HomeMy WebLinkAbout190 BURNHAM STREET (2)Exhibit C
Construction Drawings
Exhibit D
Structural Analysis Report
11 O Ft Monopole Tower Structural Analysis
Project Number 150051.001.01, Order 552626, Revision 0
TABLE OF CONTENTS
1) INTRODUCTION
2) ANALYSIS CRITERIA
Table 1 -Proposed Equipment Configuration
Table 2 -Other Considered Equipment
3) ANALYSIS PROCEDURE
Table 3 -Documents Provided
3.1) Analysis Method
3.2) Assumptions
4) ANALYSIS RESULTS
Table 4 -Section Capacity (Summary)
Table 5 -Tower Component Stresses vs. Capacity
4.1) Recommendations
5) APPENDIX A
tnxTower Output
6) APPENDIX B
Base Level Drawing
7) APPENDIX C
Additional Calculations
tnxTower Report -version 8.0.9.0
April 24, 2021
CCI BU No 806375
Page2
11 O Ft Monopole Tower Structural Analysis
Project Number 150051.001.01, Order 552626, Revision O
1) INTRODUCTION
This tower is a 110 ft. Monopole tower designed by Valmont IN January of 1991 .
2) ANALYSIS CRITERIA
TIA-222 Revision:
Risk Category:
Wind Speed:
Exposure Category:
Topographic Factor:
Ice Thickness:
Wind Speed with Ice:
Service Wind Speed:
TIA-222-H
II
125 mph
C
1
2 in
50mph
60mph
Table 1 -Proposed Equipment Configuration
Center Number Mounting Line of Antenna Antenna Model Level (ft) Elevation Antennas Manufacturer
(ft)
I 109.0 2 Antel _J._ LPA-80063/4CF -4 Antel I LPA-80080/4CF
I I 3 Commscope NHH-658-R2B
I 3 Commscope NHHSS-65B-R2B
104.0 1 Raycap RVZDC-6627-PF-48
' 108.0 ~--:Samsung Telecom. --3 MT6407-77A
3 RFV01U-D1A I L ---I Samsung Telecom. I
3 I Samsung Telecom. I RFV01U-D2A --1 -104.0 1 -Platform Mount [LP 715-1] - --
Table 2 -Other Considered Equipment
Center Number Mounting Line of Antenna Antenna Model Level (ft) Elevation Antennas Manufacturer
(ft)
9 Decibel DB844H90E-XY
97.0 97.0 2 GPS GPS -1 -Platform Mount [LP 715-1] -,--3 Argus Tech. LLPX310R
89.0 1 Dragonwave HORIZON COMPACT
~
85.0 3 Samsung Telecom. WIMAX OAP HEAD
~
1 Dragonwave A-ANT -18G -2-C ....__
85.0 1 -Side Arm Mount [SO 101-3]
tnxTower Report-version 8.0.9.0
April 24, 2021
CCI BU No 806375
Page3
Number Feed
of Feed Line
Lines Size (in)
7 1-5/8
1 1-1/2
Number Feed
of Feed Line
Lines Size (in)
12 7/8
I
I
I
j
7
1 1/2
3 5/16 I 3 1/4 I
110 Ft Monopole Tower Structural Analysis
Project Number 150051.001.01, Order 552626, Revision 0
3) ANALYSIS PROCEDURE
Table 3 -Documents Provided
I Document
Tower Manufacturer Drawing
Foundation Drawing
Geotech Report
Crown CAD Package
3.1) Analysis Method
Reference I
262106
262107
262109
Date: 04/14/2021 I
April 24, 2021
CCI BU No 806375
Page4
Source
CCI Sites
CCI Sites
CCI Sites
CCI Sites -
tnxTower (version 8.0.9.0), a commercially available analysis software package, was used to create a
three-dimensional model of the tower and calculate member stresses for various loading cases.
Selected output from the analysis is included in Appendix A. When applicable, Crown Castle has
calculated and provided the effective area for panel antennas using approved methods following the
intent of the TIA-222 standard.
3.2) Assumptions
1) The tower and structures were maintained in accordance with the -TIA-222 standard.
2) The configuration of antennas, transmission cables, mounts and other appurtenances are as
specified in Tables 1 and 2 and the referenced drawings.
This analysis may be affected if any assumptions are not valid or have been made in error. B+ T
Group should be notified to determine the effect on the structural integrity of the tower.
4) ANALYSIS RESULTS
Table 4 -Section Capacity (Summary)
!Section Elevation (ft) Component Size Critical P(K) SF•P_allow .,,.
Pass/ Fail No. Type Element (K) Capacity
L1 110-70 Pole TP25.53x15.53x0.25 1 -9.481 1143.410 54.9 Pass ---,---L2 70-34.083 Pole TP34.02x24.03x0.313 2 -15.126 1911 .770 64.1 I Pass
L3 34.083-0 I Pole TP41.9x32.164x0.344 3 -23.888 2690.860 69.7 Pass --
I Summary
r ---, ------Pole (L3) 69.7 Pass -I RATING= 69.7 Pass
tnxTower Report -version 8.0.9.0
110 Ft Monopole Tower Structural Analysis
Project Number 150051.001.01, Order 552626, Revision 0
Table 5 -Tower Component Stresses vs. Capacity
I Notes Component Elevation (ft)
1 Anchor Rods Base
1 Base Plate Base
1 Base Foundation Base
Structure Rating (max from all components) =
Notes:
% Capacity
52.4
35.0
64.2
April 24, 2021
CCI BU No 806375
Pages
Pass/ Fail
Pass
Pass
Pass
69.7%
1) See additional documentation in "Appendix C -Additional Calculations· for calculations supporting the % capacity
consumed.
2) Rating per TIA-222-H Seciion 15.5.
3) Foundation capacity determined by comparing analysis reactions to original design reactions.
4.1) Recommendations
The tower and its foundations have sufficient capacity to carry the proposed load configuration . No
modifications are required at this time.
tnxTower Report -version 8.0.9.0
Exhibit E
Mount Analysis
Replacement Mount Structural Analysis Report
(1) 12.50-ft Platform
Executive Summary:
April 30, 2021
Site ID: 468317-VZW I Burham St CT
Page 12
The objective of this report is to determine the capacity of the antenna support mount at the subject facility for the
final wireless telecommunications configuration, per the applicable codes and standards. Any modification listed
under Sources of Information was assumed completed and was included in this analysis.
This analysis is inclusive of the mount structure only and does not address the structural capacity of the supporting
structure. This mounting frame was not analyzed as an anchor attachment point for fall protection. All climbing
activities are required to have a fall protection plan completed by a competent person.
Sources of Information:
Document Type Remarks
Radio Frequency Data Sheet (RFDS) Verizon RFDS Site ID: 323512, dated September 2, 2020
Mount Mapping Report Structural Components Site ID: 16231955,
dated February 18, 2021
Failing Mount Analysis Report Maser Consulting Connecticut, Site ID: 21777001A,
dated March 26, 2021
Mount Specification Drawings Site Pro 1 Part# RMQP-496-HK
Analysis Criteria:
Codes and Standards: ANSI/TIA-222-H
Wind Parameters: Basic Wind Speed (Ultimate 3-sec. Gust), VuLr:
Ice Wind Speed (3-sec. Gust):
Design Ice Thickness:
Risk Category:
Exposure Category:
Topographic Category:
Topographic Feature Considered:
Topographic Method:
Ground Elevation Factor, Ke:
Seismic Parameters: Ss:
S1:
Maintenance Parameters: Wind Speed (3-sec. Gust):
Maintenance Live Load, Lv:
Maintenance Live Load, Lm:
Analysis Software: RISA-3D (V17)
117 mph
50 mph
1.50 in
II
C
1
N/A
N/A
0.998
0.187
0.055
30 mph
250Ibs
500Ibs
Replacement Mount Structural Analysis Report
(1) 12.50-ft Platform
Final Loading Configuration:
April 30, 2021
Site ID: 468317-VZW I Burham St CT
Page 13
The following equipment has been considered for the analysis of the mount:
Mount Equipment
Elevation Elevation Quantity Manufacturer Model Status
(ft) (ft)
109.00 2 Amphenol Antel LPA-80063-4CF-EDIN-4 Retained 4 Antel LPA-80080/ 4CF
3 Samsung MT6407-77A
3 Commscope NHH-658-R28
104.00 3 ' Commscope NHHSS-658-R28T2
108.00 3 Samsung 82/866A RRH-8R049 Added
3 Samsung 85/813 RRH-8R04C
3 Samsung C8RS RRH -RT4401-48A
1 Raycap RVZDC-6627-PF-48
Standard Conditions:
1. All engineering services are performed on the basis that the information provided to Maser Consulting
Connecticut and used in this analysis is current and correct. The existing equipment loading has been
applied at locations determined from the supplied documentation. Any deviation from the loading locations
specified in this report shall be communicated to Maser Consulting Connecticut to verify deviation will not
adversely impact the analysis.
