Loading...
HomeMy WebLinkAbout27 Amato Drive - Life Safety System Test 7 i SECURITY *Quality DYNANA;RK) MEMO CENTERS Alarm Systems TM Since 1985 P.O. Box 1170 "Nationally Known, Locally Owned" Tolland, CT 06084-1170 LIC #181641 Tel. (860) 872-4050 Fax(860) 875-0493 Westage @ South Windsor Assoc., Inc. DynamarkCT@comcast.net 348 Hartford Turnpike Vernon, CT 06066 Date: 6/27/2016 For: 28 Amato Drive, SW, Building 27 RE: FIRE ALARM TESTING Attached are copies of the"FIRE ALARM SYSTEM RECORD OF COMPLETION" and the "INSPECTION AND TESTING FORM". These forms were completed upon installation and annual testing of the fire system in your building. A copy must be kept in a file on the property for a minimum of three [3] years and available if asked for by a building official or fire marshal. Michael G Casieri CC: Fire Marshal WO# 1778 olessed 6e the Lord my rock my refuge and my fortress, my strongfiio(f, my deliverer, my shield in whom I trust. PSALM 144 i FIRE ALARM SYSTEML � RECORD OF COMPLETION Name of protected property:Westage @ South Windsor Assoc., Inc. DATE: Address: 28 Amato Drive, South Windsor, CT 06074 Representative of protected property(name/phone): /860- Authority having jurisdiction: South Windsor Fire Marshal Address/telephone number: 1540 Sullivan Avenue, South Windsor, CT 06074/860-644-2511 ext. 217 Installer: Dynamark Security Centers LLC P.O. Box 1170 Tolland, CT 06084-1170 Location of operation and maintenance manuals: Dynamark Security Centers LLC and Property Owner Location of test reports: Dynamark Security Centers LLC, Property Owner and Fire Marshal System Software: 1. Type(s)of System or Service NFPA 72, Chapter 8—Central Station Prime contractor: Remote Station: CMS P.O. Box 521769 Longwood, FL 32750 Means of transmission of signals from the protected premises to the central station: X Digital alarm communicator 2. Record of System Installation T ste h been in fled in accordance with the NFPA standards as shown below)was inspected by on /2016 includes the devices shown in 5 and 6, an has been in service since & /.7-7/2016. x NFPA 72, Chapters 4 5 6 7 810 x NFPA 70, National Electric Code,Article 760 )manufacturer's instruction _Other(speci Signed: Dated -y? Organi . n: D amar Security Centers LLC 3.Record of System Operation All operational features and functions of this system were tested by AZ on /� 016 and found to be operating properly in accordance with the requirernfints of., X NFPA 72, Chapters 4 5 6 7 810 X NFPA 70, National Electric Code, and Article 760 X Manufacturer's instruct' _Other(specify, Signed: � Dater ✓�7—l� Organiza . ynam r Se rity Centers LLC 4.Sig ailing Line Circuits: N/A 5.Alarm-Initiating Devices and Circuits Quantity Ks of initiating device circuits(see NFPA 72, Table 6.5): Quantity Style:_B MANUAL (a) Manual stations No coded Transmitters