HomeMy WebLinkAbout154 Commerce Way (2)DEPARTMENT DECISION APPLICATION FOR HVAC PERMIT PERMIT#
Application is hereby:TOWN OF SOUTH WINDSOR s 0BUILDINGDEPARTMENT
APPROVED 1540 SULLIVAN AVENUE Bldg.Permit#
b O, j A0, 644-2511 ext. 230
Date Building Inspector
Application must be printed or typed
FEE SCHEDULE Location of Job:
epmm-e,-r< kvi-7-1 I
0-$1,000=$15.00 Street No. Street Lot No.
Over$1,000=
15.00 per$1,000 1"v .Sh d,
or any fraction thereof Tenant Designation Apt.No.
E
APPLICANTS-Fe ke,
APPLICANT ADDRESS 13 o '3
APPLICANT PHONE#P 3 z0 L(2-
o* N S OWNER L t L LL
s
OWNER ADDRESS l C-''+A,z{ I G-
Sow w'Lw,V;
cc) - *OWNER PHONE
C ESTIMATED COST$
IS THIS A CONTRACT COST? Yes No
f FEE ENCLOSED$(jZ2
TYPE OF JOB:
OR-C New Installation
i
Iteration/Addition/Repair
Revised 410IH2002
APPLICATION FOR HVAC PERMIT (Continued from reverse side)
TYPE OF SYSTEM: TYPE OF BUILDING:
EATING RESIDENTIAL
r/C COMMERCIAL
VENTILATION d4dDUSTRIAL
HEATING
STEAM LOW PRESSURE LIMIT LBS. HIGH PRESSURE LIMIT LBS.
HYDRONIC WARM AIR UNIT RADIANT HEATER
EXISTING RADIATION ADDITIONAL RADIATION TOTAL RADIATION
DESIGN TEMP. OUTSIDE OF INSIDE OF DIFFERENCE OF
TOTAL HEAT LOSS(BTUH) OF(HEAT LOSS SHEET MUST ACCOMPANY
APPLICATION)
ESCRIBE
g I
ALL HEATIfN G EQUIPMS LAENTNT(INCLUDING MAKE&MODEL NO.)
GROSS HEATING CAPACITY(INPUT BTUH)300 00) NET RATING(OUTPUT—BTUH)Z O G"
TYPE OF FUEL
OIL—GPM OIL TANK LOCATION:INSIDE OUTSIDE CAPACITY
L°TTAS—INPUT LPG TANK CAPACITY ELECTRIC—KW
AIR CONDITIONING Q
DESIGN TEMP.OUTSIDE -! OF INSIDE -7 f OF DIFFERENCE `Z OF
TOTAL HEAT GAIN(BTUH) HEAT GAIN SHEET MUST ACCOMPANY APPLICATION)
DESCRI$E ALL COOLING EQUIPMENT(INCLUDING MAKE&MODEL NO.)
TONNAGE 2 1 S COOLING CAPACITY(BTUH)
VENTILATION
DESCRIBE ALL AIR HANDLING EQUIPMENT(INCLUDING KITCHEN EXHAUS EQUIPMENT)
TOTAL SIZE OF SYSTEM(CFM)6t00 FRESH AIR INTAKE(CFM) lOIJ
PLANS MUST ACCOMPANY APPLICATION)
FURTHER DESCRIPTION OF WORK
THE UNDERSIGNED HEREBY APPLIES FOR A PERMIT TO PERFORM THE WORK DESCRIBED AND IS TO
COMPLY WITH ALL LOCAL ORDINANCES AND STATE OF CONNECTICUT BUILDING CODES IN THE
PERFORMANCE OF SUCH WORK.
