Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Home
My WebLink
About
50 Talbot Lane - Building Plans & Drawin (2)
HYDRAULIC (CALCULATIONS for I Carla's Pasta 280 Nutmeg Road South South. Windsor, CT 4/16!2018 Calculated Area: FREEZER PREACTION Design Data: Occupancy Classification: Rack Storage Density: 0.25 GPM PER SQ FT Area of Application: 2600 sq ft Coverage Per Sprinkler: 85 sq ft NO. of Sprinklers Calculated: 43 Hose Streams: 500 GPM Total Water Required 1594 .25 GPM including hose streams 1594 .25 GPM required at supply pressure of 65. 10 PSI Flow at Base of Riser 1094 . 25 GPM Required Pressure at Base of Riser 42. 72 PSI Supply Data: Static (PSI) 82 Residual (PSI) 76 Flow (GPM) 1320 .. lt�;ti411�titrrit rrrxtl�r��f� Calculations by: CCK of 1 Rybak Engineering, Inc. ' t} � , �rx�'� 132 Forest Ave. Warren, MA 01083-0709 N4.18498 actor Name Legacy FiorerPrfltection, Inc. S, tC}NA�t' ��,+� 592 Center Street PO Box 58 2 Ludlow, MA 01056-0582 Authority Having Jurisdiction: Local Building Official Underwriter: - Notes: Safety Factor: 8 psi IRAs flow = 345.37 gpm, Hose stream flow: 500 gpm Flow, roof. system: 748 . 88 gpm 20180240 C:\w\20180240 carlas pasta preaction system FREEZER PREACTION 2 of 14 --- OUTLET TABLE --- OUTLET # K-FACTOR PRESSURE FLOW ELEV. (FEET) MIN. FLOW 1 8.000 7.450 21.84 52.14 21.38 2 8.000 7.488 21.89 52.10 21.38 3 8.000 7.583 22.03 52.06 21.38 4 8.000 7.767 22.30 52.03 21.38 5 8.000 8.027 22.67 51.99 21.38 6 8.000 8.251 22.98 52 .07 21.38 7 8.000 8.287 23 .03 52.04 21.38 8 8.000 8.380 23.16 52.00 21.38 9 8.000 7.373 21.72 52.34 21.38 10 8.000 7.411 21.78 52.30 21.38 11 8.000 7.505 21.92 52.26 21.38 12 8.000 7.687 22 .18 52.22 21.38 13 8.000 7.945 22.55 52 .19 21.38 14 8.000 8.167 22.86 52.27 21.38 15 8.000 8.203 22.91 52.24 21.38 16 8.000 8.295 23 .04 52.20 21.38 17 8.000 7.541 21.97 51.96 21.38 18 8.000 7.579 22.02 51.93 21.38 19 8.000 7.675 22.16 51.89 21.38 20 8.000 7.860 22.43 51.85 21.38 21 8.000 8.123 22.80 51.82 21.38 22 8.000 8.352 23 .12 51.90 21.38 23 8.000 8.389 23 .17 51.86 21.38 24 8.000 8.483 23 .30 51.83 21.38 25 8.000 7.692 22.19 51.77 21.38 26 8.000 7.731 22.24 51.73 21.38 27 8.000 7.828 22.38 51.70 21.38 28 8.000 8.016 22.65 51.66 21.38 29 8.000 8.284 23 .03 51.63 21.38 30 8.000 8.520 23.35 51.70 21.38 31 8.000 8.557 23.40 51.67 21.38 32 8.000 8.653 23.53 51.64 21.38 33 8.000 10.792 26.28 51.42 21.38 34 8.000 22.529 37.97 23.67 30.00 35 8.000 22.691 38.11 23.67 30.00 36 8.000 14.072 30.01 38.00 30.00 37 8.000 14.164 30.11 38.00 30.00 38 8.000 14.498 30.46 38.00 30.00 39 8.000 22.240 37.73 23.67 30.00 40 8.000 22.399 37.86 23 .67 30.00 41 8.000 16.040 32.04 38.00 30.00 42 8.000 16.144 32.14 38.00 30.00 43 8.000 23.689 38.94 23 .67 30.00 FREEZER PREACTION 3 of 14 --- PIPE TABLE --- FRICTION FRICTION VELOCITY PIPE NO. DIAMETER LENGTH FLOW GPM C LOSS/FOOT LOSS/TOTAL FEET/SECOND 1 2.635 9.00 21.84 100 0.0024 0.022 1:3 2 2.635 9.00 43.73 100 0.0087 0.079 2.6 3 2.635 9.00 65.76 100 0.0186 0.167 3 .9 4 2.635 7.72 88.05 100 0.0319 0.246 5.2 5 2.635 14.55 110.72 100 0.0467 0.709 6 .5 6 2.635 8.12 22.98 100 0.0027 0.022 1.4 7 2.635 8.12 46.01 100 0.0096 0.078 2 .7 8 2.635 17:11 69.17 100 0.0204 0.349 4.1 9 2.635 9.00 21.72 100 0.0024 0.022 1.3 10 2.635 9.00 43.50 100 0.0087 0.078 2 .6 11 2.635 9.00 65.42 160 0.0184 0.166 3 .8 12 2.635 7.72 87.60 100 0.0316 0.244 5.2 13 2.635 14.55 110.15 100 0.0483 0.702 6.5 14 2.635 8.12 22.86 100 0.0026 0.021 1.3 15 2.635 8.12 45.77 100 0.0095 0.077 2 .7 16 2.635 17.11 68.82 100 0.0202 0.346 4 .0 17 2.635 9.00 21.97 100 0.0024 0.022 1.3 18 2.635 9.00 43 .99 100 0.0088 0.080 2 .6 19 2.635 9.00 66.15 100 0.0188 0.169 3 .9 20 2.635 7.72 88.58 100 0.0323 0.249 5.2 21 2.635 14.55 111.38 100 0.0493 0.717 6.6 22 2.635 8 .12 23 .12 100 0.0027 0.022 1.4 23 2.635 8.12 46.29 100 0.0097 0.079 2.7 24 2.635 17.11 69.59 100 0.0206 0.353 4 .1 25 2.635 9.00 22.19 100 0.0025 0.022 1.3 26 2.635 9.00 44.43 100 0.0090 0.081 2 .6 27 2.635 9.00 66.81 100 0.0191 0.172 3 .9 28 2.635 7.72 89.46 100 0.0328 0.253 5.3 29 2.635 14.55 112.49 100 0.0502 0.730 6 .6 30 2.635 8.12 23 .35 100 0.0027 0.022 1.4 31 2.635 8.12 46.75 100 0.0099 0.080 2 .8 32 2.635 17.11 70.29 100 0.0210 0.360 4.1 33 2.635 21.78 26.28 100 0.0034 0.074 1.5 34 2.157 9.04 37.97 100 0.0178 0.161 3 .3 35 2.157 22.86 76.08 100 0.0645 1.475 6.7 36 2.157 8.00 30.01 100 0.0115 0.092 2 .6 37 2.157 8.00 60.12 100 0.0417 0.334 5.3 38 2.157 38.72 90.58 100 0.0891 3.449 8.0 39 2.157 9.04 37.73 100 0.0176 0.159 3 .3 40 2.157 27.86 75.59 100 0.0637 1.776 6.6 41 2.157 8.00 32.04 100 0.0130 0.104 2 .8 42 2.157 38.72 64.18 100 0.0471 1.824 5.6 43 2.157 27.86 36.94 100 0.0187 0.521 3 .4 44 6.357 4.00 76.08 100 0.0003 0.001 0.8 45 6.357 4.27 166.66 100 0.0014 0.006 1.7 46 6.357 4.26 242.25 100 0.0028 0.012 2 .4 47 6.357 4.27 306.43 100 0.0044 0.019 3 .1 48 6.157 242.00 345.37 100 0.0064 1.551 3 .7 FREEZER PREACTION 4 of 14 --- PIPE TABLE --- FRICTION FRICTION VELOCITY PIPE NO. DIAMETER LENGTH FLOW GPM C LOSS/FOOT LOSS/TOTAL FEET/SECOND 49 6.357 9.48 178.96 100 0.0016 0.015 1.8 50 6.357 8.32 358.85 100 0.0059 0.049 3 .6 51 6.357 9.32 539.82 100 0.0125 0.117 5.5 52 6.157 160.00 345.37 100 0.0064 1.025 3 .7 53 6.357 9.48 722.60 100 0.0215 0.204 7.3 54 6.357 48.33 748.88 100 0.0230 1.110 7.6 55 8.249 261.00 748.88 100 0.0065 1.685 4.5 56 8.249 142 .00 748.88 100 0.0065 0.917 4.5 57 8.249 99.00 748.88 100 0.0065 0.639 4.5 58 8.249 3 .00 748.88 120 0.0046 0.014 4.5 59 6.357 90.00 345.37 100 0.0055 0.494 3 .5 60 8.249 585.00 1094.25 120 0.0093 5.436 6 .6 61 8.249 112 .00 1094.25 120 0.0093 1.041 6 .6 62 7.981 19.00 1094.25 120 0.0109 8.207 7.0 63 8.260 317.00 1094.25 140 0.0069 2.201 6.6 64 8.260 695.00 1594.25 140 0.0139 9.679 9.5 65 12.330 500.00 1594.25 140 0.0020 0.990 4.3 66 2.635 17.67 178.96 120 0.0845 1.494 10.5 67 2.635 17.67 179.89 120 0.0854 1.508 10.6 68 2.635 17.67 180.97 120 0.0863 1.525 10.6 69 2.635 17.67 182.78 120 0.0879 1.553 10.8 FREEZER PREACTION 5 of 14 --- ROUTE NO. 1 DESCRIPTION --- Q-ADD DIA T PIPE PT PV REFERENCE LOSS/FT E FITTS PE PE Q-TOTAL C-FACT LT TOTAL PF PO NOTES --------------------------------------------------------------------------- OUTLET 1 21.84 2.635 0 9.0 7.45 K=8 0.00 0 0 0.02 0.00 PIPE 1 21.84 100 0 9.0 0.02 7.45 --------------------------------------------------------------------------- OUTLET 2 21.89 2.635 0 9.0 7.49 K=8 0.01 0 0 0.02 0.00 PIPE 2 43 .73 100 0 9.0 0.08 7.49 --------------------------------------------------------------------------- OUTLET 