Coded Addressable AUTOMATIC Coverage: Complete Partial Non required Selective (a) Smoke detectors: Photo-&— (b) Duct detectors: Photo_ (c) Heat detectors: FT RR FT/RR RC (d)Water Flow: (e)The alarm verification feature is disabled 6. Supervisory Signal-initialing Devices and Circuits (use blanks to indicate quantity of devices: SPRINKLER SYSTEM (a) Valve supervisory switches (b) (c) (d) 7.Annunciator(s) Number: Location: 8.Alarm Notification Appliances and Circuits Quantity and the class of notification appliance circuits connected to system (see NFPA 72, Table 6.7): Quantity:1---7 Style: B Types and quantities of notification appliances installed: (a)Strobes (b) Horn/Strobes (c) Other_�L ov A 5 9. System Power Supplies (a) Fire Alarm Control Panel: Nominal olta to v` Current rating: Overcurrent protection: Type: �e� e j Current rating: Location:CW;.V4Jf-t t-'s4 (b)Secondary(standby): Storage battery: Amp-hour rating: 7.5AH Calculated capacity to drive system, in hours: 10. Common : ( ' ned for ins Ilation cdnfractor and alarm service company Title Date Upon comple ' n of ystem(s) sa' actory test(s)witnessed (if required by the authority having jurisdiction): igned) repres tative of the authority having jurisdiction Title Date INSPECTION AND TESTING FORM WO#: 1778 DATFI" SERVICE ORGANIZATION PROPERTY NAME(USER) NAME: Dynamark Security Centers,LLC NAME: Westage @ South Windsor Assoc.,Inc rHi 27 ADDRESS: P.O.Box 1170 Tolland,CT 06084-1 1 70 ADDRESS: 28 Amato Drive REPRESENTATIVE: Michael G.Casieri South Windsor,CT 06074 LICENSE NO.: 181641 TELEPHONE: 860 TELEPHONE: (860)872-4050 CONTACT: CHECK HERE IF MAILING ADDRESS IS DIFFERENT MONITORING ENTITY APPROVING AGENCY CONTACT: CMS CONTACT: South Windsor Fire Marshal TELEPHONE: 1-866-229-7287 ADDRESS: 1540 Sullivan Avenue South Windsor,CT 06074 MONITORING ACCOUNT#: AN823257 TELEPHONE: 860-644-2511 ext.217 TYPE TRANSMISSION SERVICE ®-Digital ®-Annually PANEL MANUFAC R Fve- t� �5 M daJ �,, MODEL NO.:��d DATE INSTALLED: CIRCUIT STYLES:T�4 /it•�5� r'C,�' NO.OF CIRCUITS: �3-4 SOFTWARE REV.: LAST DATE SYSTEM HAD ANY SERVICE PERFORMED: ALARM INITIATING DEVICES AND CIRCUIT INFORMATION CKT. STYLE MANUAL STATIONS ION DETECTORS PHOTO DETECTORS DUCT DETECTORS HEAT DETECTORS WATERFLOW SWITCHES SUPERVISORY SWITCHES OTHER: (SPECIFY) ALARM INDICATING APPLIANCES AND CIRCUIT INFORMATION QTY CKT.STYLE I TYPE I ALOCATIO VISUAL FUNCTIONAL Ahvtt en r s G►' dr1 ✓L i 'w� i s o n JK&. P-= ern rn 1 NO.OF ALARM INDICATING CIRCUITS:,3 Ksek Vtif,vo,gZ ARE CIRCUITS SUPERVISED? %YES ❑NO SUPERVISORY SIGNAL INITIATING DEVICES AND CIRCUIT INFORMATION QTY CKT.STYLE BUILDING TEMP. SITE WATER TEMP. SITE WATER LEVEL FIRE PUMP POWER FIRE PUMP RUNNING FIRE PUMP AUTO POSITION FIRE PUMP OR PUMP CONTROLLER TROUBLE GENERATOR IN AUTO POSITION GENERATOR OR CONTROLLER TROUBLE SWITCH