HomeMy WebLinkAbout175 Sullivan Avenue - Life Safety System (2) CONTRACTOR'S MATERIAL & TEST CERTIFICATE FOR ABOVEGROUND PIPING
PROCEDURE
UPON COMPLETION OF WORK,INSPECTION&TESTS SHALL BE MADE BY THE CONTRACTOR'S REP.AND WITNESSED BY AN OWNER'S REP.
ALL DEFECTS SHALL BE CORRECTED AND SYSTEM LEFT IN SERVICE BEFORE CONTRACTOR'S PERSONNEL LEAVE THE JOB.
A CERTIFICATE SHALL BE FILLED OUT AND SIGNED BY BOTH THE REPRESENTATIVES. COPIES SHALL BE PREPARED FOR APPROVING AUTHORITIES,OWNERS AND
CONTRACTOR. IT IS UNDERSTOOD THE OWNER'S REPRESENTATIVE'S SIGNATURE IN NO WAY PREJUDICES ANY CLAIM AGAINST CONTRACTOR FOR FAULTY
MATERIAL,POOR WORKMANSHIP,OR FAILURE TO COMPLY WITH APPROVING AUTHORITY'S REQUIREMENTS OR LOCAL ORDINANCES.
PROPERTY NAME JOB NO. JDATE
PROPERTY ADDRESS NEW DISTRIBUTION CENTER FOR VISTAR 201000
LOT 3 175 SULLIVAN AVE., SOUTH WINDSOR,CONNECTICUT 06074
ACCEPTED BY APPROVING AUTHORITIES(NAMES)
SOUTH WINDSOR,CT
ADDRESS
PLANS 1540 SULLIVAN AVE.,SOUTH WINDSOR,CT
INSTALLATION CONFORMS TO ACCEPTED PLANS X YES NO YES eN0
EQUIPMENT USED IS APPROVED
IF NO,EXPLAIN DEVIATIONS
HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION EYES El
OF CONTROL VALVES AND CARE AND MAINTENANCE OF THIS NEW EQUIPMENT? IF NO,EXPLAIN
INSTRUCTIONS HAVE COPIES OF THE FOLLOWING BEEN LEFT ON THE PREMISES:
1. SYSTEM COMPONENTS INSTRUCTIONS X YES NO
2. CARE AND MAINTENANCE INSTRUCTIONS X YES NO
3. NFPA 25 X YES NO
LOCATION WET SYSTEM 1
MAKE MODEL YEAR OF MFG. ORIFICE SIZE QUANTITY TEMP.
RELIABLE RA1914 2015 K=16.8 441 200
SPRINKLERS
PIPE AND TYPE OF PIPE SCHEDULE 7
FITTINGS TYPE OF FITTINGS GROOVED
ALARM DEVICE MAX.TIME TO OPERATE THROUGH TEST CONN.
ALARM VALVE OR TYPE MAKE MODEL MIN. SEC.
FLOW INDICAT01 FLOW SWICTH POTTER VSR
DRY VALVE Q.O.D.
MAKE MODEL SERIAL NO. MAKE MODEL SERIAL NO.
TIME TO TRIP TIME WATER ALARM
THRU TEST WATER AIR TRIP POINT REACHED OPERATED
DRY PIPE CONNECTION* PRES. PRES. AIR PRESSURE TEST OUTLET* PROPERLY
OPERATING MIN. SEC. PSI PSI PSI MIN. SEC. YES NO
TEST WITHOUT Q.O.D.
WITH Q.O.D.
*MEASURED FROM THE TIME INSPECTOR'S TEST CONNECTION IS OPENED
OPERATION PNEUMATIC ELECTRIC HYDRAULIC
PIPING SUPERVISED YES �NO DETECTING MEDIA SUPERVISED YES ONO
DELUGE& DOES VALVE OPERATE FROM THE MANUAL TRIP AND/OR REMOTE CONTROLS STATIONS DYES ONO
PREACTION IS THERE AN ACCESSIBLE FACILITY IN EACH CIRCUIT FOR TESTING IF NO,EXPLAIN
VALVES DYES F-lNO
DOES EACH CIRCUIT OPERATE DOES EACH CIRCUIT OPERATE MAXIMUM TIME TO
MAKE MODEL SUPERVISION LOSS ALARM VALVE RELEASE OPERATE RELEASE
YES INO YES NO MIN. SEC.