5D3 Z(-) S- I c f
CONTRACTORS LICENSE N TYPE STATE
SIGNATURE OF APPLICANT DATE
S/N: RNW2 0 4 3 8 LOAD BREAKDOWNS
Units: U.S. customary (I-P) Jun 05, 2003
For:6-0 L I r,lL L L
By:1 O rh W n-o SJ-- i
Job#: machine shop
Component I Btuh/Btuh o of Heating
ft2 Btuh
Walls 4 .4 29146 10.0
Windows 0.0 0 0. 0
Doors 17.7 5 018 1 1 .71 woos Other
Ceilings 6. 4 64000 21. 9
Floors I 0. 6 I 5702 I 2.0 I Humidification
Partitions 0.0100.0
Infiltration 14 .1 * 1406980 480.2 Ceilings_
Ducts 0.0* 0 0.0IHumidification14 .7*I 47122116.21
Ventilation 0.0* 0 0.0
Totals 2 9.2* 291685 100
Infiltration
Calculated per ft2 of floor area
F
Component I Btuh/Sens. I o of Cooling
ft2 Btuh Btuh
Walls 1 .7 10959 4 . 9
Windows 0.0 0 0.0
Doors 5.5 1568 0.7 Walls, Other
Ceilings 8 . 0 79550 35.4
l
Floors 1 0. 0 1 01 0. 01 y,
Partitions 0. 0 0 0.0IInfiltrationI2. 9* 29312 1 13. 1 I Ceilings
Ducts 0.0* 0 0.0 Internal Gains
Internal Gainsl 9. 9*I 98800I44 . 1
Ventilation 0.4 * 4397 2.0
Totals 2 2.5* 224586 100
Infiltration
Calculated per ft2 of floor area
Manual N: 4th Edition Right-N: Ver.3.0.07
Certified by ACCA to meet all requirements of Manual Form N
i
SIN RNW2 0 4 3 8 RIGHT-N SHORT FORM Jun 05, 2003
Un'its:U.S. customary (I-P)
Job #:
Htg Clg
For: Outside db 6 95
Inside db 70 75
Design TD 64 20
Daily Range 20 y
Inside Humid. 50
By: Moist. Diff. 16
Inside wb 63
Outside RH 33
Outside wb 72 r
HEATING EQUIPMENT COOLING EQUIPMENT v
Make n/a Make n/a
Model n/a Model n/a
Type n/a Type n/a
Efficiency/HSPF 0.0 COP/EER/SEER 0. 0
Heating Input 0.0 MBtuh Sensible Cooling 0. 0 MBtuh
Heating Output 0.0 MBtuh Latent Cooling 0. 0 MBtuh
Humidifier 0.0 gpd Total Cooling 0. 0 MBtuh
Leaving Air Temp 0.0 OF Leaving Air Temp 0. 0 OF
Actual Heating Fan 0 cfm Actual Cooling Fan 0 cfm
Equipment Location ZONE
System Type n/a
Fan Motor Heat Type n/a
Fan&Motor Combined Efficiency 0.0 %
Static Pressure Across Fan 0.0 in H2O
NAME Area Heat Sensible Latent Htg Clg Time
f t z Loss Gain Gain cfm cfm
Goltech 11c.10000 291685 224586 18783 10016 10016 3PM
machine shop 10000 291685 224586 18783 10016 10016 3PM
F
r
J`
J'
r
I ,h
Manual N: 4th Edition Right-N: Ver.3.0.07
Certified by ACCA to meet all requirements of Manual Form N
r4
P 1:.
SIN RNW2 0 4 3 8 RIGHT-N TIME-OF-DAY SHORT FORM-LOADS Jun 05, 2003
Units:U.S. customary (I-P)
Job#:
For:
By:
Peak Time of Day: n/a Equipment located in ZONE
Name Sensible Gain at Latent Heating9AMNOON3PM6PMGainBtuh
Goltech 11c. 147829 205098 224586 188936 18783 291685 ti
machine shop 147829 205098 224586 188936 18783 291685
r
y
a.