3 22.03 2.635 0 9.0 7.58 K=8 0.02 0 0 0.02 0.00 PIPE 3 65.76 100 0 9.0 0.17 7.58 --------------------------------------------------------------------------- OUTLET 4 22.30 2.635 0 7.7 7.77 K=8 0.03 0 0 0.01 0.00 PIPE 4 88.05 100 0 7.7 0.25 7.77 --------------------------------------------------------------------------- OUTLET 5 22.67 2.635 1 2.6 8.03 K=8 0.05 0 12 0.00 0.00 PIPE 5 110.72 100 0 14.6 0.71 8.03 --------------------------------------------------------------------------- REF 925 69.17 2.635 1 0.7 8.74 0.085 0 17 0.29 PIPE 67 179.89 120 0 17.7 1.51 --------------------------------------------------------------------------- REF 907 178.96 6.357 0 8.3 10.54 0.006 0 0 0.08 PIPE 50 358.85 100 0 8.3 0.05 REF 908 180.97 6.357 0 9.3 10.66 0.013 0 0 0.08 PIPE 51 539.82 100 0 9.3 0.12 ------------------=-------------------=------------------------------------ REF 910 182.78 6.357 0 9.5 10.86 0.021 0 0 0.09 PIPE 53 722.60 100 0 9.5 0.20 --------------------------------------------------------------------------- REF 911 26.28 6.357 1 5.3 11.15 0.023 0 43 0.94 PIPE 54 748.88 100 2 48.3 1.11 REF 912 0.00 8.249 0 230.0 13 .20 0.006 0 31 14.58 PIPE 55 748.88 100 3 261.0 1.68 --------------------------------------------------------------------------- FREEZER PREACTION 6 of 14 Q-ADD DIA T PIPE PT PV REFERENCE LOSS/FT E FITTS PE PE Q-TOTAL C-FACT LT TOTAL PF PO NOTES --------------------------------------------------------------------------- REF 913 0.00 8.249 0 80.0 29.46 0.006 0 62 0.00 PIPE 56 748.88 100 6 142.0 0.92 --------------------------------------------------------------------------- REF 914 0.00 8.249 1 16.0 30.38 0.006 0 83 5.21 PIPE 57 748.88 100 0 99.0 0.64 --------------------------------------------------------------------------- REF 915 0.00 8.249 0 3.0 36.23 0.005 0 0 0.00 PIPE 58 748.88 120 0 3.0 0.01 --------------------------------------------------------------------------- REF 917 345.37 8.249 0 440.0 36.24 0.009 0 145 -9.98 PIPE 60 1094.25 120 10 585.0 5.44 --------------------------------------------------------------------------- REF 918 0.00 8.249 1 9.0 31.69 0.009 0 103 9.98 PIPE 61 1094.25 120 0 112.0 1.04 --------------------------------------------------------------------------- REF 919 0.00 7.981 0 6.0 42.72 0.011 0 13 1.30 PIPE 62 1094.25 120 1 19.0 8 .21 inc 8 psi forBFP --------------------------------------------------------------------------- REF 920 0.00 8.260 1 200.0 52 .23 0.007 0 117 0.00 PIPE 63 1094.25 140 3 317.0 2 .20 ---------------.------------------------------------------------------------ REF 921 500.00 8.260 1 540.0 54.43 0.014 0 155 0.00 PIPE 64 1594.25 140 5 695.0 9.68 ------------------------------------ --------------------- REF 922 0.00 12.330 0 500.0 64.11 0.002 0 0 0.00 PIPE 65 1594.25 140 0 500.0 0:99 --------------------------------------------------------------------------- 65.10 PSI at Supply 1594.25 GPM available at 73.49 psi FREEZER PREACTION 7 of 14 --- ROUTE NO. 2 DESCRIPTION --- Q-ADD DIA T PIPE PT PV REFERENCE LOSS/FT E FITTS PE PE Q-TOTAL C-FACT LT TOTAL PF PO NOTES -----------------------=--------------------------------------------------- OUTLET 6 22.98 2.635 0 8.1 8.25 K=8 0.00 0 0 0.01 0.00 PIPE 6 22.98 100 0 8.1 0.02 8.25 ------------------------------------ -------------------------------------- OUTLET 7 23.03 2.635 0 8.1 8.29 K=8 0.01 0 0 0.01 0.00 PIPE 7 46.01 100 0 8.1 0.08 8.29 --------------------------------------------------------------------------- OUTLET 8 23.16 2 .635 1 5.1 8.38 K=8 0.02 0 12 0.00 0.00 PIPE 8 69.17 100 0 17.1 0.35 8.38 --------------------------------------------------------------------------- REF 925 8.73 --- ROUTE NO. 3 DESCRIPTION --- Q-ADD DIA T PIPE PT PV REFERENCE LOSS/FT E FITTS PE PE Q-TOTAL C-FACT LT TOTAL PF PO NOTES --------------------------------------------------------------------------- OUTLET 9 21.72 2.635 0 9.0 7.37 K=8 0.00 0 0 0.02 0.00 PIPE 9 21.72 100 0 9.0 0.02 7.37 --------------------------------------------------------------------------- OUTLET 10 21.78 2.635 0 9.0 7.41 K=8 0.01 0 0 0.02 0.00 PIPE 10 43 .50 100 0 9.0 0.08 7.41 --------------------------------------------------------------------------- OUTLET 11 21.92 2 .635 0 9.0 7.50 K=8 0.02 0 0 0.02 0.00 PIPE 11 65.42 100 0 9.0 0.17 7.50 OUTLET 12 22.18 2.635 0 7.7 7.69 K=8 0.03 0 0 0.01 0.00 PIPE 12 87.60 100 0 7.7 0.24 7.69 --------------------------------------------------------------------------- OUTLET 13 22.55 2.635 1 2.6 7.94 K=8 0.05 0 12 0.00 0.00 PIPE 13 110.15 100 0 14.6 0.70 7.94 --------------------------------------------------------------------------- REF 924 68.82 2.635 1 0.7 8.65 0.085 0 17 0.29 PIPE 66 178.96 120 0 17.7 1.49 --------------------------------------------------------------------------- FREEZER PREACTION 8 of 14 Q-ADD DIA T PIPE PT PV REFERENCE LOSS/FT E FITTS PE PE Q-TOTAL C-FACT LT TOTAL PF PO NOTES --------------------------------------------------------------------------- REF 906 0.00 6.357 0 9.5 10.43 0.002 0 0 0.09 PIPE 49 178.96 100 0 9.5 0.02 --------------------------------------------------------------------------- REF 907 10.54 --- ROUTE NO. 4 DESCRIPTION --- Q-ADD DIA T PIPE PT PV REFERENCE LOSS/FT E FITTS PE PE Q-TOTAL C-FACT LT TOTAL PF PO NOTES --------------------------------------------------------------------------- OUTLET 14 22.86 2.635 0 8.1 8.17 K=8 0.00 0 0 0.01 0.00 PIPE 14 22 .86 100 0 8.1 0.02 8.17 --------------------------------------------------------------------------- OUTLET 15 22 .91 2.635 0 8.1 8.20 K=8 0.01 0 0 0.01 0.00 PIPE 15 45.77 100 0 8.1 0.08 8.20 --------------------------------------------------------------------------- OUTLET 16 23.04 2 .635 1 5.1 8 .29 K=8 0.02 0 12 0.00 0.00 PIPE 16 68.82 100 0 17.1 0.35 8.29 --------------------------------------------------------------------------- REF 924 8 .65 FREEZER PREACTION 9 of 14 --- ROUTE NO. 5 DESCRIPTION --- Q-ADD DIA T PIPE PT PV REFERENCE LOSS/FT E FITTS PE PE Q-TOTAL C-FACT LT TOTAL PF PO NOTES --------------------------------------------------------------------------- OUTLET 17 21.97 2.635 0 9.0 7.54 K=8 0.00 0 0 0.02 0.00 PIPE 17 21.97 100 0 9.0 0.02 7.54 --------------------------------------------------------------------------- OUTLET 18 22.02 2.635 0 9.0 7.58 K=8 0.01 0 0 0.02 0.00 PIPE 18 43.99 100 0 9.0 0.08 7.58 --------------------------------------------------------------------------- OUTLET 19 22.16 2.635 0 9.0 7.67 