HomeMy WebLinkAbout1675 MAIN ST (9) REQUIRES:. 2 #16 6 IN ROUND CEILING DIFFUSER OR 2 #24 6 X 6 INCH SQUARE DIFFUSER
REQUIRES: 1 #650 10 X 6 INCH RETURN AIR GRILL FOR ONE 3-1/4 X 14 IN-WALL RETURN
BED ROOM # 3, SOUTH & EAST HEAT COOL AREA LOSS GAIN
30 SQUARE FEET OF TYPE 2, NO SHADE 46 .7 42 . 0 30 1401 1260
CEILING UNDER VENTILATED ATTIC, R38 INS 2 .1 1 .1 192 397 211
FLOOR OVER CONDITIONING, NO LOSS/GAIN 0 . 0 0 . 0 192 0 0
WALL 13 X 8 FT, FRAME OR VENEER, R19 INS 4 .8 1.7 74 357 126
WALL 15 X 8 FT, FRAME OR VENEER, R19 INS 4 . 8 1 .7 120 580 204
ALLOWANCE FOR INFILTRATION, AVERAGE CONST 12 . 9 2 .1 192 2473 403
ALLOWANCE FOR LATENT HEAT 0 . 0 0.3 2204 0 661
TOTAL REQUIRED CFM AND BTU HEAT LOSS/GAIN CFM LOSS GAIN
CFM @ RECOMMENDED MAX VELOCITY OF 600 FPM 97 5208 2865
FOR FORCED AIR HEATING OR AIR CONDITIONING:
REQUIRES:-1 BRANCH DUCT - (6 IN ROUND) OR (6 IN OVAL) OR (3-1/4 X 10 WALL STACK
REQUIRES: 1 #661 12 X 4 SIDEWALL REGISTER OR 1 #411 4 X 10 FLOOR DIFFUSER OR
REQUIRES: 1 #16 6 IN ROUND CEILING DIFFUSER OR 1 #24 6 X 6 INCH SQUARE DIFFUSER
REQUIRES_: 1 #650 10 X 6 INCH RETURN AIR GRILL FOR ONE 3-1/4 X 14 IN-WALL RETURN
BATH RM ## 1, NORTH HEAT COOL AREA LOSS GAIN
8 .5 SQUARE FEET OF TYPE 2, NO SHADE 46 . 7 27.0 9 397 230
CEILING UNDER VENTILATED ATTIC, R19 INS 4 .3 2 .3 38 160 86
FLOOR OVER. CONDITIONING, NO LOSS/GAIN 0. 0 0 . 0 38 0 0
WALL 7 X 8 FT, FRAME OR VENEER, R19 INS 4 .8 1. 7 48 232 82
ALLOWANCE FOR INFILTRATION, AVERAGE CONST 12 . 9 2 . 1 38 489 80
ALLOWANCE FOR LATENT HEAT 0 .0 0 .3 478 0 143
ALLOWANCE FOR BATHROOM COMFORT 0.2 0 . 0 1278 256 0
TOTAL REQUIRED CFM AND BTU HEAT LOSS/GAIN CFM LOSS GAIN
CFM "@ RECOMMENDED MAX VELOCITY OF 600 FPM 21 1534 621
FOR FORCED AIR HEATING OR AIR CONDITIONING:
REQUIRES: 1 BRANCH DUCT - (5 IN ROUND) OR (5 IN OVAL) OR (3-1/4 X 8 WALL STACK)
REQUIRES: 1 #661 6 X 4 SIDEWALL REGISTER OR 1 #411 2-1/4 X 10 FLOOR DIFFUSER OR
REQUIRES: 1 #16 6 IN ROUND CEILING DIFFUSER OR 1 ##24 6 X 6 INCH SQUARE DIFFUSER
REQUIRES: 1 #650 10 X 6 INCH RETURN AIR GRILL FOR ONE 3-1/4 X 14 IN-WALL RETURN
BATH RM # 2, NORTH HEAT COOL AREA LOSS GAIN
8.5 SQUARE FEET OF TYPE 2, NO SHADE 46.7 27. 0 9 397 230
CEILING UNDER VENTILATED ATTIC, R38 INS 2.1 1.1 38 78 41
FLOOR OVER CONDITIONING, NO LOSS/GAIN 0. 0 0.0 38 0 0
WALL 7 X 8 FT, FRAME OR VENEER, R19 INS 4 .8 1.7 48 232 82
ALLOWANCE FOR INFILTRATION, AVERAGE CONST 12 . 9 2 .1 38 489 80
ALLOWANCE FOR LATENT HEAT 0. 0 0 .3 433 0 130
ALLOWANCE FOR BATHROOM COMFORT 0 .2 0 .0 1196 239 0
TOTAL REQUIRED CFM AND BTU HEAT LOSS/GAIN CFM LOSS GAIN
CFM @ .RECOMMENDED MAX VELOCITY OF 600 FPM 20 1435 563