a
Manual N: 4th Edition Right-N: Ver.3.0.07
Certified by ACCA to meet all requirements of Manual Form N
SIN RNW 2 0 4 3 8 RIGHT-N TIME-OF-DAY SHORT FORM,CFMS Jun 05, 2003Units:U.S. customary (I-P)
Job#:
For:t
By:
Peak Time of Day: n/a Equipment located in ZONE
Name Cooling estimated cfm at Actual Heating9AMNOON3PM6PMClgcfmcfm
Goltech 11c. 6673 9177 10016 8438 10016 10016
machine shop 6673 9177 10016 8438 10016 10016
w
r
Manual N: 4th Edition Right-N: Ver.3.0.07
Certified by ACCA to meet all requirements of Manual Form N
r ,
0
P
Job#: Page: 2
7. SUPPLY DUCT HEAT GAIN
Gain factor 0.00 x Line 6 Sensible Gain 0
8. COOLING FAN SIZING
Sum of Duct Gain 7 ), Line (6 ) & Drawthru Fan 220189
L 8 Sens ) / ( 1 .1 x Supply TD ) = cfm
Est Cooling cfm = ( 2 2 018 9) / ( 1 . 1 x 20.0 ) = 10 016 i
Actual Cooling Fan 10 016
9. VENTILATION
2 0 0 c fm x db Temp Diff 20.0 x 1.1 4397
x Moist. Diff 16.3 x 0.68 2 215
10. RETURN AIR LOAD FROM LIGHTING AND ROOF
Incandescent Lights 0 Watts x 3.4 x 40% 0
Fluorescent Lights 0 x 4 .1 x 40% 0
RA Roof Load from Line 3 H 0
RA Ceiling Load Credit from Line 3 (-) 0
P
11. RETURN DUCT HEAT GAIN
Gain factor 0.00 x Line 6 Sensible Gain 0
12. TOTAL COOLING LOADS ON EQUIPMENT(Btuh) 224586 18783
SPACE HEATING LOAD CALCULATION
13. HEATING DESIGN TEMPERATURE
Heating TD = (Inside DB -Outside DB) 70 - 6) = 64
Mult = 1 . 0 ]-
14. TRANSMISSION LOSSES
Type Expos GrArea NetArea Uval HTD Loss
WALL 1 s 2500 2500 0.069 64 .0 11040
WALL 2 n 2500 2500 0.069 64 .0 11040
WALL 3 w 1600 1600 0.069 64 .0 7066
DOOR 1 s 140 140 0.560 64 .0 5018
DOOR 2 s 24 24 0.560 0.0 0
DOOR 3 s 120 120 0.560 0.0 0
FLOR 1 - 330 330 0.270 64 .0 5702
ROOF 1 - 10000 10000 0.100 64 .0 64000
t
15. INFILTRATION Loss
2000 cfm x db Temp Diff 64 .0 x 1 .1 140698
16. SUBTOTAL HEATING LOAD FOR SPACE 244564
17. SUPPLY DUCT HEAT LOSS
Loss factor 0.00 x Line 16 Loss 0
18. VENTILATION
0 cfm x db Temp Diff 6 4 .0 x 1 . 1 0
r
Manual N: 4th Edition Right-N: Ver.3.0.07
Certified by ACCA to meet all requirements of Manual Form N
Job#: Page: 3
19.• HUMIDIFICATION
Inside RH desired 3 4 .6 (Max = 14 .0 for 1 pane )of Glazing panes 0.0 (Max = 34 . 6 for 2 pane )
2000 cfm x 6.35 g/100cfm/d 127 gpd 47122 Y;
r
20. RETURN DUCT HEAT LOSS
Loss factor 0.00 x Line 16 Loss 0
21. TOTAL HEATING LOAD ON EQUPMENT(Btuh) 291685
t
a
Manual N: 4th Edition Right-N: Ver.3.0.07
Certified by ACCA to meet all requirements of Manual Form N r.:
SIN RNW2 0 4 3 8 RIGHT-N ZONE SUMMARY
Units: U.S. customary (I-P) Jun 05, 2003
For:
By:
Job#: Zone: Goltech llc.
COOLING LOAD
1. DESIGN CONDITIONS at 3 PM Peak load at 3 PM
Inside: 75 OF Outside: 95 OF TD:20 OF.