K=8 0.02 0 0 0.02 0.00 PIPE 19 66.15 100 0 9.0 0.17 7.67 --------------------------------------------------------------------------- OUTLET 20 22.43 2.635 0 7.7 7.86 K=8 0.03 0 0 0.01 0.00 PIPE 20 88.58 100 0 7.7 0.25 7.86 --------------------------------------------------------------------------- OUTLET 21 22.80 2.635 1 2.6 8.12 K=8 0.05 0 12 0.00 0.00 PIPE 21 111.38 100 0 14.6 0.72 8.12 --------------------------------------------------------------------------- REF 926 69.59 2 .635 1 0.7 8.84 0.086 0 17 0.29 PIPE 68 180.97 120 0 17.7 1.52 --------------------------------------------------------------------------- REF 908 10.66 --- ROUTE NO. 6 DESCRIPTION --- Q-ADD DIA T PIPE PT PV REFERENCE LOSS/FT E FITTS PE PE Q-TOTAL C-FACT LT TOTAL PF PO NOTES --------------------------------------------------------------------------- OUTLET 22 23 .12 2.635 0 8.1 8.35 K=8 0.00 0 0 0.01 0.00 PIPE 22 23.12 100 0 8.1 0.02 8.35 --------------------------------------------------------------------------- OUTLET 23 23 .17 2.635 0 8.1 8.39 K=8 0.01 0 0 0.01 0.00 PIPE 23 46.29 100 0 8.1 0.08 8.39 OUTLET 24 23 .30 2.635 1 5.1 8.48 K=8 0.02 0 12 0.00 0.00 PIPE 24 69.59 100 0 17.1 0.35 8.48 --------------------------------------------------------------------------- REF 926 8.84 FREEZER PREACTION 10 of 14 --- ROUTE NO. 7 DESCRIPTION --- Q-ADD DIA T PIPE PT PV REFERENCE LOSS/FT E FITTS PE PE Q-TOTAL C-FACT LT TOTAL PF PO NOTES ---------------------------------------------------------------------------- OUTLET 25 22.19 2.635 0 9.0 7.69 K=8 0.00 0 0 0.02 0.00 PIPE 25 22.19 100 0 9.0 0.02 7.69 --------------------------------------------------------------------------- OUTLET 26 22 .24 2.635 0 9.0 7.73 K=8 0.01 0 0 0.02 0.00 PIPE 26 44.43 100 0 9.0 0.08 7.73 --------------------------------------------------------------------------- OUTLET 27 22.38 2.635 0 9.0 7.83 K=8 0.02 0 0 0.02 0.00 PIPE 27 66.81 100 0 9.0 0.17 7.83 --------------------------------------------------------------------------- OUTLET 28 22.65 2.635 0 7.7 8.02 K=8 0.03 0 0 0.01 0.00 PIPE 28 89.46 100 0 7.7 0.25 8.02 --------------------------------------------------------------------------- OUTLET 29 23 .03 2.635 1 2.6 8.28 K=8 0.05 0 12 0.00 0.00 PIPE 29 112.49 100 0 14.6 0.73 8.28 --------------------------------------------------------------------------- REF 927 70.29 2.635 1 0.7 9.01 0.088 0 17 0.29 PIPE 69 182.78 120 0 17.7 1.55 --------------------------------------------------------------------------- REF 910 10.86 --- ROUTE NO. 8 DESCRIPTION --- Q-ADD DIA T PIPE PT PV REFERENCE LOSS/FT E FITTS PE PE Q-TOTAL C-FACT LT TOTAL PF PO NOTES --------------------------------------------------------------------------- OUTLET 30 23 .35 2.635 0 8.1 8.52 K=8 0.00 0 0 0.01 0.00 PIPE 30 23.35 100 0 8.1 0.02 8.52 --------------------------------------------------------------------------- OUTLET 31 23.40 2:635 0 8.1 8.56 K=8 0.01 0 0 0.01 0.00 PIPE 31 46.75 100 0 8.1 0.08 8.56 --------------------------------------------------------------------------- OUTLET 32 23 .53 2.635 1 5.1 8.65 K=8 0.02 0 12 0.00 0.00 PIPE 32 70.29 100 0 17.1 0.36 8.65 --------------------------------------------------------------------------- REF 927 9.02 FREEZER PREACTION 11 of 14 --- ROUTE NO. 9 DESCRIPTION --- Q-ADD DIA T PIPE PT PV REFERENCE LOSS/FT E FITTS PE PE Q-TOTAL C-FACT LT TOTAL PF PO NOTES ------------------------ - -------------------------------------------------- OUTLET 33 26.28 2.635 1 5.8 10.79 K=8" - 0.00 0 16 " 0.29 0.00 PIPE 33 26.28 100 1 21_8 0.07 10.79 --------------------------------------------------------------------------- REF 911 11.16 --- ROUTE NO. 10 DESCRIPTION --- Q-ADD DIA T PIPE PT PV REFERENCE LOSS/FT E FITTS PE PE Q-TOTAL C-FACT LT TOTAL PF PO NOTES --------------------------------------------- ----------------------------- OUTLET 34 37.97 2.157 0 9.0 22.53 K=8 0.02 0 0 0.00 0.00 PIPE 34 37.97 100 0 9.0 0.16 22.53 --------------------------------------------------------------------------- OUTLET 35 38.11 2.157 0 13.9 22 .69 K=8 0.06 2 9 3 .76 0.00 PIPE 35 76.08 100 0 22.9 1.47 22.69 REF 901 0.00 6.357 0 4.0 27.93 0.000 0 0 0.00 PIPE 44 76.08 100 0 4.0 0.00 --------------------------------------------------------------------------- REF 902 90.58 6.357 0 4.3 27.93 0.001 0 0 0.00 PIPE 45 166.66 100 0 4.3 0.01 ----=-----------------"--------------------------------=-------------------- REF 903 75.59 6.357 0 4.3 27.93 0.003 0 0 0.00 PIPE 46 242.25 100 0 4.3 0.01 --------------------------------------------------------------------------- REF 904 64.18 6.357 0 4.3 27.95 0.004 0 0 0.00 PIPE 47 306.43 100 0 4.3 0.02 --------------------------------------------------------------------------- REF 905 38.94 6.157 0 235.0 27.97 0.006 0 7 0.00 PIPE 48 345.37 100 1 242.0 1.55 --------------------------------------------------------------------------- REF 909 0.00 6.157 0 125.0 29.52 0.006 0 35 0.00 PIPE 52 345.37 100 5 160.0 1.03 it i FREEZER PREACTION 12 of 14 Q-ADD DIA T PIPE PT PV REFERENCE LOSS/FT E FITTS PE PE Q-TOTAL C-FACT LT TOTAL PF PO NOTES --------------------------------------------------------------------------- REF 916 0.00 6.357 1 16.0 30.54 0.005 0 74 5.21 PIPE 59 345.37 100 0 90.0 0.49 --------------------------------------------------------------------------- REF 917 36.24 --- ROUTE NO. 11 DESCRIPTION --- Q-ADD DIA T PIPE PT PV REFERENCE LOSS/FT E FITTS PE PE Q-TOTAL C-FACT LT TOTAL PF PO NOTES --------------------------------------------------------------------------- OUTLET 36 30.01 2.157 0 8.0 14.07 K=8 0.01 0 0 0.00 0.00 PIPE 36 30.01 100 0 8.0 0.09 14.07 --------------------------------------------------------------------------- OUTLET 37 30.11 2.157 0 8.0 14 .16 K=8 0.04 0 0 0.00 0.00 PIPE 37 60.12 100 0 8.0 0.33 14.16 --------------------------------------------------------------------------- OUTLET 38 30.46 2.157 1 24.7 14.50 K=8 0.09 1 14 9.98 0.00 PIPE 38 90.58 100 0 38.7 3 .45 14.50 ----------------------------------------=---------------------------------- REF 902 27.93 --- ROUTE NO. 12 DESCRIPTION --- Q-ADD DIA T PIPE PT PV REFERENCE LOSS/FT E FITTS PE PE Q-TOTAL C-FACT LT TOTAL PF PO NOTES --------------------------------------------------------------------------- OUTLET 39 37.73 2.157 0 9.0 22 .24 K=8 0.02 0 0 0.00 0.00 PIPE 39 37.73 100 0 9.0 0.16 22.24 --------------------------------------------------------------------------- OUTLET 40 37.86 2.157 1 13 .9 22.40 K=8 0.06 1 14 3 .76 0.00 PIPE 40 