSATE PUMP BY UNIT MANUFACTURER.86222222PROVIDE ECONOMIZER MIXING BOX WITH ASSOCIATED SENSORS, DAMPERS, AND CONTROLS. ECONOMIZER MIXING BOX SHALL BE MANUFACURED TO SPECIFICALLY MATCH THESUPPLIED FAN COIL UNIT (MAKE AND MODEL).999999999910FAN MOTOR SHALL BE AN ELECTRICALLY COMMUNICATED MOTOR WITH ADJUSTABLE POTENTIOMETER.10PROVIDE WALL-MOUNTED, DIGITAL PROGRAMMABLE THERMOSTAT. CONTROLS SHALL HAVE LOCKOUT CAPABILITY SOADJUSTMENT CAN ONLY BE PERFORMED BY BUILDING PERSONNEL.22222233333333333COMPRESSOR DATATYPENO.4 TWIN ROTARY11FAN SHALL BE ALL ALUMINUM CONSTRUCTION.11119ROOFCARRIER 25HCB54297 1SCROLL15.08.5208V/1PHROOFCARRIER 25HCB54297 1SCROLL15.08.5208V/1PH42.067801,4001/231.542.0CARRIER FX4DNF430.4208V/1PH11.3 (15.0)42.067801,4001/231.542.0CARRIER FX4DNF430.4208V/1PH12PROVIDE DISCONNECT SWITCH BY UNIT MANUFACTURER.13PROVIDE PLUG-TYPE DISCONNECT BY UNIT MANUFACTURER.1213131312CONDENSING UNIT HAS TWO (2) SEPARATE ELECTRICAL CONNECTIONS.44REVERSE CYCLE HEATING SHALL LOCKOUT AND ELECTRIC HEAT WILL ENABLE WHEN OUTSIDE AIRTEMPERATURE IS BELOW 40 DEGREES F.10101010101010101010101010714 1514FAN SHALL HAVE SPARK RESISTANT CONSTRUCTION WITH TEFC MOTOR.15PROVIDE KYNAR COATING ON ALL PARTS EXPOSED TO AIRSTREAM.11.3 (15.0)6.0 (8.0)16MOUNT UNIT ON EQUIPMENT CURB RAILS WITH SPRING ISOLATORS.16SPLIT SYSTEM AIR CONDITIONING UNIT SCHEDULESPLIT SYSTEM VARIABLE REFRIGERANT HEAT PUMP UNIT SCHEDULESPLIT SYSTEM VARIABLE REFRIGERANT CONDENSING UNIT SCHEDULEFAN SCHEDULE208V/1PH720 0.75 1320 DIRECT 3/4EXHAUSTROOFEF-R-3,5DOWNBLASTEF-R-4ROOFEXHAUST3/4DIRECT11400.50630208V/1PHDOWNBLASTEF-R-6ROOFEXHAUST3/4DIRECT16550.50950208V/1PHDOWNBLASTEF-R-7ROOFEXHAUST3/4DIRECT20500.751400208V/1PHDOWNBLASTGREENHECK MODEL G-143HP-VGGREENHECK MODEL G-143HP-VGGREENHECK MODEL G-143HP-VGGREENHECK MODEL G-143HP-VG2221111888812121212PROVIDE ARCHITECTURAL LOUVER BY UNIT MANUFACTURER.PROVIDE UNIT MOUNTING BRACKETS/SLEEVE AND PLENUM (BETWEEN UNIT AND LOUVER) BY EQUIPMENT MANUFACTURER.INSTALL MOUNTING BRACKET AT HEIGHT NECESSARY FOR LOUVER TO MEET ARCHITECTURAL REQUIREMENTS. COORDINATE AS NECESSARY.PROVIDE ACCESS PANEL WITH RETURN AIR FILTER GRILLE AND FILTER BY UNIT MANUFACTURER. SEE ENLARGED GUEST ROOM PLANS FOR LOCATION.PROVIDE WALL MOUNTED, DIGITAL, WIRED THERMOSTAT. UNIT CONTROLS AND THERMOSTAT SHALL BE COMPATIBLE WITH AND CONNECTED TO GUESTROOM CONTROL SYSTEM.HEATER SIZES RATED AT 208V/1PH. PROVIDE SINGLE POINT POWER CONNECTION FOR UNIT AND HEATER.REVERSE CYCLE HEATING SHALL LOCKOUT AND ELECTRIC HEAT WILL ENABLE WHEN OUTSIDE AIR TEMPERATURE IS BELOW 40 DEGREES F.ORDER UNIT WITH FACTORY-SET 35-CFM OUTDOOR AIR RATE.ISLANDAIRE EZVR15B4C3.0(3.6)158.5208V/1PH3.03.367802.0(2.5)67809.910.7 15.4500ISLANDAIRE EZVR09B4B208V/1PH11.38.96.5330CFM888MEN'S [043]EF-3GREENHECK MODEL SP-A70-LEDEXHAUSTCABINET1/4DIRECT7900.1550120V/1PH1WOMEN'S [044]EF-4GREENHECK MODEL SP-A70-LEDEXHAUSTCABINET1/4DIRECT7900.1550120V/1PH41 8 10 11 121517CONTROL WITH OCCUPANCY SENSOR-CONTROLLED LIGHTING FOR CONTINUOUS OPERATION WHILE OCCUPIED.171712121ST FLOOR UNITSEF-5BY HVAC CONTRACTOREXHAUSTCABINET1/8DIRECT--0.2030120V/1PH12 1218DUCT TO SIDEWALL LOUVER AT EXTERIOR; ROUTE DUCT ABOVE DROP-CEILING.1888REVISIONSPROJECT #:DATE:phonefaxmpg-architects.com330.666.5770330.666.88123660 Embassy ParkwayFairlawn, OH 44333MECHANICAL SCHEDULESM001CAMBRIA SUITES HOTEL1000 LONGLEAF LANE,SOUTH WINDSOR, CT 060742 OF 2215815JUNE 24, 20166 11/05/2018 BULLETIN #38 12/26/2018 BULLETIN #56 EERSELECTION BASED ONREMARKS(°F)EDB EWB(°F) (MBH)SENS.COOLING COIL - SUMMER OPERATION (DRY)ELECTRIC HEATING COILUNIT DATAO.A.ELECTRICALE.S.P.H.P.MARKMOTORLDB(°F)LWB(°F)SUPPLYCFM(°F)EDB(°F)LDB(KW)INPUTMAUE-14,0004,000 1.0 5 208V/3PH 76.795.5 54.955.1 301.8172.370.0 80CARRIER 39MN SIZE 0810.96.6(°F)EDB EWB(°F)COOLING COIL - SUMMER OPERATION (WET)LDB(°F)LWB(°F)76.276.2 52.052.0(MBH)TOTALUNITNUMBERDIRECT EXPANSION COOLING COILTOTALSENSIBLE(MBH)COMPRESSOR DATANO.REMARKSLOCATIONNUMBERUNITAIR COOLED CONDENSERBASED ONSELECTION(MBH)EVAPORATOR UNITHPFANMOTORNO. OFFANSPDUE-1 2.24 1 SCROLLPDUC-1 GROUND 1 DECTRON MODEL CAY1011DTYPE208V/3PH6203,000CFMTOTAL ESPOACFM (IN. WC)AIR DATA1.0 48.045.828.6REMOVAL(LB./HR)MOIST.LOCATIONNUMBERUNITAIR COOLED CONDENSING UNITCOND.(°F)EATCOMPRESSOR DATATYPENO.BASED ONSELECTIONELECTRICALEVAPORATOR UNITMAUC-1 ROOF95.5 1 SCROLL 208V/3PH CARRIER 38APD027RTU-WNUMBERUNITSUPPLYCFMO.A.CFME.S.P. MOTOR H.P.UNIT DATAELECTRICALEDB(°F)EWB(°F)LDB(°F)LWB(°F)TOTAL(MBH)DX COOLINGSENS(MBH)RATING (MBH)GAS HEATINGGASTYPEEERSELECTIONBASED ONREMARKS700 700 1.0 1NGNG208V/3PH11.0700700RTU-NGREENHECK MODEL DGX-109-H1211.2116.5NG39.8 64.566.672.376.795.51.01.501,5501,550KMAU-1208V/3PH208V/3PHVOLT/PHDECTRON DSV-M-030-011INPUT OUTPUT107.1TOTAL (MBH) UNIT LATDB/WBUNIT AIRDEWPOINT (°F)REHEAT PUMP(MBH)SENS.325.8103.4(MBH)TOTAL# OFSTAGESGAS HEATING2PROVIDE SINGLE POINT ELECTRICAL CONNECTION.PROVIDE INSULATED ROOF CURB BY UNIT MANUFACTURER.1123PROVIDE HINGED ACCESS DOORS.4PROVIDE THRU-CURB ELECTRICAL CONNECTIONS.5PROVIDE CONTROLS IN AHU PANEL. PROVIDE SAT SENSOR, OAT SENSOR, AND CONTROLS, ENABLING UNIT TO DISCHARGEROOM NEUTRAL AIR AT 75/50% (DB/RH) AT ALL TIMES.6UNIT SHALL OPERATE VIA AUTO/ON SWITCH WITH AUTO FUNCTION CONTROLLED BY GREASE EXHAUST HOOD CONTROLS.3456123412342PROVIDE CONTROLS IN AHU PANEL. PROVIDE SAT SENSOR, SA HUMIDITY SENSOR, OAT SENSOR AND OA HUMIDITY SENSOR TOINTERFACE WITH CONTROLS, ENABLING UNIT TO DISCHARGE ROOM NEUTRAL AIR AT 75/50% (db/RH) AT ALL TIMES.4REFRIGERANT LINES TO BE SIZED PER MANUFACTURER'S RECOMMENDATIONS.1MOUNT CONDENSING UNIT ON EQUIPMENT CURB RAILS WITH SPRING ISOLATORS.312342PROVIDE UNIT WITH HINGED ACCESS DOORS.13INSTALL ADDRESSABLE-TYPE SMOKE DETECTOR IN UNIT SUPPLY DUCT. IF SMOKE DETECTED, UNIT SHALL SHUT-DOWNAND SEND SIGNAL TO FIRE ALARM PANELPROVIDE WALL-MOUNTED 7-DAY PROGRAMMABLE CONTROLLER WITH THERMOSTAT AND HUMIDISTAT. CONTROLLERSHALL HAVE OCCUPIED/UNOCCUPIED SETPOINTS, AND BATTERY BACKUP.4INSTALL EVAPORATOR UNIT ON GRADE AS SHOWN.5PROVIDE FM APPROVED GAS TRAIN.6MOUNT CONDENSING UNIT ON EQUIPMENT CURB RAILS WITH SPRING ISOLATORS.712345 77UNIT SHALL HAVE 25:1 TURNDOWN RATIO.7LDB(°F)70.0COMPRESSOR DATATYPENO.1SCROLL1SCROLL1SCROLL8PROVIDE HAIL GUARD.9INSTALL ADDRESSABLE-TYPE SMOKE DETECTOR IN UNIT RETURN DUCT, UPSTREAM OF FILTERS. IF SMOKE DETECTED,UNIT SHALL SHUT DOWN AND SEND SIGNAL TO FIRE ALARM PANEL.10UNIT SHALL OPERATE CONTINUOUSLY.11PROVIDE FACTORY INSTALLED DEHUMIDIFICATION SYSTEM WITH HOT-GAS REHEAT COIL AND ASSOCIATED CONTROLS.12PROVIDE CONTROLS IN AHU PANEL. PROVIDE SAT SENSOR, SA HUMIDITY SENSOR, OAT SENSOR AND OA HUMIDITY SENSOR TOINTERFACE WITH CONTROLS, ENABLING UNIT TO DISCHARGE ROOM NEUTRAL AIR AT 75/50% (db/RH) AT ALL TIMES.13PROVIDE VIBRATION ISOLATION.8 101112138 10111213INSTALL ADDRESSABLE-TYPE SMOKE DETECTOR IN UNIT RETURN DUCT AND SUPPLY DUCT, UPSTREAM OF FILTERS. IFSMOKE DETECTED, UNIT SHALL SHUT DOWN AND SEND SIGNAL TO FIRE ALARM PANEL.STAGES35EVAPORATOR UNIT SHALL BE SUPPLIED WITH TOP SUPPLY AND RETURN AIR DUCT CONNECTIONS.6EVAPORATOR UNIT SHALL BE SUPPLIED WITH FILTER SECTION WITH 4"-MERV 8 FILTERS.78EVAPORATOR UNIT SHALL BE INSTALLED ON 6" CONCRETE EQUIPMENT PAD, SIZED 12" LARGER THAN FOOTPRINT OF UNIT(6" LARGER ON EACH SIDE). COORDINATE WITH ARCHITECT AND STRUCTURAL ENGINEER.PROVIDE VIBRATION ISOLATION FOR EVAPORATOR UNIT.9ELECTRIC HEATING COIL SHALL BE INSTALLED UPSTREAM OF THE COOLING COIL (I.E. IN PREHEAT POSITION).10PROVIDE HAIL GUARD FOR AIR COOLED CONDENSING UNIT.11567891011REFRIGERANT LINES TO BE SIZED PER MANUFACTURER'S RECOMMENDATIONS.8EVAPORATOR UNIT SHALL BE INSTALLED ON 6" CONCRETE EQUIPMENT PAD, SIZED 12" LARGER THAN FOOTPRINT OF UNIT(6" LARGER ON EACH SIDE). COORDINATE WITH ARCHITECT.PROVIDE VIBRATION ISOLATION FOR EVAPORATOR UNIT.9PROVIDE UNIT WITH HAIL GUARDS BY UNIT MANUFACTURER.1011PROVIDE EVAPORATOR UNIT WITH FILTER SECTION FOR 4-2" MERV 8 FILTERS.12PROVIDE UNIT WITH FACTORY INSTALLED DEHUMIDIFICATION/HOT-GAS REHEAT COIL.13EVAPORATOR UNIT SHALL BE SUPPLIED WITH AIRFOIL SUPPLY FAN.1415PROVIDE EVAPORATOR UNIT WITH TOP SUPPLY AND SIDE RETURN AIR DUCT CONNECTIONS.PROVIDE EVAPORATOR UNIT WITH TOP-DUCTED OUTSIDE AIR SUPPLY AND MOTORIZED DAMPER.PROVIDE EVAPORATOR UNIT WITH AN ECONOMIZER MODE AND ASSOCIATED DAMPERS/CONTROLS.8 9 10 11 12 13 14 15PROVIDE SEPARATE ELECTRICAL CONNECTION FOR ELECTRIC HEATING COIL.1212POOL DEHUMIDIFICATION UNIT SCHEDULE100% OUTDOOR SPLIT SYSTEM MAKE-UP AIR UNITS100% OUTDOOR PACKAGE ROOFTOP MAKE-UP AIR UNITS5575.0 / 62.410.510.5 75.0 / 62.4 55-- -- --92.0 73.0 50.5 50.5 50.3233.433.4 50.3250.550.573.092.0110.1110.12280.080.0REZNOR YDMA-060100.0 12.0REZNOR YDMA-06012.0100.09937MCA3P50ABRK.ELECTRICAL11.9EERAUXILIARY DUCT HEATER208V/3PHVOLT/PH7.0MCA3P15ABRK.ELECTRICAL11.9EERMFR. & MODELUNITNUMBERDUCTINLET