RE 50 % Moisture: 16 gr/lb Mult: 1.0 Ins.wb 63 °F
Sensible Latent
2. SOLAR RADIATION THROUGH GLASS 0
3. TRANSMISSION GAINS Sensible 92077
Walls: 10959
Glass: 0
Doors: 1568
Partitions: 0
Floors: 0
Roofs/Ceilings:79550
Return Air Ceiling: 0
4. INTERNAL HEAT GAIN Sensible Latent 98800 1800
Occupants:1800 1800
Lights: 8200 0
Motors: 88800 0
Appliances &Other: 0 0
5. INFILTRATION: Outside air cfm: 1333 29312 14768
6. SUBTOTAL: Space load 220189 16568
7. SUPPLY DUCT 0
8. SUBTOTAL: Bldg comp's and supply duct 220189
Actual cfm: 10016 at Supply TD:20
9. VENTILATION: Make-up air cfm: 200 4397 2215
10. RETURN AIR LOAD: Lighting&roof(net) 0
11. RETURN DUCT 0
12. TOTAL LOADS ON EQUIPMENT 224586 18783 1
HEATING LOAD
13. DESIGN CONDITIONS Mult: 1.0
Inside: 70 OF Outside: 6 °F TD:64 OF
14. TRANSMISSION LOSSES 103866
Walls: 29146
Glass: 0
Doors: 5 018
Partitions: 0
Floors: 5702 r
Roofs/Ceilings:64000
Return Air Roof: 0
15. INFILTRATION:Outside air cfm: 2000 140698
16. SUBTOTAL: Building components 244564
17. SUPPLY DUCT: 0
18. VENTILATION: Make-up air cfm:0 0
19. HUMIDIFICATION 47122
20. RETURN DUCT 0
21. TOTAL HEATING LOAD ON EQUIPMENT 291685
Manual N: 4th Edition Right-N: Ver.3.0.07
Certified by ACCA to meet all requirements of Manual Form N
f
w
SIN RNW2 0 4 3 8 RIGHT-N ZONE SUMMARY
Units: U.S. customary (I-P) Jun 05, 2003 a
For:
By:
Job#: Zone: machine shop
Y
1
COOLING LOAD
1. DESIGN CONDITIONS at 3 PM Peak load at 3 PM
Inside: 75 OF Outside: 95 OF TD:20 OF
RH:50 % Moisture: 16 gr/lb Mult: 1 .0 Ins.wb 63 °F
Sensible Latent
2. SOLAR RADIATION THROUGH GLASS 0
3. TRANSMISSION GAINS Sensible 92077
Walls: 10959
Glass: 0
Doors: 1568
Partitions: 0
Floors: 0
Roofs/Ceilings:79550
Return Air Ceiling: 0
4. INTERNAL HEAT GAIN Sensible Latent 98800 1800
Occupants:1800 1800
Lights: 8200 0
Motors: 88800 0
Appliances &Other: 0 0
5. INFILTRATION: Outside air cfm: 1333 29312 14768
6. SUBTOTAL: Space load 220189 16568
7. SUPPLY DUCT 0
8. SUBTOTAL: Bldg comp's and supply duct 220189
Actual cfm: 10016 at Supply TD:20 f
9. VENTILATION: Make-up air cfm: 200 4397 2215
10. RETURN AIR LOAD: Lighting&roof(net) 0
11. RETURN DUCT 0
12. TOTAL LOADS ON EQUIPMENT 224586 18783 µ
HEATING LOAD
13. DESIGN CONDITIONS Mult: 1 .0
Inside: 70 OF Outside:60 F TD:64 OF
14. TRANSMISSION LOSSES 103866
Walls: 29146
Glass: 0
Doors: 5 018
Partitions: 0
Floors: 5702
Roofs/Ceilings:64000
Return Air Roof: 0
15. INFILTRATION:Outside air cfm: 2000 140698
16. SUBTOTAL: Building components 2 4 4 5 64
17. SUPPLY DUCT: 0
18. VENTILATION: Make-up air cfm:0 0
19. HUMIDIFICATION 47122
20. RETURN DUCT 0
21. TOTAL HEATING LOAD ON EQUIPMENT 291685
Manual N: 4th Edition Right-N: Ver.3.0.07
Certified by ACCA to meet all requirements of Manual Form N
ti.
r
uN y tG o H s— doc
37 s ov o 4 TJ f lE"'r " t
4c- I tl j 4 S rc 3v / -'Id CGw0 1!lh r
fvfply r4R A/A V ec rr:To=
yysv Z N N 1
yyr 51 R Cl'Vi-u TN WOf
I
r
lye
i yro z Eofpct
r
g
i 1
G
pricie
7 I
V-r-
n V y N 1 r _—
prwiC 4,t_