HomeMy WebLinkAbout19 Cody Circle (2)DEPARTMENT DECISION APPLICATION FOR HVAC PERMIT
TOWN OF SOUTH WINDSOR PERMIT#
Application is hereby:
BUILDING DEPARTMENT
APPROVE 1540 SULLIVAN AVENUE Bldg.Permit#
A 644-2511 ext. 230
Date Building Inspector
Application must be printed or typed
FEE SCHEDULE Location of Job:
e re e
0-$1,000=$W,80/-5- Street No. Street Lot No.
Over$1,000=
per$1,000
or any fraction thereof Tenant Designation Apt.No.
APPLICANT P
APPLICANT ADDRESS 76/ 0 r-
d------ Z6,; a 5-or- r,-7--' e 6 ef"7
APPLICANT PHONE#
W N S OWNER //7,4`7 dl/- Y Q c
Ns
q OWNER ADDRESS 167ore7
N. E., OWNER PHONE i
pCESTIMATEDCOST$
U
IS THIS A CONTRACT COST? &Yes 0 No
f Q C FEE ENCLOSED$ (n Ca
F
O TYPE OF JOB:
OR•C
New Installation
Iteration/Addition/Repair Revised 8/99
3
APPLICATION FOR HVAC PERMIT (Continued from reverse side
TYPE OF SYSTEM: TYPE OF BUILDING: 4
HEATING 21-RESIDENTIAL 7,/ G1,
M.A/C COMMERCIAL
VENTILATION INDUSTRIAL
HEATING
STEAM LOW PRESSURE LIMIT LBS. HIGH PRESSURE LIMIT LBS.
HYDRONIC WARM AIR UNIT RADIANT HEATER
EXISTING RADIATION ADDITIONAL RADIATION TOTAL RADIATION
DESIGN TEMP. OUTSIDE OF INSIDE OF DIFFERENCE OF
TOTAL HEAT LOSS(BTUH) OF(HEAT LOSS SHEET MUST ACCOMPANY
APPLICATION)
DESCRIBE ALL HEATING EQUIPMENT(INCLUDING MAKE&MODEL NO.)
GROSS HEATING CAPACITY(INPUT-BTUH) NET RATING(OUTPUT BTUH)
TYPE OF FUEL
OIL-GPM OIL TANK LOCATION:INSIDE OUTSIDE CAPACITY
GAS-INPUT LPG TANK CAPACITY ELECTRIC-KW
AIR CONDITIONING
DESIGN TEMP.OUTSIDE °F INSIDE`F DIFFERENCE Z"O OF
TOTAL HEAT GAIN(BTUH)V5,2- (HEAT GAIN SHEET MUST ACCOMPANY APPLICATION)
DESCRIBE ALL COOLING EQUIPMENT(INCLUDING MAKE&MODEL NO.)
7Aa o / Z. /,
TONNAGE f COOLING CAPACITY(BTUH)_Z; g
VENTILATIONDESCRIBE ALL AIR HANDLING EQUIPMENT(INCLUDING KITCHEN EXHAUST EQUIPMENT)
TOTAL SIZE OF SYSTEM(CFM) FRESH AIR INTAKE(CFM)
PLANS MUST ACCOMPANY APPLICATION)
FURTHER DESCRIPTION OF WORK
THE UNDERSIGNED HEREBY APPLIES FOR A PERMIT TO PERFORM THE WORK DESCRIBED AND IS TOCOMPLYWITHALLLOCALORDINANCESANDSTATEOFCONNECTICUTBUILDINGCODESINTHE
PERFORMANCE OF SUCH WORK.
jej y l
CONTRACTORS LICENSE NO. STATE
SIGNATURE OF APPLICANT - i- DA L 3 Z
i
BEAULIEU
HVAC LOAD ANALYSIS
for
RHVACCOMbtERCU11,WAC LOAM
Prepared By:
Stephen P.Smith
Advanced Heating&AC Inc.
701 Nutmeg Rd.North
So.Windsor,Ct.08074
860)282-0205
0SQ3J02
Project: Beaulieu Company: Advanced Heating&AC Inc.
Client: Matt and Cindy Beaulieu Representative: Stephen P. Smith
Addr ss: 19 Cody Circle Address: 701 Nutmeg Rd. North
City: So. Windsor, Ct. 06074 City: So. Windsor, Ct. 06074
Phone: Phone:860)282-0205
Fax: Fax: 860)528-2949
Comment:
Project Nam Beaulieu
Reference City: Hartford, Connecticut
Daily Temperature Range: Medium
Latitude: 41 Degrees
El vation: 19 Feet
Elevation Sensible Adj. Factor 1.000
Elevation Total Adj. Factor 1.000
Outdoor Outdoor Indoor Indoor Grains
Bulb We Bulb Rel.Hum. Dry Bulb Difference
Winter: 7 N/A N/A 72 N/A
Summer: 95 73 50% 75 22
Total Building Supply CFM: 313 CFM per square foot:0.92
Square feet of room area: 340 Square feet per ton: 456.761
Total heating required with outside air: 13,516 Btuh 13.516 MBH
Total sensibl gain: 6,878 Btuh 94 %
Total latent gain: 407 Btuh 6 %
Total cooling required with outside air: 7,285 Btuh 0.607 Tons(based on sensible+latent)
0.744 Tons(based on 77%sensible capacity)
Calculations are based on 7th edition of ACCA Manual J.