(OVER)
LOCATION MAKE& STATIC PRESSURE RESIDUAL PRESSURE(FLOWING) FLOW RATE
PRESSURE &FLOOR MODEL SETTING INLET(PSI) JOUTLET(PSI) INLET(PSI) OUTLET(PSI) FLOW(GPM)
REDUCING
VALVE TEST
TEST PRESSURE IN EXCESS OF 150 PSI(10.2 BARS)FOR TWO HOURS. DIFFERENTIAL DRY PIPE VALVE CLAPPERS SHALL BE LEFT OPEN
DESCRIPTION DURING TEST TO PREVENT DAMAGE. ALL ABOVEGROUND PIPING LEAKAGE SHALL BE STOPPED.
24 HOURS. TEST PRESSURE TANKS AT NORMAL WATER LEVEL AND AIR PRESSURE AND MEASURE AIR PRESSURE DROP WHICH
SHALL NOT EXCEED 1 '/z PSI(0.1 BARS)IN 24 HOURS.
ALL PIPING HYDROSTATICALLY TESTED AT j PSI FOR 2 HRS. IF NO,STATE REASON
DRY PIPING PNEUMATICALLY TESTED BYES BNO
EQUIPMENT OPERATED PROPERLY YES NO
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT ADDITIVES AND CORROSIVE CHEMICALS,SODIUM SILICATE OR
DERIVATIVES OF SODIUM SILICATE,BRINE,OR OTHER CORROSIVE CHEMICALS WERE NOT USED FOR TESTING SYSTEMS OR
TESTS STOPPING LEAKS? ®YES BNO
DRAIN I STATIC PRESSURE READING OF GAGE LOCATED NEAR WATER RESIDUAL PRESSURE WITH VALVE IN TEST
TEST SUPPLY TEST CONNECTION PSI CONNECTION OPEN WIDE PSI
UNDERGROUND MAINS AND LEAD IN CONNECTION TO SYSTEM RISERS FLUSHED BEFORE CONNECTION MADE TO SPRINKLER PIPING,
AND VERIFIED BY COPY OF FORM NO.13U BYES ONO OTHER EXPLAIN
FLUSHED BY INSTALLER OF UNDERGROUND
SPRINKLER PIPING BYES BNO
IF POWDER-DRIVEN FASTENERS ARE USED IN
CONCRETE,HAS REPRESENTATIVE SAMPLE BYES BNO NA
TESTING BEEN SATISFACTORILY COMPLETED?
BLANK TESTING Number Used Locations Number Removed
GASKETS 0 0
WELDED PIPE ®YES BNO
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT WELDING PROCEDURES COMPLY WITH THE
REQUIREMENTS OF AT LEAST AWS D10,9,LEVEL AR-3 ®YES BNO
WELDING DO YOU CERTIFY THAT THE WELDING WAS PERFORMED BY WELDERS QUALIFIED IN COMPLIANCE WITH THE
REQUIREMENTS OF AT LEAST AWS D10,9,LEVEL AR-3 ®YES El NO
DO YOU CERTIFY THAT WELDING WAS CARRIED OUT IN COMPLIANCE WITH A DOCUMENTED QUALITY CONTROL
PROCEDURE TO INSURE THAT ALL DISC ARE RETRIEVED,THAT OPENINGS IN PIPING ARE SMOOTH,THAT SLAG AND
OTHER WELDING RESIDUE ARE REMOVED,AND THAT THE INTERNAL DIAMETERS OF PIPING ARE NOT PENETRATED. ®YES [:]NO
CUTOUTS(DISKS) DO YOU CERTIFY THAT YOU HAVE A CONTROL FEATURE THAT INSURES THAT ALL
CUTOUTS(DISCS)ARE RETRIEVED? ®YES BNO
HYDRAULIC DATA NAME PLATE PROVIDED IF NO,EXPLAIN
NAMEPLATE ®YES BNO
DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN:
REMARKS
NAME OF SPRINKLER CONTRACTOR
F.E. Moran Fire Protection,3001 Research Road,Suite A,Champaign, Illinois 61822
TEST WITNESS BY
SIGNATURES F6R PRO RTY ER(SIGNED) TITLE DATE
ek
FelfSEfR,( (SI 'ED) TITLE,/ j DATE
ADDITIONAL EXPLANATION AQID TE
CONTRACTOR'S MATERIAL & TEST CERTIFICATE FOR ABOVEGROUND PIPING
UPON COMPLETION OF WORK,INSPECTION&TESTS SHALL BE MADE BY THE CONTRACTOR'S REP.AND WITNESSED BY AN OWNER'S REP.
