HomeMy WebLinkAbout1675 MAIN ST (10) FOYER, SOUTH HEAT COOL AREA LOSS GAIN
15 SQUARE FEET OF TYPE 2, NO SHADE 46.7 42 . 0 15 700 630
1 DOOR 36 X 80 IN, TYPE 4 25.8 10 . 0 20 515 200
CEILING UNDER CONDITIONING, NO LOSS/GAIN 0 . 0 0 .0 0 0 0
HARDWOOD FLOOR, NO INS OVER ENCLOSED SPACE 12 .5 0 . 0 160 2006 0
WALL 15 X 8 FT, FRAME OR VENEER, R19 INS 4 .8 1.7 85 411 145
ALLOWANCE FOR INFILTRATION, AVERAGE CONST 12 . 9 2 .1 160 2061 336
ALLOWANCE FOR LATENT HEAT 0 . 0 0 .3 1311 0 393
TOTAL REQUIRED CFM AND BTU HEAT LOSS/GAIN CFM LOSS GAIN
CFM @ RECOMMENDED MAX VELOCITY OF 600 FPM 79 5693 1704
FOR FORCED AIR HEATING OR AIR CONDITIONING:
REQUIRES: 'I BRANCH DUCT - (6 IN ROUND) OR (6 IN OVAL) OR (3-1/4 X 10 WALL STACK
REQUIRES: 1 #661 12 X 4 SIDEWALL REGISTER OR 1 #411 4 X 10 FLOOR DIFFUSER OR
REQUIRES.: 1 ##16 6 IN ROUND CEILING DIFFUSER OR 1 #24 6 X 6 INCH SQUARE DIFFUSER
REQUIRES: - 1 #650 10 X 6 INCH RETURN AIR GRILL FOR ONE 3-1/4 X 14 IN-WALL RETURN
BED ROOM # 1,- NORTH & WEST HEAT COOL AREA LOSS GAIN
29 SQUARE FEET OF TYPE 2, NO SHADE 46 .7 27. 0 29 1354 783
CEILING UNDER VENTILATED ATTIC, R38 INS 2 . 1 1.1 244 505 268
HARDWOOD FLOOR, NO INS OVER ENCLOSED SPACE 12 .5 0. 0 244 3059 . 0
WALL 17 X 8 FT, FRAME OR VENEER, R19 INS 4 . 8 1 . 7 107 517 182
WALL 15 X 8 FT, FRAME OR VENEER, R19 INS 4 . 8 1.7 120 580 204
ALLOWANCE FOR INFILTRATION, AVERAGE CONST 12 , 9 2 . 1 244 3143 512
ALLOWANCE FOR LATENT HEAT 0 . 0 0 .3 1949 0 585
TOTAL REQUIRED CFM AND BTU HEAT LOSS/GAIN CFM LOSS GAIN
CFM @ RECOMMENDED MAX VELOCITY OF 600 FPM 128 9158 2534
FOR FORCED AIR HEATING OR AIR CONDITIONING:
REQUIRES: 2 BRANCH DUCT - (5 IN ROUND) OR (5 IN OVAL) OR (3-1/4 X 8 WALL STACK)
REQUIRES: 2 #661 10 X 4 SIDEWALL REGISTER OR 2 #411 2-1/4 X14 FLOOR DIFFUSER OR
REQUIRES: 2 #16 6 IN ROUND CEILING DIFFUSER OR 2 #24 6 X 6 INCH SQUARE DIFFUSER
REQUIRES: 1 #650 10 X 6 INCH RETURN AIR GRILL FOR ONE 3-1/4 X 14 IN-WALL RETURN
BED ROOM # 2, WEST & SOUTH HEAT COOL AREA LOSS GAIN
CEILING UNDER VENTILATED ATTIC, R38 INS 2 .1 1.1 192 397 211
HARDWOOD FLOOR, NO INS OVER ENCLOSED SPACE 12 .5 0 . 0 192 2407 0
WALL 15 X 8 FT, FRAME OR VENEER, R19 INS 4. 8 1.7 120 580 204
30 SQUARE FEET OF TYPE 2, NO SHADE 46. 7 42. 0 30 1401 1260
WALL 13 X 8 FT, FRAME OR VENEER, R19 INS 4 .8 1.7 74 357 126
ALLOWANCE FOR INFILTRATION, AVERAGE CONST 12. 9 2.1 192 2473 403
ALLOWANCE- FOR LATENT HEAT 0 . 0 0.3 2204 0 661
TOTAL REQUIRED CFM AND BTU HEAT LOSS/GAIN CFM LOSS GAIN
CFM @ RECOMMENDED MAX VELOCITY OF 600 FPM 106 7615 2865
FOR FORCED AIR HEATING OR AIR CONDITIONING:
REQUIRES: 2 BRANCH DUCT - (5 IN ROUND) OR (5 IN OVAL) OR (3-1/4 X 8 WALL STACK)
REQUIRES: 2 ##661 10 X 4 SIDEWALL REGISTER OR 2 #411 2-1/4 X14. FLOOR DIFFUSER OR