OUTLETVOLT/PH2PROVIDE VENT AND FLUE PIPES TO EXTERIOR WALL LOUVER WITH FLUE LOUVER AS HIGH AS POSSIBLE BELOW 2ND-FLOOR AND VENT LOUVER MIN. 3'-0" BELOW FLUE LOUVER.13PROVIDE CONTROLS FROM PDUE-1 TO OPERATE DUCT FURNACE WHEN SYSTEM CALLS FOR HEAT.MOUNT EQUIPMENT SUCH THAT INLET DUCT COMPLIES WITH MFR'S INSTALLATION INSTRUCTIONS FOR PROPER AIRFLOW ACROSS HEAT EXCHANGER.4PROVIDE FM APPROVED GAS TRAIN.5PROVIDE ACCESS PANEL--IF REQUIRED--FOR MAINTENANCE ACCESSIBILITY.612345PROVIDE INLINE POWER VENT TYPE TJERNLUND HS1-6, 115/1/60, 2A, 3000 RPM, INTERLOCK WITH DUCT FURNACE OPERATION.DUCT FURNACE SCHEDULEFLA BRK.ELECTRICALCFM2251P15A2REZNOR EEDU-2253000120/123"x18"23"x18"DF-1FLUENATURAL GAS175 4"INPUT(MBH)OUTPUT(MBH)283 LBSWEIGHT MFR. & MODEL REMARKS6VENT5"REVISIONSPROJECT #:DATE:phonefaxmpg-architects.com330.666.5770330.666.88123660 Embassy ParkwayFairlawn, OH 44333MECHANICAL SCHEDULESM002CAMBRIA SUITES HOTEL1000 LONGLEAF LANE,SOUTH WINDSOR, CT 060743 OF 2215815JUNE 24, 2016 EWH-ANUMBERUNITTYPESTAGESNO. OFCFMELECTRIC HEATING COILKWBASED ONSELECTIONREMARKSQTY.ELECTRICALEWH-BEWH-CBBH-ABBH-BBBH-CFAN FORCEDWALL HEATER175 2 1 1 120V/1PH MARKEL MODEL 3320MARKEL MODEL 3320208V/1PH3MARKEL MODEL 3320414N/ABASEBOARDHEATER1.2541.5MARKEL MODEL 3700MARKEL MODEL 3700MARKEL MODEL 3700FAN FORCEDWALL HEATERFAN FORCEDWALL HEATER611111175 3175 2BASEBOARDHEATERBASEBOARDHEATERECH-AMARKEL MODEL 34805FAN FORCEDCLNG HEATER1425 1SUNITNUMBERSERVICEPANEL SIZEA1NECK/DUCTSIZESELECTIONBASED ONREMARKSREX 24x24 SEE PLANS TITUS PASMATERIALSTEELN/AN/A208V/1PH208V/1PH208V/1PH208V/1PH208V/1PH12342PROVIDE SEMI-RECESSED MOUNTING KIT WITH REMOVABLE FRONT COVER.PROVIDE THERMAL SAFETY CUTOUT WITH MANUAL RESET.14PROVIDE INTEGRAL DISCONNECT SWITCH.5PROVIDE MOUNTING KIT AND PLASTER TRIM BY UNIT MANUFACTURER FOR INSTALLATION IN HARD ARCHITECTURALCEILING6UNIT SHALL BE U.L. LISTED.3PROVIDE SURFACE MOUNTING KIT WITH REMOVABLE FRONT COVER.7PROVIDE BLANK SECTIONS BETWEEN HEATERS TO FORM CONTINUOUS APPEARANCE.78PROVIDE INTEGRAL THERMOSTAT BY UNIT MANUFACTURER.7726146146146146146146A2A3A4A5B1B2B3C1D1D2D3E1E2E3E4F1F2F3STEEL24x12STEEL12x12TITUS OMNI12x1224x24TITUS PAR24x24XTITUS 50F24x24XTITUS 50F12x12XTITUS 272RL6x6X6x6X12x10XALUMINUM TITUS 350FL36x14XTITUS 50F6x68x824x1212x12TITUS 2-SLOT MLR-3948" LONGXXSTEELXXXXXTITUS PASTITUS PASTITUS OMNISEE PLANSSEE PLANSSEE PLANSSEE PLANSSEE PLANSSEE PLANSSEE PLANSSEE PLANSSEE PLANSSEE PLANSSEE PLANSSEE PLANSSEE PLANSSEE PLANSSEE PLANSSTEELSTEELSTEELALUMINUMALUMINUMSTEELSTEELSTEELALUMINUMSTEELSTEELXXXXF4ALUMINUMXSEE PLANSTITUS 50FTITUS 50FTITUS 50FTITUS 2-SLOT ML-39TITUS 4-SLOT MLR-39TITUS 4-SLOT ML-39E5 12x10 SEE PLANS ALUMINUMXTITUS 50FALUMINUMALUMINUMALUMINUM59PROVIDE INTEGRAL, STRATIFICATION-TYPE THERMOSTAT BY UNIT MANUFACTURER.898888848" LONG48" LONG48" LONGTITUS 350RLTITUS 350RL2PROVIDE FRAME AND BORDER FOR MOUNTING IN 2'x2' LAY-IN ACOUSTICAL TILE CEILING (T-BAR).PROVIDE FRAME AND BORDER FOR MOUNTING IN HARD ARCHITECTURAL CEILING.14PROVIDE DEVICES WITHOUT AIR DEFLECTORS.5PROVIDE DEVICES WITH 1" SLOT WIDTHS.3PROVIDE FRAME AND BORDER FOR SIDEWALL SURFACE MOUNTING.2221111111111113333445555C2TITUS 272RLSEE PLANSXSEE PLANS STEEL 3OUTPUTUH-AMARKNATURAL GASGASTYPE1/15H.P.45.0INPUTMOTORRATING (MBH)208V/1PH36.0ELECTRICALMODINE MODEL HDS 45BASED ONSELECTIONREMARKSLOCATIONLAUNDRY [153]ENTERINGAIRFLOW (CFM)720DATAPROVIDE THERMAL SAFETY CUTOUT WITH MANUAL RESET.12UNIT SHALL BE U.L. LISTED.3PROVIDE INTEGRAL THERMOSTAT BY UNIT MANUFACTURER.123B4TITUS 50F24x12X SEE PLANS ALUMINUM 113C3TITUS 272RL12x8XSEE PLANS STEEL 3SEE PLANSSEE PLANSSEE PLANSD4STEEL18x10X3SEE PLANSD5STEEL18x12X3SEE PLANSTITUS 350RLTITUS 350RLC4TITUS 272RL12x10XSEE PLANS STEEL 3C5TITUS 272RL10x10XSEE PLANS STEEL 3E6 6x6 SEE PLANS STEELXTITUS 350RL 3ELECTRIC HEATER SCHEDULEAIR DISTRIBUTION DEVICE SCHEDULEGAS-FIRED UNIT HEATER SCHEDULELV-1ALUMINUMX 4"Ø BY HVAC CONTRACTOR6" X 6"6OUTDOOR STATIONARY LOUVER; MOUNT RECESSED WITHIN EXTERIOR STONE AT 11'-0" TO BOTTOM. VERIFY IN-FIELD & COORDINATE WITH OWNER PRIOR TO ROUGH-IN.688REVISIONSPROJECT #:DATE:phonefaxmpg-architects.com330.666.5770330.666.88123660 Embassy ParkwayFairlawn, OH 44333MECHANICAL SCHEDULESM003CAMBRIA SUITES HOTEL1000 LONGLEAF LANE,SOUTH WINDSOR, CT 060744 OF 2215815JUNE 24, 20168 12/26/2018 BULLETIN #5 1,1145467157159361031603676139168862930210,149RTU-W TOTAL[CALCULATIONS BASED ON 2003 INTERNATIONAL MECHANICAL CODE]MAXIMUM #OCCFCU-1-1UNITDESCRIPTION(SF)AREACODE O.A.REQUIREMENT(PER PERSON)CFM O.A.(CFM)(CFM)ACTUAL O.A. OCC. DENSITY(#/1,000 SF)(PER SF)CFM O.A.TOTAL CODE REQUIRED OUTSIDE AIR IS THE SUM OF O.A. CFM PER PERSON AND O.A. CFM PER SQUARE FOOT.TOTALREQUIRED(CFM)FACTOREFFECTIVENESSHEATING EFFECTIVENESS FACTOR SHOWN. COOLING EFFECTIVENESS FACTOR IS 1.0 AND THEREFORE HEAT REPRESENTS WORST CASE SCENARIO.1FLOOR12125529781FCU-1-216211715FCU-1-3165FCU-1-56512201FCU-1-61601603FCU-1-71FCU-1-86761924FCU-1-91688FCU-1-121302FCU-1-133841715FCU-1-42206511629FCU-1-14RTU-WRTU-N1 CORRIDORS2 CORRIDORS3 CORRIDORS4 CORRIDORS23SYSTEM VENTILATION (OUTSIDE AIR) SCHEDULE814814814490467RM#016025026024017016012012036010011011007010013003039151-005006CORRIDORHANGOUTCOFFEE HOUSE PUBPREFUNCTIONMEETING ROOMBOH CORRIDORMARKETOFFICE SPACESFITNESS CENTERWELCOME LOBBYKITCHENELEVATOR LOBBYPREFUNCTIONCOFFEE HOUSE PUBGUEST LAUNDRYMEETING ROOMBREAK ROOMENG. OFFICELINEN STORAGELAUNDRYBOH CORRIDORMAU-1 TOTALSUBTOTALSUBTOTALSUBTOTALSUBTOTALSUBTOTALSUBTOTALSUBTOTALSUBTOTALSUBTOTALSUBTOTALSUBTOTALSUBTOTAL3840.80.80.80.80.80.80.80.80.80.80.87.52250.0630 19 1807.57650.18100 66 6127.5820.0630 7 660.80.852790.0650 36 2300.80.823000.062905540.0615 5 435770.0654 61203190.0610 37 2557.51160.0610 7 9304520.600 3627.5310.0610 2 257.5820.0630 7 667.57650.18100 66 6127.5240.0620 2 1952790.0650 36 2300.830420.0.063750.80.80.85120.0651 100150.1210 1 12252290.0010 6 1830.823000.062904,1253,936755422522510077375354125116475452900878875871300279300279756630028528000.06350-429000.063700.849000.066100.849000.066100.849000.066100.840000.065000.840000.065000.8662CORRIDORS662CORRIDORS2,9321986220 700150 70040000.065000.8662CORRIDORS151251351451250350450RTU-N TOTALREVISIONSPROJECT #:DATE:phonefaxmpg-architects.com330.666.5770330.666.88123660 Embassy ParkwayFairlawn, OH 44333MECHANICAL SCHEDULESM004CAMBRIA SUITES HOTEL1000 LONGLEAF LANE,SOUTH WINDSOR, CT 060745 OF 2215815JUNE 24, 2016 Make-up Aire As Built FCU-2-1VTAC-BVTAC-AVTAC-AVTAC-BVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-BVTAC-AVTAC-BVTAC-BVTAC-BVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AEF-2-2FCU-2-3FCU-2-2FCU-2-4M7013M70148"x8"8"x8"12M7017M7016M7015FSD, TYP.C5320 CFM10x10C5315 CFM10x10D418x10EF-2-13D.51SUPPLY DUCT FOR FAN COIL UNIT SHALL BE FULL SIZE OF UNITCONNECTION.KEYED NOTES:2RETURN DUCT FOR FAN COIL UNIT SHALL BE FULL SIZE OF UNITCONNECTION.3COORDINATE LOCATION OF FCU AND ASSOCIATED DUCTWORK,PIPING, ETC. TO AVOID ELECTRICAL EQUIPMENT AND REQUIREDCLEARANCES.CCDDC.5C.5AABBEEHHJFB.5B.5L.8L.6L.6MMLH.8H.8H.2H.2D.7D.5D.5A.5A.5554321762.57.27.27.57.598.88.888.98.93.54.58M304TYP.N44TITUS ML-39 2-SLOT DIFFUSER. 48"x6" MODULE58"x8" DUCT THROUGH SOFFIT66"x4" DOWN - 8"x8" UP5678"x8" UP457810"x10" EXHAUST DUCT UP920"x10" CEILING GRILL AT BOTTOM OF DUCT; PROVIDE FIRE DAMPER@ SHAFT PENETRATION1022"x8" EXHAUST1132"x8" SUPPLY AIR891011200 CFM1210"x4" OFFSET TRANSFER GRILLE134" DIAMETER EXHAUST RISER TO PLENUM DUCT ABOVE 4TH FLOORCEILING. MECHANICAL CONTRACTOR TO COORDINATE WITHSTRUCTURE FOR HORIZONTAL CHASE WITHIN ROOF TRUSSES PRIORTO FABRICATION OF TRUSSES.230 CFM13TYP.12204KING 01202KING 03206DQ 04208ADA KING 01210DQ 04212DQ 04214DQ 04216DQ 04218KING 01220KING 01222KING 02224ADA DQ 01203DQ 02201DQ 02205DQ 02207DQ 02209KING 01211DQ 02213DQ 02215KING 01226DQ 04228DQ 04230DQ 04232DQ 04234KING 01236KING 01238DQ 04240DQ 042291 BR SUITE 03231DQ 02233DQ SUITE235DQ SUITE237DQ SUITE239KING 01241KING 01ELEVATORLOBBY217LINEN219ELEC.225TELE/DATA223CORRIDOR251CORR.250CORR.250253STAIR B252STAIR AVENDING221242LINEN CHUTEFIREPLACE CONCENTRIC VENT UP & DND.5148" DIAMETER SUPPLY FROM VTAC UNIT, CONCEALED IN SOFFIT ANDABOVE BATHROOM CEILING.C3200 CFM12x81415AT EACH FLOOR, CONTRACTOR TO PROVIDE A CLEANOUT WITHACCESS PANEL (2-HOUR RATED) FOR THE KITCHEN EXHAUST PERREQUEST FROM FIRE MARSHAL15FSD, TYP.888888888888888808'16'20'1/8" = 1'-0"12'REVISIONSNPROJECT #:DATE:phonefaxmpg-architects.com330.666.5770330.666.88123660 Embassy ParkwayFairlawn, OH 44333SECOND FLOOR MECHANICAL PLANM102CAMBRIA SUITES HOTEL1000 LONGLEAF LANE,SOUTH WINDSOR, CT 060747 OF 2215815JUNE 24, 2016 1/8" = 1'-0"12ND FLOOR PLAN - MECHANICAL222 8/8/2016 ADD. #28 12/26/2018 BULLETIN #5 VTAC-AVTAC-AVTAC-BVTAC-AVTAC-BFCU-3-1VTAC-AVTAC-AVTAC-BVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-BVTAC-AVTAC-AVTAC-AVTAC-AVTAC-BVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-BVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AFCU-3-4FCU-3-2FCU-3-3128"x8"8"x8"M7023M7021M7018M7022FSD, TYP.C5320 CFM10x10C5315 CFM10x10D418x103D.51SUPPLY DUCT FOR FAN COIL UNIT SHALL BE FULL SIZE OF UNITCONNECTION.KEYED NOTES:2RETURN DUCT FOR FAN COIL UNIT SHALL BE FULL SIZE OF UNITCONNECTION.3COORDINATE LOCATION OF FCU AND ASSOCIATED DUCTWORK,PIPING, ETC. TO AVOID ELECTRICAL EQUIPMENT AND REQUIREDCLEARANCES.CCDDC.5C.5AABBEEHJFB.5B.5L.8L.6MMLH.8H.8H.2H.2D.7D.5D.5A.5A.5554321762.57.27.27.57.598.88.888.98.93.54.5N44TITUS ML-39 2-SLOT DIFFUSER. 