2. Mounts are assumed to have been properly fabricated, installed and maintained in good condition, twist
free and plumb in accordance with its original design and manufacturer's specifications.
Obvious safety and structural issues/deficiencies noticed at the time of the mount mapping and reported in
the Mount Mapping Report are assumed to be corrected and documented as part of the PMI process and
are not considered in the mount analysis.
The mount analysis and the mount mapping are not a condition assessment of the mount. Proper
maintenance and condition assessments are still required post analysis.
3. For mount analyses completed from other data sources (including new replacement mounts) and not
specifically mapped by Maser Consulting Connecticut, the mounts are assumed to have been properly
fabricated, installed and maintained in good condition, twist free and plumb in accordance with its original
design and manufacturer's specifications.
4. All member connections are assumed to have been designed to meet or exceed the load carrying capacity
of the connected member unless otherwise specified in this report.
5. The mount was checked up to, and including, the bolts that fasten it to the mount collar/attachment and
threaded rod connections in collar members if applicable. Local deformation and interaction between the
mount collar/attachment and the supporting tower structure are outside the scope of this analysis.
6. All services are performed, results obtained, and recommendations made in accordance with generally
accepted engineering principles and practices. Maser Consulting Connecticut is not responsible for the
conclusion, opinions, and recommendations made by others based on the information supplied.
Replacement Mount Structural Analysis Report
(1) 12.50-ft Platform
April 30, 2021
Site ID: 468317-VZW I Burham St CT
Page 14
7. Structural Steel Grades have been assumed as follows, if applicable, unless otherwise noted in this
analysis:
o Channel, Solid Round, Angle, Plate
o HSS (Rectangular)
o Pipe
o Threaded Rod
o Bolts
ASTM A36 (Gr. 36)
ASTM 500 (Gr. 8-46)
ASTM A53 (Gr. 8-35)
F1554 (Gr. 36)
ASTM A325
Discrepancies between in-field conditions and the assumptions listed above may render this analysis
invalid unless explicitly approved by Maser Consulting Connecticut.
Analysis Results:
Component Utilization % Pass/Fail
Face Horizontal 23.2% Pass
Standoff Horizontal 21.4% Pass
Platform Crossmember 14.6% Pass
Mount Pipe 82.8% Pass
Corner Plate 25.2 % Pass
Grating Support 15.7% Pass
Cross Arm Plate 30.1% Pass
Support Rail 59.0% Pass
Support Rail Corner 77.7% Pass
Kicker 11.4% Pass
Mount Connection 19.5 % Pass
Structure Rating -(Controlling Utilization of all Components) 82.8%
Recommendation:
The proposed mount is SUFFICIENT for the final loading configuration and do not require modifications.
ANSI/ASSP rigging plan review services compliant with the requirements of ANSI/TIA 322 are available for a
Construction Class IV site or other, if required. Separate review fees will apply.
Attachments:
1. Specification Drawings
2. Mount Mapping Report (for reference only)
3. Analysis Calculations
4. Contractor Required Post Installation Inspection (PMI) Report Deliverables
5. Antenna Placement Diagrams
6. TIA Adoption and Wind Speed Usage Letter
Exhibit F
Power Density/RF Emissions Report
1
I
I ..
Site Name: BURNHAM ST CT
Cumulative Power Density
Operating Number of ERP Per Distance to Calculated Maximum Fraction of Operator Total ERP Power Permissible Frequency Trana. Trana. Target Density Exposure* MPE
(MHz) (watts) (watts) (feet) (mW/cmA2) (mW/cmA2) (%)
VZW700 751 4 679 2716 108 0.0084 0.5007 1.67%
VZWCDMA 869 2 401 802 108 0.0025 0.5793 0.43%
VZWCellular 869 4 689 2756 108 0.0085 0.5793 1.47%
VZWPCS 1980 4 1486 5944 108 0.0183 1.0000 1.83%
VZWAWS 2125 4 1652 6608 108 0.0204 1.0000 2.04%
VZWCBAND 3730 4 6531 26124 108 0.0805 1.0000 8.05%
VZWCBRS 3625 4 12 48 108 0.0001 1.0000 0.01%
Total Percentage of Maximum Permissible Exposure
*Guidelines adopted by the FCC on August 1, 1996, 47 CFR Part 1 based on NCRP Report 86, 1986 and generally on ANSI/IEEE C95.1-1992
**Calculation includes a -10 dB Off Beam Antenna Pattern Adjustment pursuant to Attachments Band C of the Siting Council's November 10, 2015 Memorandum for Exempt Modification filings
MHz = Megahertz
mW/cm"2 = milliwatts per square centimeter
ERP = Effective Radiated Power
Absolute worst case maximum values used.
INSPECTION FIELD SHEET 05/13/11 08:13:13 Printed by Peart, Dayshell
INSPECTION: 39094 FOOTING
LOCATION: 190 BURNHAM STREET
SOUTH WINDSOR
PROPERTY ID: 15600190
OWNER: BURNHAM STREET LLC
CONTRACTOR:
REQUEST BY:
PERMIT:
STATUS:
APPLICATION: 201100324
DESCRIPTION: BRING KITCHEN UP TO CODE. INSTALL FRP ON WALL. NEW CEILING
WORK ORDER:
INSPECTOR: ROSE
REQUESTED:
SCHEDULED:
UNPAID FEES:
COMMENTS:
ALL INSPECTIONS:
INSPECTED INSPECTOR
05/13/11 ROSE
05/13/11 ROSE
05/13/11 ROSE 05/13/11 ROSE
05/13/11 ROSE
04/13/01 DOUG 05/06/11 DOUG
04/29/11 SUMM
04/29/11 SUMM 05/05/11 ROY
.00
RESULT
N/A
N/A
N/A
N/A
N/A
PASS PASS
PASS
PASS PASS
RESULT:
PRIORITY:
N/A
05/13/11 Date COMPLETED:
TIME: TRAVEL
Time
ONSITE
INSP
B002
B003
B004
BOOS
B006
B009
BOlO
F020
F040 V035
DESCRIPTION
FOUNDATION
FRAMING (ROUGH)
INSULATION
FIREPLACE/ CHIMNEY
WOOD/ GAS STOVE
OTHER FINAL
FM HOOD EXTINGUISH SYSTEM
CO -FIRE MARSHAL INSPECTION
HEALTH FINAL
INSPECTION FIELD SHEET
Printed by Peart, Dayshell
INSPECTION: 32883 FOOTING PERMIT
09/14/10
11:08:54
STATUS APPLICATION 201000811 LOCATION: 190 BURNHAM STREET
SOUTH WINDSOR
PROPERTY ID: 15600190
OWNER: GLASSMAN ABRAHAM & BEVERLY TRUSTEES
CONTRACTOR:
DESCRIPTION: ADD ANTENNAS ABD EQUIPMENT TO EXISTING TOWER
WORK ORDER:
INSPECTOR: DOUG
REQUESTED:
SCHEDULED :
UNPAID FEES:
COMMENTS:
ALL INSPECTIONS:
INSPECTED INSPECTOR
08/30/10 DOUG
08/30/10 DOUG
08/30/10 DOUG
08/30/10 DOUG
08/30/10 DOUG
08/30/10 DOUG
08/30/10 DOUG
08/16/10 ROSE
07/22/10 ROSE
07/28/10 ROSE
.00
RESULT
N/A
N/A
N/A
N/A
N/A
N/A
N/A
PASS
PENDING
PASS
RESULT:
COMPLETED:
N/A
08/30/10
Date
TIME: TRAVEL
Time
ONSITE
INSP
B002
B003
B004
BOOS
B006
B009
BOlO
BOlO
EOOl
EOOl
DESCRIPTION
FOUNDATION
FRAMING (ROUGH)
INSULATION
FIREPLACE/ CHIMNEY
WOOD/ GAS STOVE
OTHER
FINAL
FINAL
ELECTRIC SERVICE
ELECTRIC SERVICE
11 0 Ft Monopole Tower Structural Analysis
Project Number 308725, Application 91527, Revision 1
TABLE OF CONTENTS
1) INTRODUCTION
2) ANALYSIS CRITERIA
Table 1 -Proposed Antenna and Cable Information
Table 2 -Existing and Reserved Antenna and Cable Information
Table 3 -Design Antenna and Cable Information
3) ANALYSIS PROCEDURE
Table 4 -Documents Provided
3.1) Analysis Method
3.2) Assumptions
4) ANALYSIS RESULTS
Table 5 -Tower Component Stresses vs. Capacity
4.1) Recommendations
5) APPENDIX A
RISATower Output
6) APPENDIX B
Base Level Drawing
7) APPENDIX C
Additional Calculations
RISATower Report -version 5.3.1.0
December 17, 2009
CCI BU No 806375
Page2
11 0 Ft Monopole Tower Structural Analysis
Project Number 308725, Application 91527, Revision 1
Table 3 -Design Antenna and Cable Information
Center Number Mounting Line of Antenna Antenna Model Level (ft) Elevation Antennas Manufacturer
(ft)
107 107 I 4 -I PD10017's
! -100.5 -r r -----100.5 12 -PD1132's ---
3) ANALYSIS PROCEDURE
Table 4 -Documents Provided
I Document Remarks Reference
4-GEOTECHNICAL REPORTS EDP/TRIGGS 262109
4-TOWER FOUNDATION . -fl 7--DRAWINGS/DESIGN/SPECS Leinweber & Assoc. 262107
' 4-TOWER MANUFACTURER l
DRAWINGS Valmont I 262106
- ----------
3.1) Analysis Method
December 17, 2009
CCI BU No 806375
Page4
Number Feed
of Feed Line
Lines Size (in)
-I -
-
Source
CCISITES
T ~c1s1~;s
I CCISITES
--
RISATower (version 5.3.1.0), a commercially available analysis software package, was used to create
a three-dimensional model of the tower and calculate member stresses for various loading cases.
