HomeMy WebLinkAboutFood Service Establishment 793 Pleasant JUAquatek Labs
3 Research Drive-Woodbridge, CT06525
WATER ANALYSIS REPORT
TEST ID: F08081510
TO: HAYNES,TODD DATE SAMPLED: 8/7/2015
SAMPLE POINT: KITCHEN SINK
AFTER TREATMENT SYSTEM
SAMPLED BY: MICHAEL CUNNINGHAM
PROPERTY LOCATION: 793 PLEASANT VALLEY ROAD-SOUTH WINDSOR, CT .
BACTERIA LIMITS METHOD
COLIFORM(total) ❑ ABSENT ❑ PRESENT ABSENT P SM 9223
E.COLI(fecal) ABSENT ❑ PRESENT ABSENT P SM 9223
CHLORINE ABSENT ❑ PRESENT ABSENT -
PHYSICAL PARAMETERS RESULT UNITS LIMITS MRL METHOD
pH 7.9 SU 6.4-10 S 0 SM 4500-H B
TURBIDITY 1.10 NTU 5 - 0.10 SM 2130 B
COLOR ND CU 15 S 5 SM 2120 B
ODOR 0 TON 2 S 0 SM 2150
CHEMICALS RESULT UNITS LIMITS MRL METHOD
FLUORIDE ND mg/L 4 P 0.3 EPA 300.0
CHLORIDE 9 mg/L 250 P 3 EPA 300.0
NITRITE NITROGEN ND mg/L 1 P 0.1 EPA 300.0
NITRATE NITROGEN 2.8 mg/L 10 P 1 EPA 300.0
* SULFATE 265 mg/L 250 S 4 EPA 300.0
CALCIUM 117 mg/L NONE - 0.5 SM 3111 B
MAGNESIUM 4 mg/L NONE - 0.5 SM 3111 B
* HARDNESS 307 mg/L 200 S 4 SM 2340 B
SODIUM 10.2 mg/L 28 S 0.5 SM 3111 B
COPPER ND mg/L 1.3 S 0.04 SM 3111 B
IRON ND mg/L 0.3 S 0.04 SM 3111 B
MANGANESE ND mg/L 0.05 S 0.04 SM 3111 B
RADON WATER RESULT UNITS LIMITS MRL METHOD
SINGLE RADON WATER 624 pCi/L 5,000 S 51 SM 7500-Rn
CONCLUSION: Based on the above results,this water was safe for drinking purposes at the time of collection.
P=Primary limit,used to judge potability
S=Secondary limit,recommended but not required �+--
MRL=Minimum Reportable Level
*Limit exceeded
ND=None Detected David M. Graham, Ph.D.
CT License#PH-0466,Aquatek Labs Laboratory Director
Page 1 of 1 for test#F08081510