75.59 .100 0 27.9 1.78 22.40 --------------------------------------------------------------------------- REF 903 27.94 FREEZER PREACTION 13 of 14 --- ROUTE NO. 13 DESCRIPTION --- Q-ADD DIA T PIPE PT PV REFERENCE LOSS/FT E FITTS PE PE Q-TOTAL C-FACT LT TOTAL PF PO NOTES --------------------------------------------------------------------------- OUTLET 41 32.04 2.157 0 6.0 16.04 K=8 0.01 0 0 0.00 0.00 PIPE 41 32.04 100 0 8.0 0.10 16.04 --------------------------------------------------------------------------- OUTLET 42 32.14 2.157 1 24.7 16.14 K=8 0.05 1 14 9.98 0.00 PIPE 42 64.18 100 0 38.7 1.82 16.14 --------------------------------------------------------------------------- REF 904 27.95 --- ROUTE NO. 14 DESCRIPTION --- Q-ADD DIA T PIPE PT PV REFERENCE LOSS/FT E FITTS PE PE Q-TOTAL C-FACT LT TOTAL PF PO NOTES --------------------------------------------------------------------------- OUTLET 43 38.94 2.157 1 13 .9 23 .69 K=8 0.02 1 14 3 .76 0.00 PIPE 43 38.94 100 0 27.9 0.52 23.69 --------------------------------------------------------------------------- REF 905 27.97 FLOW CURVE- P (PSI)vs Q^1.85(GPM) 100 LEGEND A-Supply Static Pressure B-Supply Residual Pressure and Flow 90 C-Static System Pressure loss(i.e.Elev and BFP) D-System Demand Without Hose Streams E-Total Demand(System plus Hose) 80 / - EF 70 D E 60 P 50 _ 40 30 C 20 10 0 1000 2000 2500 3000 3500 4000 4500 5000 Q^1.85(GPM) Water Supply Graph Information City Data: Project Data: Static: 82 psi Design for Legacy Fire Protection, Inc. Residual: 76 psi at Design Density 0.25gpm/sq ft Flow: 1320 gpm Area of Application: 2600 sq ft System Demand Data: Total Demand of 1,594.3 gpm available at 73.5 System Flow: 1094.25 gpm 2,311.4 gpm available at system pressure of 65.1 psi System Pressure: 65.10 psi Approx. discharge density when operating area is Hose Streams: 500 gpm balanced to city supply: .292 gpm./sq.ft. Curve By Rybak Engineering, Inc. -CCK HYDRAULIC CALCULATIONS for Carla's Pasta 280 Nutmeg Road South South Windsor.., CT 3/26f 20'.8 Calculated Area: PALLETIZING DRY SYSTEM Design Data: Occupancy Classification: Ordinary Hazard II Density: 0 .20 GPM PER SQ FT Area of Application: 1, 950 sq ft Coverage Per Sprinkler: 95 sq ft NO. of Sprinklers Calculated: 22 Hose Streams: 250GPM Total Water Required 760 , 69 GPM including hose streams 760. 69 GPM required at supply pressure of 59.70 PSI Flow at Base of Riser.. 51.0.69 GPM Required Pressure at Base of Riser 45.51 PSI Supply Data: Static (PSI) 82 Residual (PSI) 76 Flow (GPM) 1320 �is+sua r�rfr�! Calculations by: CCK of � Rybak. Engineering, Inc. ct : 132 Forest Ave. Warren, MA 01083-070.9 Name 'Of Contractor Legacy Fire Protection, Inc. 592 Center Street PG Box 582 .Ludlow, MA 01056--058.2 Authority Having Jurisdiction: Local. Building official Underwriter: - Notes: Safety Factor: 20 psi 20180240 C:\w\20180240 carless pasta palletized dry sys PALLETIZING DRY SYSTEM 2 of 9 --- OUTLET TABLE --- OUTLET # K-FACTOR PRESSURE FLOW ELEV. (FEET) MIN. FLOW 1 8.000 7.003 21.17 30.10 21.17 2 8.000 7.065 21.26 30.08 21.17 3 8.000 7.271 21.57 30.06 21.17 4 8.000 7.701 22.20 30.04 21.17 5 8.000 8.441 23.24 30.02 21.17 6 8.000 9.587 24.77 30.00 21.17 7 8.000 7.042 21.23 30.10 21.17 8 8.000 7.105 21.32 30.08 21.17 9 8.000 7.311 21.63 30.06 21.17 10 8.000 7.744 22.26 30.04 21.17 11 8.000 8.487 23 .31 30.02 21.17 12 8.000 9.639 24.84 30.00 21.17 13 8.000 7.181 21.44 30.10 21.17 14 8.000 7.245 21.53 30.08 21.17 15 8.000 7.455 21.84 30.06 21.17 16 8.000 7.895 22.48 30.04 21.17 17 8.000 8.652 23 .53 30.02 21.17 18 8.000 9.825 25.08 30.00 21.17 19 8.000 10.600 26.05 30.06 21.17 20 8.000 10.688 26.15 30.04 21.17 21 8.000 10.986 26.52 30.02 21.17 22 8.000 11.612 27.26 30.00 21.17 PALLETIZING DRY SYSTEM 3 of 9 --- PIPE TABLE --- FRICTION FRICTION VELOCITY PIPE NO. DIAMETER LENGTH FLOW GPM C LOSS/FOOT LOSS/TOTAL FEET/SECOND 1 2.157 9.00 21.17 100 0.0061 0.054 1.9 2 2.157 9.00 42.43 100 0.0219 0.197 3 .7 3 2.157 9.00 64.01 100 0.0469 0.422 5.6 4 2.157 9.00 86.21 100 0.0813 0.732 7.6 5 2.157 9.00 109.45 100 0.1264 1.138 9.6 6 2.157 18.15 134.22 100 0.1844 3.347 11.8 7 2.157 9.00 21.23 100 0.0061 0.055 1.9 8 2.157 9.00 42.55 100 0.0220 0.198 3 .7 9 2.157 9.00 64.18 100 0.0471 0.424 5.6 10 2.157 9.00 86.45 100 0.0817 0.735 7.6 11 2.157 9.00 109.75 100 0.1271 1.144 9.6 12 2.157 18.15 134.59 100 0.1853 3.364 11.8 13 2.157 9.00 21.44 100 0.0062 0.056 1.9 14 2.157 9.00 42.97 100 0.0224 0.202 3 .8 15 2.157 9.00 64.82 100 0.0480 0.432 5.7 16 2.157 9.00 87.29 100 0.0832 0.749 7.7 17 2.157 9.00 110.83 100 0.1294 1.164 9.7 18 2.157 18.15 135.90 100 0.1887 3.425 11.9 19 2.157 9.00 26.05 100 0.0089 0.080 2 .3 20 2.157 9.00 52.20 100 0.0321 0.289 4 .6 21 2.157 9.00 78.72 100 0.0687 0.618 6.9 22 2.157 18.15 105.98 100 0.1191 2.162 9.3 23 4.260 10.17 134.22 100 0.0067 0.068 3 .0 24 4.260 10.17 268.81 100 0.0242 0.246 6.1 25 4.260 10.17 404.71 100 0.0517 0.525 9.1 26 4.260 54.00 510.69 100 0.0794 4.289 11.5 27 4.260 131.00 510.69 100 0.0794 10.406 11.5 28 4.260 67.00 510.69 100 0.0794 5.322 11.5 29 8.249 3 .00 510.69 120 0.0023 0.007 3 .1 30 8.249 585.00 510.69 120 0.0023 1.327 3 .1 31 8.249 112 .00 510.69 120 0.0023 0.254 3 .1 32 7.981 19.00 510.69 120 0.0027 8.051 3 .3 33 8.260 317.00 510.69 140 0.0017 0.537 3 .1 34 8.260 695.00 760.69 140 0.0035 2.462 4.6 35 12.330 500.00 760.69 140 0.0005 0.252 2.0 � L PALLETIZING DRY SYSTEM 4 of 9 --- ROUTE NO. 1 DESCRIPTION -- Q-ADD DIA T PIPE PT PV REFERENCE LOSS/FT E FITTS PE PE Q-TOTAL C-FACT LT TOTAL PF PO NOTES ---------------------------------------------------------- OUTLET 1 21.17 2.157 0 9.0 7.00 K=8 0.01 0 0 0:01 0.00 PIPE 1 21.17 100 0 9.0 0.05 7.00 --------------------------------------------------------------------------- OUTLET 2 21.26 2.157 0 9.0 7.07 K=8 0.02 0 0 0.01 0.00 PIPE 2 42.43 100 0 9.0 0.20 7.07 ------------------------------------------------------- OUTLET 3 21.57 2.157 0 9.0 7.27 K=8 0.05 0 0 0.01 0.00 PIPE 3 64.01 100 0 9.0 0.42 7.27 -------------------------------------------------------- OUTLET 4 22.20 2.157 0 9.0 7.70 K=8 0.08 0 0 0.01 0.00 PIPE 4 86.21 100 0 9.0 0.73 7.70 ----------------------------------------------------- OUTLET 5 23 .24 2.157 0 9.0 8.44 K=8 0.13 0 0 0.01 0.00 PIPE 5 109.45 100 0 9.0 1.14 8.44 --------------------------------------------------- OUTLET 6 24.77 2.157 1 4.2 9.59 K=8 0.18 1 14 0.87 0.00 PIPE 6 134.22 100 0 18.2 3 .35 9.59 -------------------------------------------------- REF 901 0.00 