Selected output from the analysis is included in Appendix A.
3.2) Assumptions
1) Tower and structures were built in accordance with the manufacturer's specifications.
2) The tower and structures have been maintained in accordance with the manufacturer's
specification.
3) The configuration of antennas, transmission cables, mounts and other appurtenances are as
specified in Tables 1 and 2 and the referenced drawings.
4) When applicable, transmission cables are considered as structural components for calculating
wind loads as allowed by TIA/EIA-222-F.
5) The base plate grout was not considered in this analysis.
This analysis may be affected if any assumptions are not valid or have been made in error. Crown
Castle should be notified to determine the effect on the structural integrity of the tower.
4) ANALYSIS RESULTS
Table 5 -Section Capacity (Summary)
Section Elevation (ft) Component Size Critical p (K) SF*P_allow % Pass /Fall No. Type Element (K) Capacity
L1 110-70 Pole TP25.53x15.53x0.25 1 -6.48 1016.11 61.9 Pass
L2 70 • 34.0833 Pole TP34.02x24.03x0.3125 2 -11.20 1698.94 71.3 Pass
L3 34.0833 -0 Pole TP41.9x32.1645x0.3438 3 -18.49 2385.98 73.1 Pass
Summary
Pole (L3) 73.1 Pass
I RATING= 73.1 Pass
Table 6-Tower Component Stresses vs. Capacity-LC1
RISATower Report -version 5.3.1.0
110 Ft Monopole Tower Structural Analysis
Project Number 308725, Application 91527, Revision 1
I Notes Component Elevation (ft)
1 Anchor Rods 0
1 1 BasePl~te 0
1,2 I Base Foundation 0
Structure Rating (max from all components) =
Notes:
% Capacity
59.3
42.6
75.0
December 17, 2009
CCI BU No 806375
Page5
Pass / Fail
Pass
Pass
Pass
75%
1) See additional documentation in "Appendix C -Additional Calculations" for calculations supporting the% capacity
consumed.
2) Foundation capacity determined by comparing analysis reactions to original design reactions.
4.1) Recommendations
The tower and its foundation have sufficient capacity to carry the existing, reserved, and proposed
loads. No modifications are required at this time.
RISATower Report -version 5.3.1.0
110 Ft Monopole Tower Structural Analysis
Project Number 308725, Application 91527, Revision 1
RISATower Report -version 5.3.1.0
APPENDIX A
RISA TOWER OUTPUT
December 17, 2009
CCI BU No 806375
Page 6
RISATower Job Page
BU #806375 1 of 11
Project Date Cro11111 Castle USA Inc.
2()()() Corporate Dril'e 15:37:37 12/17/09
Ca,ro11sburg. PA /5317 Client Designed by
Pho,re: (724) 416-21179 Crown Castle
FAX: (724) 4/6-4879
Tower Input Data
There is a pole section.
This tower is designed using the TIA/EIA-222-F standard.
The following design criteria apply:
Tower is located in Hartford County, Connecticut.
Basic wind speed of 80 mph.
Nominal ice thickness of0.5000 in.
Ice density of 56 pcf.
A wind speed of 69 mph is used in combination with ice.
Deflections calculated using a wind speed of50 mph.
A non-linear (P-delta) analysis was used.
Pressures are calculated at each section.
Stress ratio used in pole design is 1.333.
tstyran
Local bending stresses due to climbing loads, feed line supports, and appurtenance mounts are not considered.
Consider Moments -Legs
Consider Moments -Horizontals
Consider Moments -Diagonals
Use Moment Magnification
Use Code Stress Ratios
Use Code Safety Factors -Guys
Escalate Ice
Always Use Max Kz
Use Special Wind Profile
Include Bolts In Member Capacity
Leg Bolts Are Al Top Of Section
Secondary Horizontal Braces Leg
Use Diamond Inner Bracing (4 Sided)
Add IBC .6D+W Combinauon
Section Elevation Section
le,rgth
ft Ji
LI 110.00-70.00 40.00
L2 70.00-34.08 39.92
L3 34.08-0.00 3900
Options
Distribute Leg Loads As Uniform
Assume Legs Pinned
Assume Rigid Index Plate
Use Clear Spans For Wind Area
Use Clear Spans For KUr
Retension Guys To Initial Tension
Bypass Mast Stability Checks
Use Azimuth Dish Coefficients
Project Wind Area of Appun.
Autocalc Torque Arm Areas
SR Members Have Cut Ends
Son Capacity Repons By Component
Triangulate Diamond Inner Bracing
Treat Feedline Bundles As Cylinder
Use ASCE IO X-Brace Ly Rules
Calculate Redundant Bracing Forces
Ignore Redundant Members in FEA
R Leg Bolts Resist Compression
All Leg Panels Have Same Allowable
Offset Gin At Foundation ✓ Consider Feedlme Torque
Include Angle Block Shear Check
Poles ✓ Include Shear-Torsion Interaction
Always Use Sub-Critical Flow
Use Top Mounted Sockets
Tapered Pole Section Geometry
Splice Number Top 80110m Wall Be,rd Pole Grade
le,rgth of Diameter Diameter Thickness Radius
r, Sides i,r i,r in in
4.00 12 15.5300 25.5300 0.2500 1.0000 A572-65
(65 ksi)
4.92 12 24.0300 34.0200 0.3125 1.2500 A572-65
(65 ksi)
12 32.1645 41.9000 0.3438 1.3750 A572-65
65 ksi
Tapered Pole Properties
RISATower Job Page
BU #806375 2 of 11
Project Date Cro11111 Cosde USA /11c.