48"x6" MODULE58"x8" DUCT THROUGH SOFFIT68"x8" DOWN - 12"x10" UP56710"x10" UP & 8"x8" DOWN457814"x12" UP & 10"x10" DOWN920"x10" WALL GRILLE MOUNTED MINIMUM OF 7'-2" A.F.F., PROVIDEFIRE DAMPER @ SHAFT PENETRATION, TYP.1022"x8" EXHAUST1132"x8" SUPPLY AIR8910111210"x4" OFFSET TRANSFER GRILLE144" DIAMETER EXHAUST RISER TO PLENUM DUCT ABOVE 4TH FLOORCEILING. MECHANICAL CONTRACTOR TO COORDINATE WITHSTRUCTURE FOR HORIZONTAL CHASE WITHIN ROOF TRUSSES PRIORTO FABRICATION OF TRUSSES.1213(2) 4" DIAMETER RISERS FROM BELOW, (2) 4" DIAMETER & (1) 6" RISERTO ABOVE.121314TYP.14TYP.14TYP.14TYP.200 CFM230 CFM12304KING 01302KING 03306DQ 04308ADA KING 01310DQ 04312DQ 04314DQ 04316DQ 04318KING 01320KING 013221 BR SUITE 02303DQ 02301DQ 02305DQ 02307DQ 02309KING 01311KING 01313DQ 02315KING 013261 BR SUITE 01328DQ 04330ADA KING 01332DQ 04334KING 01336KING 01338DQ 04340DQ 043291 BR SUITE 03331DQ 02333DQ SUITE335DQ SUITE337DQ SUITE339KING 01341KING 01ELEVATORLOBBY317LINEN319ELEC.325TELE/DATA323CORRIDOR351CORR.350353STAIR B352STAIR AVEND'G321340LINEN CHUTEFIREPLACE CONCENTRIC VENT UP & DND.5C3200 CFM12x8158" DIAMETER SUPPLY FROM VTAC UNIT, CONCEALED IN SOFFIT ANDABOVE BATHROOM CEILING.151616AT EACH FLOOR, CONTRACTOR TO PROVIDE A CLEANOUT WITHACCESS PANEL (2-HOUR RATED) FOR THE KITCHEN EXHAUST PERREQUEST FROM FIRE MARSHAL22FSD, TYP.8888888888888888808'16'20'1/8" = 1'-0"12'REVISIONSNPROJECT #:DATE:phonefaxmpg-architects.com330.666.5770330.666.88123660 Embassy ParkwayFairlawn, OH 44333THIRD FLOOR MECHANICAL PLANM103CAMBRIA SUITES HOTEL1000 LONGLEAF LANE,SOUTH WINDSOR, CT 060748 OF 2215815JUNE 24, 2016 1/8" = 1'-0"13RD FLOOR PLAN - MECHANICAL1 7/27/2016 ADD. #12 8/8/2016 ADD. #28 12/26/2018 BULLETIN #5 VTAC-AVTAC-AVTAC-BVTAC-AVTAC-BVTAC-BVTAC-AVTAC-AFCU-4-1VTAC-AVTAC-AVTAC-BVTAC-AVTAC-BVTAC-AVTAC-BVTAC-BVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AFCU-4-4FCU-4-2M7024DNUPFSD, TYP.D.51SUPPLY DUCT FOR FAN COIL UNIT SHALL BE FULL SIZE OF UNITCONNECTION.KEYED NOTES:2RETURN DUCT FOR FAN COIL UNIT SHALL BE FULL SIZE OF UNITCONNECTION.3COORDINATE LOCATION OF FCU AND ASSOCIATED DUCTWORK,PIPING, ETC. TO AVOID ELECTRICAL EQUIPMENT AND REQUIREDCLEARANCES.CCDDC.5C.5AABBEEHJFB.5B.5L.8L.6MMLH.8H.8H.2H.2D.7D.5D.5A.5A.5554321762.57.27.27.57.598.88.888.98.93.54.5N44TITUS ML-39 2-SLOT DIFFUSER. 200 CFM, 48"x6" MODULE58"x8" DUCT THROUGH SOFFIT612"x10" DOWN - 12"x12" UP56457712"x10" UP & 10"x10" DOWN816"x14" UP & 14"x12" DOWN920"x10" WALL GRILL MOUNTED MINIMUM OF 7'-2" A.F.F.; PROVIDE FIREDAMPER @ SHAFT PENETRATION, TYP.1022"x8" EXHAUST1132"x8" SUPPLY AIR891011121210"x4" OFFSET TRANSFER AIR GRILLE121212FCU-4-3128"x8"8"x8"C5320 CFM10x10C5315 CFM10x10D518x103EF-R-6EF-R-5EF-R-4EF-R-313(2) 4" DIAMETER & (1) 6" DIAMETER RISERS FROM BELOW14(2) 4" DIAMETER RISERS FROM BELOW15(3) 4" DIAMETER RISERS FROM BELOW16(4) 4" DIAMETER RISERS FROM BELOW17(5) 4" DIAMETER RISERS FROM BELOW18(6) 4" DIAMETER RISERS FROM BELOW8"Ø10"Ø12"Ø14"Ø14"Ø12"Ø10"Ø8"Ø8"Ø6"Ø12"Ø12"Ø8"Ø6"Ø6"Ø8"Ø10"Ø12"Ø10"Ø8"Ø6"Ø6"Ø8"Ø10"Ø12"Ø10"Ø8"Ø6"Ø16161815161816171614136"Ø14161416161616141612404KING 01402KING 03406DQ 044081 BR SUITE ADA4121 BR SUITE 04414DQ 04416DQ 04418KING 01420KING 014221 BR SUITE 02403DQ 02401DQ 02405DQ 02407DQ 02409KING 01411KING 01413DQ 02415KING 014261 BR SUITE 01428DQ 04430ADA KING 01432DQ 04434KING 01436KING 01438DQ 04440DQ 044291 BR SUITE 03431DQ 02433DQ SUITE435DQ SUITE437DQ SUITE439KING 01441KING 01ELEVATORLOBBY417LINEN419ELEC.425TELE/DATA423CORRIDOR451CORR.450453STAIR B452STAIR AVEND'G421442LINEN CHUTE200 CFM240 CFMFIREPLACE CONCENTRIC VENT UP & DND.5TRUSS PROFILE NOTE:ROOF TRUSS CONTRACTOR/ENGINEER IS TO PROVIDE A MINIMUM 24" WIDE CONTINUOUS CHASE WITHIN TRUSS PROFILE FOR EXHAUST DUCTWORK TO EXHAUST FANS. COORDINATE WITH SHEET S204 FOR MORE INFORMATION.C3200 CFM12x8198" DIAMETER SUPPLY FROM VTAC UNIT, CONCEALED IN SOFFIT ANDABOVE BATHROOM CEILING.19A3200 CFM12x12208" DIAMETER SUPPLY FROM VTAC UNIT, CONCEALED IN SOFFIT ANDABOVE SITTING ROOM CEILING (CEILING IS TO BE RECESSED INROOM 412 ONLY)21AT EACH FLOOR, CONTRACTOR TO PROVIDE A CLEANOUT WITHACCESS PANEL (2-HOUR RATED) FOR THE KITCHEN EXHAUST PERREQUEST FROM FIRE MARSHAL21808'16'20'1/8" = 1'-0"12'REVISIONSNPROJECT #:DATE:phonefaxmpg-architects.com330.666.5770330.666.88123660 Embassy ParkwayFairlawn, OH 44333FOURTH FLOOR MECHANICAL PLANM104CAMBRIA SUITES HOTEL1000 LONGLEAF LANE,SOUTH WINDSOR, CT 060749 OF 2215815JUNE 24, 2016 1/8" = 1'-0"14TH FLOOR PLAN - MECHANICAL222 8/8/2016 ADD. #28 12/26/2018 BULLETIN #5 KEF-1MAUC-1CU-R-1CU-1-6 CU-1-1 CU-1-5CU-1-2CU-1-3 CU-1-4CU-1-8CU-1-9CU-1-12CU-1-13CU-1-14EF-R-1KMAU-1CU-1-7CU-1-10CU-1-1112"x14"12"x18"FIREPLACE CONCENTRIC ROOF VENT OR FAN BY OTHERSCLEARANCE, TYP.KEYED NOTES:1112SSMOKE DETECTORMD.51PERMANENT MAINTENANCE ACCESS OVER DUCTWORK.2DUCT MOUNTED HIGH, ACCESS PATH IS BELOW.3ELEVATOR GRAVITY VENT WITH SMOKE DAMPER CONTROLLED BY120-VOLT ACTUATOR. GREENHECK PEV-400 OR EQUAL.CCDDC.5C.5AABBEEHJFB.5B.5L.8L.6MMLH.8H.8H.2H.2D.7D.5D.5A.5A.5544332211762.52.57.27.598.888.93.53.54.54.5NEF-R-6EF-R-4EF-R-34412"x12" DOWN THROUGH 2-HOUR RATED SHAFT512"x10" DOWN THROUGH 1-HOUR RATED SHAFT5632"x8" TO FIRST FLOOR, THROUGH 2-HOUR RATED SHAFT67722"x8" FROM FIRST FLOOR, THROUGH 2-HOUR RATED SHAFTEF-R-78816"x14" EXHAUST DUCT FROM 4TH FLOOR (CONTINUOUS OPERATION)10RTU-WRTU-WRTU-N111099999EF-R-5999999939EXHAUST PLENUM LOCATED ABOVE 4TH FLOOR CEILING & ROUTEDTHROUGH ROOF TRUSSES1012"x12" FROM RTU TO ABOVE 4TH FLOOR CORRIDOR CEILING1112"x12" HORIZONTAL SUPPLY DUCT ABOVE 4TH FLOOR CEILINGSHOWN ON THIS PLAN FOR ROUTING CLARITY ONLY.D.5TRUSS PROFILE NOTE:ROOF TRUSS CONTRACTOR/ENGINEER IS TO PROVIDE A MINIMUM 24" WIDE CONTINUOUS CHASE WITHIN TRUSS PROFILE FOR EXHAUST DUCTWORK TO EXHAUST FANS. COORDINATE WITH SHEET S204 FOR MORE INFORMATION.12AT TOP OF CHASE, CONTRACTOR TO PROVIDE A CLEANOUT FOR THEKITCHEN EXHAUST PER REQUEST FROM FIRE MARSHAL12808'16'20'1/8" = 1'-0"12'REVISIONSNPROJECT #:DATE:phonefaxmpg-architects.com330.666.5770330.666.88123660 Embassy ParkwayFairlawn, OH 44333ROOF MECHANICAL PLANM105CAMBRIA SUITES HOTEL1000 LONGLEAF LANE,SOUTH WINDSOR, CT 0607410 OF 2215815JUNE 24, 2016 1/8" = 1'-0"1ROOF PLAN - MECHANICAL8 12/26/2018 BULLETIN #5 FCU-1-1MAUE-1FCU-1-2FCU-1-4 FCU-1-3FCU-1-7FCU-1-6FCU-1-5FCU-1-8FCU-1-10FCU-1-9FCU-1-11FCU-1-12FCU-1-13FCU-1-14RS&L PIPING, SIZED PERMANUFACTURER'SRECOMMENDATIONS, TYP.RS&L PIPING UP TO ROOFRS&L PIPING UP TO ROOFRS&L PIPING UP TO ROOFRS&L PIPING UP TO ROOFRS&L PIPING UP TO ROOFRS&L PIPING UP TO ROOFRS&L PIPING UP TO ROOFRS&L PIPING UP TO ROOF1-1/4" CD TO FLOOR DRAIN, TERMINATE W/ INDIRECT CONN., SEE PLUMBING PLANS FOR ADDITIONAL INFORMATION1-1/4" CD1-1/4" CDCD DN TO HUBDRAIN A/C,TERMINATE W/ INDIRECT CONN., TYP. 41" CD3/4" CD1-1/4" CD1" CDCD DN TO HUBDRAIN A/C, TERMINATE W/ INDIRECT CONN., TYP. 2CD DN TO FLOOR DRAIN, TERMINATE W/ INDIRECT CONN., TYP. 2CD, SIZED PER MANUFACTURER'S RECOMMENDATIONSCD DN TO FLOOR DRAIN, TERMINATE W/ INDIRECT CONN.CD DN TO MOP SINK, TERMINATE W/ INDIRECT CONN.1-1/4" CD1-1/4" CD1-1/4" CD1-1/4" CD1-1/4" CD1" CD1-1/4" CD1-1/4" CD3/4" CD1" CDCD CN TO FLOORDRAIN, TERMINATE W/ INDIRECT CONN., TYP. 41" CD1-1/4" CD3/4" CD1-1/4" CD1-1/4" CD1-1/4" CD1-1/4" CD1-1/4" CD1" CD3/4" CD1" CD1-1/4" CDCD CN TO FLOORDRAIN, TERMINATE W/ INDIRECT CONN., TYP. 21-1/4" CDCD DN TO HUBDRAIN A/C, TERMINATE W/ INDIRECT CONN., TYP. 23/4" CD1-1/4" CD TO FLOOR DRAIN, TERMINATE W/ INDIRECT CONN., SEE PLUMBING PLANS FOR ADDITIONAL INFORMATION1-1/4" CD TO FLOOR DRAIN, TERMINATE W/ INDIRECT CONN., SEE PLUMBING PLANS FOR ADDITIONAL INFORMATION1212P1P2D.5KEYED NOTES:1PROVIDE AND INSTALL RS&L PIPING TO CONNECT FREEZER/COOLERTO OUTDOOR CONDENSING UNIT(S). COORDINATE EXACT LOCATIONWITH ARCHITECT AND FOOD AND BEVERAGE VENDOR.2PROVIDE AND INSTALL CONDENSATE PIPING TO CONNECTFREEZER/COOLER EVAPORATOR UNIT(S) TO NEARBY FLOOR DRAIN.SIZED PER MANIFACUTRER'S RECOMMENDATIONS.CCDDC.5C.5AABBEEHHJJGGFA.3B.5B.5K.8K.8L.8L.6MMLK.2H.8H.8H.2H.2D.7D.5D.5A.5A.5B.3554321762.57.27.22.87.57.58.598.88.882.68.98.93.54.58.7NVTAC-A VTAC-AVTAC-AVTAC-AVTAC-BVTAC-AP1P2D.5CD DN TO