Loading...
HomeMy WebLinkAboutWell Correspondence 369 Avery Street 5Aquatek Labs 3 Research Drive-Woodbridge, CT 06525 Water Analysis Report TEST ID: F070916006 DATE SAMPLED: 7/8/2016 TO: GREAT PRO-SPECTS 424 SAMPLE POINT: KITCHEN NO TREATMENT SAMPLED BY: MIKE CUNNINGHAM PROPERTY LOCATION: 369 AVERY STREET-SOUTH WINDSOR , CT BACTERIA ABSENT PRESENT LIMITS REF METHOD Coliform(Total) G ❑ ABSENT P SM 9223 E.Coli(Fecal) G ❑ ABSENT P SM 9223 Chlorine(Total) G ❑ ABSENT SM 4500-CI G PHYSICAL PARAMETERS RESULT UNITS LIMITS MRL REF METHOD pH 7.5 SU 6.4-10 S 0 SM 4500-H B Turbidity 0.40 NTU 5 0.10 SM 2130 B Color ND CU 15 S 5 SM 2120 B Odor 0 TON 2 S 0 SM 2150 CHEMICALS RESULT UNITS LIMITS MRL REF METHOD Flouride ND mg/L 4 P 0.3 EPA 300.0 Chloride 67 mg/L 250 P 3 EPA 300.0 Nitrite Nitrogen ND mg/L 1 P 0.1 EPA 300.0 Nitrate Nitrogen 4.2 mg/L 10 P 1 EPA 300.0 Sulfate 8 mg/L 250 S 4 EPA 300.0 Calcium 77 mg/L NONE 0.5 SM 3111 B Magnesium 8 mg/L NONE 0.5 SM 3111 B * Hardness 223 mg/L 200 S 4 SM 2340 B Sodium 17.2 mg/L 100 S 0.5 SM 3111 B Copper 0.04 mg/L 1.3 S 0.04 SM 3111 B Iron ND mg/L 0.3 S 0.04 SM 3111 B Manganese ND mg/L 0.05 S 0.04 SM 3111 B RADON WATER SINGLE RESULT UNITS LIMITS MRL REF METHOD Radon Water Single 353 pCi/L 5000 S 51 SM 7500-RN CONCLUSION: Based on the above results, this water was safe for drinking purposes at the time of collection. P=Primary limit,used to judge potability S=Secondary limit,recommended but not required / e�eta MRL=Minimum Reportable Level �1"/ 0, *Limit exceeded Michael F. Berman, Ph.D. ND=None Detected Laboratory Director CT License#PH-0466,Aquatek Labs R=Reference Lab Work Page 1 of 1 for test# F070916006