TRANSFER GENERATOR ENGINE RUNNING OTHER: POWER SUPPLIES: Prim (Main):Nominal Voltage ,Am s: Overcurrent Protection Type S: Location(Panel Number): Disconnecting Means Location: , b. Second (Standb ): Storage Battery#I: Amp-Hr.Rating: VDC: / AH: �Instaltd Storage Batte #2: Am -Hr.Rating: VDC: AH: Calculated capacity to o e I system,in hours: 160 TYPE BATTERY ®Sealed Lead-Acid PRIOR TO ANY TESTING NOTIFICATIONS ARE MADE: YES O WHO TBIE MONITORING ENTITY BUILDING OCCUPANTS BUILDING MANAGEMENT OTHER SPECIFY AHJ OTIFIED OF ANY IMPAIRMENTS Li I SYSTEM TESTS AND INSPECTIONS TYPE VISU FUNCTI COMMENTS CONTROLPANEL INTERFACE E E- LAMPS/LEDS FUSES PRIMARY POWER SUPPLY TROUBLE SIGNALS DISCONNECT SWITCHES GROUND FAULT MONITORING SECONDARY POWER TYPE VISUAL FUNCTIONAL COMMENTS BATTERY CONDITION LOAD VOLTAGE DISCHARGE TEST CHARGER TEST 72-114 _ NATIONAL FIRE ALARM CODE TYPE VISUAL FUNCTIONAL COMMENTS REMOTE ANNUNCIATORS ❑ ❑ NOTIFICATION APPLIANCES AUDIBLE ❑ VISUAL 1 ❑ INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS LOCATION DEVICE VISUAL FUNCTION FACTORY MEAS. PASS FAIL TYPE CHECK TEST SETTING SETTING Basement Laundry Heat Detector D— ❑ Basement Storage K&L Smoke Detector Basement Near Stairs Smoke Detector ❑ Basement Storage I Smoke Detector ❑ Basement Storage J Smoke Detector ❑ Basement Storage G&H Smoke Detector ET Basement Near Stairs Smoke Detector [' ❑ Storage E&F Smoke Detector If ❑ Storage B Smoke Detector z ❑ Basement Near Stairs Smoke Detector Outside Boiler Smoke Detector Boiler Heat Detector EK Laundry Heat Detector Over Oil Tanks Heat Detector ❑ Near Panel Pull Station ❑ Next Hallway Pull Station ❑ Last Hallway Pull Station Rr y ❑ I't Floor A-D Smoke Detector LZ ❑ 2'd Floor A-D Smoke Detector ❑ I'Floor E-H Smoke Detector ❑ 2° Floor E-H Smoke Detector ❑ 1"Floor I-L Smoke Detector ❑ 2'd Floor I-L Smoke Detector ❑ Unit J Heat Detector ❑ Unit L Heat Detector ❑ Unit I Heat Detector ❑ Unit K Heat Detector I ❑ Unit B Heat Detector ❑ Unit D Heat Detector ❑ Unit A Heat Detector ❑ Unit C Heat Detector ®� ❑ Unit E Heat Detector ❑ Unit G Heat Detector [�' ❑ Unit H Heat Detector -44 0" ❑ Unit F Heat Detector []� ❑ COMMENTS: VISUAL DEVICE SIMULATED OPERATION OPERATION INTERFACE EQUIPMENT SP ❑ ❑ ❑ SPECIAL HAZARD SYSTEMS SPEC ❑ ❑ ❑ { 72-115 INSPECTION.TESTING.AND MAINTENANCE SPECIAL PROCEDURES/COMMENTS: ON/OFF PREMISES MONITORING YES NO TIME COMMENTS ALARM SIGNAL ❑ ALARM RESTORAL ❑ TROUBLE SIGNAL ❑ SUPERVISORY SIGNAL ❑ ❑ SUPERVISORY RESTORAL ❑ ❑ NOTIFICATION THAT THIS YES NO WHO TIME TESTING IS COMPLETE: BUILDING MANAGEMENT ❑ ❑ MONITORING AGENCY ❑ BUILDING OCCUPANTS ❑ OTHER SPECIFY) ❑ ❑ SYSTEM RESTORED TO NORMAL OPERATION: DATE 2-1��1� TIME/,pZ,6 0 THIS TESTING WAS PER D C RDANCE APPLICABLE NFPA STANDARDS. NAME OF INSPECTOR DATE: 7--`r-raq SIGNATURE: NAME OF O R OR REPRESENTATIVE: DATE: SIGNATURE: