Thursday, August 24, 2017
J.E. Shepard Co.
200 Sullivan Ave. Suite 4
South Windsor, CT 06074
A1111.: Mr. Stafford "James" King
.I.E. Shepurd Co. Property Manager
File: J.E. Shepard Co.
25 Bidwell Road Facility
South Windsor. CT
Re.: Existing Automatic Fire Sprinkler System Area Coverage
Dear Mr. King,
We appreciate your concern with regards to the existing fire sprinkler system that protects the facility
located at 25 Bidwell Road in South Windsor- specifically related to fire sprinkler spray-pattern
coverage along the tenant area demising wall that is positioned perpendicular to the west exterior wall
adjacent to the overhead door on the -Pete's Tire Barns" tenant area side.
The closest row of fire sprinklers is currently located 6'-9 1/2" from the demising wall interior plywood
"face". Please know that the distance does comply with NFPA-13 (2010 edition); 8.5.3.2.1
(Maximum Distance from Walls)and Table 8.6.2.2.1 (b)(Protection Areas and Maximum Spacing of
Standard Pendent and Upright Spray Sprinklers for Ordinary Hazard (occupancies)). For your
convenience. we have attached partial copies of the code verbiage listed above.
If you have any questions, please do not hesitate to call.
Best regards.
Dignaliy signeo by lay Morello
ON:cn=.ay Morello,-CentralJa y Morel l o System=.Inc.,o—President.
emad-Imorello@Komcastnet.c-US
Date:2017;24 06 06:04-04'00'
Jay Morello
President
Central Systems, Inc.
INFORMATION ACQUIRED; NFPA-13 (2010 Edition)
shall be 8.5.3.2 Maximum Distance from Walls.
8.5.3.2.1 The distance from sprinklers to walls shall not ex-
IC, sprin- ceed one-half of the allowable maximum distance between
to clear- sprinklers.
8.5.3.2.2 The distance from the wall to the sprinkler shall be
S. measured perpendicular to the wall.
8.5.3.2.3 The distance from the wall to the sprinkler shall be
oned in measured to the wall behind furniture, such as wardrobes,
cabinets, and trophy cases.
)tection 8.5.3.2.4 The distance from the wall to the sprinkler shall be
its stan- measured to the wall when sprinklers are spaced near windows
I of cov- and no additional floor space is created.
8.5.3.3 Minimum Distance from Walls.
-.pply to 8.5.3.3.1 The minimum distance permitted between a sprin-
rules in kler and the wall shall comply with the value indicated in the
applicable section for each type or style of sprinkler.
I ' kicc 0.V.4.4.1.1.
Table 8.6.2.2.1 (b) Protection Areas and Maximum Spacing Table 8.6.2
of Standard Pendent and Upright Spray Sprinklers for of Standarc
Ordinary Hazard Hazard
Protection Maximum
Area Spacing
Construction System Constructi4
Type Type ft2 In ft In Type
All All 130 12. 1 15 4.6 All
r All
All
8.6.2.2.1.1 Where the dimension perpendicular to the slope
exceeds 8 ft (2.4 m) , the minimum pressure shall be 20 psi
(1 .4bar) .
8.6.2.2.2 In any case, the maximum area of coverage of a *In building
sprinkler shall not exceed 225 ft2 (21 m2) . It "(7.6 r11 wide
Central Systems, Inc. In voici
�S 211 Pokorny Road
Higganum, CT 06441 Date Invoice N
860-345-8551 / 860-345-7352 Fax 8/14/2017 8040
Bill To Ship To
J.E.Shepard Company JE Shepard-Property Management/Develo
Attn:Mr.Stafford King 25 Bidwell Road Facility
i 200 Sullivan Avenue-Suite 4 South Windsor,CT
i East Windsor Hill,CT 06074
i
I
1
P.O. Number Terms Rep Ship via F.O.B.
---�— ------ Project
Net Due 30 8/14/2017
Quantity Item Code _ Description I Price Each
Amount
INST-LABOR I All services used to modify the existing automatic fire sprinkler I 2,063.00
I system to adequately 2,063•(
Y q y protect WinAir/Pete's Tire tenant area I
demising wall(Win-Air side only)as previously discussed&
i quoted,as requested by Mr.Stafford King.
CT Sales Tax 6.35%j 131.0
I � j
t
Total $2,194.00
Report of Inspection & Testing = � l
of Dry Pipe Fire Protection Systems
Monthly and/or Quarterly Items To Be Reviewed
ALL QUESTIONS ARE TO BE FULLY ANSWERED AND ALL BLANKS TO BE FILLED
(Weekly Inspection tasks are included in this report.)