All computed results are estimates as building use and weather may vary.Be sure to select a unit that meets both sensible and latent loads.
Tuesday,May 21,2002
Component Area Sen. Lat. Sen. Total
Description Quan Loss Gain Gain Gain
3C Window Double Pane Clear Glass Metal Frame 74 3,488 0 3,878 3,878
12H Wall R-19+ 1/2"Gypsum Board(R-0.5) 538 2,098 0 762 762
16G Ceiling R-30 Insulation 340 729 0 494 494
19D Floor Over Basement/Encl Crawl Hardwood+ R-19 340 575 0 0 0
Subtotals for structure: 1,292 6,890 0 5,134 5,134
Active People: 0 0 0 0 0
Inactiv People: 0 0 0 0 0
Appliances:0 0 0 0 0
Lighting: 0 0 0
Ductwork: 0 2,253 0 1,146 1,146
Infiltration: Winter CFM:61.2, Summer CFM: 27.2 74 4,373 407 598 1,005
Ventilation: Winter CFM: 0.0, Summer CFM: 0.0 0 0 0 0 0
Sensible Gain Total: 6,878
Temperature Swing Multiplier:X1.00
Building Load Totals: 13,516 407 6,878 7,285
Total Building Supply CFM: 313 CFM per square foot:0.92
Square feet of room area: 340 Square feet per ton: 456.761
Total h ating required with outside air: 13,516 Btuh 13.516 MBH
Total sensible gain: 6,878 Btuh 94 %
Total latent gain: 407 Btuh 6 %
Total cooling required with outside air:7,285 Btuh 0.607 Tons(based on sensible+latent)
0.744 Tons(based on 77%sensible capacity)
Calculations are based on 7th edition of ACCA Manual J.
All computed results are estimates as building use and weather may vary.
B sur to select a unit that meets both sensible and latent loads.
Tuesday,May21,2002
s
Room Length: 20.0 Feet System Number: 1
Room Width: 17.0 Feet Zone Number 1
Area: 340.0 Square Feet Supply Air: 313 CFM
C iling H ight: 12.0 Feet Required Vent.Air:0 CFM
Volume: 4,080.0 Cubic Feet Actual Winter Ventilation Air. 0 CFM
Number of R gisters: 3 of Supply:0 %
Runout Air 104 CFM Actual Summer Ventilation Air 0 CFM
Runout Duct Size: 6 Inches of Supply:0 %
Runout Air Velocity: 531 Feet/Minute Actual Winter Infiltration Air: 61 CFM alloc.
Design Loss: 0.100 In.wg/100 Ft. Actual Summer Infiltration Air 27 CFM allot.
Actual Loss: 0.181 In.wg/100 Ft.
Item Area U- Htg Sen.Clg Latent Sen.
D scription Quantity Value HTM Loss HTM Gain Gain
W-WALL-121-1 20 X 9 168 0.060 3.9 655 1.4 0 238
E-WALL-121-1 20 X 9 158 0.060 3.9 616 1.4 0 224
S-WALL-121-1 17 X 12 170 0.060 3.9 663 1.4 0 241
N-WALL-12H 4 X 12 42 0.060 3.9 164 1.4 0 59
W-GLAS-3C 2-P 0-0 S-1 0%S 12 0.725 47.1 566 72.0 0 864
E-GLAS-3C 2-P 0-0 S-1 0%S 22 0.725 47.1 1,037 72.0 0 1,584
S-GLAS-3C 2-P 0-0 S-1 0%S 34 0.725 47.1 1,602 38.0 0 1,292
N-GLAS-3C 2-P 0-0 S-1 100%S 6 0.725 47.1 283 23.0 0 138
UP-CEIL-16G DARK 20 X 17 340 0.033 2.1 729 1.5 0 494
FLOOR-19D 17 X 20 340 0.052 1.7 575 0.0 0 0
Subtotals for structure: 1,292 6890 0 5134
Infiltration: Winter. 61.2, Summer: 27.2: 74 59.095 4,373 8.081 407 598
Ductwork: 0.200 2253 0.200 0 1146
Active People: 230 lat/per, 300 sen/per 0 0 0
Inactiv People: 150 lat/per, 250 sen/per 0 0 0
Appliances: 0 0
Lighting: 0
S nsibl Gain Total: 6878
Temperature Swing Multiplier X1 00
Room Totals: 13,516 407 6,878
Tuesday,May 21,2002
i
i
Htg Htg Run Run Clg Cig Clg Zone Clg Air
Room Area Sens Nom Duct Duct Sens Lat Nom Adj Adj Sys
No Name SF Btuh CFM Size Vel Btuh Btuh CFM Fact CFM CFM_
Zone 1-
1 New Family 340 13,516 176 3-6 531 6,878 407 313 1.17 365 313
Room
System 1 Totals 340 13,516 176 6,878 407 313 365 313
Main Trunk Size: W in.
1 i
I
f
Cooling Sensible/Latent Sensible Latent Total
Tons Split Btuh Btuh Btuh
Net Required:0.607 94%/6% 6,878 407 7,285
Recommended: 0.744 77%/23%6,878 2,054 8,932