ALL DEFECTS SHALL BE CORRECTED AND SYSTEM LEFT IN SERVICE BEFORE CONTRACTOR'S PERSONNEL LEAVE THE JOB.
A CERTIFICATE SHALL BE FILLED OUT AND SIGNED BY BOTH THE REPRESENTATIVES. COPIES SHALL BE PREPARED FOR APPROVING AUTHORITIES,OWNERS AND
CONTRACTOR. IT IS UNDERSTOOD THE OWNER'S REPRESENTATIVE'S SIGNATURE IN NO WAY PREJUDICES ANY CLAIM AGAINST CONTRACTOR FOR FAULTY
MATERIAL,POOR WORKMANSHIP,OR FAILURE TO COMPLY WITH APPROVING AUTHORITY'S REQUIREMENTS OR LOCAL ORDINANCES.
PROPERTY NAME JOB NO. DATE
PROPERTY ADDRESS NEW DISTRIBUTION CENTER FOR VISTAR 201000
LOT 3 175 SULLIVAN AVE.,SOUTH WINDSOR, CONNECTICUT 06074
ACCEPTED BY APPROVING AUTHORITIES(NAMES)
SOUTH WINDSOR,CT
ADDRESS
PLANS 1540 SULLIVAN AVE., SOUTH WINDSOR, CT
INSTALLATION CONFORMS TO ACCEPTED PLANS EYES NO
EQUIPMENT USED IS APPROVED )( YES NO
IF NO,EXPLAIN DEVIATIONS
HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION MYES 1:1NO
OF CONTROL VALVES AND CARE AND MAINTENANCE OF THIS NEW EQUIPMENT? IF NO,EXPLAIN
INSTRUCTIONS HAVE COPIES OF THE FOLLOWING BEEN LEFT ON THE PREMISES:
1. SYSTEM COMPONENTS INSTRUCTIONS )( YES NO
2. CARE AND MAINTENANCE INSTRUCTIONS X YES NO
3. NFPA 25 X YES NO
LOCATION WET SYSTEM 2
MAKE MODEL YEAR OF MFG. ORIFICE SIZE QUANTITY TEMP.
RELIABLE RA1914 2015 K=16.8 539 200
SPRINKLERS
PIPE AND TYPE OF PIPE SCHEDULE 7
FITTINGS TYPE OF FITTINGS GROOVED
ALARM DEVICE MAX.TIME TO OPERATE THROUGH TEST CONN.
ALARM VALVE OR TYPE I MAKE MODEL MIN. SEC.
FLOW INDICATOF FLOW SWICTH POTTER VSR
DRY VALVE Q.O.D.
MAKE MODEL SERIAL NO. MAKE MODEL SERIAL NO.
TIME TO TRIP TIME WATER ALARM
THRU TEST WATER AIR TRIP POINT REACHED OPERATED
DRY PIPE CONNECTION PRIES. PRIES. AIR PRESSURE TEST OUTLET` PROPERLY
OPERATING MIN. SEC. PSI PSI PSI MIN. SEC. YES NO
TEST WITHOUT Q.O.D.