(THERE IS NOT A SCHEDULED MONTHLY TESTING TASK REQUIREMENT. SEE THE QUARTERLY SCHEDULE)
Inspecting Firm:(Contractor)
Name of Property: J E Shepard Company - Biannual Inspections Bidwell Rd.25,South Windsor,CT 06074
Inspector Name:
Page 1 of 3
Inspection Frequency: Monthly Ljouartedy Annually ✓ Other.
Dry Pipe Sprinkler System Inspection
A-1.1 Air pressure Gauge 28 psi Y N/A N
Accelerate or Quick A-7.1 Exterior Alarms properly Identified:
A-1.2 Opening Device Gauge: psi A-7.2 Exterior alarms appear operational:
A-1.3 Water pressure Gauge: 76 psi A-7.3 Interior alarms appear operational:
A-1.4 Water Supply Gauge: psi A-8.1 Extra Heads in Spare head cabinet
A-8.2 Heads appear to be proper temperature:
Y WA N A-8.3 Head Wrench for each type of Head:
A-2.0 System in service on Inspection: A-8.6 Head in Coder appears free of ice,corrosion:
A-2.1 Dry Pipe Valve appears free of damage: A-8.7 Head appears free of leakage or damage: v(
A-2.2 Trim valves in appropriate position: A-8.8 Head appears free of paint:
A-2.3 Alarm Test valve closed: A-8.9 Head appears free of non-approved coverings:
A-2.4 Intermediate Chamber leak tight: 7 n A-9.0 Standard Head less than 50 year.
A-3.1 Valve Enclosure Secured: _ ,/ A-10.0 Residential Head less than 20 year.
A-3.2 Heater Operational: n A-11.1 Hose/Hydrant House free of damage:
A-3.3 Low Temperature Alarm Operational: 8 A-11.2 Hose/Hydrant House fully equipped: 7
A-4.1 Compressor Operational: 7 A-11.3 Hose/Hydrant House is accessible:
A-4.2 Oil level Full: / I r^ A-12.1 Wet pipe areas appear properly heated ❑ ❑ ❑
A-4.3 HigtVLow Pressure Switches operational: �/ (Wet SSP on Dry Pipe Sys.?)
A-4.4 Auto.Air Maint.Devices operational: �/ A-13.1 Low point drum drips drained: Ell a ❑
A-5.1 Control Va.Lockedi7amper Open: �/ (As frequently as needed)
A-5.2 Backflow Va.Locked OperVTamper. �/ A-13.2 All low points drained �/
A-5.3 Tamper switches appear operational: L,/ A-14.1 All valves identified with signage /
A-5.4 Valve area accessible: �/ A-14.2 Hydraulic nameplate attached V/
A-5.6 Control Valves accessible: A-18.0 ALARM PANEL CLEAR:
A-5.7 Main Check Valve holding pressure: A-19.0 SYSTEM IN SERVICE:
A-6.1 FDC plainly visible: A-20.0 COMMENTS: OSBY main control valves are not
A-6.2 FDC easily accessible: supervised or locked in the'open"position.
A-6.3 FDC swivels non-binding rotation: V The low-air supervisory switch is not in operation.
A-6.4 FDC Caps/Plugs in place: Valve I.D.signs are missing.
A-6.5 FDC gaskets/signs in place �/ (�I The backflow preventer is tested annually by others__
A-6.6 FDC check valve drip tree: �/ �j No records found on-site indicating that a 5 year
A-6.7 FDC ball drip drain drip free: ) -Obstruction Test"or maintenance was performed.
(All"NO"answers to be fully explained.)
INSPECTOR'S INITIAL D.A.Z. OWNER/DESIGNATED REP.INITIAL_ __ _ DAB 7-11-1T (AFSA Form 94•t07A)
Page 1 of 3
A
- API
Report of Inspection & Testing -of Dry Pipe Fire Protection Systems
Quarterly and Annual Items To Be Reviewed
ALL <JOEST iONS ARE TO BE FULLY'ANSV'JEPED AND ALL BLANKS TO BE FILLED
Inspecting Firm:(Contractor) Central Systems, Inc. Inspection Contract If
Name of Property.J E Shepard Company - Biannual Inspections Bidwell Rd.25,South Windsor,CT 06074 _
Inspector Name: Dean Shefcyk Date:7-11-17
Page z of 3 ----
Inspection Frequency: ETMonthly Ouarterly -� jAnnuaHy �/ Other.
QUARTERLY TESTING ANNUAL INSPECTION
REQUIREMENTS OF
FOR A DRY PIPE SPRINKLER SYSTEM DRY PIPE SPRINKLER SYSTEM
Y WA N Y WA N
C t.t Quick Opening Devices Tested during D-t.t Interior of Dry Pipe Valve in good ✓
Semi-Annual Inspections: cordtion: El D
G1.2 Quick Opening Device Test Date: D-1.2 Interior of Quick Opening Device in
G1.3 Priming Water at proper level: good condition:
G2.1 Low Air Pressure Alarm"iested: D-1.3 Inspect interior of Strainers,Filters,
G3.1 Main Drain(low test with 2 inch Restricted Orifices every a
valve full open: 5th year.Date:
63.2 Spkr.Supply Gauge 76 Ps, D-1.4 Inspect interior of Main Check Valve r�
G3.3 Spkr.Supply Gauge with Main every 5th year.Date:
drain flow: 72 ps D-2.1 Visual inspection:HangedSeismic
Bracing appear attached and secure:
Y N/A N D-3.1 Visual inspection:"exposed"piping
C-3.4 Gauges operating: �/ •� appears in good condition:
C-4.1 Water flow alarm devices activated: I ,/ D-3.2 Piping appears free of mechanical damage. ,/
G4.2 Interior Bldg.Alamo operate: LrJ D-3.3 Piping appears free of leakage:
C-4.3 Exterior alarms operate: �/ 6-3.4 Exterior of Piping appears free of corrosion:
C-4.6 Did alarm Supervisory Company D-3.6 Piping appears property aligned:
receive signal: D-3.7 Piping appears free of external loads:
C-4.7 Did Alarm Panel reset: �/ D-4.1 Sprinklers appear free of corrosion: f
C-18.0 ALARM PANEL CLEAR D-4.2 Sprinklers appear properly positioned:
C-19A SYSTEM IN SERVICE: - -- 7117 D-4.3 Sprinklers appear properly spaced: /
C-20.0 COMMENTS: Alarm related switches are in place, D-4.6 Sprinklers appear free of foreign material:
but are_not tied to any active alarm panels. The water D-4.7 Sprinkler spray patterns appear free of ❑
motor gong did did not sound when the system was obstructions:
tested_-inoperable. 0-18.0 ALARM PANEL CLEAR
The quick-opening device(exhauster)is out of service. D-19.0 SYSTEM IN SERVICE:
THERE ARE NO OPERABLE ALARMS ON THE SYSTEM D-20.0 COMMENTS: At inspection,all system pressure
AT ALL AT THIS TIME-THIS SHOULD BE ADDRESSED monitoring gauges were replaced due to age(over 5
ASAP. -- -- - years old). ----- -- -
(All"NO"answers to be fully explained.) (AFSA Form 94-107A)
INSPECTOR'S INITIAL D.A.S. OWNER/DESIGNATED REP.INITIAL DATE 7.11.17
- - Page 2 of 3
44
ANNUAL TESTING AND MAINTENANCE TASKS THAT ARE IN ADDITION TO
OTHER FREQUENCY TASKS - FOR DRY PIPE SYSTEM
Y N/A N Y WA N
E-1.1 Dry Pipe Valve: (Annually) �/ TEST FREQUENCY ITEMS OF 5 YEARS UNLESS NOTED
E•2.1 Quick Opening Devices(Semi-Annually) V/ F-1.1 Gauge Maintenance Test: (5 year)
E-3.1 Dry Pipe Valve Trip Tested with Control F-1.2 Replaced Date: 7-11-17 ✓
Valve Partially Open: Date: F-1.3 Calibrated Date: ✓
E 3.2 Trip test with Control Valve Fully Open when system Is F-2.1 Sprinkler Maintenance Test Frequencies-
altered or every 3rd year. Date: 7-11-17 F-2.2 (5 year)High Temp. Date:
(EXCEPTION When protecting a Cooler or Freezer, DO NOT F-2.3 (20 year,then 10 year thereafter)
introduce moisture into syslem) Fast Response Date: _
F-2.4 (50 year,then 10 year thereafter)
Standard Sprinkler Date:197111 ❑✓ ❑
Y NIA N - ❑❑
E-4.1 Strainers and Filters and Restricted Orifices F3.1 Other
cleaned after Trip Test or every 5 years: ❑✓ ❑
E-4.2 Information on last trip test recorded ✓ F-4.1 SUPPLEMENTAL INFORMATION ON DRY PIPE VALVE
AND SYSTEM CONDITION REPORT(ANNUAL)
E-5.1 Automatic Air Maintenance Device ❑ ❑ Entire Building-
�/ F 4.2 Dry System Controls Sprinklers In
Tested and Operating properly two separate tenant areas.