FLOORDRAIN,TERMINATE W/ INDIRECT CONN.006HANGOUT001VESTIBULE002CART031OFFICE032OFFICE029WORK AREA033IT ROOM034DOS OFFICE112ADA KING 02110DQ 04108ADA KING 02106DQ 04104KING 01102KING 03043STORAGE042POOL MECH.ROOM040INDOORSWIMMING POOL039FITNESS CENTER037CORRIDOR151CORRIDOR009MEN TLT008WOMEN TLT010COFFEE HOUSEPUB003WELCOME LOBBY010COFFEE HOUSEPUB011PREFUNCTION012MEETING ROOM015FUNCTION STOR.013KITCHEN017BREAK RM028ELEC.023MECH. RM025LAUNDRY026LINEN STOR.027LINEN CHUTEBOHCORRIDOR016EMP.TLT019LOCKERS018LAUNDRYOFFICE024BOHCORRIDOR016ELEVATORLOBBY007WELCOMEDESK004ELEV.EQ.RM035POOLTOILET038POOLEQPMRM041152STAIR A153STAIR BPDUC-108'16'20'1/8" = 1'-0"12'REVISIONSNPROJECT #:DATE:phonefaxmpg-architects.com330.666.5770330.666.88123660 Embassy ParkwayFairlawn, OH 44333FIRST FLOOR PIPING PLANM201CAMBRIA SUITES HOTEL1000 LONGLEAF LANE,SOUTH WINDSOR, CT 0607411 OF 2215815JUNE 24, 2016 1/8" = 1'-0"11ST FLOOR PIPING PLAN - MECHANICAL FCU-2-1FCU-2-3FCU-2-2FCU-2-41111BRANCH CONTROLLERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERREFRIGERANTPIPING RISERREFRIGERANTPIPING RISERREFRIGERANTPIPING RISERREFRIGERANTPIPING RISERREFRIGERANTPIPING RISERREFRIGERANTPIPING RISERREFRIGERANTPIPING RISERREFRIGERANTPIPING RISERREFRIGERANTPIPING RISERREFRIGERANTPIPING RISERREFRIGERANTPIPING A/CREFRIGERANTPIPING A/CREFRIGERANTPIPING A/CCD PIPING RISER2D.51ROUTE 3/4" CONDENSATE DRAIN PIPING TO FLOOR DRAIN IN VENDINGAND TERMINATE WITH INDIRECT CONNECTION.KEYED NOTES:2COORDINATE LOCATION OF FCU AND ASSOCIATED DUCTWORK,PIPING, ETC. TO AVOID ELECTRICAL EQUIPMENT AND REQUIREDCLEARANCES.CCDDC.5C.5AABBEEHHJJFFB.5B.5L.8L.6MMLH.8H.8H.2H.2D.7D.5D.5A.5A.554321762.57.22.87.598.882.68.93.54.5NVTAC-BVTAC-AVTAC-AVTAC-BVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-BVTAC-AVTAC-BVTAC-BVTAC-BVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AD.5CD PIPING RISER08'16'20'1/8" = 1'-0"12'REVISIONSNPROJECT #:DATE:phonefaxmpg-architects.com330.666.5770330.666.88123660 Embassy ParkwayFairlawn, OH 44333SECOND FLOOR PIPING PLANM202CAMBRIA SUITES HOTEL1000 LONGLEAF LANE,SOUTH WINDSOR, CT 0607412 OF 2215815JUNE 24, 2016 1/8" = 1'-0"12ND FLOOR PIPING PLAN - MECHANICAL FCU-3-1FCU-3-3FCU-3-2 FCU-3-41111BRANCH CONTROLLERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERREFRIGERANTPIPING RISERREFRIGERANTPIPING RISERREFRIGERANTPIPING RISERREFRIGERANTPIPING RISERREFRIGERANTPIPING RISERREFRIGERANTPIPING RISERREFRIGERANTPIPING RISERREFRIGERANTPIPING RISERREFRIGERANTPIPING RISERREFRIGERANTPIPING RISERREFRIGERANTPIPING A/CREFRIGERANTPIPING A/CCD PIPING RISER2D.51ROUTE 3/4" CONDENSATE DRAIN PIPING TO FLOOR DRAIN IN VENDINGAND TERMINATE WITH INDIRECT CONNECTION.KEYED NOTES:2COORDINATE LOCATION OF FCU AND ASSOCIATED DUCTWORK,PIPING, ETC. TO AVOID ELECTRICAL EQUIPMENT AND REQUIREDCLEARANCES.CCDDC.5C.5AABBEEHJFB.5B.5L.8L.6MMLH.8H.8H.2H.2D.7D.5D.5A.5A.5554321762.57.27.27.57.598.88.888.98.93.54.5NVTAC-AVTAC-AVTAC-BVTAC-AVTAC-BVTAC-AVTAC-AVTAC-BVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-BVTAC-AVTAC-AVTAC-AVTAC-AVTAC-BVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-BVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AD.5CD PIPING RISER08'16'20'1/8" = 1'-0"12'REVISIONSNPROJECT #:DATE:phonefaxmpg-architects.com330.666.5770330.666.88123660 Embassy ParkwayFairlawn, OH 44333THIRD FLOOR PIPING PLANM203CAMBRIA SUITES HOTEL1000 LONGLEAF LANE,SOUTH WINDSOR, CT 0607413 OF 2215815JUNE 24, 2016 1/8" = 1'-0"13RD FLOOR PIPING PLAN - MECHANICAL FCU-4-1FCU-4-4FCU-4-21111BRANCH CONTROLLERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERCD PIPING RISERREFRIGERANTPIPING RISERREFRIGERANTPIPING RISERREFRIGERANTPIPING RISERREFRIGERANTPIPING RISERREFRIGERANTPIPING RISERREFRIGERANTPIPING RISERREFRIGERANTPIPING RISERREFRIGERANTPIPING RISERREFRIGERANTPIPING RISERREFRIGERANTPIPING RISERREFRIGERANTPIPING A/CREFRIGERANTPIPING A/CM3011M3013M3014CD PIPING RISERD.51ROUTE 3/4" CONDENSATE DRAIN PIPING TO FLOOR DRAIN IN VENDINGAND TERMINATE WITH INDIRECT CONNECTION.KEYED NOTES:2ROUTE 3/4" CONDENSATE DRAIN PIPING UP THRU ROOF.CCDDC.5C.5AABBEEHJFB.5B.5L.8L.6MMLH.8H.8H.2H.2D.7D.5D.5A.5A.5554321762.57.27.27.57.598.88.888.98.93.54.5NM3013SimM3013SimM3013SimM3013SimM3013SimM3013SimM3013SimM3013SimM3013SimM3013SimM3011SimM3011SimM3014SimM3014SimM3014SimM3014SimM3014SimVTAC-AVTAC-AVTAC-BVTAC-AVTAC-BVTAC-B VTAC-AVTAC-AVTAC-AVTAC-AVTAC-BVTAC-AVTAC-BVTAC-AVTAC-BVTAC-BVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AVTAC-AD.5M3014SimM3014SimCD PIPING RISERFCU-4-308'16'20'1/8" = 1'-0"12'REVISIONSNPROJECT #:DATE:phonefaxmpg-architects.com330.666.5770330.666.88123660 Embassy ParkwayFairlawn, OH 44333FOURTH FLOOR PIPING PLANM204CAMBRIA SUITES HOTEL1000 LONGLEAF LANE,SOUTH WINDSOR, CT 0607414 OF 2215815JUNE 24, 2016 1/8" = 1'-0"14TH FLOOR PIPING PLAN - MECHANICAL NAILS (GALVANIZED)PIPE STRAPS (GALV. OR S.S.)WOOD SCREWS (GALV.)ROOFREFRIGERANT LINES24"x12" "CAREY TREAD" SHALL BE INSTALLEDUNDER ALL PIPE SUPPORTS4"x4"x24" LONG WEATHER-TREATEDREDWOOD SUPPORTS (TWO REQUIRED) AT10'-0" ON CENTER AND AT EACH CHANGE OFDIRECTION.KMAU-1F/PFANKEF-1CU-R-1CU-1-7CU-1-11 CU-1-10MAUC-1CU-1-4CU-1-3CU-1-2CU-1-5CU-1-1CU-1-6CU-1-8CU-1-9CU-1-12CU-1-13CU-1-14RS&L PIPING SIZED PER MANUFACTURER'S RECOMENDATIONS, TYP.ROOF PIPING PENETRATION, TYP.CLEARANCE, TYP.REFRIGERANT PIPING DOWN, TYP.REFRIGERANT PIPING ON ROOF, TYP.D.5CCDDC.5C.5AABBEEHJFB.5B.5L.8L.6MMLH.8H.8H.2H.2D.7D.5D.5A.5A.5554321762.57.27.27.57.598.88.888.98.93.54.5RTU-WRTU-ND.5ROOF PIPING PENETRATION, TYP.08'16'20'1/8" = 1'-0"12'REVISIONSNPROJECT #:DATE:phonefaxmpg-architects.com330.666.5770330.666.88123660 Embassy ParkwayFairlawn, OH 44333ROOF MECHANICAL PLANM205CAMBRIA SUITES HOTEL1000 LONGLEAF LANE,SOUTH WINDSOR, CT 0607415 OF 2215815JUNE 24, 2016 1/8" = 1'-0"1ROOF PIPING PLAN - MECHANICALREFRIGERANT PIPE SUPPORT DETAIL2 FLOOR 4FLOOR 3FLOOR 2FLOOR 1FLOOR 4FLOOR 3FLOOR 2FLOOR 1FLOOR 4FLOOR 3FLOOR 2FLOOR 1FLOOR 4FLOOR 3FLOOR 2FLOOR 1VTAC, TYP. 3/4"1"3/4"3/4"3/4"1-1/4"VTAC, TYP. 3/4"3/4"3/4"3/4"3/4"1"SEE PLANS FOR ADDITIONAL INFORMATION.ROUTE CONDENSATE DRAIN TO FLOOR DRAIN.VTAC, TYP. 3/4"1"3/4"3/4"1-1/4"SEE FLOOR PLANS FOR CONTINUATION.VTAC, TYP. 3/4"3/4"3/4"3/4"1"SEE FLOOR PLANS FOR CONTINUATION.SEE PLANS FOR ADDITIONAL INFORMATION.ROUTE CONDENSATE DRAIN TO FLOOR DRAIN.GUESTROOM CONDENSATE DRAIN RISER (TWO ROOM WEST)NOT TO SCALE1GUESTROOM CONDENSATE DRAIN RISER (ONE ROOM WEST)NOT TO SCALE2GUESTROOM CONDENSATE DRAIN RISER (TWO ROOM NORTH)NOT TO SCALE3GUESTROOM CONDENSATE DRAIN RISER (ONE ROOM NORTH)NOT TO SCALE44TH-FLOORROOF3RD-FLOOR2ND-FLOORGRILLEGRILLEGRILLEEFEXH. FAN30 CFM30 CFM30 CFM4"ØEXTERIOR LOUVER1ST-FLOOR CLG12330 CFM30 CFM30 CFM4TH-FLOORROOF3RD-FLOOR2ND-FLOORGRILLEGRILLEGRILLEEF123REVISIONSPROJECT #:DATE:phonefaxmpg-architects.com330.666.5770330.666.88123660 Embassy ParkwayFairlawn, OH 44333MECHANICAL RISERSM301CAMBRIA SUITES HOTEL1000 LONGLEAF LANE,SOUTH WINDSOR, CT 0607416 OF 2215815JUNE 24, 2016EXHAUST RISER 1ST-4THAEXHAUST RISER 2ND-4THBEXHAUST RISER FLAG NOTES:1. ROOFTOP EXHAUST FAN, TYPICAL OF (4) - SIZES VARY. SEE EXHAUST FAN SCHEDULE SHEET M001.2. EXHAUST PLENUM LOCATED ABOVE FOURTH FLOOR CORRIDOR CEILING. SEE SHEETS M104 & M105 FOR ROUTING. NOTE: THERE ARE LOCATIONS THAT HAVE 6" DIAMETER DUCTS, REFER TO PLANS.3. 4" DIAMETER HARDPIPE EXHAUST DUCT CONNECTION INTO EXHAUST PLENUM, U.O.N. PROVIDE VOLUME DAMPER WITH ACCESS FOR SYSTEM BALANCING.4. NO RADIATION DAMPER IS REQUIRED WHERE DUCT PENETRATIONS THROUGH RATED ASSEMBLIES ARE LOCATED WITHIN THE CAVITY OF A WALL AND DO NOT PASS THROUGH ANOTHER DWELLING UNIT OR TENANT SPACE, PER MECHANICAL CODE.GUEST BATHROOM EXHAUST NOISE NOTE:EXHAUST SYSTEMS SERVING GUEST BATHROOMS WERE DESIGNED TO ACHIEVE AN ACOUSTICAL NOISE RATING OF 25. PRIOR TO CHOICE BRAND REVIEW OF THE GUESTROOMS, MECHANICAL CONTRACTOR MUST PERFORM A NOISE TEST THROUGHOUT THE HOTEL TO CONFIRM THAT THE INSTALLED SYSTEM COMPLIES.4FIRE RATED DUCT PENETRATIONSALL DUCTS WHICH PENETRATE 1-HOUR FIRE BARRIERS SHALL BE CONSTRUCTED OF SHEET STEEL NOT LESS THAN 26-GAUGE THICKNESS PER THE 2016 CONNECTICUT MECHANICAL CODE (IBC 2012) 607.5.2(3) AND FIRE CAULKED AT EACH PENETRATION.ALL DUCTS WHICH PENETRATE 1-HOUR FIRE PARTITIONS SHALL BE CONSTRUCTED OF APPROVED MATERIALS IN ACCORDANCE WITH SECTION 603 OF THE CONNECTICUT MECHANICAL CODE (IBC 2012) AND COMPLY WITH THE REQUIREMENTS OF 607.5.3.3.ALL DUCTS WHICH PENETRATE RATED HORIZONTAL ASSEMBLIES SHALL BE PROVIDED WITH A LISTED FIRE DAMPER AT EACH PENETRATION OF THE RATED SHAFT ENCLOSURE IN ACCORDANCE WITH THE CONNECTICUT MECHANICAL CODE (IBC 2012) 607.6.1.ALL DUCTS WITH PENETRATE HORIZONTAL MEMBRANES SHALL BE PROVIDED WITH A RADIATION DAMPER AT EACH PENETRATION OF THE MEMBRANE IN ACCORDANCE WITH SECTION 607.6.2 OF THE CONNECTICUT MECHANICAL CODE (IBC 2012).4-INCH ROUND DUCTS WICH ARE CONSTRUCTED OF SHEET STEEL NOT LESS THAN 26-GAUGE THICKNESS AND FIRE-CAULKED AT EACH PENETRATION, ARE PERMITTED TO PENETRATE (3) FLOORS OR LESS OF RATED HORIZONTAL ASSEMBLIES WITHOUT A FIRE DAMPER AT EACH FLOOR IN ACCORDANCE WITH SECTION 607.6.1 OF THE CONNECTICUT MECHANICAL CODE (IBC 2012).4 6/25/2018 BULLETIN #18 12/26/2018 BULLETIN #58 NOTES:NOTES:NOTES:NOTES:NOTES:NOTES:NOTES:NOTES:NOTES:~~~~~~~~~~CAULKCONCRETESOLIDCONNECTION AT DUCT.DETAIL OF CLIP ANGLEBIRDSCREENCLIP ANGLEDUCTMINIMUM OFSAME GUAGEAS DUCTWORKRETURN OR SUPPLYGRILLE OR REGISTERRETAINING ANGLESNUG TO WALLSEE NOTE 2TYPE ANOSINGMETALNOTE 1SEE6" MAX.SIDESON ALLSLEEVE1/4" TO 1/2"CLEARANCESDUCT LINERDUCT LINER 2"INSULATION OVERLAP22" MINIMUMSUB-DUCTFIRE RATED CHASE WALLEXHAUST RISERSEAL DUCT PENETRATION THROUGHCHASE WALL WITH NON-HARDENINGFIRE RETARDENT SEALANTAIRFLOWALUMINUM FLASHING. TYP.WALL STRUCTURE. SEE ARCHITECTURAL ANDSTRUCTURAL PLANS FOR DETAILS.16 GA GALV SHEET METAL WALL SLEEVESECURE WALL SLEEVE TO WALL WITH ANGLEIRON AND SCREWS 12" O.C. ALL AROUND.1/2" - 5/8" ANNULAR SPACE BETWEEN SLEEVE ANDDUCT. PACK WITH LOOSE GLASS FIBER AND CAULKAIRTIGHT ALL AROUND WITH WEATHER RESISTANTMASTIC.MASTICOUTSIDEINSIDESEE PLANS FORDUCT SIZE ANDCONTINUATION.ROOF OPENING SIZED FOR DUCTSIZE SHOWN PLUS 2 INCHS FORSLEEVE AND INSULATION.FLASH FROM WALL ACROSSSLEEVED SECTION TO OVERJACKETED SECTION. CAULKJOINTS WATERTIGHT. ALUMINUMFLASHING TO COVER TOP ANDSIDES AND EXTEND BELOWDUCTING AT LEAST 6 INCHES.INSULATED EXTERIORDUCT MOUNTED ONSUPPORTS ONEQUIPMENT-CURBS, (SEEOTHER DETAIL)(OR INTERNAL AS SPECIFIED)COVER SLEEVE WITHDUCTWRAP INSULATION ALLAROUND BOTH SIDES WHEREDUCT IS LINED.COVER SLEEVE WITHDUCTWRAP INSULATION ALLAROUND BOTH SIDES WHEREDUCT IS LINED.FIRE RATED WALLCONSTRUCTION12" INTEGRAL WALL SLEEVE BY FIREDAMPER MANUFACTURER. SLEEVE TOBE MINIMUM 16 GA. WITH 3/16"EXPANSION CRACK TWO SIDES ANDTOP BETWEEN SLEEVE AND WALL.SEAL EXPANSION CRACK WITH FIRERETARDANT NON-HARDENING MASTIC.INSULATED ACCESS DOOR(INSTALL ON SIDE MOSTACCESSIBLE TO DAMPER)EXTERNAL DUCT INSULATIONAPPROVED SLIP JOINTDAMPER MANUFACTURERRETAINING ANGLES BY FIREAIR STREAM FIRE DAMPER.CURTAIN TYPE, OUT OF THEAIR FLOWWITH DUCTWRAP.FIRE RATEDLOW PRESSUREBELLMOUTH FITTING (WHERE DUCT DEPTH ISAVAILABLE) OR SPIN-IN FITTING WITHBUTTERFLY DAMPER IF DUCT DEPTH IS NOTHIGH ENOUGH FOR BELLMOUTH.TRUNK ORBRANCH DUCTPOSITIONHORIZONTAL @ WIDE OPENDEVICE. MOUNT WITH BLADE INMANUAL DAMPER WITH LOCKINGGALVANIZED STEEL STRAP DUCTSUPPORTGASKETINSTALLED FLEXIBLE DUCT. LENGTHNOT TO EXCEED 5'-0". IF FLEXIBLE DUCTCONNECTION RADIUS IS GREATER THAN90 DEGREES PROVIDE HARD 90° ELBOW.METAL DUCTWORK REFER TOPLANS FOR SIZE, INSULATELAY-IN TILE CEILINGDIFFUSERDAMPEROPERATORARCHITECTURAL DRAWINGSFOR ACTUAL CEILING TYPE.STRAP, TYP.NYLON TIEWITH POSITION LOCKVOLUME DAMPERSYSTEM SHOWN. REFER TOAIR DISTRIBUTION DEVICE, SURFACEMOUNTING AS NEEDED. SEE AIRMOUNTED IN AN INACCESSIBLEFRAME AND BORDER FOR SURFACEARCHITECTURAL CEILING. PROVIDEFOR ADDITIONAL INFORMATION.DEVICE SCHEDULE AND SPECIFICATIONSHARD ARCHITECTURALCEILINGADJUSTMENT OF ACTUATORAIR DEVICE WITH ACCESS FORTO COLLARBRACKET SECUREADJUSTMENT SLOTWHICHEVER IS CLOSER.6' UPSTREAM OF DEVICE,AT DEVICE TAKE-OFF ORVOLUME DAMPER ASSEMBLY.SUPPLY DUCTDUCT/PLENUM PENETRATIONNEOPRENE BUSHING ATCABLEFLEXIBLEPLENUM AT SUPPLY AIR DEVICEBRANCH DUCTMANUAL VOLUME DAMPERTRUNK DUCT45 ° BRANCH DUCT TAKE-OFF PER SMACNA.USE AT ALL BRANCH TAKE-OFF'S UNLESSOTHERWISE INDICATED.AIRFLOWAIRFLOWALL THREAD ROD, SECURE TO STRUCTUREADJUSTABLE CLEVIS HANGERCLEVIS PIPE HANGERPROVIDE HIGH COMPRESSIVESTRENGTH INSULATION INSERTUNDER INSULATION SHIELDPIPE INSULATION(VAPOR BARRIER ISREQUIRED FOR LOWTEMPERATURE PIPE)HEAVY GUAGEMETAL INSULATION SHIELD(12" IN. LONG MIN.)PIPERUNOUT TO DIFFUSER SHALL BE SAME SIZE AS AIR DISTRIBUTIONDEVICE NECK UNLESS OTHERWISE NOTED ON PLANS1.OVERALL SIZE OF OPENING SHOULD BE 1/4" GREATER INBOTH DIRECTIONS THAN SIZE OF LOUVER.LOUVER BLADES SHOULD NOT EXCEED 5 FT. IN WIDTH.USE MULLION CONNECTED SECTIONS FOR GREATERWIDTHS.CAULKING AS SPECIFIED.1.WHEN MULTIPLE DAMPED ASSEMBLIES ARE JOINED OR FASTENINGDAMPER TO SLEEVE DAMPER SHALL BE FASTENED WITH - 20 BOLTS,NO. 10 SCREWS OR 1/2" LAGGED WELDS STAGGERED INTERMITTENTLYAND SPACED 6" MAXIMUM CENTER TO CENTER.RETAINING ANGLES SHALL BE A MINIMUM OF 1 1/2" X 1 1/2" X 14GUAGE. ANGLES SHALL OVERLAP WALL BY A MINIMUM OF ONE INCH(1").1.SEE PLANS FOR RISER AND SUB DUCT SIZES.SUB DUCT DETAIL TYPICAL FOR ALL EXHAUST RISERS. WHERE THERE ISINSUFFICIENT HEIGHT FOR 22" SUB-DUCT, A FIRE DAMPER MUST BEPROVIDED IN THE FIRE RATED WALL; REFER TO FIRE DAMPER DETAILS.1.THIS DETAIL IS FOR REFERENCE ONLY. INSTALLATION SHALL BE INSTRICT COMPLIANCE WITH U.L. LISTING AND MANUFACTURER'SINSTRUCTIONS.1.2.3.2.2.ALL THREAD ROD SHALL BE 1/2"WITH 25"MAX LENGTH FOR PIPE SIZES 3" ANDSMALLER OR 5/8" FOR PIPE SIZES 4" ANDLARGER.PROVIDE 3/8" BOLTS.1.2.REFER TO PLANS FOR DUCT SIZES, APPLIES TO ALL SUPPLY, RETURN &EXHAUST DUCTS.1.TO DUCTSLEEVEMAX.6"ANGLESMOUNTINGACTUATORINSULATION1" MIN. TYP.OVERLAP ONOF DAMPERALL SIDESCAULKING MATERIALFIRE RATEDS-JOINT SLEEVEDUCTBLOCK WALL1/4" MIN.(INTERLOCK WITH FIRE ALARM SYSTEM)(WHERE APPLICABLE)DRAINPITCH TODRAIN LINE SHALL BE AT LEASTC.O. AT EVERY CHANGETHE SAME SIZE AS THE NIPPLEIN DIRECTION.ON THE DRAIN PAN.C.O.W/ SUFFICIENT TRAP SEALTO OFFSET PRESSURE ATCONDENSATE DRAIN TRAPDRAIN PAN.DRAIN PANCONDENSATE PIPING.INSULATE TRAP AND12INDIRECT CONNECTION.TERMINATE WITHANCHOR TO STRUCTURE(2) CLAMP OR (4) BOLT SOCKETCLAMP AND WASHERSSUPPORT STRUCTUREU.L. LISTED FIRE STOP PENETRATIONMANUFACTURER'S INSTALLATION INSTRUCTIONS SHALL BEMADE AVAILABLE TO THE INSPECTING AUTHORITY.FIRE/SMOKE DAMPERS SHALL BE RUSKIN SERIES FSD-60 OREQUAL, EXCEPT WHERE OTHERWISE NOTED. FIRE/SMOKEDAMPERS MUST COMPLY WITH U.L. STANDARD 555 AND 555SAND BE INSTALLED STRICTLY PER MANUFACTURER'S U.L. LISTEDPRINTED INSTRUCTIONS. PROVIDE SLEEVE TYPE INSTALLATIONAT ALL CONTINUOUS DUCTED WALL PENETRATIONS AND GRILLEINSTALLATION AT ALL SIDEWALL PENETRATIONS.THIS DETAIL IS FOR REFERENCE ONLY. INSTALLATION SHALL BEIN STRICT COMPLIANCE WITH U.L. LISTING ANDMANUFACTURERS INSTRUCTIONS.INSTALL ACCESS DOOR(S) AS REQUIRED TO PROVIDEUNIMPEDED ACCESS FOR MAINTENANCE AND INSPECTION OFFSD'S FUSIBLE LINKS AND ACTUATORS. WHERE DAMPER HASMULTIPLE FUSIBLE LINKAGE ASSEMBLIES, PROVIDE ACCESS TOEACH (DOORS MAY BE COMBINED, AND SIZED ACCORDINGLY,WHERE POSSIBLE).INSTALL FIRE ALARM RELAY AND MOTOR/ACTUATOR ON SAMESIDE OF FIRE/SMOKE DAMPER. PERMANENTLY MARK ROTATINGASSEMBLY (SHAFT) TO INDICATE DAMPER POSITION FROMDEVICE EXTERIOR.DAMPER ACTUATOR SHALL HAVE 120V/1PH POWER CONNECTIONUNLESS NOTED OTHERWISE.1.2.3.4.5.6.HEIGHT OF FALL SHALL BE A MINIMUM OF 1/2" GREATER THAN THE TOTALSTATIC PRESSURE OF THE AIR HANDLING UNIT.HEIGHT OF TRAP SHALL BE A MINIMUM OF 1/2" GREATER THAN THE TOTALSTATIC PRESSURE OF THE AIR HANDLING UNIT.1.2.LOUVER MOUNTING DETAILNOT TO SCALE4DIFFUSER/DUCTWORK DETAILSNOT TO SCALE7FIRE DAMPER AND SIDEWALLGRILLE MOUNTING DETAILNOT TO SCALE3EXHAUST RISER SUB-DUCT DETAILNOT TO SCALE9DUCT THRU EXTERIOR WALLNOT TO SCALE6VERTICAL FIRE DAMPER DETAILNOT TO SCALE2CLEVIS PIPE HANGERNOT TO SCALE11BRANCH DUCT TAKE-OFF DETAILNOT TO SCALE5REMOTE CABLE-OPERATEDDAMPER DETAILNOT TO SCALE8FIRE/SMOKE DAMPER DETAILNOT TO SCALE1CONDENSATE DRAIN TRAP DETAILNOT TO SCALE12STANDARD RISER PIPE SUPPORTNOT TO SCALE10REVISIONSPROJECT #:DATE:phonefaxmpg-architects.com330.666.5770330.666.88123660 Embassy ParkwayFairlawn, OH 44333MECHANICAL DETAILSM302CAMBRIA SUITES HOTEL1000 LONGLEAF LANE,SOUTH WINDSOR, CT 0607417 OF 2215815JUNE 24, 2016 MAX PIPEORCONDUITDIAM IN.F RATING HR T RATING HR1 (25) 1 OR 2 0+, 1 OR 21 (25) 3 OR 4 3 OR 44 (102) 1 OR 2 06 (152) 3 OR 4 012 (305) 1 OR 2 0NOTES:NOTES:NOTES:NOTES:12"UNIT BASEGASKET(FIELD INSTALLED)WOOD NAILERCOUNTER FLASHING(FIELD SUPPLIED)RIGID INSULATION(RIELD SUPPLIED)ROOFING FELT(FIELD SUPPLIED)CANT STRIP(FIELD SUPPLIED)AS NOTED ON DRAWINGS. INSULATEMFGR'S RECOMMENDATIONS ORMECHANICAL PIPING, SIZED PERROOF STRUCTURECURBROOF(FIELD SUPPLIED), TYP.CANT STRIP(FIELD SUPPLIED), TYP.ROOFING MEMBRANE(FIELD SUPPLIED), TYP.