WITH Q.O.D.
*MEASURED FROM THE TIME INSPECTOR'S TEST CONNECTION IS OPENED
OPERATION PNEUMATIC ELECTRIC HYDRAULIC
PIPING SUPERVISED YES NO DETECTING MEDIA SUPERVISED YES El NO
DELUGE& DOES VALVE OPERATE FROM THE MANUAL TRIP AND/OR REMOTE CONTROLS STATIONS YES �NO
PREACTION IS THERE AN ACCESSIBLE FACILITY IN EACH CIRCUIT FOR TESTING IF NO,EXPLAIN
VALVES MYES ONO
DOES EACH CIRCUIT OPERATE DOES EACH CIRCUIT OPERATE MAXIMUM TIME TO
MAKE MODEL SUPERVISION LOSS ALARM VALVE RELEASE OPERATE RELEASE
YES NO YES INO MIN. SEC.
(OVER)
LOCATION MAKE& STATIC PRESSURE RESIDUAL PRESSURE(FLOWING) FLOW RATE
PRESSURE &FLOOR MODEL I SETTING INLET(PSI) OUTLET(PSI) INLET(PSI) OUTLET(PSI) FLOW(GPM)
REDUCING
VALVE TEST
TEST PRESSURE IN EXCESS OF 150 PSI(10.2 BARS)FOR TWO HOURS. DIFFERENTIAL DRY PIPE VALVE CLAPPERS SHALL BE LEFT OPEN
DESCRIPTION DURING TEST TO PREVENT DAMAGE. ALL ABOVEGROUND PIPING LEAKAGE SHALL BE STOPPED.
z
24 HOURS. TEST PRESSURE TANKS AT NORMAL WATER LEVEL AND AIR PRESSURE AND MEASURE AIR PRESSURE DROP WHICH
SHALL NOT EXCEED 1'/2 PSI(0.1 BARS)IN 24 HOURS.
ALL PIPING HYDROSTATICALLY TESTED AT Is PSI FOR 2 HRS. IF NO,STATE REASON
DRY PIPING PNEUMATICALLY TESTED eYES BNO
EQUIPMENT OPERATED PROPERLY YES NO
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT ADDITIVES AND CORROSIVE CHEMICALS,SODIUM SILICATE OR
DERIVATIVES OF SODIUM SILICATE,BRINE,OR OTHER CORROSIVE CHEMICALS WERE NOT USED FOR TESTING SYSTEMS OR
TESTS STOPPING LEAKS? ®YES EDNO
DRAIN I STATIC PRESSURE READING OF GAGE LOCATED NEAR WATER RESIDUAL PRESSURE WITH VALVE IN TEST
TEST SUPPLY TEST CONNECTION PSI CONNECTION OPEN WIDE PSI
UNDERGROUND MAINS AND LEAD IN CONNECTION TO SYSTEM RISERS FLUSHED BEFORE CONNECTION MADE TO SPRINKLER PIPING,
AND VERIFIED BY COPY OF FORM NO.13U FlYES 0NO OTHER EXPLAIN
FLUSHED BY INSTALLER OF UNDERGROUND
SPRINKLER PIPING YES 1:1NO
IF POWDER-DRIVEN FASTENERS ARE USED IN
CONCRETE,HAS REPRESENTATIVE SAMPLE YES 0NO NA
TESTING BEEN SATISFACTORILY COMPLETED?
