Loading...
HomeMy WebLinkAbout1735 Ellington Road (12)October 2, 2002 Mr. John Collins Chief Building Official Town of South Windsor 1540 Sullivan AveW A South Windsor, CT 06074 w aRE: Town Center Plaza Retail rSouthWindsv o , TC AG O w Mr. Collins: F z In response to your comments from the permit meeting with Rob Forsyth of Bartlett, Brainard, and Eacott, I submit the following: z z 1. The cover sheet shall be revised to indicate a building construction d classification of 5A in lieu of 2C as shown. This was a typographical error on a the drawing that will be corrected. 2. The drawings shall be modified to indicate a single layer of 5/8"FC GWB to w be applied on wood furring to the underside of the wood trusses. 3. By copy of this letter, BB&E is to direct the Sprinkler sub-contractor to prepare F.,his design layout to provide coverage above and below the ceiling as well as above the layer of GWB added to the underside of the trusses. His design a 0 layout shall be forwarded to you and/or the Fire Official for final review and x comment. U d I understand that by receipt of this letter a building permit shall be issued. I will forward a copy of the corrected plans as soon as possible for your files. If you have any questions or concerns, please do not hesitate to contact our office. Sincerel David A. Campbe I, RA Associate/Senior Architect cc: Rob Forsyth, BB&E D OCT 4 2002 South Windsor 389 MAIN sIxEET BUILDING DEPARTMENT 2nd FLOOR SAT FM,N.H. 03079 TEL: (603)890-6414 FAX: (603)894-4358 RICHARD E.LANDRY,AIA