20()(} Corporate Drive 15:37:3712/17/09
Canonsburg. PA 15317 Client Designed by
Phone: (724) 416-2/J79 Crown Castle
FAX: (724) 416-4H79
Section Tip Dia. Area I r C /IC J 1119 w wit
in in1 in4 in in in1 in4 in in
LI 16.0778 12.3004 366.5658 5.4702 8.0445 45.5670 742.7616 6 0539 3.4920 13.968
26.4306 20.3504 1660.0189 9.0502 13 2245 125.5256 3363.6484 10 0158 61720 24.688
L2 25.9141 23.8657 1713.5571 8.4909 12.4475 137.6623 3472.1312 11.7460 5.6025 17.928
35.2201 33.9182 4918.9394 12.0673 17.6224 279.1306 9967.1048 16.6935 8.2799 26.496
L3 34.5698 35.2216 4552.1411 11.3918 16.6612 273.2179 9223.8721 17.3350 7.6988 22.397
43.3781 45.9976 10138.9640 14.8771 21.7042 467.1429 20544.2898 22.6386 10.3080 29.987
Tower
Elei·ation
Gusset Gusset Gusset Grade Adjust. Factor Adjust. Weight Mult. Double Angle Double Angle
LI
110.00-70.00
L2 70 00-34.08
L3 34 08-0.00
Area
(per face)
r'
Thickness A1 Factor
A,
in
S1i1ch Boll S1i1ch Boll
Spacing Spacing
Diagonals Horizon1als
in in
Feed Line/Linear Appurtenances -Entered As Area
Descriplion Face Allow Component Placemen/ To1al C,.A, Weigh/
or Shield Type Number
le I ;' I kif
1 IJ7-50A(l-5/8") C No Inside Pole 108.00-0 00 15 No Ice 0.00 000
1/2" Ice 0.00 000
AL7-50( I 5/8") C 0 CaAa(Out Of 108.00-0 00 2 No Ice 000 000
Face) 1/2" Ice 0.00 0.00
AL7-50(1 5/8") C No CaAa (Out Of I 08.00 - 0.00 No Ice 0.20 0.00
Face) 1/2" Ice 0.30 0.00
LDF5-50A(7/8") B No Inside Pole 97.00-0.00 II No Ice 0.00 0.00
1/2" Ice 0.00 0.00
FSJ l-50A(l /4") C No CaAa(Out Of 86.00-0.00 3 No Ice 0.00 0.00
Face) 1/2" Ice 0.00 0.00
FSJ4-50B( 1/2") C No CaAa(OutOf 86.00-0.00 No Ice 0.00 0.00
Face) 1/2" Ice 0.00 0.00
FSJ4-50B( I /2") C No CaAa(Out Of 86.00-0 00 3 No Ice 0.05 0.00
Face) 1/2" Ice 0.15 0.00
HJ4.5-50(5/8") C No CaAa(OutOf 86.00-0.00 3 No Ice 0.00 000
Face) 1/2" Ice 0.00 0.00
9207(5/16") C No CaAa(Out Of 86.00-0.00 No Ice 0.00 0.00
Face) 1/2" Ice 0.00 0.00
Feed Line/Linear Appurtenances Section Areas
Tower Tower Face A, A, C,.A, C,.AA Weigh1
Sec1ion Elevation In Face Out Face
I ;1 ;1 ;1 ;1 K
LI 110.00-70.00 A 0.000 0.000 0.000 0.000 0.00
B 0.000 0.000 0.000 0.000 0.10
C 0.000 0.000 0.000 9.944 0.69
L2 70.00-34.08 A 0.000 0.000 0.000 0.000 0.00
B 0.000 0.000 0.000 0.000 0.13
C 0.000 0.000 0.000 12.643 0.71
L3 34.08-0.00 A 0.000 0.000 0.000 0.000 0.00
B 0.000 0.000 0.000 0.000 0.12
tstyran
RISATower Job Page
BU #806375 3 of 11
Crow11 Castle USA Inc. Project Date
2(){)() Corporate Drive 15:37:37 12/17/09
Canonsburg, PA /5317 Client Designed by
Phone: (724) 4/6-2879 Crown Castle tstyran FAX: (724) 4/6-4879
Tower Tower Face A• A, C,.AA C,A, Weight
Section E/el'Otion Ill Face Out Face
t r i' i' i' K
C 0.000 0000 0.000 11 997 0.67
Feed Line/Linear Aeeurtenances Section Areas -With Ice
To·wer Tower Face Ice A, A, C,.A, C . .A., Weight
Section Elevation or Thick11ess In Face Out Face
I!. leg_ in [! [! [! rr K
LI 11000-70.00 A 0500 0.000 0.000 0.000 0.000 000
8 0000 0.000 0.000 0.000 0.10
C 0.000 0000 0.000 18.544 0.97
L2 70.00-34.08 A 0.500 0000 0.000 0.000 0.000 0.00
8 0.000 0.000 0.000 0.000 0.13
C 0.000 0.000 0000 27.0IO 1.12
L3 34.08-0.00 A 0 500 0.000 0.000 0.000 0.000 0.00
B 0.000 0.000 0.000 0.000 0.12
C 0000 0000 0.000 25 631 I 06
Feed Line Center of Pressure
Section Elevation CP, CP, CPr CP,
Ice Ice
t in in ill in
LI 1 I0.00-70.00 -0 2949 0.1702 -0.4860 0.2806
L2 70 00-34 08 -0.4000 0.2310 -0.7293 0.4211
L3 34 08-0.00 -04111 0.2374 -0.7715 0.4454
Discrete Tower Loads
Description Face Offset Offsets: Azimuth Placement C_,A, C_,A, Weight
or Type Hon Adjustment Fro/II Side
Leg Lateral
Vert
ft ft fl fl K
ft
••
(2) DB948F85T2E-M w/ A From Leg 4.00 0.0000 108.00 Noice 2.13 4.45 0.D3
Mount Pipe 0.00 1/2" Ice 2.49 5.12 0.06
1.00
BXA-70063/6CFx2 w/ Mount A From Leg 4.00 0.0000 108.00 No Ice 7.97 5.40 0.04
Pipe 000 1/2" Ice 8.61 6.55 0.10
1.00
(2) LPA-80080/4CF w/ A From Leg 4.00 0.0000 108.00 Noice 2.86 7.23 0.03
Mount Pipe 0.00 1/2" Ice 3.22 7.92 0.D7
1.00
(2) DB948F85T2E-M w/ B From Leg 4.00 0.0000 108.00 No Ice 2.13 4.45 0.03
Mount Pipe 0.00 1/2" Ice 2.49 5.12 0.06
1.00
BXA-70063/6CFx6 w/ Mount B From Leg 4.00 0.0000 108.00 No Ice 7.97 5.40 0.03
RISATower Job Page
BU #806375 4 of 11
Crown Castle USA Inc. Project Date
2000 Corporate Drfre 15:37:37 12/17/09
Canonsburg. PA 15317 Client Designed by Phone: (724) 416-2879 Crown Castle tstyran FAX: (724) 416--4879
Description Face Offiet Offiets: Azimuth Placeme/11 C,A, C,A, Weight
or Type Horz Adjustment From Side
Leg Lateral
Verr
Ji Ji fr fr K
Ji
fi
Pipe 0.00 1/2" Ice 8.61 6.55 0.08
1.00
(2) LPA-80080/4CF w/ B From Leg 4.00 00000 108.00 No Ice 2.86 7.23 0.03
Mount Pipe 0.00 1/2" Ice 3.22 7.92 0.07
1.00
(2) DB948F85T2E-M w/ C From Leg 400 0.0000 108 00 No Ice 2.13 4.45 O.oJ
Mount Pipe 0.00 1/2" Ice 2.49 512 0.06
1.00
BXA-70063/6CFx6 w/ Mount C From Leg 4.00 0.0000 108.00 No Ice 7.97 5.40 0.03
Pipe 0.00 1/2" Ice 8.61 6.55 0.08
1.00
(2) LPA-80063/4CF w/ C From Leg 4.00 0.0000 108.00 No Ice 7.25 7.26 0.04
Mount Pipe 000 1/2" Ice 7.72 7.96 0.10
1.00
Platform Mount (LP 101-1 ) C None 0.0000 108.00 No Ice 36.21 36.21 1.50
1/2" Ice 42 82 42.82 2.30 ••
(3) ALP 9212-N w/ Mount A From Leg 4.00 0.0000 97 00 No Ice 6.02 7.05 0.04
Pipe 0.00 1/2" Ice 6.51 7.83 0.09
0.00
(3) ALP 9212-N w/ Mount B From Leg 4.00 0.0000 97 00 No Ice 6.02 7.05 0.04
Pipe 0.00 1/2" Ice 6.51 7 83 009
0.00
TIMING2000 B From Leg 4.00 0.0000 97.00 No Ice 0.13 0.13 0.00
000 1/2" Ice 0.18 0.18 000
000
(3) ALP 9212-N w/ Mount C From Leg 4.00 00000 97 00 No Ice 6.02 7.05 0.04
Pipe 0.00 1/2" Ice 6.51 7.83 0.09
0.00
TIMING2000 C From Leg 4.00 0.0000 97.00 No Ice 0.13 013 000
0.00 1/2" Ice 0.18 0.18 0.00
0.00
Platform Mount (LP 101-1) C None 0.0000 97 00 No Ice 36.21 36.21 1.50
1/2" Ice 42.82 42.82 2.30 ••
LLPXJIOR w/ Mount Pipe A From Leg 3.00 00000 8600 No Ice 5 07 2.98 0.05
0.00 1/2" Ice 5.48 3.53 0.08
1.00
HORIZON COMPACT A From Leg 3.00 0.0000 86.00 No Ice 0 84 0.43 0.01
0.00 1/2" Ice 0.97 0.52 0.02
-4.00
WIMAX DAP HEAD A From Leg 3.00 0.0000 86.00 No Ice 1.80 0.78 0.03
0.00 1/2" Ice 1.99 0.92 0.04
1.00
LLPX3 I OR w/ Mount Pipe B From Leg 3.00 0.0000 8600 No Ice 5.07 2.98 0.05
0.00 1/2" Ice 5.48 3.53 0.08
1.00
HORIZON COMPACT B From Leg 3.00 00000 86.00 No Ice 0 84 0.43 0.01
0.00 1/2" Ice 0.97 0.52 0.02
-4.00
WIMAX DAP HEAD B From Leg 3.00 0.0000 86.00 Noice 1.80 0.78 O.oJ
0.00 1/2" Ice 1.99 0.92 0.04
1.00
LLPXJ I OR w/ Mount Pipe C From Leg 3.00 0.0000 86.00 Noice 5.o7 2.98 0.05
0.00 1/2" Ice 5 48 3.53 0.08
1.00
HORIZON COMPACT C From Leg 3.00 0.0000 86.00 No Ice 0.84 0.43 o.oi
RISATower Job
Crown Castle USA Inc. Project
2()()() Corporate Drive
Canonsburg. PA 15317 Client
Phone: (724) 4/6-2879
FAX: (724) 4/6-41179
Description Face Offset
or Type
Leg
TIMING2000 C From Leg
WIMAX DAP HEAD C From Leg
T-Ann Mount fTA 702-3] C None
Description Face Dish
or Type
Leg
A-ANT-I 8G-2-C A Paraboloid w/o
Radome
A-ANT-I 8G-2-C B Paraboloid w/o
Radome
A-ANT-18G-2-C C Paraboloid w/o
Comb.