BLANK TESTING Number Used Locations Number Removed
GASKETS 0 1 1 0
WELDED PIPE ®YES 1:1NO
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT WELDING PROCEDURES COMPLY WITH THE
REQUIREMENTS OF AT LEAST AWS D10,9,LEVEL AR-3 ®YES 1:1NO
WELDING DO YOU CERTIFY THAT THE WELDING WAS PERFORMED BY WELDERS QUALIFIED IN COMPLIANCE WITH THE
REQUIREMENTS OF AT LEAST AWS D10,9,LEVEL AR-3 ®YES 1:1NO
DO YOU CERTIFY THAT WELDING WAS CARRIED OUT IN COMPLIANCE WITH A DOCUMENTED QUALITY CONTROL
PROCEDURE TO INSURE THAT ALL DISC ARE RETRIEVED,THAT OPENINGS IN PIPING ARE SMOOTH,THAT SLAG AND
OTHER WELDING RESIDUE ARE REMOVED,AND THAT THE INTERNAL DIAMETERS OF PIPING ARE NOT PENETRATED. ®YES [:]NO
CUTOUTS(DISKS) DO YOU CERTIFY THAT YOU HAVE A CONTROL FEATURE THAT INSURES THAT ALL
CUTOUTS(DISCS)ARE RETRIEVED? ®YES 1:1NO
HYDRAULIC DATA NAME PLATE PROVIDED IF NO,EXPLAIN
NAMEPLATE ®YES 1-1 NO
DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN:
REMARKS
NAME OF SPRINKLER CONTRACTOR
Moran Fire Protection, 3001 Research Road,Suite A,Champaign, Illinois 61822
TEST WITNESS BY
SIGNATURE / FOR PROPE TY 9 ER(SIGNED) TITL DATE `
FOR OR GN TITLES DAT
ADDITIONAL EXPLA I N N TE
CONTRACTOR'S MATERIAL & TEST CERTIFICATE FOR ABOVEGROUND PIPING
PROCEDURE
UPON COMPLETION OF WORK,INSPECTION&TESTS SHALL BE MADE BY THE CONTRACTOR'S REP.AND WITNESSED BY AN OWNER'S REP.
ALL DEFECTS SHALL BE CORRECTED AND SYSTEM LEFT IN SERVICE BEFORE CONTRACTOR'S PERSONNEL LEAVE THE JOB.
A CERTIFICATE SHALL BE FILLED OUT AND SIGNED BY BOTH THE REPRESENTATIVES. COPIES SHALL BE PREPARED FOR APPROVING AUTHORITIES,OWNERS AND
CONTRACTOR. IT IS UNDERSTOOD THE OWNER'S REPRESENTATIVE'S SIGNATURE IN NO WAY PREJUDICES ANY CLAIM AGAINST CONTRACTOR FOR FAULTY
MATERIAL,POOR WORKMANSHIP,OR FAILURE TO COMPLY WITH APPROVING AUTHORITY'S REQUIREMENTS OR LOCAL ORDINANCES.
PROPERTY NAME JOB NO. DATE
NEW DISTRIBUTION CENTER FOR VISTAR 201000
PROPERTY ADDRESS
LOT 3 175 SULLIVAN AVE.,SOUTH WINDSOR, CONNECTICUT 06074
ACCEPTED BY APPROVING AUTHORITIES(NAMES)
SOUTH WINDSOR,CT
ADDRESS
PLANS 1540 SULLIVAN AVE.,SOUTH WINDSOR,CT
INSTALLATION CONFORMS TO ACCEPTED PLANS X YES eNO
EQUIPMENT USED IS APPROVED YES NO
IF NO,EXPLAIN DEVIATIONS
HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION YES �NO
OF CONTROL VALVES AND CARE AND MAINTENANCE OF THIS NEW EQUIPMENT? IF NO,EXPLAIN
INSTRUCTIONS HAVE COPIES OF THE FOLLOWING BEEN LEFT ON THE PREMISES:
1. SYSTEM COMPONENTS INSTRUCTIONS EYES
YES NO
2. CARE AND MAINTENANCE INSTRUCTIONS YES NO
3. NFPA 25 NO
LOCATION WET SYSTEM 3
MAKE MODEL YEAR OF MFG. ORIFICE SIZE QUANTITY TEMP.
RELIABLE RA1914 2015 K=16.8 490 200
RELIABLE R4842 2015 K=8.0 17 155
SPRINKLERS
PIPE AND TYPE OF PIPE SCHEDULE 7
FITTINGS TYPE OF FITTINGS GROOVED
ALARM DEVICE MAX.TIME TO OPERATE THROUGH TEST CONN.
ALARM VALVE OR TYPE MAKE MODEL MIN. SEC.
FLOW INDICATOI FLOW SWICTH POTTER VSR
DRY VALVE Q.O.D.
MAKE MODEL SERIAL NO. MAKE MODEL SERIAL NO.
TIME TO TRIP TIME WATER ALARM
THRU TEST WATER AIR TRIP POINT REACHED OPERATED
DRY PIPE CONNECTION* PRES. PRES. AIR PRESSURE TEST OUTLET* PROPERLY
OPERATING MIN. SEC. PSI PSI PSI MIN. SEC. YES NO
TEST WITHOUT Q.O.D.
WITH Q.O.D.
*MEASURED FROM THE TIME INSPECTOR'S TEST CONNECTION IS OPENED
OPERATION PNEUMATIC ELECTRIC HYDRAULIC
PIPING SUPERVISED YES �NO DETECTING MEDIA SUPERVISED YES 1:1NO
DELUGE& DOES VALVE OPERATE FROM THE MANUAL TRIP AND/OR REMOTE CONTROLS STATIONS YES 1:1NO
PREACTION IS THERE AN ACCESSIBLE FACILITY IN EACH CIRCUIT FOR TESTING IF NO,EXPLAIN
VALVES DYES FjNO
DOES EACH CIRCUIT OPERATE DOES EACH CIRCUIT OPERATE MAXIMUM TIME TO
MAKE MODEL SUPERVISION LOSS ALARM VALVE RELEASE OPERATE RELEASE
YES NO YES INO MIN. SEC.
(OVER)
LOCATION MAKE& STATIC PRESSURE RESIDUAL PRESSURE(FLOWING) FLOW RATE
PRESSURE &FLOOR MODEL SETTING INLET(PSI) JOUTLET(PSI) INLET(PSI) OUTLET(PSI) FLOW(GPM)
REDUCING
VALVE TEST
TEST PRESSURE IN EXCESS OF 150 PSI(10.2 BARS)FOR TWO HOURS. DIFFERENTIAL DRY PIPE VALVE CLAPPERS SHALL BE LEFT OPEN
DESCRIPTION DURING TEST TO PREVENT DAMAGE. ALL ABOVEGROUND PIPING LEAKAGE SHALL BE STOPPED.
PNEUMATIC: ESTABLISH 40 PSI(2.7 BARS)AIR FRESSURE AND MEASURE DROP WHIGH SHALL NO I EXCEED 1 z
24 HOURS. TEST PRESSURE TANKS AT NORMAL WATER LEVEL AND AIR PRESSURE AND MEASURE AIR PRESSURE DROP WHICH
SHALL NOT EXCEED 1 '/PSI(0.1 BARS)IN 24 HOURS.
ALL PIPING HYDROSTATICALLY TESTED AT 9.)5 PSI FOR 2 HRS. IF NO,STATE REASON
DRY PIPING PNEUMATICALLY TESTED eYES eNO
EQUIPMENT OPERATED PROPERLY YES NO
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT ADDITIVES AND CORROSIVE CHEMICALS,SODIUM SILICATE OR
DERIVATIVES OF SODIUM SILICATE,BRINE,OR OTHER CORROSIVE CHEMICALS WERE NOT USED FOR TESTING SYSTEMS OR
TESTS STOPPING LEAKS? ®YES El NO
DRAIN STATIC PRESSURE READING OF GAGE LOCATED NEAR WATER RESIDUAL PRESSURE WITH VALVE IN TEST
TEST SUPPLY TEST CONNECTION PSI CONNECTION OPEN WIDE PSI
UNDERGROUND MAINS AND LEAD IN CONNECTION TO SYSTEM RISERS FLUSHED BEFORE CONNECTION MADE TO SPRINKLER PIPING,
AND VERIFIED BY COPY OF FORM NO.13U YES 1:1NO OTHER EXPLAIN
FLUSHED BY INSTALLER OF UNDERGROUND
SPRINKLER PIPING YES 1:1NO
IF POWDER-DRIVEN FASTENERS ARE USED IN
CONCRETE,HAS REPRESENTATIVE SAMPLE YES 1:1NO NA
TESTING BEEN SATISFACTORILY COMPLETED?