(FIELD SUPPLIED), TYP.RIGID INSULATIONCOUNTER FLASHINGWOOD NAILER, TYP.STEEL CURB CAPCURB, SEAL PENETRATION(FIELD INSTALLED)GASKETW/ SILICON SEALANT.RS&L LINES THRU SIDES OF6" OC, SEAL WITH18 GA. GAL.SILICON SEALANTSHEET METAL SCREWSPER SPECIFICATIONS.ALL ROOFING WORK TO BE PERFORMED BY LANDLORD APPROVED VENDOR.1.ENCLOSURE 2" BELOWBOTTOM EDGE OFDUCTWORKEXTEND EXTERIORCONTINUOUS WATERPROOFED INSULATION ENCLOSUREWITH WATERPROOF SEAMS, HELD IN PLACE BY STRAPSUNDERNEATH AT 3'-0" INTERVALS. ENCLOSURE SHALLINCLUDE TWO (2) LAYERS OF 2" ARMAFLEX ARMATUFFCLOSED CELL ELASTOMERIC FOAM INSULATION. PROVIDESHEET TYPE ALUMINUM JACKETING WITH ADHESIVEBACKING. LAP EDGES AND SEAL ALL JOINTS WITHWEATHERPROOF SEALANT.ADDITIONAL 2" THICK, INSULATION, CROWNFOR POSITIVE DRAINAGE.SECURE TO CURB RAILS. SEEROOF DUCT SUPPORT DETAIL ANDMECHANICAL SPECIFICATIONSFOR ADDITIONAL INFORMATION.GALVANIZED STEELANGLE SUPPORTS1. Floor or Wall Assembly - Lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Except as notedin table under Item 4, min thickness of solid concrete floor or wall assembly is 4-1/2 in. (114 mm). Floor may also beconstructed of any min 6 in. (152 mm) thick UL Classified hollow core. When floor is Precast Concrete Units*constructed of hollow core precast concrete units, packing material (Item 3) and caulk fill material (Item 4) to beinstalled symmetrically on both sides of floor, flush with floor surface. Wall assembly may also be constructed of any ULClassified Concrete Blocks*. Max diam of opening is in solid lightweight or normal weight concrete. Floor is 32 in. (813mm). Max diam of opening in floor constructed of hollow-core precast concrete units is 7 in. (178 mm).See Concrete Blocks (CAZT) and Precast Concrete Units (CFTV) categories in the Fire Resistance Directory fornames of manufacturers.1A. Steel Sleeve (Optional, not shown) - Nom. 16 in. (406 mm) diam. (or smaller) Schedule 10 (or heavier) steelsleeve cast or grouted into floor or wall assembly. Sleeve may extend a max of 2 in. (51 mm) above top of floor orbeyond either surface of wall. As an alternate, nom. 16 in. (406 mm) diam. (or smaller) min 0.028 (0.71 mm) thickgalvanized sheet steel sleeve cast or grouted into floor or wall assembly flush with floor or wall surfaces.2. Through Penetrants - One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically withinthe firestop system. Max annular space between pipe, conduit or tubing and edge of through opening or sleeve isdependent on the parameters shown in Item 4. Min annular space between pipe or conduit and edge of through openingis 0 in. (point contact). Max. annular space to be as shown in the table in Item 4. Pipe, conduit or tubing to be rigidlysupported on both sides of floor or wall assembly. The following types and sizes of metallic pipes, conduits or tubingmay be used.A.Steel Pipe - Nom 30 in. (762 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.B. Iron Pipe - Nom 30 in. (762 mm) diam (or smaller) cast or ductile iron pipe.C. Conduit - Nom 6 in. (152 mm) diam (or smaller) rigid steel conduit.D.Conduit - Nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing.E. Copper Tubing - Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tube.F. Copper Pipe - Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe.3. Packing Material - Polyethylene backer rod or nom 1 in. (25 mm) thickness of tightly-packed mineral wool batt orglass fiber insulation firmly packed into opening as a permanent form. Packing material to be recessed from top surfaceof floor or from both surfaces of wall as required to accommodate the required thickness of caulk fill material (Item 4). 3A. Forming MateriaL - As an alternate to the packing material in Item. 3, nom. 4 in. (102 mm) wide strips of min.1/2 in (13 mm) thick compressible mat to be stacked to a thickness greater than the width of the annular space andcompression-fitted, edge-first, to fill the annular space to a min. 4 in. (102 mm) depth. As an option, the strips ofmin. 1/2 in. (13 mm) thick compressible mat may be folded in half, lengthwise, and stacked to a thickness greaterthan the width of the annular space and compression-fitted, edge-first, to fill the annular space to a min. 2 in. (51mm) depth. Top of forming material to be recessed from top furface of floor or from both surfaces of wall asnecessary to accommodate the rquired thickness of caulk fill material. 3M COMPANY - Fire Barrier Packing Material.4. Fill,Void or Cavity Material* - Caulk, Sealant - Applied to fill the annular space flush with top surface of floor. In wallassemblies, required caulk thickness to be installed symmetrically on both sides of wall, flush with wall surface. At pointcontact location between penetrant and sleeve or between penetrant and concrete, a min 1/4 in. (6 mm) diam bead ofcaulk shall be applied at top surface of floor and at both surfaces of wall. The hourly F Ratings and the min requiredcaulk thicknesses are dependent upon a number of parameters, as shown in the following table:a. Min 2 in. (51 mm) thickness of mineral wool batt insulation or forming material (Item 3A) required in annular space.b. Min 1 in. (25 mm) thickness of mineral wool batt insulation required in annular space on both sides of floor or wallassembly. Min 1 in. (25 mm) thickness of caulk to be installed flush with each surface of floor or wall assembly.3M COMPANY - CP 25WB + or FB-3000 WT. (Note: W Rating applies only when FB-3000 WT sealant is used.)*Bearing the UL Classification MarkingCopyright 2010 by Underwriters Laboratories Inc.Min Floor or WallThkns In. (mm)Nom Pipe Tube or ConduitDiam in. (mm)Max Annular Spacein. (mm)Min Caulk Thkns in.(mm)F Rating Hr2-1/2 (64) 1/2-12 (13-305) 1-3/8 (35) 1/2 (13) 22-1/2 (64) 1/2-12 (13-305) 3-1/4 (83) 1 (25) 24-1/2 (114) 1/2-6 (13-152) 1-3/8 (35) 1/4 (6) (a) 24-1/2 (114) 1/2-12 (13-305) 1-1/4 (32) 1/2 (13) 34-1/2 (114) 1/2-20 (13-508) 2 (51) 1 (25) 34-1/2 (114) 1/2-20 (13-508) 2 (51) 1 (25) 34-1/2 (114) 1/2-12 (13-305) 3-1/4 (83) 1 (25) 34-1/2 (114) 22-30 (558-762) 2 (51) 2 (51) 35-1/2 (140) 1/2-6 (13-152) 1-3/8 (35) 1 (25) (b) 4F Ratings - 2, 3, and 4 Hr (See item 2A and 4)T Rating - 0 HrL Rating @ Ambient - 2 CFM/sq ftL Rating @ 400 F - less than 1 CFM/sq ftW Rating - Class I (See Item 4)SECTION A-A41234AA2SYSTEM NO. C-AJ-1044F Ratings - 1, 2, 3 and 4 Hr (See Items 2 and 3)T Ratings - 0, 1, 2, 3, and 4 Hr (See Item 3)L Rating @ Ambient - less than 1 CFM/sq ftL Rating @ 400° F - less than 1 CFM/sq ft1. Wall Assembly - The 1, 2, 3 or 4 hr fire-rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in themanner described in the individual U300 or U400 Series Wall or Partition Designs in the UL Fire Resistance Directory and shall includethe following construction features:A. Studs - Wall framing may consist of either wood studs (max 2 hr fire rated assemblies) or steel channel studs. Wood studs toconsist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC with nom 2 by 4 in. (51 by 102 mm) lumber endplates and cross braces. Steel studs to be min 3-5/8 in. (92 mm) wide by 1-3/8 in. (35 mm) deep channels spaced max 24 in.(610 mm) OC.B. Gypsum Board* - Nom 1/2 or 5/8 in. (13 or 16 mm) thick, 4 ft. (122 cm) wide with square or tapered edges. The gypsumwallboard type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300 orU400 Series Design in the UL Fire Resistance Directory. Max diam of opening is 26 in. (660 mm).2. Through Penetrant - One metallic pipe, conduit or tubing installed either concentrically or eccentrically within the firestop system. Theannular space between pipe, conduit or tubing and periphery of opening shall be min of 0 in. (0 mm) (point contact) to max 2 in. (51mm). Pipe, conduit or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes,conduits or tubing may be used:A. Steel Pipe - Nom 24 in. (610 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.B. Iron Pipe - Nom 24 in. (610 mm) diam (or smaller) service weight (or heavier) cast iron soil pipe, nom 12 in. (305 mm) diam(or smaller) or Class 50 (or heavier) ductile iron pressure pipe.C. Conduit - Nom 6 in. (152 mm) diam (or smaller) steel conduit or nom 4 in. (102 mm) diam (or smaller) steel electrical metallictubingD. Copper Tubing - Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tubingE. Copper Pipe - Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe.F. Through Penetrating Product* - Flexible Metal Piping - The following types of steel flexible metal gas piping may be used:1. Nom 2 in. (51 mm) diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be removedon both sides of floor or wall assembly.OMEGA FLEX INC2. Nom 1 in. (25 mm) diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be removedon both sides of floor or wall assembly.GASTITE, DIV. OF TITEFLEX3. Nom 1 in. (25 mm) diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be removedon both sides of floor or wall assembly.WARD MFG INC3. Fill,Void or Cavity Material* - Caulk or Sealant - Min 5/8. 