HomeMy WebLinkAbout1974-10-2 - 130 Buckland Road - Septic LetterMEMORANDUM
PUBLIC WORKS DEPARTMENT
POLLUTION CONTROL DIVISION 02 October, 1974
TO Donald McLaughlin -- Building Inspector
FROM : Melvin Edwards, Jr. -- Superintendent of Pollution Control
SUBJECT WILLIAM KRAWSKI PROPERTY ... BUCKLAND ROAD
This Division has received a copy of Douglas Prior's Sanitary Report on the
subject property. Dated 17 June, 1974, this Report shows a percolation rate of
one (1) inch in twenty (20) minutes. Per Section 19-13-B201 of the State Public
Health Code the minimum effective leaching area at this rate is 675 square feet,
with an additional area of 225 square feet for each bedroom above three (3).
At a 3-foot trench width a minimum field for this building would have to be 225
running feet - not 190 as shown on Prior's plan.
With careful installation and inspection I see no reason why a septic system
will not function properly.
Should you have any questions, or need additional information, please feel
free to contact me.
ME/
cc: file