BLANK TESTING Number Used Locations Number Removed
GASKETS 0 1 1 0
WELDED PIPE ®YES 1:1NO
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT WELDING PROCEDURES COMPLY WITH THE
REQUIREMENTS OF AT LEAST AWS D10,9,LEVEL AR-3 ®YES 1:1NO
WELDING DO YOU CERTIFY THAT THE WELDING WAS PERFORMED BY WELDERS QUALIFIED IN COMPLIANCE WITH THE
REQUIREMENTS OF AT LEAST AWS D10,9,LEVEL AR-3 ®YES F-1NO
DO YOU CERTIFY THAT WELDING WAS CARRIED OUT IN COMPLIANCE WITH A DOCUMENTED QUALITY CONTROL
PROCEDURE TO INSURE THAT ALL DISC ARE RETRIEVED,THAT OPENINGS IN PIPING ARE SMOOTH,THAT SLAG AND
OTHER WELDING RESIDUE ARE REMOVED,AND THAT THE INTERNAL DIAMETERS OF PIPING ARE NOT PENETRATED. ®YES [:]NO
CUTOUTS(DISKS) DO YOU CERTIFY THAT YOU HAVE A CONTROL FEATURE THAT INSURES THAT ALL
CUTOUTS(DISCS)ARE RETRIEVED? ®YES 1:1NO
HYDRAULIC DATA NAME PLATE PROVIDED IF NO,EXPLAIN
NAMEPLATE ®YES 1:1No
DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN:
REMARKS
NAME 90f_aFRINKLER CONTRACTOR
F.E. oran Fire Protection, 3001 Research Road, Suite A, Champaign, Illinois 61822
TEST WITNESS BY
SIGNATURES OR PROPER OWN SIGNED) TIT DATE
FOR LE TOR-{S NE TITLE DATE,
ADDITIONAL EXPLANATI N NOTESd� �!
CONTRACTOR'S MATERIAL & TEST CERTIFICATE FOR ABOVEGROUND PIPING
PROGEDUKh
UPON COMPLETION OF WORK,INSPECTION&TESTS SHALL BE MADE BY THE CONTRACTOR'S REP.AND WITNESSED BY AN OWNER'S REP.
ALL DEFECTS SHALL BE CORRECTED AND SYSTEM LEFT IN SERVICE BEFORE CONTRACTOR'S PERSONNEL LEAVE THE JOB.
A CERTIFICATE SHALL BE FILLED OUT AND SIGNED BY BOTH THE REPRESENTATIVES. COPIES SHALL BE PREPARED FOR APPROVING AUTHORITIES,OWNERS AND
CONTRACTOR. IT IS UNDERSTOOD THE OWNER'S REPRESENTATIVE'S SIGNATURE IN NO WAY PREJUDICES ANY CLAIM AGAINST CONTRACTOR FOR FAULTY
MATERIAL,POOR WORKMANSHIP,OR FAILURE TO COMPLY WITH APPROVING AUTHORITY'S REQUIREMENTS OR LOCAL ORDINANCES.