1-1/4,1-7/8 and 2-1/2 in. (16, 32, 48 and 64 mm) thickness of caulk for 1,2, 3 and 4 hr rated assemblies, respectively, applied within annulus, flush with both surfaces of wall. Min 1/4 in. (6 mm) diam bead ofcaulk applied to gypsum board/penetrant interface at point contact location on both sides of wall.The hourly F Rating of the firestop system is dependent upon the hourly fire rating of the wall assembly in which it is installed, as shownin the following table.The hourly T Rating of the firestop system is dependent upon the type or size of the pipe or conduit and the hourly fire rating of the wallassembly in which it is installed, as tabulated below:+When copper pipe is used, T Rating is 0 hr.3M COMPANY - CP 25WB + or FB-3000 WT ,*Bearing the UL Classification Marking Copyright 2010 Underwriters Laboratories Inc.SECTION A-ASYSTEM NO. W-L-10011A331B2AAPROVIDE SUPPORTS, SPACED A MAXIMUM OF 6'-0" ON CENTER, FOR ALL EXPOSEDSUPPLY, RETURN AND OUTSIDE AIR DUCTWORK EXPOSED TO THE WEATHER.SECURE DUCT SUPPORTS TO CURB WITH ANGLE IRON OR UNISTRUT BOLTED TOEQUIPMENT SUPPORTS. SEE MECHANICAL SPECIFICATIONS FOR ADDITIONALINFORMATION.1.EXTERIOR DUCT W/ 3"INSULATION ANDALUMINUM JACKETFLASHING, TYP.ALUMINUM CURB W/CURB FLASHINGFLANGETHERMAL INSULATIONROOF OPENING INACCORDANCE WITHMANUFACTURER'S APPROVEDSHOP DRAWINGS.1" DUCT LINERSECURE W/ ANGLE IRON &SCREWS 12" O.C. ALLAROUND (8" MIN.)ROOFING TO EXTENDUP AND OVER CURBAS SHOWN.SECURE CURB TO ROOFUSING FASTENERS AT 12"O.C. BEFORE APPLYINGROOFING AND INSULATION.FASTENERS SHALL BECONSISTENT WITHSPECIFIC ROOF TYPE.ROOF STRUCTURE. SEEARCHITECTURAL AND STRUCTURALPLANS FOR DETAILS ANDSLOPE OF ROOF.SEE PLANS FORDUCT SIZE ANDCONTINUATION.PAINT ENTIRE SUPPORT ASSEMBLY WITH TWO (2) COATSOF OUTDOOR ACRYLIC.1.SILICONE CAULK ALLPENETRATIONS INCOUNTER FLASHINGROOF STRUCTURE. SEEARCHITECTURAL AND STRUCTURALPLANS FOR DETAILS ANDSLOPE OF ROOF.ROOFING TO EXTENDUP AND OVER CURBAS SHOWN.CHANNEL STRUT BASEPLATE,SECURE TO EQUIPMENT CURBWITH LAG BOLTS AND WASHERSCOUNTER FLASHING"PATE" MODEL ES OR EQUALEQUIPMENT SUPPORT RAILROOF CURB/PLATFORM COVER ASMANUFACTURED BY CURB'S PLUS,NEOPRENE FLEXIBLEFAN HOUSING DRAINCONNECTIONGALVANIZEDSTEEL DUCTFLASHING BYGENERAL CONTRACTORCOUNTER FLASHING BYHVAC CONTRACTORSEE PLANS FOR DUCTSIZE AND CONTINUATIONMODEL CPPF-1 OR EQUAL.CONDUIT TOMOTOR COMPT.SECURE FAN TOCURB W/ NON-FLASH ANDCOUNTERFLASH.PLANS FOR SIZE ANDEXHAUST DUCT. SEECONTINUATION.FERROUS SCREWS.SPUN ALUMINUMCENTRIFUGALEXHAUSTERBIRDSCREENPREFAB ROOFDAMPERMANUFACTURER.CURB BY FANBACKDRAFT4' VENT STACK12"1"SHUT-OFF VALVEDIRT LEGPRESSURE REGULATORNATURAL GAS PIPINGGAS PIPING TO MECHANICAL EQUIPMENTFLEXIBLE PIPE CONNECTIONUNION, TYP.GAS-RATEDTHREADED CAPPRESSURE REGULATING VALVE VENT SHALL EXTEND TO BUILDING EXTERIOR.1.ROOF PIPING PENETRATIONCURB DETAILNOT TO SCALE5RTU ROOF CURB DETAILNOT TO SCALE4EXPOSED HORIZONTAL DUCT DETAILNOT TO SCALE7VERTICAL UL PIPE PENETRATIONDETAILNOT TO SCALE1HORIZONTAL UL PIPE PENETRATION DETAILNOT TO SCALE2DUCT THRU ROOF CURBNOT TO SCALE8ROOF DUCT SUPPORT DETAILNOT TO SCALE6UTILITY FAN EXHAUST FAN DETAILNOT TO SCALE9CENTRIFUGAL EXHAUST FANDETAILNOT TO SCALE10GAS PIPING DETAILNOT TO SCALE3REVISIONSPROJECT #:DATE:phonefaxmpg-architects.com330.666.5770330.666.88123660 Embassy ParkwayFairlawn, OH 44333MECHANICAL DETAILSM303CAMBRIA SUITES HOTEL1000 LONGLEAF LANE,SOUTH WINDSOR, CT 0607418 OF 2215815JUNE 24, 2016 NOTES:NOTES:INLINE FANNOTES:SUPPLY GRILLE, SEE TYPICALGUESTROOM PLANS FORADDITIONAL INFOTMATIONVTAC CLOSET WALLVTACCONDENSATE RISER, SEEM302 FOR ADDITIONALINFORMATIONFINISHED FLOORCEILINGWALL PLENUM WITHINTEGRAL PLENUMDIVIDER BY VTACMANUFACTURERARCHITECTURALLOUVER, SEEARCHITECTURAL PLANSFOR MOUNTING HEIGHTRIGID DUCTWORK, FULLSIZE OF UNITCONNECTIONEXTERIOR WALLDRAIN PAN BY VTACMANUFACTURERPLATFORM FABRICATEDAND INSTALLED BYCONTRACTOR~~~~FCUEDHOUTSIDEAIR LOUVERMMOTOR OPERATEDDAMPER, TYP.OAMN.C.N.O.RELIEF LOUVEROARAMANUAL DAMPERN.C.RETURN AIRFROM SPACEOUTSIDE AIR FROM MAUE-1,SEE MECHANICALSCHEDULES FOR QUANTITIESSM45-58 °FOUTSIDE AIR FORECONOMIZER MODEOUTDOOR AIRENTHALPY SENSORSA~~~SUPPLY AIRTO SPACEALL THREADED GALVANIZEDHANGER ROD TOSTRUCTURE (TYP.)SPRING ISOLATORRETURN DUCTCEILING SYSTEM.FILTER DRYERFLEXIBLE CONNECTION (TYP).SOLENOID VALVEDAUXILIARY DRAIN PAN WITH LEAK DETECTORDETECTOR BELOW ENTIRE UNIT AND VALVING.ROUTE CONDENSATE DRAIN TONEAREST FLOOR DRAIN UNLESSOTHERWISE SHOWN ON PLANSFLOWAIRFLOWAIRSUPPLY DUCTLIQUID LINESLSIGHT GLASSTEMPERATURE SENSING BULBTHERMOSTATIC EXPANSIONVALVEVERIFY DX COIL PIPING AND VALVING REQUIREMENTS FOR SPECIFIC INSTALLATIONWITH UNIT MANUFACTURER.1.ALL THREADED GALVANIZEDHANGER ROD TOSTRUCTURE (TYP.)SPRING ISOLATORRETURN DUCTLAY-IN TILECEILING SYSTEM.FILTER DRYERFLEXIBLE CONNECTION (TYP).SOLENOID VALVEDAUXILIARY DRAIN PAN BELOW ENTIRE UNITAND VALVING. ROUTE DRAIN TO ESCUTCHEONPLATE IN CEILING OF ADJACENT CORRIDORUNLESS OTHERWISE SHOWN ON PLANS.ROUTE CONDENSATE DRAIN TONEAREST FLOOR DRAIN UNLESSOTHERWISE SHOWN ON PLANSFLOWAIRFLOWAIRSUPPLY DUCTLIQUID LINESLSIGHT GLASSTEMPERATURE SENSING BULBTHERMOSTATIC EXPANSIONVALVEVERIFY DX COIL PIPING AND VALVING REQUIREMENTS FOR SPECIFIC INSTALLATIONWITH UNIT MANUFACTURER.1.FLEXIBLE CONNECTIONNEOPRENE VIBRATION ISOLATORSPER MFRS' RECOMMENDATIONSCEILING( TYPICAL )AIR FLOWEXHAUST DUCT FROM TOILETSSTRUCTURE W/ 3/8"SUPPORT UNIT FROMALL THREADED RODSAS REQUIRED (TYP.)LAY-IN TILEMDMDSENSOR SHALL INTERLOCK WITH FCU AND CU CONTROLS TODISABLE/LOCKOUT COMPRESSORDURING FULL ECONOMIZER MODE.OUTDOOR AIR TEMPERATURE SENSOR PROVIDED WITH PACKAGED ECONOMIZERPLENUM.1.INCLUDED IN FCU, SEEMECHANICAL SCHEDULE FORSIZING (SHOWN HERE FORREFERENCE ONLY)PACKAGED AIR-SIDEECONOMIZER MIXINGPLENUM, SPECIFICALLY MADEFOR SUPPLIED FCU'SFILL HOLE UP TO GRADEWITH WASHED COARSE GRAVELFIN. GRADEDRAIN (SEE PLANSFOR SOURCE)SCHED 40 PVC OR CONC. PIPE,24 INCH DIA AND 24 INCH LONG,BURIED 36 INCH BELOW GRADE.6 INCH BELOW GRADE, MINIMUM.12 INCH (APPROX)SCHED 40 STEEL WALL SLEEVE, 2 INCH DIALARGER THAN DRAIN. CAULK WATERTIGHT.ADDRESSABLE-TYPESMOKE DETECTORRETURN SECTION BETWEENECONOMIZER BOX AND FAN COILUNIT CONNECTION. INSTALL WHEREFAN COIL UNIT REQUIRES SMOKEDETECTOR. SEE MECHANICAL SCHEDULEFOR MORE INFORMATIONADJUSTABLELOUVERSFLOWAIRALL THREADEDGALVANIZED HANGER RODTO STRUCTURECONCENTRIC VENT/AIRINTAKE STACK SIZED PERMANUFACTURER'SRECOMMENDATIONS.GAS PIPING FROMBUILDING. SEE GASPIPING DETAIL FORADDITIONALINFORMATION.MANUFACTURER'SHORIZONTALCONCENTRIC VENT KIT;INSTALLED PERMANUFACTURER'SRECOMMENDATIONS.ECONOMIZING MIXINGBOX CONTROLLERFAN COIL UNIT AIR-SIDE ECONOMIZER DETAILNOT TO SCALE4STANDARD DIRECT EXPANSION FANCOIL UNIT PIPING/DUCTWORK DETAILNOT TO SCALE2KITCHEN DIRECT EXPANSION FANCOIL UNIT PIPING/DUCTWORK DETAILNOT TO SCALE3INLINE FAN MOUNTINGDETAILNOT TO SCALE1DRYWELL DETAILNOT TO SCALE6GAS FIRED UNIT HEATER DETAILNOT TO SCALE7SECTION VIEW AT VTAC CLOSETNOT TO SCALE8REVISIONSPROJECT #:DATE:phonefaxmpg-architects.com330.666.5770330.666.88123660 Embassy ParkwayFairlawn, OH 44333MECHANICAL DETAILSM304CAMBRIA SUITES HOTEL1000 LONGLEAF LANE,SOUTH WINDSOR, CT 0607419 OF 2215815JUNE 24, 2016 B574 EDGEROUTERCAT 5POEB574 EDGEROUTERB574 EDGEROUTERSWITCHCAT 5POECAT5 (OR HIGHER) NETWORK CABLE, TYP. LOW VOLTAGE COMMUNICATION CABLE, SHIELDED TWISTED 2 PAIR, 24 AWG MINIMUM, 1200HM IMPEDANCE, 12-16 PF/FT CAPACITANCE.CAT 5POEGENERAL NOTES:COORDINATE WITH LOW VOLTAGE PLANS (BY OWNER) FOR ADDITIONAL INFORMATION AND SWITCH PROVISIONS. CONTRACTOR SHALL COORDINATE WORK BETWEEN TRADES SO THAT A COMPLETE AND FUNCTIONAL SYSTEM IS PROVIDED, WITH ALL REQUIRED COMPONENTS.1.FLOOR LEVELPOE SWITCHIN IDF RME528THERMOSTATHOTEL PMSSERVERHOTEL SWITCHIN MDF RMCONTROLSSERVERTO FLOORLEVEL SWITCHESB574 EDGEROUTERTYPICAL FLOORCAT5POETCP/IP NETWORK CABLES CAT5 (OR HIGHER), TYP.RS232CABLESEE CONTROLS FLOORPLAN FORDEVICE QUANTITY REQUIRED.ONE THERMOSTAT REQUIRED FOREACH GUESTROOM HVAC UNIT.WIRELESS COMMHOTEL PMS SERVER PROVIDED BY OTHERS (PROPERTY)CONTROLS SERVER SHALL BE RACK MOUNTED IN MDF ROOMGUESTROOM CONTROLS:CONTROLS NETWORK DESCRIPTION:SEQUENCE OF OPERATIONS:S217 S-SERIES MASTER LIGHTING SWITCHWITH ONE BUTTONE528 DIGITAL THERMOSTAT WITHINTEGRAL OCCUPANCY SENSOR. THERMOSTAT TO CONNECTTO CONTROLS ROUTER VIA WIRELESSRF COMMUNICATION.S241 MAGNETIC DOOR SENSORVTACTHERMOSTAT WIRE, 18-8 MINIMUMX09X09 MASTER RELAY FOR GUESTROOMLIGHTING MASTER SWITCH. CONNECTTO S5 BUS, MASTER LIGHTING SWITCH,LIGHTING POWER AND LOADS ASREQUIRED. CONTRACTOR TO PROVIDEDOUBLE-GANG BOX FOR MOUNTING.VTACE528THERMOSTATS241MAGNETICDOOR SWITCHX09 MASTERRELAY2 CONDUCTOR3 CONDUCTOR18-8 TWPOWER FORLIGHTINGTO LIGHTINGLOADSPROJECT SCOPE INCLUDES CONNECTING GUESTROOM HVAC UNITS AND LIGHTING TO A GUESTROOM CONTROLS SYSTEM. THE GUESTROOM CONTROLS SYSTEM SHALL BE SPECIFICALLY DESIGNED FOR THIS APPLICATION. ROOMS SHALL BE EQUIPPED WITH THERMOSTATS, OCCUPANCY SENSORS, DOOR CONTACT SENSORS, MASTER LIGHTING SWITCHES, ETC. AS INDICATED IN THESE DOCUMENTS.PROJECT SHALL INCLUDE ALL COMPONENTS NECESSARY FOR A COMPLETE CONTROL SYSTEM, INCLUDING, BUT NOT LIMITED TO: ROOM SENSORS, WIRELESS ROUTERS AND COMMUNICATION