4.260 0 10.2 13 .80 0.007 0 0 0.00 PIPE 23 134.22 100 0 10.2 0.07 ---------------------------------------------- REF 902 134.59 4.260 0 10.2 13 .87 0.024 0 0 0.00 PIPE 24 268.81 100 0 10.2 0.25 --------------------------------------------- REF 903 135.90 4.260 0 10.2 14.12 0.052 0 0 0.00 PIPE 25 404.71 100 0 10.2 0.53 -------------------- ---------------------------- REF 904 105.98 4.260 1 35.0 14.64 0.079 0 19 5.64 PIPE 26 510.69 100 0 54.0 4.29 ------------------------------------------------- REF 905 0.00 4.260 2 70.0 24 .58 0.079 0 61 0.00 PIPE 27 510.69 100 4 131.0 10.41 ----------------------------------------------- I i PALLETIZING DRY SYSTEM 5 of 9 Q-ADD DIA T PIPE PT Pg i REFERENCE LOSS/FT E FITTS PE PE Q-TOTAL C-FACT LT TOTAL PF PO NOTES ---------- -------------------------------------- REF 906 0.00 4.260 1 16.0 34.98 0.079 0 51 5.21 PIPE 28 510.69 100 0 67.0 5.32 ----------------------------------------------- REF 907 0.00 8.249 0 3.0 45.51 0.002 0 0 0.00 PIPE 29 510.69 120 0 3 .0 0.01 ----------------------------------------------- REF 908 0.00 8.249 0 440.0 45.52 0.002 0 145 -9.98 PIPE 30 510.69 120 10 585.0 1.33 -------------------------------------------------- REF 909 0.00 8.249 1 9.0 36.86 0.002 0 103 9.98 PIPE 31 510.69 120 0 112.0 0.25 -------------------------------------------- REF 910 0.00 7.981 0 6.0 47.10 0.003 0 13 1.30 PIPE 32 510.69 120 1 19.0 8.05 inc 8 psi forBFP ----------------------------------------------------- REF 911 0.00 8.260 1 200.0 56.45 0.002 0 117 0.00 PIPE 33 510.69 140 3 317.0 0.54 ------------------------------------------------ REF 912 250.00 8.260 1 540.0 56.99 0.004 0 155 0.00 PIPE 34 760.69 140 5 695.0 2 .46 ---------------------------------------------- REF 913 0.00 12!330 0 500.0 59.45 0.001 0 ' 0 0.00 PIPE 35 760.69 140 0 500.0 0.25 ---------------------------------------------- 59.70 PSI at City Main 760.69 GPM available at 79.84 psi PALLETIZING DRY SYSTEM 6 of 9 --- ROUTE NO. 2 DESCRIPTION --- Q-ADD DIA T PIPE PT PV REFERENCE LOSS/FT E FITTS PE PE Q-TOTAL C-FACT LT TOTAL PF PO NOTES -------------------------- _ ------------------------ OUTLET 7 21.23 2.157 0 9.0 7.04 K=8 0.01 0 0 0.01 0.00 PIPE 7 21.23 100 0 9.0 0.05 7.04 ----------------------------------------------------- OUTLET 8 21.32 2.157 0 9.0 7.10 K=8 0.02 0 0 0.01 0.00 PIPE 8 42.55 100 0 9.0 0.20 7.10 --------------------------------------------------- OUTLET 9 21.63 2.157 0 9.0 7.31 K=8 0.05 0 0 0.01 0.00 PIPE 9 64.18 100 0 9.0 0.42 7.31 ------------------------------------------------- OUTLET 10 22.26 2.157 0 9.0 7.74 K=8 0.08 0 0 0.01 0.00 PIPE 10 86.45 100 0 9.0 0.74 7.74 ------------------------------------------------- OUTLET 11 23 .31 2.157 0 9.0 8.49 K=8 0.13 0 0 0.01 0.00 PIPE 11 109.75 100 0 9.0 1.14 8.49 ------------------------------------------------- OUTLET 12 24.84 2.157 1 4.2 9.64 K=8 0.19 1 14 0.87 0.00 PIPE 12 134.59 100 0 18.2 3 .36 9.64 ------------------------------------------------- REF 902 13 .87 PALLETIZING DRY SYSTEM 7 of 9 --- ROUTE NO. 3 DESCRIPTION --- Q-ADD DIA T PIPE PT pV REFERENCE LOSS/FT E FITTS PE PE Q-TOTAL C-FACT LT TOTAL PF O NOTES ---------------------- OUTLET 13 21.44 2.157 0 9.0 7.18 K=8 0.01 0 0 0.01 0.00 PIPE 13 21.44 100 0 9.0 0.06 7.18 ------------------------------------------------- OUTLET 14 21.53 2.157 0 9.0 7.25 K=8 0.02 0 0 0.01 0.00 PIPE 14 42.97 100 0 9.0 0.20 7.25 ------------------------------------------------- OUTLET 15 21.84 2.157 0 9.0 7.46 K=8 0.05 0 0 0.01 0.00 PIPE 15 64.82 100 0 9.0 0.43 7.46 ----------------------------------------------- OUTLET 16 22.48 2.157 0 9.0 7.90 K=8 0.08 0 0 0.01 0.00 PIPE 16 87.29 100 0 9.0 0.75 7.90 ----------------------------------------------- OUTLET 17 23 .53 2.157 0 9.0 8.65 K=8 0.13 0 0 0.01 0.00 PIPE 17 110.83 100 0 9.0 1.16 8.65 ----------------------------------------------- OUTLET 18 25.08 2.157 1 4.2 9.83 K=8 0.19 1 14 0.87 0.00 PIPE 18 135.90 100 0 18.2 3 .43 9.83 ---------------------------------------------- REF 903 14.12 y PALLETIZING DRY SYSTEM 8 of 9 --- ROUTE NO. 4 DESCRIPTION --- Q-ADD DIA T PIPE PT PV REFERENCE LOSS/FT E FITTS PE PE Q-TOTAL C-FACT LT TOTAL PF PO NOTES ---------------------------------------------------- OUTLET 19 26.05 2.157 0 9.0 10.60 K=8 0.01 0 0 - 0.01 0.00 PIPE 19 26.05 100 0 9.0 0.08 10.60 ---------------------- --------------------------------------------------- OUTLET 20 26.15 2.157 0 9.0 10.69 K=8 0.03 0 0 0.01 0.00 PIPE 20 52.20 .100 0 9.0 0.29 10.69 ------------------------------------------------------ OUTLET 21 26.52 2.157 0 9.0 10.99 K=8 0.07 0 0 0.01 0.00 PIPE 21 78.72 100 0 9.0 0.62 10.99 ---------------------------------------------------- OUTLET 22 27.26 2.157 1 4.2 11.61 K=8 . 0.12 1 14 0.87 0.00 PIPE 22 105.98 .100 0 18.2 2 .16 11.61 -------------------------------------------------- REF 904 14.64 FLOW CURVE- P (PSI)vs Q^1.85 (GPM) 100 i 90 I F 80 B 70 60 E P 50 40 30 20 LEGEND C A-Supply Static Pressure B-Supply Residual Pressure and Flow C-Static System Pressure loss(i.e.Elev and BFP) 10 D-System Demand Without Hose Streams E-Total Demand(System plus Hose) 0 400 800 1000 1200 1400 1600 1800 - 2000 Q^1.85(GPM) Water Supply Graph Information City Data: Project Data: Static: 82 psi Design for Legacy Fire Protection, Inc. Residual: 76 psi at Design Density 0.20gpm/sq ft Flow: 1320 gpm Area of Application: 1,950 sq ft System Demand Data: Total Demand of 760.7 gpm available at 79.8 System Flow: 510.69 gpm 2;685.5 gpm available at system pressure of 59.7 psi System Pressure: 59.70 psi Approx. discharge density when operating area is Hose Streams: 250 gpm balanced to city supply: .254 gpm./sq.ft. Curve By Rybak Engineering, Inc. -CCK i i HYDRAULIC CALCULATIONS for Carla's Pasta 280 Nutmeg Road South South Windsor, CT 4/19/2018 Calculated Area: Production Area Design Data: Occupancy Classification: Ordinary Hazard I Density: 0 .20 GPM PER SQ FT Area of Application : 1., 500 sq ft Coverage Per Sprinkler: 95 sq ft NO. of Sprinklers Calculated: 1.8 Hose Streams: 250 GPM Total Water Required 649. 13 GPM including hose streams 649. 13 GPM required at supply pressure of 57 .37 PSI Flow at Base of Riser 399. 13 GPM Required Pressure at Base of Riser 45. 68 PSI Supply Data : Static (PSI) 82 Residual (PSI) 76 Flow (GPM) 1.320 ,ZA ti V Calculations by: CCR of . .� Rybak Engineering, Inc. 132 Forest Ave. a 13 Warren, MA 01083-0709 �f ''rurr i Name Of Contractor Legacy Fire Protection, Inc. 592 Center Street PO .Box 582 Ludlow, MA 01056-0582 Authority Having Jurisdiction: Local Building Official Underwriter: - Notes: Safety Factor: 23 psi 20180240 C:\w\20180240 carlas pasta production wet hvd I i Production Area 2 of 8 --- OUTLET TABLE --- OUTLET # K-FACTOR PRESSURE FLOW ELEV. (FEET) MIN. FLOW 1 8.000 7.678 22.17 31.00 21.17 2 8.000 7.854 22.42 31.00 21.17 3 8.000 8.495 23.32 31.00 21.17 4 8.000 7.024 21.20 31.00 21.17 5 8.000 7.186 21.44 31.00 21.17 6 8.000 7.776 22.31 31.00 21.17 7 8.000 7.653 22.13 31.00 21.17 8 8.000 7.829 22.38 31.00 21.17 9 8.000 8.468 23.28 31.00 21.17 10 8.000 7.001 21.17 31.00 21.17 11 8.000 7.162 21.41 31.00 21.17 12 8.000 7.751 22.27 31.00 21.17 13 8.000 7.767 22.30 31.00 21.17 14 8.000 7.945 22.55 31.00 21.17 15 8.000 8.593 23 .45 31.00 21.17 16 8.000 7.106 21.33 31.00 21.17 17 8.000 7.270 21.57 31.00 21.17 18 8.000 7.867 22.44 31.00 21.17 Production Area 3 of 8 --- PIPE TABLE --- FRICTION FRICTION VELOCITY PIPE NO. DIAMETER LENGTH FLOW GPM C LOSS/FOOT LOSS/TOTAL FEET/SECOND 1 1.610 9.00 22.17 120 0.0195 0.176 3 .5 2 1.610 9.00 44.59 120 0.0712 0.641 7.0 3 1.610 9.57 67.91 120 0.1550 1.484 10.7 4 1.810 9.00 21.20 120 0.0180 0.162 3 .3 5 1.610 9.00 42.65 120 0.0656 0.590 6.7 6 1.610 15.43 64.95 120 0.1428 2.203 10.2 7 1.610 9.00 22.13 120 0.0195 0.175 3 .5 8 1.610 9.00 44.52 120 0.0710 0.639 7.0 9 1.610 9.57 67.79 120 0.1546 1.480 10.7 10 1.610 9.00 21.17 120 0.0179 0.161 3 .3 11 1.610 9.00 42.58 120 0.0654 0.588 6.7 12 1.610 15.43 64.85 120 0.1424 2.196 10.2 13 1.610 9.00 22.30 120 0.0198 0.178 3 .5 14 1.610 9.00 44.85 120 0.0720 0.648 7.1 15 1.610 9.57 68.30 120 0.1567 1.500 10.8 16 1.610 9.00 21.33 120 0.0182 0.164 3 .4 17 1.610 9.00 42.90 120 0.0663 0.597 6.8 18 1.610 15.43 65.33 120 0.1444 2.227 10.3 19 4.260 10.50 132.64 120 0.0047 0.049 3 .0 20 4.260 10.50 265.50 120 0.0169 0.177 6.0 21 4.260 405.00 399.13 120 0.0359 14.553 9.0 22 4.260 81.00 399.13 120 0.0359 2.911 9.0 23 7.981 19.00 399.13 120 0.0017 8.032 2.6 24 8.260 317.00 399.13 140 0.0011 0.341 2 .4 25 8.260 695.00 649.13 140 0.0026 1.836 3 .9 26 12.330 500.00 649.13 140 0.0004 0.188 1.7 27 1.610 11.00 132.64 120 0.5350 5.885 20.9 28 1.610 11.00 132.86 120 0.5366 5.903 20.9 29 1.610 11.00 133.63 120 0.5424 5.967 21.1 Production Area 4 of 8 --- ROUTE NO. 1 DESCRIPTION --- Q-ADD DIA T PIPE PT PV REFERENCE LOSS/FT E FITTS PE PE Q-TOTAL C-FACT LT TOTAL PF PO NOTES ------------------ ------------------------------------------------- OUTLET 1 22.17 1.610 0 9.0 7.68 K=8 0.02 0 0 0.00 0.00 PIPE 1 22.17 120 0 9.0 0.18 7.68 ---------------------- ---------------------------- OUTLET 2 22.42 1.610 0 9.0 7.85 K=8 0.07 0 0 0.00 0.00 PIPE 2 44.59 120 0 9.0 0.64 7.85 ----------------------------------------------- OUTLET 3 23.32 1.610 1 1.6 8 .50 K=8 0.16 0 8 0.00 0.00 PIPE 3 67.91 120 0 9.6 1.48 8.50 ------------------------------- REF 911 64.95 1.610 1 3 .0 9.98 0.537 0 8 1.30 PIPE 28 132.86 120 0 11.0 5.90 -------------------------------------------- REF 902 132.64 4.260 0 10.5 17.18 0.017 0 0 0.00 PIPE 20 265.50 120 0 10.5 0.18 ------------------------------------------------- REF 903 133.63 4.260 1 315.0 17.36 0.036 0 90 0.00 PIPE 21 399.13 120 8 405.0 14.55 --------------------------------------------- REF 904 0.00 4.260 1 9.0 31.91 0.036 0 72 10.85 PIPE 22 399.13 120 0 81.0 2 .91 --------------------------- ------------------ REF 905 0.00 7.981 0 6.0 45.68 0.002 0 13 1.30 PIPE 23 399.13 120 1 19.0 8.03 'inc '8 psi forBFP REF 906 0.00 8.260 1 200.0 55.01 0.001 0 117 0.00 PIPE 24 399.13 140 3 317.0 0.34 ---------------------------------------------- REF 907 250.00 8.260 1 540.0 55.35 0.003 0 155 0.00 PIPE 25 649.13 140 5 695.0 1.84 -------------------------------------------------=- REF 908 0.00 12.330 0 500.0 57.19 0.000 0 0 0.00 PIPE 26 649.13 140 0 500.0 0.19 ----------------------------------------------- Production Area 5 of 8 Q-ADD DIA T PIPE PT PV REFERENCE LOSS/FT E FITTS PE PE Q-TOTAL C-FACT LT TOTAL PF PO NOTES --------------------------------------------------- 57.37 PSI at Supply 649.13 GPM available at 80.39 psi --- ROUTE NO. 2 DESCRIPTION --- Q-ADD DIA T PIPE PT PV REFERENCE LOSS/FT E FITTS PE PE Q-TOTAL C-FACT LT TOTAL PF PO NOTES ------------------------------------------------------------ OUTLET 4 21.20 1.610 0 9.0 7.02 K=8 0.02 0 0 0.00 0.00 PIPE 4 21.20 120 0 9.0 0.16 7.02 -------------------------------------------------------------- OUTLET 5 21.44 1.610 0 9.0 7.19 K=8 0.07 0 0 0.00 0.00 PIPE 5 42.65 120 0 9.0 0.59 7.19 --------------------------------------------------------------- OUTLET 6 22.31 1.610 1 7.4 7.78 K=8 0.14 0 8 0.00 0.00 PIPE 6 64.95 120 0 15.4 2.20 7.78 -------------------------------------------------------------- REF 911 9.98 Production Area 6 of 8 --- ROUTE NO. 3 DESCRIPTION --- Q-ADD DIA T PIPE PT PV REFERENCE LOSS/FT E FITTS PE PE Q-TOTAL C-FACT LT TOTAL PF PO NOTES I ------------------------ ------------------------------------------------ OUTLET 7 22.13 1.610 0 9.0 7.65 K=8 0.02 0 0 0.00 0.00 PIPE 7 22.13 120 0 9.0 0.18 7.65 --------------------------------------------------- OUTLET 8 22.38 1.610 0 9.0 7.83 K=8 0.07 0 0 0.00 0.00 PIPE 8 44.52 120 0 9.0 0.64 7.83 ------------------------------------------ OUTLET 9 23.28 1.610 1 1.6 8.47 K=8 0.15 0 8 0.00 0.00 PIPE 9 67.79 120 0 9.6 1.48 8.47 -------------------------------------------------- REF 910 64.85 1.610 1 3.0 9.95 0.535 0 8 1.30 PIPE 27 132.64 120 0 11.0 5.89 ----------------------------------------------- REF 901 0.00 4.260 0 10.5 17.13 0.005 0 0 0.00 PIPE 19 132.64 120 0 10.5 0.05 --------------------------------------------- REF 902 17.18 --- ROUTE NO. 4 DESCRIPTION --- Q-ADD DIA T PIPE PT PV REFERENCE LOSS/FT E FITTS PE PE Q-TOTAL C-FACT LT TOTAL PF PO NOTES --------------------------------------------------- OUTLET 10 21.17 1.610 0 9.0 7.00 K=8 0.02 0 0 0.00 0.00 PIPE 10 21.17 120 0 9.0 0.16 7.00 --------------------- ------------------------------ OUTLET 11 21.41 1.610 0 9.0 7.16 K=8 0.07 0 0 0.00 0.00 PIPE 11 42.58 120 0 9.0 0.59 7.16 --------------------------------------------------- OUTLET 12 22.27 1.610 1 7.4 7.75 K=8 0.14 0 8 0.00 0.00 PIPE 12 64.85 120 0 15.4 2.20 7.75 -------------------------------------------------- REF 910 9.95 --- Production Area 7 of 8 --- ROUTE NO. 5 DESCRIPTION --- Q-ADD DIA T PIPE PT Pv REFERENCE LOSS/FT E FITTS PE PE Q-TOTAL C-FACT LT TOTAL PF PO NOTES --------------------------------------------- --------------------------- OUTLET 13 22.30 1.610 