No.
I
2
3
4
5
6
7
8
9
10
II
12
13
14
15
16
Radome
Dead Only
Dead+Wind O deg -No Ice
Dead+Wind 30 deg -No Ice
Dead+Wind 60 deg -No Ice
Dead+Wind 90 deg -No Ice
Dead+Wind 120 deg-No Ice
Dead+Wind 150 deg -o Ice
Dead+Wind 180 deg -No Ice
Dead+Wind 210 deg -No Ice
Dead+Wind 240 deg -No Ice
Dead+Wind 270 deg -No Ice
Dead+Wind 300 deg -No Ice
Dead+Wind 330 deg -No Ice
Dead+Ice
Dead+Wind O deg+Ice
Dead+Wind 30 deg+lce
Offset
Type
From
Leg
From
Leg
From
Leg
Page
BU #806375 5 of 11
Date
15:37 :37 12/17 /09
Designed by
Crown Castle tstyran
Offsets: Azimuth Placement C,,A, C,A, Weight
Hon Adjustment Front Side
Lateral
Vert
ft ft fr fr K
ft
t
0.00 1/2" Ice 0.97 0.52 0.02
-4.00
3.00 0.0000 86.00 No Ice 0.13 0.13 0.00
0.00 1/2" Ice 0.18 0.18 0.00
1.00
3.00 0.0000 86.00 No Ice I 80 0.78 0.03
000 1/2" Ice 199 092 0.04
1.00
00000 8600 No Ice 5 64 5.64 0.34
1/2" Ice 6.55 6.55 0.43
Dishes
Offsets: Azimuth 3d8 Elevation Outside Aperture Weight
Hon Adjustment Beam Diameter Area
Lateral Width
Vert
I . t ft i1 K
3.00 0.0000 86.00 2.17 No Ice 3.72 0.oJ
0.00 1/2" Ice 4 01 0.03
-4.00
3.00 0.0000 86.00 2.17 No Ice 3.72 0.oJ
000 1/2" Ice 4.01 0.oJ
-4.00
3.00 0.0000 86.00 2.17 No Ice 3.72 0.oJ
0.00 1/2" Ice 401 0.oJ
-4.00
Load Combinations
Description
Comb.
No.
17
18
19
20
21
22
23
24
25
26
27
28
29
JO
31
32
33
34
35
36
37
38
RISATower
Crown Castle USA Inc.
2000 Corporate Drfre
Ca11011sburg, PA 15317
Phone: (TU) 4/6-2/J79
FAX: (724) 416-4X79
Dead+Wind 60 deg+lce
Dead+Wind 90 deg+lce
Dead+Wmd 120deg+lce
Dead+Wind 150 deg+lce
Dead+Wind 180 deg+lce
Dead+Wind 210 deg+lce
Dead+Wind 240 deg+lce
Dead+Wind 270 deg+lce
Dead+Wind 300 deg+lce
Dead+Wmd 330 deg+lce
Dead+Wind O deg• Service
Dead+Wind 30 deg• Service
Dead+Wmd 60 deg• Service
Dead+Wind 90 deg• Service
Dead+Wind 120 deg• erv1ce
Dead+Wind 150 deg• Service
Dead+Wind 180 deg• Service
Dead+Wmd 210 deg• Service
Dead+Wind 240 deg• Service
Dead+Wind 270 deg• Service
Dead+Wmd 300 deg• Service
Dead+Wind 330 deg• Service
Job
Project
Client
Section Elel'ation
No. ft
Component
Type
LI 110-70
L2 70 • 34.0833
L3 34.0833 -0
location
Pole
Pole
Pole
Condition Gov.
load
Comb.
BU #806375
Crown Castle
Description
Maximum Member Forces
Condition Go,•. Force
Load
Comb. K
Max Tension 24 0.00
Max. Compression 14 -10.89
Max. Mx II -6.49
Max. My 2 -6.51
Max. Vy II -12.19
Max. Vx 2 -12.10
Max. Torque 20
Max Tension I 0.00
Max. Compression 14 -16.35
Max. Mx II -11.21
Max. My 2 -11.22
Max. Vy II -15.23
Max. Vx 2 -15.14
Max. Torque 20
Max Tension I 0.00
Max. Compression 14 -24.57
Max. Mx II -18.49
Max. My 2 -18.49
Max. Vy II -18.77
Max. Vx 2 -18.68
Max. Torque 20
Maximum Reactions
Vertical
K
Horizontal, X
K
Major Axis
Moment
kipfl
-0.00
0.53
303.15
-5. I 5
303.15
-5.15
000
1.07
782 90
-10.33
782.90
-10.33
0.00
1.87
1444.92
-15.95
1444.92
-15.95
Horizontal, Z
K
Page
6 of 11
Date
15:37:37 12/17 /09
Designed by
tstyran
Minor Axis
Moment
kip-ft
0.00
-0.24
-4.48
297.50
-4.48
297.50
-0.15
000
-0.56
-6 22
773.66
-6.22
773.66
-0.33
0.00
-1.02
-8.13
1431.69
-8.13
1431.69
-0.58
RISATower Job Page
BU #806375 7 of 11
Crow11 Castle USA Inc. Project Date
20()() Corporate Drive 15:37:37 12/17/09
Canonsburg. PA /5317 Client Designed by
Phone: (724) 416-2879 Crown Castle tstyran FAX: (724) 4/6-4879
location Condition Gov. Vertical Horizontal. X Horizontal. Z
load K K K
Comb.
Pole Max Vert 24 24.57 1607 -0 03
Max. H, II 18.50 18.76 -0 04
Max. H, 2 18.50 -0.15 18 66
Max. M, 2 1431.69 -0.15 1866
Max. M, 5 1443.89 -18 76 0 25
Max. Torsion 26 0.58 8.01 13.70
Mm. Vert I 18.50 0.00 000
Mm.H, 5 18 50 -18 76 0.25
Mm.H, 8 18.50 015 -18 62
Min.M, 8 -1428.59 0.15 -18.62
Mm.M, II -1444.92 18 76 -0 04
Mm. Torsion 20 -0.58 -7.86 -13.79
Tower Mast Reaction Summary
load Vertical Shear, Shear, Overlllrning O.•erturning Torque
Combination Moment,M, Moment, M,
K K K kie_-f!. kie_-f!. kie_-f!.