DEVICES, SWITCHING HARDWARE, CONTROLS SERVER, CONTROLS SOFTWARE, FULLY PROGRAMMED FOR SPECIFIC INSTALLATION AND INTEGRATED WITH HOTEL PMS SERVER/SOFTWARE, LOW VOLTAGE WIRING, CONTROL POWER, ETC.CONTRACTOR SHALL COORDINATE BETWEEN ALL NECESSARY TRADES (MECHANICAL, ELECTRICAL, CONTROLS, LOW VOLTAGE, FACILITY STAFF, ETC.) TO PROVIDE A COMPLETE AND FUNCTIONAL SYSTEM. PROGRAMMING AND COMMISSIONING OF CONTROLS SYSTEM SHALL ONLY BE PERFORMED BY PERSONNEL AUTHORIZED BY CONTROLS MANUFACTURER (PROVIDE WRITTEN VERIFICATION WITH SUBMITTALS).SEE MECHANICAL SPECIFICATIONS FOR ADDITIONAL INFORMATION.SYSTEM SHALL BE INNCOM OR APPROVED EQUIVALENT.THE CONTROLS NETWORK PROVIDES COMMUNICATION BETWEEN EACH GUESTROOM AND THE CENTRAL INTERFACE (CONTROLS) SERVER. THIS SHALL BE ACHIEVED WITH A DEEP MESH NETWORK (DMN), WHICH IS A SELF-FORMING RF NETWORK, BASED ON AN ENHANCED ZIGBEE IEEE 802.15.4 STANDARD.THE CONTROLS DMN SHALL BE CAPABLE OF FORMING CONCURRENT IN-ROOM COMMUNICATION AND BACKHAUL NETWORKS. IT SHALL USE A SINGLE RADIO ARCHITECTURE DESIGNED TO INTEGRATE WITH ZIGBEE PRO AND CAN BE INTEGRATED WITH ZIGBEE 2006, 6LOWPAN, AND SHALL SUPORT HTNG ROOM CONTROL PROTOCOL.EACH GATEWAY DEVICE SHALL COMMUNICATE WITH ALL OTHER DEVICES WITHIN ITS RANGE, CREATING AN RF MESH. EACH GATEWAY DEVICE SHALL PASS ALL INFORMATION ACROSS THE MESH, TO A WIRELESS ROUTER, WHICH COMMUNICATES (THRU WIRED SWITCHES) WITH THE CONTROLS SERVER.EACH GUESTROOM SHALL BE PROVIDED WITH AN RF ENABLED DEVICE (THERMOSTAT) TO ACT AS THE GATEWAY TO THE B574 EDGE ROUTER(S). EACH B574 EDGE ROUTER SHALL BE CONNECTED TO A POWER-OVER-ETHERNET (POE) SWITCH. ROUTERS MUST BE INSTALLED AT LEAST SIX FEET AWAY FROM ANY WI-FI ACCESS POINT (WAP). CONFIRM QUANTITY OF ROUTERS WITH BUILDING MATERIALS AND CONSTRUCTION; INCREASE QUANTITY SHOWN ON DRAWINGS, IF REQUIRED.POWER REQUIREMENT: 5 WATTS CONSUMPTION, BY POE ENABLED SWITCH.PROTOCOL: ZIGBEE RF 802.15.4IP ADDRESS: DHCP/STATICNETWORK CONNECTIVITY: EACH B574 EDGE ROUTER REQUIRES A PORT ON THE MANAGED ETHERNET SWITCH. PROVIDE CABLES BETWEEN THE SWITCHES AND ROUTERS AS INDICATED IN THESE DOCUMENTS.THE CONTROLS SERVER SHALL BE RACK MOUNTED TYPE, LOCATED IN THE MDF ROOM. THERMOSTATS SHALL BE MOUNTED AT HEIGHTS DICTATED BY THE ADA CODE.THE SYSTEM WILL BE PROGRAMMED WITH DIFFERENT SETPOINTS FOR “OCCUPIED” AND “UNOCCUPIED” CONDITIONS. ROOM SENSORS SHALL AUTOMATICALLY CHANGE THE STATE OF THE HVAC EQUIPMENT AND LIGHTING FOR EACH ROOM ACCORDING TO OCCUPANCY. THE GUESTROOM CONTROLS SYSTEM SHALL HAVE AN INPUT INTERFACE AT THE CHECK-IN DESK, BY WAY OF THE HOTEL PMS SERVER, SO THAT FACILITY STAFF CAN ALSO CHANGE THE STATE OF EACH GUESTROOM REMOTELY.ROOM RENTED AND OCCUPIED:THERMOSTAT SHALL OPERATE HVAC EQUIPMENT TO MEET GUEST TEMPERATURE SETPOINT. WHEN ROOM FIRST CHANGED FROM“NOT RENTED” TO “RENTED AND OCCUPIED”, BEFORE ADJUSTED BY THE GUEST, THE DEFAULT SETTINGS SHALL BE 75 DEGREES (COOLING) AND 70 DEGREES (HEATING).ROOM RENTED AND UNOCCUPIED:THERMOSTAT SETTINGS SHALL ALLOW THE ROOM TEMPERATURE TO FLOAT +/- 5 DEGREES OF THE GUEST TEMPERATURE SETPOINT.ROOM NOT RENTED AND UNOCCUPIED:DEFAULT THERMOSTAT SETTINGS SHALL BE 85 DEGREES (COOLING) AND 85 DEGREES (HEATING). THIS SHALL BE ADJUSTABLE IN THE CONTROLS SOFTWARE.MAGNETIC DOOR SENSORS AND PASSIVE INFRARED (PIR) SENSORS INTEGRAL IN THE HVAC THERMOSTATS SHALL BE USED FOR OCCUPANCY DETECTION IN EACH GUESTROOM. WHILE THE DOOR IS CLOSED, ACTIVATION OF ANY SWITCH ON THE THERMOSTAT OR ANY LIGHT SWITCH CONNECTED TO THE CONTROL SYSTEM SHALL PLACE THE ROOM IN OCCUPIED MODE. SYSTEM PROGRAMMING SHALL INCLUDE A CONTROL ALGORITHM TO ACCOMMODATE SLEEPING OCCUPANTS.THE CURRENT OCCUPANCY STATE OF EACH GUESTROOM SHALL BE AVAILABLE TO THE ROOM CONTROLLER, THE CENTRAL INTERFACE (CONTROLS) SERVER, AND THE FRONT DESK WORKSTATIONS. THE ROOMS SHALL DEFAULT TO “RENTED AND OCCUPIED” IN THE EVENT OF COMMUNICATIONS FAILURE AT A GUESTROOM.TREVISIONSPROJECT #:DATE:phonefaxmpg-architects.com330.666.5770330.666.88123660 Embassy ParkwayFairlawn, OH 44333MECHANICAL CONTROLS DETAILSM305CAMBRIA SUITES HOTEL1000 LONGLEAF LANE,SOUTH WINDSOR, CT 0607420 OF 2215815JUNE 24, 2016 1/8" = 1'-0"1GUESTROOM CONTROLS FLOOR DETAILCONTROLS NETWORK TOPOGRAPHY2BID ALTERNATES #3 - WIRED THERMOSTATS: CONTRACTOR IS TO PROVIDE A DEDUCT ALTERNATE TO HVAC BID WHICH REMOVES ALL WIRELESS THERMOSTATS AND ALL SUPPORTING CONTROL SYSTEMS. WIRED THERMOSTAT, TYPE ISLANDAIRE 6040927, OR EQUAL, IS TO BE USED IN LIEU OF THE REMOVED WIRELESS THERMOSTATS. COORDINATE ELECTRICAL ROUG-IN AND CONTROL WIRING W/ ELECTRICAL CONTRACTOR. 1/8" = 1'-0"3TYPICAL GUESTROOM CONTROLS DETAILS VTAC, TYP. 2TTACCESS PANEL WITH INTEGRAL RETURN AIR GRILLE, BY VTAC MANUFACTURER, TYP. 2THERMOSTAT, TYP.12TYP. 2THERMOSTAT, TYP.C238VTACTTHERMOSTATACCESS PANEL WITH INTEGRAL RETURN AIR GRILLE, BY VTAC MANUFACTURER124"øC238TTHERMOSTATACCESS PANEL WITH INTEGRAL RETURN AIR GRILLE, BY VTAC MANUFACTURER23VTAC1C24"ø84"ø4"øACCESS PANEL WITH INTEGRAL RETURN AIR GRILLE, BY VTAC MANUFACTURER, TYP. 2VTAC, TYP. 221TTTHERMOSTAT, TYP.C2, TYP. 2, TYP. 238TTTHERMOSTAT, TYP.4"ø4"ø4"øACCESS PANEL WITH INTEGRALRETURN AIR GRILLE, BY VTACMANUFACTURERVTAC, TYP. 221C2, TYP. 2ACCESS PANEL WITH INTEGRALRETURN AIR GRILLE, BY VTACMANUFACTURER338TTHERMOSTAT4"øACCESS PANEL WITH INTEGRAL RETURN AIR GRILLE, BY VTAC MANUFACTURERVTAC21C238TTHERMOSTATVTACACCESS PANEL WITH INTEGRAL RETURN AIR GRILLE, BY VTAC MANUFACTURER124"øC3384"øACCESS PANEL WITH INTEGRALRETURN AIR GRILLE BY VTACMANUFACTURER, TYP. 2TTTHERMOSTAT, TYP.VTAC, TYP. 21C2C22233221 BR SUITE 0248REVISIONSPROJECT #:DATE:phonefaxmpg-architects.com330.666.5770330.666.88123660 Embassy ParkwayFairlawn, OH 44333TYPICAL GUEST ROOM MECHANICAL PLANSM701CAMBRIA SUITES HOTEL1000 LONGLEAF LANE,SOUTH WINDSOR, CT 0607421 OF 2215815JUNE 24, 2016 1/4" = 1'-0"3TYPICAL DQ 04 / KING 01 LAYOUT 1/4" = 1'-0"4TYPICAL KING 01 LAYOUT 1/4" = 1'-0"1TYPICAL ADA KING 02 LAYOUT 1/4" = 1'-0"2TYPICAL KING 02 / DQ 04 LAYOUT 1/4" = 1'-0"5TYPICAL KING 02 / ADA DQ LAYOUT 1/4" = 1'-0"6TYPICAL DQ03 LAYOUT 1/4" = 1'-0"7TYPICAL DQ 01 LAYOUT 1/4" = 1'-0"8TYPICAL 1 BR SUITE 02 LAYOUTKEYED NOTES:1SEE FLOOR PLANS FOR VTAC TAG/DESIGNATION AND MECHANICALSCHEDULES FOR VTAC SIZE BASED ON DESIGNATION.2PROVIDE SIDEWALL GRILLE ACCORDING TO THE FOLLOWINGSCHEDULE:VTAC-A: 12x6 VTAC-B: 10x10 VTAC-C: 12x10 VTAC-D: 18x10 3EXHAUST GRILLE IN CEILING TO SIMULATE EXHAUST FAN, TYPICAL.BID ALTERNATES #3 - WIRED THERMOSTATS: CONTRACTOR IS TO PROVIDE A DEDUCT ALTERNATE TO HVAC BID WHICH REMOVES ALL WIRELESS THERMOSTATS AND ALL SUPPORTING CONTROL SYSTEMS. WIRED THERMOSTAT, TYPE ISLANDAIRE 6040927, OR EQUAL, IS TO BE USED IN LIEU OF THE REMOVED WIRELESS THERMOSTATS. COORDINATE ELECTRICAL ROUG-IN AND CONTROL WIRING W/ ELECTRICAL CONTRACTOR.410"x4" OFFSET TRANSFER GRILLE8 12/26/2018 BULLETIN #5 4"øTHERMOSTAT, TYP.TTACCESS PANEL WITH INTEGRAL RETURN AIR GRILLE BY VTAC MANUFACTURER, TYP. 2VTAC, TYP. 21C223261 BR SUITE 01348TTTHERMOSTAT, TYP.ACCESS PANEL WITH INTEGRAL RETURN AIR GRILLE, BY VTAC MANUFACTURER, TYP. 2124"ø4"øC2, TYP. 2VTAC, TYP. 2328DQ 04330ADA KING 01338TTHERMOSTAT, TYP.4"øACCESS PANEL WITH INTEGRAL RETURN AIR GRILLE, BY VTAC MANUFACTURERVTAC21TC23291 BR SUITE 033C3200 CFM12x848TTTTTHERMOSTAT, TYP. 54"ø4"ø4"øACCESS PANEL WITH INTEGRAL RETURN AIR GRILLE PROVIDED BY VTAC MANUFACTURER, TYP. 4VTAC, TYP. 421TC2, TYP. 43334081 BR SUITE ADA4121 BR SUITE 04414DQ 0444A3200 CFM12x125588REVISIONSPROJECT #:DATE:phonefaxmpg-architects.com330.666.5770330.666.88123660 Embassy ParkwayFairlawn, OH 44333TYPICAL GUEST ROOM MECHANICAL PLANSM702CAMBRIA SUITES HOTEL1000 LONGLEAF LANE,SOUTH WINDSOR, CT 0607422 OF 2215815JUNE 24, 2016 1/4" = 1'-0"1TYPICAL 1 BR SUITE 01 LAYOUT 1/4" = 1'-0"3TYPICAL DQ 04 / ADA KING 01 LAYOUT 1/4" = 1'-0"2TYPICAL 1 BR SUITE 03 LAYOUT 1/4" = 1'-0"4TYPICAL 1 BR SUITE ADA / 1 BR SUITE 04 /DQ 04 LAYOUTKEYED NOTES:2PROVIDE SIDEWALL GRILLE ACCORDING TO THE FOLLOWINGSCHEDULE:VTAC-A: 12x6 VTAC-B: 10x10 VTAC-C: 12x10 VTAC-D: 18x10 1SEE FLOOR PLANS FOR VTAC TAG/DESIGNATION AND MECHANICALSCHEDULES FOR VTAC SIZE BASED ON DESIGNATION.3EXHAUST GRILLE IN CEILING TO SIMULATE EXHAUST FAN, TYPICAL.BID ALTERNATES #3 - WIRED THERMOSTATS: CONTRACTOR IS TO PROVIDE A DEDUCT ALTERNATE TO HVAC BID WHICH REMOVES ALL WIRELESS THERMOSTATS AND ALL SUPPORTING CONTROL SYSTEMS. WIRED THERMOSTAT, TYPE ISLANDAIRE 6040927, OR EQUAL, IS TO BE USED IN LIEU OF THE REMOVED WIRELESS THERMOSTATS. COORDINATE ELECTRICAL ROUG-IN AND CONTROL WIRING W/ ELECTRICAL CONTRACTOR.48" DIAMETER SUPPLY FROM VTAC UNIT, CONCEALED IN SOFFIT ANDABOVE BATHROOM CEILING.58" DIAMETER SUPPLY FROM VTAC UNIT, CONCEALED IN SOFFIT ANDABOVE SITTING ROOM CEILING (CEILING IS TO BE RECESSED INROOM 412 ONLY)8 12/26/2018 BULLETIN #5