HomeMy WebLinkAbout50 Andrews Way - SFMO Modification - Fir (7) STATE OF CONNECTICUT
DEPARTMENT OF ADMINISTRATIVE SERVICES
.Division of Construction Services
OFFICE OF STATE FIRE MARSHAL.,
MODIFICATION REQUEST # FM-0239-15
PROJECT NAME: EVERGREEN WALK
ADDRESS: ANDREWS, WAY
TOWN: SOUTH WINDSOR
STATE FIRE MARSHAL
In accordance with Section 29-296 of the Connecticut General Statutes, the decision
of the Office of the State Fire Marshal in this matter is:
This request seeks to utilize the provisions of Section
1021.2 and Table 1021.2(1) of the 2012 International Fire
Code (IFC) in lieu of the provisions of Part III Section
1018.2 and Table of the 2005 CTSTATEFIRE SAFETY CODE
WITH THE 2009 AND 2012 AMENDMENTS concerning
buildings with one exit versus stories with one exit and
the additional exit access travel. Given that the State
intends to adopt this provision of the 2012 IFC, this
request is deemed ACCEPTABLE.
Evaluated by:
Terry A. Brouwer
Decision endorsed by:
a
William Abbott
STATE FIRE MARSHAL
Date: September 8, 2015
"In accordance with Connecticut General Statute 29-309, any person determined to have the right to appeal
may appeal the decision of the State Fire.Marshal in this matter to the State Codes&Standards Committee
within thirty(30)days after receipt."
State Codes&Standards Committee
165 Capitol Avenue Room 265,Hartford CT 06106
Tel:860-713-5900 Fax:860-713-7410
i
STATE OF CONNECTICUT
DEPARTMENT OF ADMINISTRATIVE SERVICES
Division of Construction Services r
OFFICE OF STATE FIRE MARSHAL
1
MODIFICATION REQUEST # FM-0318-15 I
r
PROJECT NAME: EVERGREEN WALK
ADDRESS: ANDREWS WAY
TOWN: SOUTH WINDSOR
STATE FIRE MARSHAL
In accordance with Section 29-296 of the Connecticut General Statutes,the decision
of the Office of the State Fire Marshal in this matter is:
This request seeks to utilize the provisions of Section
903.3.1.2 of the 2012 International Fire Code in lieu of the
provisions of Part III Section 903.3.1.2 of the 2005 CT i
a
STATE FIRE SAFETY CODE WITH THE 2009 AND 2012
AMENDMENTS concerning the use of an NFPA 13R fire
sprinkler system in a mixed use building. Given that the
driving force behind the need for automatic fire sprinklers
is the Group R-2 occupancy, this request to utilize and
�i
NFPA 13R system in the Group R occupancy and a I
NFPA 13 system in the Group S-2 occupancy with the fire �t
resistive separation being provided between the
occupancies, this request is deemed ACCEPTABLE.
Evaluated by:
1
Terry A. Brouwer
Decision endorsed by:
I
William Abbott k
STATE FIRE MARSHAL
Date: November 30, 2015
"In accordance with Connecticut General Statute 29-309, any per son determined to have the right to appeal
may appeal the decision of the State Fire Marshal in this matter to the State Codes&Standards Committee .
within thirty(30)days after-receipt."
State Codes&Standards Committee
165 Capitol Avenue Room 265,Hartford CT 06106 I
Tel:860-713-5900 Fax:860-713-7410 !,
f'
It