Dead Only 18.50 0.00 0.00 025 0.50 0.00
Dead+Wmd O deg -No Ice 18 50 0.15 -18.66 -1431 69 -15.95 -0.32
Dead+Wind 30 deg-No Ice 18.50 9.59 -16.12 -1238.11 -743.38 -0.18
Dead+Wmd 60 deg-No Ice 18.50 16.35 -9.44 -728 14 -1261.10 0.02
Dead+Wmd 90 deg -No Ice 18.50 18.76 -0.25 -24.80 -1443.89 0.21
Dead+Wmd 120 deg-No Ice 18.50 16.24 9.20 701 97 -1247.82 0.34
Dead+Wind 150 deg -No Ice 18.50 9.16 16.07 1230.80 -700.02 0.38
Dead+Wind 180 deg -No Ice 18.50 -0.15 18.62 1428.59 16.98 0.33
Dead+Wind 210 deg -No Ice 18.50 -942 16 22 1247 20 729.54 0.19
Dead+Wmd 240 deg -No Ice 18.50 -16.38 9.46 730.45 1265.26 -0.02
Dead+Wind 270 deg -No Ice 18 50 -18.76 0.04 8 13 1444.92 -0 22
Dead+Wmd 300 deg -No Ice 18 50 -16.20 -9.18 --099.66 1245.72 -0.35
Dead+Wind 330 deg -No Ice 18.50 -9.34 -15.97 -1221.70 715.93 -0.38
Dead+lce 24.57 000 0.00 I 02 1.87 0.00
Dead+Wmd O deg+lce 24.57 0.11 -16.00 -1239.80 -10.91 -0.49
Dead+Wmd 30 deg+lce 24.57 8.20 -13.82 -1071.84 --040.42 -0.28
Dead+Wmd 60 deg+lce 24.57 14.00 -8.08 --02899 -1089.34 0.02
Dead+Wind 90 deg+lce 24.57 16.07 -0.20 -18.80 -1248.39 0.31
Dead+Wmd 120 deg+lce 24.57 13.91 7.90 610.36 -1079.10 0.51
Dead+Wind 150 deg+Jce 24.57 7.86 13.79 1068.15 -606.07 0.58
Dead+Wmd 180 deg+lce 24.57 -0.11 15.97 1238.94 14.74 0.50
Dead+Wind 210 deg+lce 24.57 -8.06 13.90 1080.94 632.10 0.28
Dead+Wind 240 deg+lce 24.57 -14.03 8.10 632.55 1095.72 -0.02
Dead+Wind 270 deg+lce 24.57 -16.07 0.03 6.85 1252.22 -0.31
Dead+Wind 300 deg+lce 24.57 -13.88 -7.88 -606.80 1080.38 -0.52
Dead+Wind 330 deg+lce 24.57 -8.01 -13.70 -1059.05 622.06 -0.58
Dead+Wind O deg-Service 18.50 0.06 -7.29 -559.53 -5.92 -0.13
Dead+Wind 30 deg -Service 18.50 3.75 -6.30 -483.86 -290.30 -0.07
Dead+Wmd 60 deg-Service 18.50 6.39 -3.69 -284.50 -492.70 0.01
Dead+Wind 90 deg -Service 18.50 7.33 -0.10 -9.54 -564.14 0.08
Dead+Wind 120 deg-erv1ce 18.50 6.34 3.60 274.57 -487.48 0.13
Dead+Wind 150 deg -Service 18.50 3.58 6.28 481.29 -273.33 0.15
Dead+Wind 180 deg -Service 18.50 -0.06 7.27 558.62 6.96 0.13
Dead+Wind 2 IO deg -Service 18.50 -3.68 6.34 487.73 285.52 0.07
Dead+Wind 240 deg -Service 18.50 --0.40 3.69 285.72 494.96 -0.01
Dead+Wind 270 deg -Service 18.50 -7.33 0.02 3.33 565.18 -0.08
Dead+Wind 300 deg -Service 18.50 --0.33 -3.59 -273.35 487.30 -0.13
Dead+Wind 330 d9l -Service 18.50 -3.65 --0.24 -477.43 280.18 -0.15
RISATower Job Page
BU #806375 8 of 11
Crown Castle USA Inc. Project Date
2000 Corporare Drive 15:37:37 12/17/09
Canonsburg, PA /5317 Client Designed by
Phone: (724) 4/6-2879 Crown Castle tstyran FAX: (724) 416-41179
Solution Summary
Sum of Applied Forces Sum of Reacrions
Load PX PY Pl PX PY Pl %Error
Comb. K K K K K K
I 0.00 -18.50 0.00 0.00 18.50 0.00 0.000%
2 0.15 -18.50 -18.66 -0.15 18.50 18.66 0.000%
3 9.59 -18.50 -16.12 -9 59 18.50 16.12 0000%
4 16.35 -18.50 -9.44 -16.35 18.50 9.44 0 000°/o
5 18.76 -18.50 -0.25 -18 76 18 50 0.25 0.000°/o
6 16.24 -18.50 9.20 -16.24 18.50 -9.20 0.000°/o
7 9.16 -18.50 16.07 -9 16 18.50 -16.07 0000°/o
8 -0.15 -18 50 18.62 015 18.50 -18.62 0.000°/o
9 -9.42 -18.50 16.22 9.42 18.50 -16.22 0.000°/o
10 -16.38 -18.50 9.46 16.38 18.50 -946 0000%
II -18.76 -18 50 0.04 18 76 18.50 -0 04 0000%
12 -16.20 -18.50 -9.18 16.20 18.50 9.18 0.000%
13 -9.34 -18.50 -15.97 9.34 18.50 15.97 0.000%
14 0.00 -24.57 0.00 0.00 24.57 0.00 0.000%
15 0 I I -24.57 -16.00 -0 11 24.57 16.00 0.000%
16 8.20 -24.57 -13.82 -8 20 24.57 13.82 0.000%
17 14.00 -24.57 -8.08 -14.00 24.57 8.08 0.000%
18 16.07 -24.57 -0.20 -16 07 24.57 0.20 0.000%
19 13.91 -24.57 7.90 -13.91 24.57 -7.90 0.000%
20 7 86 -24 57 13.79 -7.86 24.57 -13.79 0.000%
21 -0.11 -24.57 15.97 0.11 24.57 -15.97 0.000°/o
22 -8.06 -24.57 13.90 8.06 24.57 -13.90 0.000°/o
23 -14.03 -24.57 8.10 14.03 24 57 -8.10 0.000%
24 -16.07 -24.57 0.03 16.07 24.57 -0.03 0.000%
25 -13.88 -24.57 -7.88 13.88 24.57 7.88 0.000%
26 -8.01 -24 57 -13 70 8 01 24.57 13.70 0.000%
27 0.06 -18.50 -7.29 -0.06 18.50 7.29 0.000%
28 3.75 -18.50 -6.30 -3 75 18.50 6.30 0.000%
29 6.39 -18.50 -3.69 -6.39 18.50 3.69 0.000%
30 7.33 -18 50 -0.10 -7.33 18.50 0.10 0.000%
31 6.34 -18.50 3.60 -6.34 18.50 -3 .60 0.000%
32 3.58 -18.50 6.28 -3.58 18.50 -6.28 0.000%
33 -0.06 -18 50 7.27 0.06 18.50 -7 .27 0.000%
34 -3.68 -18.50 6.34 3.68 18.50 -6.34 0.000%
35 -6.40 -18.50 3.69 6.40 18.50 -3 69 0.000%
36 -7.33 -18.50 0.02 7.33 18.50 -0 02 0.000%
37 -6.33 -18 50 -3 59 6 33 18.50 3.59 0.000%
38 -3.65 -18.50 -6.24 3.65 18.50 6.24 0.000%
Non-Linear Convergence Results
Load Com•erged? Number Displacemenr Force
Combinarion o{Cycles Tolerance Tolerance
I Yes 4 0.00000001 0.00000001
2 Yes 4 0.00000001 0. 000063 72
3 Yes 5 0.00000001 0.00008898
4 Yes 5 0.00000001 0.00008939
5 Yes 4 0.00000001 0.00011863
6 Yes 5 0.00000001 0.00008585
7 Yes 5 0.00000001 0.00008279
8 Yes 4 0.00000001 0.00015253
RISATower Job Page
BU #806375 9 of 11
Crown Castle USA Inc. Project Date
2000 Corporate Dri,•e 15:37:37 12/17/09
Canonsburg, PA /53/7 Client Designed by Phone: (724) 4/6-21179 Crown Castle tstyran FAX: (724) 4/6-41179
9 Yes 5 0.00000001 0.00008899
10 Yes 5 0 0000000 I 0.00009005
II Yes 4 0.00000001 0.00009816
12 Yes 5 000000001 0.00008394
13 Yes 5 0.00000001 0 00008551
14 Yes 4 0.00000001 0.00000001
15 Yes 4 000000001 0 00013884
16 Yes 5 0.00000001 0.00021303
17 Yes 5 0.00000001 0.00021512
18 Yes 4 0.00000001 0.00016990
19 Yes 5 0.00000001 0.00020689
20 Yes 5 000000001 0.00019602
21 Yes 4 0.00000001 0.00029995
22 Yes 5 0.00000001 000021600
23 Yes 5 0.00000001 0.00021879
24 Yes 4 0.00000001 0.00021435
25 Yes 5 0.00000001 0.00019997
26 Yes 5 0.00000001 0.00020602
27 Yes 4 000000001 0.00001641
28 Yes 4 0.00000001 0 00032846
29 Yes 4 0.00000001 0.00033263
30 Yes 4 0.00000001 0.00001741
31 Yes 4 0.00000001 0.00031547
32 Yes 4 0.00000001 0.00029525
33 Yes 4 0.00000001 000002644
34 Yes 4 0.00000001 0.00033211
35 Yes 4 000000001 0.00033790
36 Yes 4 0.00000001 0.00002134
37 Yes 4 000000001 0.00030209
38 Yes 4 0.00000001 0.00031266
Maximum Tower Deflections -Service Wind
Section Ele,•ation Hon. Gov. Tilt Twist
No. Deflection load
t in Comb.
LI 110-70 22 497 35 I 8207 0.0009
L2 74 -34 0833 10.062 35 1.3303 0.0005
L3 39-0 2.708 35 0.6443 0.0002
Critical Deflections and Radius of Curvature -Service Wind
Elel'Otio11 Appurtenance Gov. Deflection Tilt Twist Radius of
load Curvature
t Comb. in I
108.00 (2) DB948F85T2E-M w/ Mount 35 21.751 1.7992 0.0009 18904
Pipe
97.00 (3) ALP 9212-N w/ Mount Pipe 35 17.696 1.6759 0.0007 7270
86.00 LLPXJ l OR w/ Mount Pipe 35 13.841 1.5318 0.0006 3937
82.00 A-ANT-180-2-C 35 12.522 1.4708 0.0006 3375
Maximum Tower Deflections -Design Wind
RISATower Job Page
BU #806375 10 of 11
Crow11 Castle USA foe. Project Date
2(}()() Corpora1e Drive 15:37 :37 12/17 /09
Canonsburg. PA /5317 Client Designed by Phone: (724) 4/6-ll/79 Crown Castle tstyran FAX: (724) 4/6-4l/79
Sec1io11 Elel'afio11 Hon. Gov. Tiff Twisf
No. Dejlec1io11 Load
ill Comb.
