HomeMy WebLinkAbout50 Andrews Way - Life Safety System Test (5) CONTRACTOR'S MATERIAL TEST CERTIFICATE FOR ABOVEGROUND PIPING
PROCEDURE
Upon completion of work,inspection and tests shall be made by the contracor's representative and witnessed by an owner's representative. All
defects shall be corrected and system left in service before contractor's personnel finally leave the job.
A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities,owners and contractor.
It is understood the owner's representative's signature in no way prejudices and claim against contractor for faulty material,poor workmanship
or failure to comply with aproving authority's requirements or local ordinances.
PROPERTY NAME DATE
Continental Residence at Evergreen 3/17/2017
PROPERTY ADDRESS
50 Andrews Way South Windsor CT 06074
ACCEPTED BY APPROVING AUTHORITY('S)NAMES
Walter Summers
ADDRESS
PLANS 232 West Rd South Windsor 06074
INSTALLATION CONFORMS TO ACCEPTED PLANS 0 YES EJ NO
EQUIPMENT USED IS APPROVED Q YES NO
IF NO,EXPLAIN DEVIATIONS
HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION X❑ YES NO
OF CONTROL VALVES AND CARE AND MAINTENANCE OF THIS NEW EQUIPMENT
IF NO,EXPLAIN
INSTRUCTIONS
HAVE COPIES OF APPROPRIATE INSTRUCTIONS AND CARE AND MAINTENANCE CHARTS YES X NO
AND NFPA 25 BEEN LEFT ON PREMISES
The builder has been notified that Hart Mechanical,Inc does not perform the required NFPA 25 quarterly inspections and that they
need to hire their own inspection company.
LOCATION OF
SYSTEM SUPPLIES BLDGS. Building 2-Wet System
MAKE/MODEL HEAD TYPE YEAR ORIFICE SIZE QUANITIY TEMPERATURE RATING
Tyco-LFII Res Concealed Pend 2016 1/2" 186 160°
Tyco-TYFRB Standard Pendent 2016 1/2" 25 200°
SPRINKLERS Tyco-LFII Residential Sidewall 2016 1/2" 80 155°
Tyco-DS-1 Dry Sidewall 2016 1" 24 155°
PIPE AND PIPE CONFORMS TO NFPA13 STANDARD AYES 0 NO
FITTINGS FITTINGS CONFORM TO AWWA STANDARD AYES NO
IF NO,EXPLAIN
ALARM DEVICE MAXIMUM TIME TO OPERATE THROUGH TEST PIPE
ALARM VALVE TYPE MAKE MODEL MIN. SEC.
OR FLOW Pressure Switch System Sensor ESP-40 5
INDICATOR Low Air Switch System Sensor EPS-45-2V
DRY VALVE Q.O.D.
MAKE MODEL SERIAL NO. MAKE MODELI SERIAL NO.
Victaulic 768-NXT NIA
TRIP POINT TIME WATER
WATER AIR AIR REACHED TEST ALARM OPERATED
DRY PIPE TIME TO TRIP" PRESSURE PRESSURE PRESSURE OUTLET* PROPERLY
OPERATING TEST MIN. SEC. PSI PSI PSI MIN. SEC. YES NO
I ou
Q.O.D.
Q.O.D
IF NO,EXPLAIN
*MEASURED FROM THE TIME INSPECTOR'S TEST CONNECTION VALVE IS OPENED.
HAProjectst20MContinental Residence @ Evergreen\Fire Protection\Closeout DocumentsWbove Gound Certificate 1xls (OVER)
CONTRACTOR'S MATERIAL TEST CERTIFICATE FOR ABOVEGROUND PIPING
OPERATION DPNEUMATIC ELECTRIC Lj HYDRUALIC
SUPERVISED YES NO I DETECTING MEDIA SUPERVISED S Ej NO
DELUGE& DOES VALVE FROM THE MANUAL TRIP AND/OR REMOTE CONTROL STATIO YES NO
PREACTION IS THERE AN ACCESSIBLE FA EACH CIRCUIT FOR TESTING PLAIN
VALVES YES
OES EACH CIR DOES EACH CIRCUIT
OPERATE SUPERVISION VALVE MAXIMUM TIME TO OPERATE
M MODEL LOSS ALARM RELEASE___
ELEASE RELEASE
YES NO YES NO SEC.