0 9.0 7.77 K=8 0.02 0 0 0.00 0.00 PIPE 13 22.30 120 0 9.0 0.18 7.77 ---------------------------------------------------- OUTLET 14 22.55 1.610 0 9.0 7.95 K=8 0.07 0 0 0.00 0.00 PIPE 14 44.85 120 0 9.0 0.65 7.95 -------------------------------------------------- OUTLET 15 23 .45 1.610 1 1.6 8.59 K=8 0.16 0 8 0.00 0.00 PIPE 15 68.30 120 0 9.6 1.50 8.59 ------------------------------------------------ REF 912 65.33 1.610 1 3.0 10.09 0.542 0 8 1.30 PIPE 29 133.63 120 0 11.0 5.97 ---------------------------------------------- REF 903 17.36 --- ROUTE NO. 6 DESCRIPTION --- Q-ADD DIA T PIPE PT PV REFERENCE LOSS/FT E FITTS PE PE Q-TOTAL C-FACT LT TOTAL PF PO NOTES -------------------------------------------------- OUTLET 16 21.33 1.610 0 9.0 7.11 K=8 0.02 0 0 0.00 0.00 PIPE 16 21.33 120 0 9.0 0.16 7.11 ------------------------ OUTLET 17 21.57 1.610 0 9.0 7.27 K=8 0.07 0 0 0.00 0.00 PIPE 17 42.90 120 0 9.0 0.60 7.27 -------------------------------------------------- OUTLET 18 22.44 1.610 1 7.4 7.87 K=8 0.14 0 8 0.00 0.00 PIPE 18 65.33 ; 120 ' 0 15.4 2 .23 7.87 -------------------------------------------------- REF 912 10.09 FLOW CURVE -P (PSI)vs Q^1.85 (GPM) 100 90 80 B 70 60 P E 50 -- 40 30 )- LEGEND 20 A-Supply Static Pressure B-Supply Residual Pressure and Flow C-Static System Pressure loss(i.e.Elev and BFP) D-System Demand Without Hose Streams 10 E-Total Demand(System plus Hose) 0 -1 1 —..[ -"** --*,—"-"-,-- L - , 400 800 1000 1200 1400 1600 1800 2000 Q^1.85(GPM) Water Supply Graph Information City Data: Project Data: Static: 82 psi Design for legacy Fire Protection, Inc. Residual: 76 psi at Design Density 0.20gpm/sq ft Flow: 1320 gpm Area of Application: 1,500 sq ft System Demand Data: Total Demand of 649.1 gpm available at 80.4 System Flow: 399.13 gpm 2,833.8 gpm available at system pressure of 57.4 psi System Pressure: 57.37 psi Approx. discharge density when operating area is Hose Streams: 250 gpm balanced to city supply: .267 gpm./sq.ft. Curve By Rybak Engineering, Inc. -CCK HYDRAULIC CALCULATIONS for Carla`s Pasta 280 Nutmeg Road South South Windsor_, CT - 3/26/2018 Calculated Area: PALLETIZING DRY SYSTEM Design Data: Occupancy Classification: Ordinary Hazard II Density: 0.20 GPM PER SQ FT Area of Application: 1, 950 sq ft Coverage Per Sprinkler: 95 sq ft NO. of Sprinklers Calculated: 22 Hose Streams: 250 GPM Total Water Required 760 .69 GPM including hose streams 760. 69 GPM required at supply pressure of 59.70 PSI Flow at Base of Riser 510. 69 GPM Required Pressure at Base of Riser 45.51 PSI Supply Data: Static (PSI) 82 Residual (PSI) 76 Flow (GPM) 1320 litttit�a �ttrt�r Calculations by: CCK of � ..... Rybak Engineering, Inc. C-1 ;• 132 Forest Ave. Warren, MA 01083-070'9 * No.18498 Name O_ Contractor ., S Y + r �1 d Legacy Fire Protection, Inc. �l`''�,,,, A1. 592 Center Street PC' Fox 582 Ludlow, MA 01056-0582 Authority Having Jurisdiction: Local Building official Underwriter: - Notes: Safety Factor: 20 psi 20180240 C:\w\20180240 carlas pasta palletized dry sys PALLETIZING DRY SYSTEM 2 of 9 --- OUTLET TABLE --- OUTLET # K-FACTOR PRESSURE FLOW ELEV. (FEET) MIN. FLOW 1 8.000 7.003 21.17 30.10 21.17 2 8.000 7.065 21.26 30.08 21.17 3 8.000 7.271 21.57 30.06 21.17 4 8.000 7.701 22.20 30.04 5 8.000 8.441 23.24 30.02 21.17 21.17 6 8.000 9.587 24.77 30.00 21.17 7 8.000 7.042 21.23 30.10 21.17 8 8.000 7.105 21.32 30.08 21.17 9 8.000 7.311 21.63 30.06 21.17 10 8.000 7.744 22.26 30.04 21.17 11 8.000 8.487 23.31 30.02 21.17 12 8.000 9.639 24.84 30.00 21.17 13 8.000 7.181 21.44 30.10 21.17 14 8.000 7.245 21.53 30.08 21.17 15 8.000 7.455 21.84 30.06 21.17 16 8.000 7.895 22.48 30.04 21.17 17 8.000 8.652 23.53 30.02 21.17 18 8.000 9.825 25.08 30.00 21.17 19 8.000 10.600 26.05 30.06 21.17 20 8.000 10.688 26.15 30.04 21.17 21 8.000 10.986 26.52 30.02 21.17 22 8.000 11.612 27.26 30.00 21.17 PALLETIZING DRY SYSTEM 3 of 9 --- PIPE TABLE --- FRICTION FRICTION VELOCITY PIPE NO. DIAMETER LENGTH FLOW GPM C LOSS/FOOT LOSS/TOTAL FEET/SECOND 1 2.157 9.00 21.17 100 0.0061 0.054 1.9 2 2.157 9.00 42.43 100 0.0219 0.197 3 .7 3 2.157 9.00 64.01 100 0.0469 0.422 5.6 4 2.157 9.00 86.21 100 0.0813 0.732 7.6 5 2.157 9.00 109.45 100 0.1264 1.138 9.6 6 2.157 18.15 134.22 100 0.1844 3.347 11.8 7 2.157 9.00 21.23 100 0.0061 0.055 1.9 8 2.157 9.00 42.55 _ 100 0.0220 0.198 3 .7 9 2.157 9.00 64.18 100 0.0471 0.424 5.6 10 2.157 9.00 86.45 100 0.0817 0.735 7.6 11 2.157 9.00 109.75 100 0.1271 1.144 9.6 12 2.157 18.15 134.59 100 0.1853 3.364 11.8 13 2.157 9.00 21.44 100 0.0062 0.056 1.9 14 2.157 9.00 42.97 100 0.0224 0.202 3 .8 15 2.157 9.00 64.82 100 0.0480 0.432 5.7 16 2.157 9.00 87.29 100 0.0832 0.749 7.7 17 2.157 9.00 110.83 100 0.1294 1.164 9.7 18 2.157 18.15 135.90 100 0.1887 3.425 11.9 19 2.157 9.00 26.05 100 0.0089 0.080 2 .3 20 2.157 9.00 52.20 100 0.0321 0.289 4 .6 21 2.157 9.00 78.72 100 0.0687 0.618 6.9 22 2.157 18 .15 105.98 100 0.1191 2.162 9.3 23 4.260 10.17 134.22 100 0.0067 0.068 3 .0 24 4.260 10.17 268.81 100 0.0242 0.246 6.1 25 4.260 10.17 404.71 100 0.0517 0.525 9.1 26 4.260 54.00 510.69 100 0.0794 4.289 11.5 27 4.260 131.00 510.69 100 0.0794 10.406 11.5 28 4.260 67.00 510.69 100 0.0794 5.322 11.5 29 8.249 3 .00 510.69 120 0.0023 0.007 3 .1 30 8.249 585.00 510.69 120 0.0023 1.327 3.1 31 8.249 112.00 510.69 120 0.0023 0.254 3 .1 32 7.981 19.00 510.69 120 0.0027 8.051 3 .3 33 8.260 317.00 510.69 140 0.0017 0.537 3 .1 34 8.260 695.00 760.69 140 0.0035 2.462 4 .6 35 12.330 500.00 760.69 140 0.0005 0.252 2 .0 PALLETIZING DRY SYSTEM 4 of 9 --- ROUTE NO. 1 DESCRIPTION --- Q-ADD DIA T PIPE PT PV REFERENCE LOSS/FT E FITTS PE PE Q-TOTAL C-FACT LT TOTAL PF PO NOTES ----------------------------------------------------- OUTLET 1 21.17 2.157 0 9.0 7.00 K=8 0.01 0 0 0.01 0.00 PIPE 1 21.17 100 0 9.0 0.05 7.00 --------------------------------------------- OUTLET 2 21.26 2.157 0 9.0 7.07 K=8 0.02 0 0 0.01 0.00 PIPE 2 42.43 100 0 9.0 0.20 7.07 ----------------------------- ---------------------------------------------- OUTLET 3 21.57 2.157 0 9.0 7.27 K=8 0.05 0 0 0.01 0.00 PIPE 3 64.01 100 0 9.0 0.42 7.27 ----------------------------------------------- OUTLET 4 22.20 2.157 0 9.0 7.70 K=8 0.08 0 0 0.01 0.00 PIPE 4 86.21 100 0 9.0 0.73 7.70 ----------------------------------------------- OUTLET 5 23.24 2.157 0 9.0 8 .44 K=8 0.13 0 0 0.01 0.00 PIPE 5 109.45 100 0 9.0 1.14 8.44 ---------------------------------------------- OUTLET 6 24.77 2.157 1 4.2 9.59 K=8 0.18 1 14 0.87 0.00 PIPE 6 134.22 100 0 18.2 3.35 9.59 ----------------- ------------------------------- REF 901 0.00 4.260 0 10.2 13 .80 0.007 0 0 0.00 PIPE 23 134.22 100 0 10.2 0.07 ----------------------------------------------- REF 902 134.59 4.260 0 10.2 13 .87 0.024 0 0 0.00 PIPE 24 268.81 100 0 10.2 0.25 ------------------------------------------------ REF 903 135.90 4.260 0 10.2 14.12 0.052 . 