E-6.1 Control valve Lubricated: _ �/ ❑
E-6.2 Control valve operated to Closed position ✓ ❑ ❑and returned to Open position:
E 6.3 Backflow Assembly Control Valves F-4.3 D P.V Trip Test Satisfactory.
Lubricated: ❑ ❑ F-4 4 Reason For Failure/or Partly Satisfactory The system
E-6.6 Backflow Assembly Control Valves Oper- tripped as required, however the water delivery
ated and returned to Open Position 7 ❑ ❑ time to the inspector's test failed(over 1 minute).
E 6.7 Post indicator valve operated with El ❑ F-4.5 Condition:Interior of Body in good condition ✓ ❑ ❑
24 number of turns recorded ✓ F-4.6 Condition.Water From Test Pipe in good condition
E-6.8 Post indicator valve returned to open ✓ El ❑ F-4.7 Condition:Moving Parts In good condition ✓
position _ F-4.8 Condition:Seats in good condition V
(All Above listed Control Valves to be left 1,14 turn from wide open) F-4.9 Condition.Rubber Facing in good condition ✓
F-4.10 0.0.0 Operation Indicate Satisfactory• �/
E 7.1 All low points drained RRR
F-4.11 Q.O.D Operation Indicate Failed:
E 7 2 Internal Pipe Inspection Recommence F-a 12 O.O.D Operation Indicate Shut Ott:
F-10.0 Comments Quick opening device was found closed before testing,so the'Trip Test'was performed with it off. It
is unknown as to why the QOD was disabled, however It Is safe to assume that there was/is an issue with it.
Post indicator valve is not electronically supervised or secured in the"open"position at this time.
Trip Test Table
Dry Valve Size B" Year 1982 O.O.D. Year 1981
Make Model Serial No Make Model Serial No
Time Water Alarm
Dry Pipe Time to Trip Water Air Trip Pont Reached Operated
Operating Thru Test Pipe Pressure Pressure Air Pressure Test Outle'.
Test Min Sec PS' PSI PSI Min Sec Yes No
Without 0.0 D 1 18 76 38 10 1 40 ❑ ❑✓
With O.O.D ❑
It No Explain: There are no operable alarms on the system at this time and the system is not monitored remotely.
(All"NO'answers to be fully explained.) (AFSA Form 94.107A)
INSPECTOR'S INITIAL OWNERIDESIGNATED REP.INITIAL DATE 7_11-17
Page 3 of 3
Backflow Prevention Device
Inspection and Maintenance
Report Form
Return Form By:
Owner of Property h�"��nC�PQ(�I �o Facility Name
Mailing Address C(i t�jox l N Test Date 1 o- 20-.14
6'.'ll_ U
(Town) (STI (Zip)
Contact Person I�,I �i RPBP cD/DCV El PVB
Device Address r-J�-i( RPDA DDCV ❑ SVB
\.)1 IW �&,0 l Permit Number
Rom) (sT) (zip)
Exact Location 5r,,,VIL- 0� Make U� 5 Model No. 77t(k
I -113
Size � Serial No. CVO
Reduced Pressure Backflow Preventer
Line PSI Pressure Vacuum Breaker
Double Check Valve Assembly
Check Valve No. 1 Check Valve No.2 Relief Valve Check Valve Air Inlet
Initial Test Closed Tight Closed Tight 2/ Opened at Closed Tight ❑ Opened at
PASS [a/ Leaked ❑ Leaked ❑ PSID Leaked ❑ PSID
FAIL ❑ l�� � PSID �`� PSID Did Not Open ❑ PSID Did Not Open ❑
Repairs
Closed Tight ❑ Closed Tight ❑ Opened at ❑ Closed Tight ElOpened at
Final Test
PSID PSID PSID PSID PSID
PASS ❑
Condition of No.2 Shutoff Valve Closed Tight ❑ Leaked
Notes: USC 10th Edit.
Certification: On this date,the above device was tested per applicable codes and the required performance standards.
Test Type Gauge No. Testing Firm ��� P I�t-y►
Fester Name 6 Tester Certification No. )9
Tester Signature: / �/ / h `' Date: �D 2-.4117 -/L