HYDROSTATIC: Hydrostatic tests shall be made at not less than 200 psi(13.6 bars)for two hours or 50 psi(3.4 bars)above static
pressure in excess of 150 psi(10.2 bars)for two hours. Differential dry-pipe valve clappers shall be left open during test to prevent damage.
TEST All aboveground piping leakage shall be stopped.
DESCRIPTION FLUSHING: Flow the required rate until water is clear as indicated by no collection of foreign material in burlap bags at outles such as
hydrants and blow-offs. Flush at flows not less tan 400 GPM(1514 Umin)for 4-inch pipe,600 GPM(2271 L/min)for 5-inch pipe
750 GPM(2839 Umin)for 6-inch pipe,1000 GPM(3785 Umin)for 8-inch pipe,1500 GPM(5678 Umin)for 10-inch pipe and 2000
GPM(7570Umin)for 12-inch pipe. When supply cannot produce stipulated flow rates,obtain maximum available.
PNEUMATIC: Establish 40 psi(2.7 bars)air pressure and measure drop which shall not exceed 1-1/2 psi(0.1 bars)in 24 hours. Test
pressure tanks at normal water level and air Pressure and measure air pressure drop which shall not exceed 1-1/2 psi(0.1 bars)in 24 hours
ALL PIPING HYDROSTATICALLY TESTED AT 200 PSI FOR 2 HRS. IF NO,STATE REASON
HYDROSTATICALLY TESTED: ;$l3012016;
DRY PIPING PNEUMATICALLY TESTED AYES ❑ NO
EQUIPMENT OPERATES PROPERLY X YES ❑ NO
TESTS DRAIN READING OF GAGE LOCATED NEAR WATER SUPPLY TEST PIPE: RESIDUAL PRESSURE WITH VALVE IN TEST
TEST STATIC PRESSURE PSI PIPE OPEN WIDE ;PSI
Underground mains and lead in connections to system risers flushed before connection made to sprinkler piping.
VERIFIED BY COPY OF THE U FROM NO.85B AYES ❑ NO OTHER EXPLAIN
FLUSHED BY INSTALLED OF UNDER- BY Others
GROUND SPRINKLER PIPING ❑ YES ❑ NO
BLANK TESTING NUMBER USED LOCATIONS N/A NUMBER REMOVED
GASKETS
WELDED PIPING X YES NO
IF YES...
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT WELDING PROCUDURES COMPLY
WITH THE REQUIREMENTS OF AT LEAST AWS D10.9,LEVEL AR-3 0 YES ❑ NO
SO YOU CERTIFY THAT THE WELDING WAS PERFORMED BY WELERS QUALIFIED IN
WELDING COMPLIANCE WITH THE REQUIREMENTS OF AT LEAST AWS D10.9,AR-3 0 YES. ❑ NO
DO YOU CERTIFY THAT WELDING WAS CARRIED OUT IN COMPLIANCE WITH A
DOCUMENTED QUALITY CONTROL PROCEDURE TO INSURE THAT ALL DISCS ARE
RETRIEVED,THAT OPENINGS IN PIPING ARE SMOOTH,THAT SLAG AND OTHER
WELDING RESIDUE ARE REMOVED,AND THAT THE INTERNAL DIAMETERS OF
PIPING ARE NOT PENETRATED X YES NO
HYDRAULIC DATA NAMEPLATE PROVIDED TF
NO,EXPLAIN
NAMEPLATE X YES NO
DATE LEFT IN SERVICE WITH A L C NTROL VALVES OPEN:
REMARKS Date Tested.:"` Date Left Open a
NAME OF SPRINKLER CON CTOR Hart Mechanical,Inc.
TESTS WITNESSED BY
SIGNATURES FOR PROPERTY NER( GN TITLE DATE
v -ao
FOR SPR N ACTOR(SIGNED) TITLE DATE
ADDITIONAL EXPLANATION AND NOTES