LI 110-70 57 415 10 4.6488 0.0032
L2 74 -34 0833 25.701 10 3.3984 0.0019
L3 39-0 6921 10 1.6466 0.0009
Critical Deflections and Radius of Curvature -Design Wind
Elel'afio11 Appur1e11a11ce Gov. Dejleclion Till Twisl Radius of
Load Curva1ure
I Comb. in {
108 00 (2) DB948F85T2E-M w/ Mount 10 55.513 4.5906 00031 7493
Pipe
97.00 (3) ALP 9212-w/ Mount Pipe 10 45.173 4.2614 0.0027 2880
86.00 LLPX3 I OR w/ Mount Pipe 10 35.341 3 8909 0.0023 1558
82 00 A-ANT-l8G-2-C 10 31.976 3.7390 0.0021 1335
Compression Checks
Pole Design Data
Sec1io11 Elevation Size L L. K/lr F. A Ac1ual Allow. Ra1io
No. p P, p
ft ft ft ksi j,rl K K P.
LI 110-70 (I) TP25.53x I 5.53x0.25 40.00 0.00 0.0 39.000 19.5454 -6.48 762.27 0.008
L2 70 -34.0833 (2) TP34.02x24.03x0.3125 39.92 0.00 00 39.000 32.6800 -1 1.20 1274.52 0.009
L3 34.0833 -0 (3) TP4 I .9x32.1645x0.3438 3900 0.00 0.0 38.914 45.9976 -18.49 1789.93 00IO
Pole Bending Design Data
Sec1io11 Elel'alio11 Size Aclllal Aclllal Allow. Ratio Actual Aclllal Allow. Ra1io
No. M, J,,, F,,, _A_ M, J., F., _b_ ft kip-fl ksi ksi F,,, kip-ft ksi ksi F.,
LI 110-70(1) TP25.53x I 5.53x0.25 306.86 31.814 39.000 0.816 0.00 0.000 39.000 0.000
L2 70-34.0833 TP34.02x24.03x0.3 I 25 792.48 36.71 2 39.000 0.941 0.00 0.000 39.000 0.000
(2)
L3 34.0833 -0 (3) TP4 I .9x32. I 645x0 3438 1460.97 37.529 38.914 0.964 0.00 0.000 38.914 0.000
Pole Shear Design Data
Sec1ion Elevation Size Actual Aclllal Allow. Ratio Actual Aclllal Allow. Ralio
No. V f. F. _L T f., F., __f::__
ft K ksi ksi F. kip-ft ksi ksi F,.
RISATower Job Page
BU #806375 11 of 11
Crown Castle USA Inc. Project Date
2000 Corporate Drive 15:37:37 12/17/09
Ca11011sburg, PA 15317 Client Designed by Phone: (724) 416-21179 Crown Castle tstyran FAX: (724) 4/6-41179
Section Elevatio11 Size Actual Actual Allow. Ratio Actual Actual Allow. Ratio
No. V f., F, _f:__ T f., F., ___£_
Ji K ksi ksi F, kip-Ji ksi ksi F.,
LI I 10-70(1) TP25.53x 15.53x0.25 12.36 0632 26.000 0.049 0.02 0.001 26.000 0.000
L2 70 -34.0833 TP34.02x24.03x0.3125 15.40 0.471 26.000 0.037 0.02 0.000 26.000 0.000
(2)
L3 34.0833 -0 (3) TP41 .9x32. I 645x0.3438 18 93 0.412 26.000 0.032 0.02 0000 26.000 0.000
Pole Interaction Design Data
Sectio11 Elevatio11 Ratio Ratio Ratio Ratio Ratio Comb. Allow. Criteria
No. p f.,, Ji,, f., f .. Stress Stress
Ji P. F., F,., F, F., Ratio Ratio
LI I 10-70(1) 0.008 0.816 0.000 0.049 0.000 0.825 1.333 Hl-3+VT v'° v"
L2 70-34 0833 0.009 0.941 0000 0.037 0.000 0.950 1.333 Hl-3+VT v'° (2) v"
L3 34.0833 -0 (3) 0.010 0.964 0000 0.032 0000 0.975 1.333 Hl-3+VT V v"
Section Capacity Table
Sectio11 Ele1•atio11 Compo11e11t Size Critical p SF•P.,.,. % Pass
No. Ji Type Element K K Capacity Fail
LI I 10-70 Pole TP25.53x I 5.53x0.25 I -6.48 1016.11 61.9 Pass
L2 70-34.0833 Pole TP34.02x24.03x0.3125 2 -11.20 1698.94 71.3 Pass
L3 34 0833 -0 Pole TP41.9x32.1645x0.3438 3 -18.49 2385.98 73.1 Pass
Summary
Pole (L3) 73.1 Pass
RATI G = 73.1 Pass
Program Version 5.3.1.0-10/3/2008 File://Ccicusphotosl/cad/SA Models -Letters/Work Area/Mac/806375/806375.eri
11 0 Ft Monopole Tower Structural Analysis
Project Number 308725, Application 91527, Revision 1
RISATower Report-version 5.3.1.0
APPENDIX B
BASE LEVEL DRAWING
December 17, 2009
CCI BU No 806375
Page 7
110 Ft Monopole Tower Structural Analysis
Project Number 308725, Application 91527, Revision 1
RISATower Report -version 5.3.1.0
APPENDIX C
ADDITIONAL CALCULATIONS
December 17, 2009
CCI BU No 806375
Page 8
FOUNDATION REACTION COMPARISON
REACTIONS
MOMENT (kip-ft)
SHEAR (kips)
BU #806375
WO#308725
DESIGN
REACTIONS
1,947.4
24.2
Design loads from: CClsites Doc #262106
CURRENT
REACTIONS
1,461.0
19.0
%CAPACITY
75.0%
78.5%
Although the shear capacity is at 82.6%, the moment reaction is the governing criteria for a monopole
drilled pier foundation. Therefore, the overall capacity for this foundation is 77.0%.
