Loading...
HomeMy WebLinkAboutWell 793 Pleasant Valley JUAquatek Labs 3 Research Drive-Woodbridge, CT06525 WATER ANALYSIS REPORT TEST ID: F08081510 TO: HAYNES,TODD DATE SAMPLED: 8/7/2015 SAMPLE POINT: KITCHEN SINK AFTER TREATMENT SYSTEM SAMPLED BY: MICHAEL CUNNINGHAM PROPERTY LOCATION: 793 PLEASANT VALLEY ROAD-SOUTH WINDSOR, CT . BACTERIA LIMITS METHOD COLIFORM(total) ❑ ABSENT ❑ PRESENT ABSENT P SM 9223 E.COLI(fecal) ABSENT ❑ PRESENT ABSENT P SM 9223 CHLORINE ABSENT ❑ PRESENT ABSENT - PHYSICAL PARAMETERS RESULT UNITS LIMITS MRL METHOD pH 7.9 SU 6.4-10 S 0 SM 4500-H B TURBIDITY 1.10 NTU 5 - 0.10 SM 2130 B COLOR ND CU 15 S 5 SM 2120 B ODOR 0 TON 2 S 0 SM 2150 CHEMICALS RESULT UNITS LIMITS MRL METHOD FLUORIDE ND mg/L 4 P 0.3 EPA 300.0 CHLORIDE 9 mg/L 250 P 3 EPA 300.0 NITRITE NITROGEN ND mg/L 1 P 0.1 EPA 300.0 NITRATE NITROGEN 2.8 mg/L 10 P 1 EPA 300.0 * SULFATE 265 mg/L 250 S 4 EPA 300.0 CALCIUM 117 mg/L NONE - 0.5 SM 3111 B MAGNESIUM 4 mg/L NONE - 0.5 SM 3111 B * HARDNESS 307 mg/L 200 S 4 SM 2340 B SODIUM 10.2 mg/L 28 S 0.5 SM 3111 B COPPER ND mg/L 1.3 S 0.04 SM 3111 B IRON ND mg/L 0.3 S 0.04 SM 3111 B MANGANESE ND mg/L 0.05 S 0.04 SM 3111 B RADON WATER RESULT UNITS LIMITS MRL METHOD SINGLE RADON WATER 624 pCi/L 5,000 S 51 SM 7500-Rn CONCLUSION: Based on the above results,this water was safe for drinking purposes at the time of collection. P=Primary limit,used to judge potability S=Secondary limit,recommended but not required �+-- MRL=Minimum Reportable Level *Limit exceeded ND=None Detected David M. Graham, Ph.D. CT License#PH-0466,Aquatek Labs Laboratory Director Page 1 of 1 for test#F08081510