0 0 0.00 PIPE 25 404.71 • 100 0 10.2 0.53 -------------------------------------------------- REF 904 105.98 4.260 1 35.0 14.64 0.079 0 19 5.64 PIPE 26 510.69 100 0 54.0 4.29 ----------------------------------------------- REF 905 0.00 4.260 2 70.0 ' 24.58 0.079 0 61 0.00 PIPE 27 510.69 100 4 131.0 10.41 ------------------------------------------- PALLETIZING DRY SYSTEM 5 of 9 Q-ADD DIA T PIPE PT PV REFERENCE LOSS/FT E FITTS PE PE Q-TOTAL C-FACT LT TOTAL PF PO NOTES --------------------------------------------------------------------------- REF 906 0.00 4.260 1 16.0 34.98 0.079 0 51 5.21 PIPE 28 510.69 100 0 67.0 5.32 --------------------------------------------------------------------------- REF 907 0.00 8.249 0 3.0 45.51 0.002 0 0 0.00 PIPE 29 510.69 120 0 3.0 0.01 --------------------------------------------------------------------------- REF 908 0.00 8.249 0 440.0 45.52 0.002 0 145 -9.98 PIPE 30 510.69 120 10 585.0 1.33 --------------------------------------------------------------------------- REF 909 0.00 8.249 1 9.0 36.86 0.002 0 103 9.98 PIPE 31 510.69 120 0 112.0 0.25 --------------------------------------------------------------------------- REF 910 0.00 7.981 0 6.0 47.10 0.003 0 13 1.30 PIPE 32 510.69 120 1 19.0 8 .05 inc 8 psi forBFP --------------------------------------------------------------------------- REF 911 0.00 8.260 1 200.0 56.45 0.002 0 117 0.00 PIPE 33 510.69 140 3 317.0 0.54 --------------------------------------------------------------------------- REF 912 250.00 8.260 1 540.0 56.99 0.004 0 155 0.00 PIPE 34 760.69 140 5 695.0 2 .46 --------------------------------------------------------------------------- REF 913 0.00 12.330 0 500.0 59.45 0.001 0 0 0.00 PIPE 35 760.69 140 0 500.0 0.25 --------------------------------------------------------------------------- 59.70 PSI at City Main 760.69 GPM available at 79.84 psi PALLETIZING DRY SYSTEM 6 of 9 -- ROUTE NO. 2 DESCRIPTION --- Q-ADD DIA T PIPE PT PV REFERENCE LOSS/FT E FITTS PE PE Q-TOTAL C-FACT' LT TOTAL PF PO NOTES --------------------------------------------------------------------------- OUTLET 7 21.23 2.157 0 9.0 7.04 K=8 0.01 0 0 0.01 0.00 PIPE 7 21.23 100 0 9.0 0.05 7.04 --------------------------------------------------------------------------- OUTLET 8 21.32 2 .157 0 9.0 7.10 K=8 0.02 0 0 0.01 0.00 PIPE 8 42.55 100 0 9.0 0.20 7.10 --------------------------------------------------------------------------- OUTLET 9 21.63 2 .157 0 9.0 7.31 K=8 0.05 0 0 0.01 0.00 PIPE 9 64.18 100 0 9.0 0.42 7.31 --------------------------------------------------------------------------- OUTLET 10 22.26 2 .157 0 9.0 7.74 K=8 0.08 0 0 0.01 0.00 PIPE 10 86.45 100 0 9.0 0.74 7.74 --------------------------------------------------------------------------- OUTLET 11 23.31 2 .157 0 9.0 8.49 K=8 0.13 0 0 0.01 0.00 PIPE 11 109.75 100 0 9.0 1.14 8.49 --------------------------------------------------------------------------- OUTLET 12 24.84 2 .157 1 4.2 9.64 K=8 0.19 1 14 0.87 0.00 PIPE 12 134.59 100 0 18.2 3 .36 9.64 --------------------------------------------------------------------------- REF 902 13 .87 PALLETIZING DRY SYSTEM 7 of 9 --- ROUTE NO. 3 DESCRIPTION --- Q.-ADD DIA T PIPE PT PV REFERENCE LOSS/FT E FITTS PE PE Q-TOTAL C-FACT LT TOTAL PF PO NOTES -----------------------------------=--------------------------------------- OUTLET 13 21.44 2.157 0 9.0 7.18 K=8 0.01 0 0 0.01 0.00 PIPE 13 21.44 100 0 9.0 0.06 7.18 --------------------------------------------------------------------------- OUTLET 14 21.53 2.157 0 9.0 7.25 K=8 0.02 0 0 0.01 0.00 PIPE 14 42.97 100 0 9.0 0.20 7.25 --------------------------------------------------------------------------- OUTLET 15 21.84 2.157 0 9.0 7.46 K=8 0.05 0 0 0.01 0.00 PIPE 15 64.82 100 0 9.0 0.43 7.46 --------------------------------------------------------------------------- OUTLET 16 22.48 2.157 0 9.0 7.90 K=8 0.08 0 0 0.01 0.00 PIPE 16 87.29 100 0 9.0 0.75 7.90 ---------------------------------------------------------------------- OUTLET 17 23 .53 2.157 0 9.0 8.65 K=8 0.13 0 0 0.01 0.00 PIPE 17 110.83 100 0 9.0 1.16 8.65 --------------------------------------------------------------------------- OUTLET 18 25.08 2.157 1 4.2 9.83 K=8 0.19 1 14 0.87 0.00 PIPE 18 135.90 100 0 18.2 3 .43 9.83 ------------------------------------------------------------------------- REF 903 14.12 PALLETIZING DRY SYSTEM 8 of 9 --- ROUTE NO. 4 DESCRIPTION --- Q-ADD DIA T PIPE PT PV REFERENCE LOSS/FT E FITTS PE PE Q-TOTAL C-FACT LT TOTAL PF PO NOTES --------------------------------------------------------------------------- OUTLET 19 26.05 2.157 0 9.0 10.60 K=8 0.01 0 0 0.01 0.00 PIPE 19 26.05 100 0 9.0 0.08 10.60 --------------------------------------------------------------------------- OUTLET 20 26.15 2.157 0 9.0 10.69 K=8 0.03 0 0 0.01 0.00 PIPE 20 52.20 100 0 9.0 0.29 10.69 --------------------------------------------------------------------------- OUTLET 21 26.52 2.157 0 9.0 10.99 K=8 0.07 0 0 0.01 0.00 PIPE 21 78.72 100 0 9.0 0.62 10.99 --------------------------------------------------------------------------- OUTLET 22 27.26 2.157 1 4.2 11.61 K=8 0.12 1 14 0.87 0.00 PIPE 22 105.98 100 0 18.2 2 .16 11.61 --------------------------------------------------------------------------- REF 904 14.64 FLOW CURVE- P (PSI)vs Q^1.85 (GPM) i 100 90 F 80 B 70 60 E P 50 40 30 LEGEND 20 C A-Supply Static Pressure B-Supply Residual Pressure and Flow C-Static System Pressure loss(i.e.Elev and BFP) 10 D-System Demand Without Hose Streams E-Total Demand(System plus Hose) 0 400 800 1000 1200 1400 1600 1800 2000 Q^1.85(GPM) Water Supply Graph Information City Data: Project Data: Static: 82 psi Design for Legacy Fire Protection, Inc. Residual: 76 psi at Design Density 0.209pm/sq ft Flow: 1320 gpm Area of Application: 1,950 sq ft System Demand Data: Total Demand of 760.7 gpm available at 79.8 System Flow: 510.69 gpm 2,685.5 gpm available at system pressure of 59.7 psi System Pressure: 59.70 psi Approx. discharge density when operating area is Hose Streams: 250 gpm balanced to city supply: .254 gpm./sq. ft. Curve By Rybak Engineering, Inc. -CCK