SITENAME · --. · r ·· ~, --· -:--·-■ I ,; ",·.,•j --~')'~\ :-,' J ECP-CELL # 8 I 37
LATITUDE ,_. ,.-·---, --·, ", •. ·;•~·..:--'< '; ., W GITUDE P:.:•.,r;· ---\{": -~:~ '·-~-C• ... _.,
Ac:l,1itional Comments: Remove Center mounted 850 antenna and Add 3 700 SAVEBUTfO • ;'_ •-<~~i.:\ ::.•.:, 1·· ~~-· ~r _,;\' .A•~ ,,
Antennas and 3 Cables. STRUCTURE TYPE ~i~t-._.,.,..,
700 Mhz -L TE ANTENNA ADD ALPHA BETA GAMMA
EQUIPMENT TYPE eNodeB eNodeB eNodeB
ANTENNA TYPE BXA-70063-6CF-2-750MHZ BXA-70063-6CF-6-750MHZ BXA-70063-6CF-6-750MHZ
QTY OF ANTENNAS PER FACE 1 1 1
ORIENTATION (DEG) 0 150 270
DOW TILT (MECH/DEG) 2 3 3
RAD CTR (Ff AGL) 111 111 111
TMA -QTY / MODEL I I
DIPLEXER -QTY/ MODEL I I
IMCP A BRICKS (QTY)
850 Celluar -Current Config ALPHA BETA -GAMMA
EQUIPMENT TYPE Modcell 4.0 HD Modcell 4.0 HD Modcell 4.0 HD
ANTENNA TYPE DB844F90A-SX_0 DB844F90A-SX_0 DB844F90A-SX_0
QTYOFANTE ASPER FACE 2 2 2
ORIENTATION (DEG) 0 150 270
DOWN TILT (MECH/DEG) 0 0 0
RAD CTR (Ff AGL) 111 111 111
IMA-QTY/ MODEL I I
DIPLEXER -QTY/ MODEL I I
MCP A BRICKS (QTY)
850 Celluar -Future Config ALPHA BETA GAMMA
EQUIPMENT TYPE Modcell 4.0 HD Modcell 4.0 HD Modcell 4.0 HD
ANTENNA TYPE LPA-80080/4CF LP A-80080/4CF LP A-80063/4CF
QTYOF TE ASPER FACE 2 2 2
ORJENT ATlON (DEG) 0 150 270
DOW TILT (MECH/DEG) 2 2 3
RAD CTR (FT AGL) 111 111 111
TMA -QTY/ MODEL I I
DIPLEXER -QTY/ MODEL I I
MCPA BRICKS (QTY)
1900 Cellular -Current Config ALPHA I BETA GAMMA -
EQUIPMENT TYPE PCS Modcell 4.0 PCS Modcell 4.0 PCS Modcell 4.0
ANTENNA TYPE 948F85T2E-M_2 948F85T2E-M_2 948F85T2E-M_2
QTY OF ANTENNAS PER FACE ~ 2 2 2
ORIENTATIO (DEG) -· 0 150 270
DOWN TILT (MECH/DEG) 0 0 0
RAD CTR (Ff AGL) 111 111 111
TMA -QTY/ MODEL I I
DIPLEXER -QTY/ MODEL I I
MCPA BRICKS (QTY)
1900 Cellular -Future Config ALPHA BETA GAMMA
EQUIPMENT TYPE PCS Modcell 4.0 PCS Modcell 4.0 PCS Modcell 4.0
ANTENNA TYPE 948F85T2E-M_2 948F85T2E-M_2 948F85T2E-M_2
QTY OF ANTENNAS PER FACE 2 2 2
ORJE TATIO (DEG) 0 150 270
DOWN TILT (MECH/DEG) 0 0 0
RAD CTR (Ff AGL) 111 111 111
IMA -QTY/ MODEL I I
rr cROWN
\._,/._,CASTLE
October 4, 2021
Melanie A. Bachman
Executive Director
Connecticut Siting Council
IO Franklin Square
ew Britain, CT 06051
11 Cityplace Dr, Suite 490
I Creve Coeur. MO 63141
RE: Notice of Exempt Modification for Verizon
Crown Site ID# 806375, Verizon Site ID#468317
190 BURNHAM ST, South Windsor, CT. 06074
Latitude: 41° 48' 0.49"/ Longitude: -72° 36' 57.15"
Dear Ms. Bachman:
Phone: (31 4) 513-0147
www.crowncastle.com
Verizon currently maintains six (6) antennas at the 109-foot mount and nine (9) antennas at the
108-foot mount on the existing 110-foot Monopole Tower located at. The property is owned by 190
Burnham LLC and the Tower by Crown Castle. Verizon now intends to replace nine (9) existing
antennas and add nine (9) antennas. This modification/proposal includes hardware that is both 4G(L TE)
and 5G capable through remote software configuration and either or both services may be turned on or off
at various times.
Planned Modifications:
Tower:
REMOVE AND REPLACE
(3) Kathrein -742213 Antennas (REMOVE), (3) Samsung -MT6407-77A Antennas (REPLACE)
(3) Kathrein -742213 Antennas (REMOVE) (3) Commscope -NHH-65B-R2B Antennas (REPLACE)
(2) Andrew -LNX65 I 4DSAIM Antennas (REMOVE) (2) Commscope -NHHSS-65B-R2B Antennas
(REPLACE)
(l) CSS -X7C-FRO-660-V-06 Antenna (REMOVE), (1) Commscope -NHHSS-65B-R2B Antenna
(REPLACE)
(I) OVP Box -RFS-DB-Bl-6C12AB-OZ (REMOVE), (l) OVP Box -RAYCAP -RVZDC-6627-PF-48
(REPLACE)
(3) Nokia UHBB B 13 Remote Radio heads (REMOVE) (3) Samsung -RFVO 1 U-D2A Remote Radio
Heads (REPLACE)
(3) okia UNHID B4 Remote Radio heads (REMOVE) (3) Samsung -RFV0l U-DlA Remote Radio
Heads (REPLACE)
Th Foundation or a Wlr I World.
CrownC ti .com
1
Exhibit A
Original Facility Approval
DOCKET NO. 137 -An application of Metro Mobile Connecticut
CTS of Hartford, Inc., for a Certificate of
Environmental Compatibility and Public Need Siting
for the construction, maintenance, and
operation of cellular facilities in the Towns Council
of East Hartford, South Windsor, and Windsor,
Connecticut. November 14, 1990
Decision and Order
Pursuant to the foregoing Findings of Fact and Opinion, the
Connecticut Siting Council finds that the effects associated
with the construction, operation, and maintenance of two
cellular telecommunications towers and associated equipment at
t he proposed Windsor and alternate South Windsor sites
including effects on the natural environment; ecological
integrity and balance; public health and safety; scenic,
historic, and recreational values; forests and parks; air and
water purity; and fish and wildlife need not be in conflict
either alone or cumulatively with other effects, are not in
conflict with the policies of the State concerning such
effects, and are not sufficient reason to deny the application,
and therefore directs that a Certificate of Environmental
Compatability and Public Need (Certificate), as provided by
section 16-50k of the Connecticut General Statutes (CGS), be
issued to Metro Mobile CTS of Hartford, Inc., for the
construction, operation, and maintenance of a cellular
telecommunications tower, associated equipment, and building at
the proposed Windsor site and alternate South Windsor site.
The facilities shall be constructed, operated, and maintained
substantially as specified in the Council's record in this
matter, and subject to the following conditions:
1. The facilities shall be constructed in accordance with
the State of Connecticut Basic Building Code.
2. The self-supporting monopole towers shall be no taller
than necessary to provide the proposed communication
service and in no event shall the towers exceed a total
height of 123 feet above ground level (AGL) at the
alternate South Windsor site and 113 feet AGL at the
proposed Windsor site, with antennas and appurtenances.
3. The Certificate holder shall prepare a Development and
Management (D&M) Plan, for approval by the Council, for
these sites in compliance with sections 16-S0j-75
through 16-50j-77 of the Regulations of State Agencies.
The D&M plan shall include detailed plans of the towers,
tower foundations, soil boring reports, equipment
buildings, access roads, security fences, erosion and
sedimentation control plans consistent with the
Connecticut Guidelines of Soil Erosion and Sedimentation
Control, and landscaping plans.
Docket 137
Decision & Order
Page 2
At the alternate South Windsor site the applicant shall
relocate the tower on the eastern half the leased parcel to
reduce the amount of properties within the fall zone.
All pine trees bordering the alternate South Windsor site
shall be flagged and protected from removal during site
construction.
At the proposed Windsor site the applicant shall plant
additional shrubs and trees along the border of the leased
parcel facing the playing fields.
4. The Certificate Holder shall comply with any existing and
future radio frequency (RF) standard promulgated by State
or federal regulatory agencies. Upon the establishment of
any new governmental RF standards, the facilities granted
in this Decision and Order shall be brought into compliance
with such standards.
5. The Certificate Holder shall provide the Council a
recalculated report of electromagnetic radio frequency
power density if and when circumstances in operation cause
a change in power densities above the levels originally
calculated and provided in the application.
6. The Certificate Holder shall permit public or private
entities to share space on the proposed towers for fair
consideration, or shall provide any requesting entity with
specific legal, technical, environmental, or economic
reasons precluding such tower sharing.
7. If the facilities do not initially provide, or permanently
cease to provide cellular service following completion of
construction, this Decision and Order shall be void, and
the tower(s) and all associated equipment shall be
dismantled and removed or reapplication for any new use
shall be made to the Council before any such new use is
made.
8. Unless otherwise approved by the Council, this Decision and
Order shall be void if all construction authorized herein
is not completed within three years of the effective date
of this Decision and Order or within three years after all
appeals to this Decision and Order have been resolved.
Pursuant to Section 16-S0p, we hereby direct that a copy of
the Findings of Fact, Opinion, and Decision and Order be
served on each person listed below, and notice of issuance
shall be published in the Hartford Courant and Journal
Inquirer.
Docket 137
Decision & Order
Page 3
By this Decision and Order, the Council disposes of the
legal rights, duties, and privileges of each party named or
admitted to the proceeding in accordance with section
16-50j-17 of the Regulations of State Agencies.
The parties to this proceeding are:
(PARTIES)
Metro Mobile CTS of
Hartford, Inc.
20 Alexander Drive
P.O. Box 5029
Wallingford, CT. 06492
Attn: Gary Schulman
Town of East Hartford
(INTEVENORS)
Town of South Windsor
SNET Cellular, Inc.
4854E
(ITS REPRESENTATIVES)
Robinson & Cole
One Commercial Plaza
Hartford, CT. 06103 -3597
Attn: Earl W. Phillips
Mr. G. Barry Goodberg
Asst. Corp. Counsel
Town of East Hartford
740 Main Street
East Hartford, CT. 06108
(ITS REPRESENTATIVES)
Jean E. zurbrigen
Town Manager
Town of South Windsor
1540 Sullivan Avenue
South Windsor, CT. 06074
Peter J. Tyrrell, Esq.
SNET Cellular, Inc.
227 Church Street
New Haven, CT 06506
Exhibit B
Property Card