HomeMy WebLinkAbout1675 MAIN ST (26) FOR FORCED AIR HEATING OR AIR CONDITIONING:
REQUIRES: 1 BRANCH DUCT - (5 IN ROUND) OR (5 IN OVAL) OR (3-1/4 X 8 WALL STACK)
REQUIRES: 1 #661 6 X 4 SIDEWALL REGISTER OR 1 #411 2-1/4 X 10 FLOOR DIFFUSER OR
REQUIRES: 1 ##16 6 IN ROUND CEILING DIFFUSER OR 1 #24 6 X 6 INCH SQUARE DIFFUSER
REQUIRES: 1 #650 10 X 6 INCH RETURN AIR GRILL FOR ONE 3-1/4 X 14 IN-WALL RETURN
KITCHEN, NORTH & WEST & SOUTH HEAT COOL AREA LOSS GAIN
8 . 7 SQUARE FEET OF TYPE 2, NO SHADE 46 .7 27 . 0 9 406 235
CEILING UNDER VENTILATED ATTIC, R38 INS 2 . 1 1 .1 128 264 140
FLOOR OVER CONDITIONING, NO LOSS/GAIN 0 . 0 0 . 0 128 0 0
WALL 10 X 8 FT, FRAME OR VENEER, R19 INS 4 .8 1.7 71 343 121
WALL 8 X 8 FT, FRAME OR VENEER, R19 INS 4 .8 1 .7 64 309 109
WALL 10 X 8 FT, FRAME OR VENEER, R19 INS 4.8 1.7 80 386 136
XLLOWANCE-FOR INFILTRATION, AVERAGE CONST 12 . 9 2 .1 128 1649 269
ALLOWANCE -FOR LATENT HEAT 0 . 0 0.3 1010 0 303
ALLOWANCE FOR APPLIANCES AND MOTORS 0 .0 2 .0 600 0 1200
TOTAL REQUIRED CFM AND BTU HEAT LOSS/GAIN CFM LOSS GAIN
CFM Q RECOMMENDED MAX VELOCITY OF 600 FPM 85 3357 2513
FOR FORCED AIR HEATING OR AIR CONDITIONING:
REQUIRES: 1 BRANCH DUCT - (6 IN ROUND) OR (6 IN OVAL) OR (3-1/4 X 10 WALL STACK
REQUIRES: 1 #661 12 X 4 SIDEWALL REGISTER OR 1 #411 4 X 10 FLOOR DIFFUSER OR
REQUIRES: 1 #16 6 IN ROUND CEILING DIFFUSER OR 1 #24 6 X 6 INCH SQUARE DIFFUSER
REQUIRES: 1 #650 10 X 6 INCH RETURN AIR GRILL FOR ONE 3-1/4 X 14 IN-WALL RETURN
LIVING ROOM, NORTH & EAST HEAT COOL AREA LOSS GAIN
1 WINDOW 72 X 80 IN, TYPE 2, NO SHADE 46.7 27.0 40 1868 1080
CEILING UNDER VENTILATED ATTIC, R38 INS 2 .1 1 .1 168 348 185
FLOOR OVER CONDITIONING, NO LOSS/GAIN 0 .0 0 .0 168 0 0
WALL 14 X 8 FT, FRAME OR VENEER., R19 INS 4 .8 1.7 72 348 122
WALL 12 X $ FT, FRAME OR VENEER, R19 INS 4 . 8 1. 7 96 464 163
ALLOWANCE FOR INFILTRATION, AVERAGE CONST 12.9 2 .1 168 2164 353
ALLOWANCE FOR LATENT HEAT 0 . 0 0 .3 1903 0 571
TOTAL REQUIRED CFM AND BTU HEAT LOSS/GAIN CFM LOSS GAIN
CFM @ RECOMMENDED MAX VELOCITY OF 600 FPM 84 5192 2474
FOR FORCED AIR HEATING OR AIR CONDITIONING:
REQUIRES: 1 BRANCH DUCT - (6 IN ROUND) OR (6 IN OVAL) OR (3-1/4 X 10 WALL STACK
REQUIRES: 1 #661 12 X 4 SIDEWALL REGISTER OR 1 #411 4 X 10 FLOOR DIFFUSER OR
REQUIRES: 1 ##16 6 IN ROUND CEILING DIFFUSER OR 1 #24 6 X 6 INCH SQUARE DIFFUSER
REQUIRES: 1 #650 10 X 6 INCH RETURN AIR GRILL FOR ONE 3-1/4 X 14 IN-WALL RETURN
BED ROOM # 4, EAST & SOUTH HEAT COOL AREA LOSS GAIN
15 SQUARE FEET OF TYPE 2, NO SHADE 46 . 7 76 . 0 15 700 1140
CEILING UNDER VENTILATED ATTIC, R38 INS 2 . 1 1 .1 170 352 187
HARDWOOD FLOOR, NO INS OVER ENCLOSED SPACE 12 . 5 0 . 0 170 2131 0
WALL 10 X 8 FT, FRAME OR VENEER, R19 INS 4 .8 1 . 7 65 314 111
WALL 17 X 8 FT, FRAME OR VENEER, R19 INS 4 . 8 1 .7 136 657 231
ALLOWANCE FOR INFILTRATION, AVERAGE CONST 12 . 9 2 .1 170 2190 357