PROPERTY NAME JOB NO. JDATE
NEW DISTRIBUTION CENTER FOR VISTAR 201000
PROPERTYADDRESS
LOT 3 175 SULLIVAN AVE.,SOUTH WINDSOR,CONNECTICUT 06074
ACCEPTED BY APPROVING AUTHORITIES(NAMES)
SOUTH WINDSOR, CT
ADDRESS
PLANS 1540 SULLIVAN AVE.,SOUTH WINDSOR,CT
INSTALLATION CONFORMS TO ACCEPTED PLANS X YES BNO
EQUIPMENT USED IS APPROVED YES NO
IF NO,EXPLAIN DEVIATIONS
HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION EYES 1-1 NO
OF CONTROL VALVES AND CARE AND MAINTENANCE OF THIS NEW EQUIPMENT? IF NO,EXPLAIN
INSTRUCTIONS HAVE COPIES OF THE FOLLOWING BEEN LEFT ON THE PREMISES:
1. SYSTEM COMPONENTS INSTRUCTIONS E
YES NO
2. CARE AND MAINTENANCE INSTRUCTIONS YES NO
3. NFPA 25 YES NO
LOCATION ,1 , p aG e- WET SYSTEM 4
MAKE MODEL YEAR OF MFG. ORIFICE SIZE QUANTITY TEMP.
RELIABLE R3672 2015 K=8.0 23 200
RELIABLE R4842 2015 K=8.0 44 155
SPRINKLERS
PIPE AND TYPE OF PIPE SCHEDULE 7
FITTINGS TYPE OF FITTINGS GROOVED
ALARM DEVICE MAX.TIME TO OPERATE THROUGH TEST CONN.
ALARM VALVE OR TYPE MAKE MODEL MIN. SEC.
FLOW INDICATOI FLOW SWICTH POTTER VSR
DRY VALVE Q.O.D.
MAKE MODEL SERIAL NO. MAKE MODEL SERIAL NO.
TIME TO TRIP TIME WATER ALARM
THRU TEST WATER AIR TRIP POINT REACHED OPERATED
DRY PIPE CONNECTION PRES. PRES. AIR PRESSURE TEST OUTLET* PROPERLY
OPERATING MIN. I SEC. PSI PSI PSI MIN. SEC. YES NO
TEST WITHOUT Q.O.D.
WITH Q.O.D.
MEASURED FROM THE TIME INSPECTOR'S TEST CONNECTION IS OPENED
OPERATION PNEUMATIC ELECTRIC HYDRAULIC
PIPING SUPERVISED YES El NO DETECTING MEDIA SUPERVISED YES 1:1NO
DELUGE& DOES VALVE OPERATE FROM THE MANUAL TRIP AND/OR REMOTE CONTROLS STATIONS YES 1:1NO
PREACTION IS THERE AN ACCESSIBLE FACILITY IN EACH CIRCUIT FOR TESTING IF NO,EXPLAIN
VALVES DYES 1:1NO
DOES EACH CIRCUIT OPERATE DOES EACH CIRCUIT OPERATE MAXIMUM TIME TO
MAKE MODEL SUPERVISION LOSS ALARM VALVE RELEASE OPERATE RELEASE
YES NO YES NO MIN. SEC.
(OVER)
LOCATION MAKE& STATIC PRESSURE RESIDUAL PRESSURE(FLOWING) FLOW RATE
PRESSURE &FLOOR MODEL SETTING INLET(PSI) JOUTLET(PSI) INLET(PSI) OUTLET(PSI) FLOW(GPM)
REDUCING
VALVE TEST
TEST PRESSURE IN EXCESS OF 150 PSI(10.2 BARS)FOR TWO HOURS. DIFFERENTIAL DRY PIPE VALVE CLAPPERS SHALL BE LEFT OPEN
DESCRIPTION DURING TEST TO PREVENT DAMAGE. ALL ABOVEGROUND PIPING LEAKAGE SHALL BE STOPPED.
PNEUMAJ IG: ES I ABLISH 40 PSI(2.7 BARS)AIR PRESSURE ANu MEASURE DROP WHICH SHALL NO I LXULLL)1 z PSI(0.1 BAR
24 HOURS. TEST PRESSURE TANKS AT NORMAL WATER LEVEL AND AIR PRESSURE AND MEASURE AIR PRESSURE DROP WHICH
SHALL NOT EXCEED 1'/z PSI(0.1 BARS)IN 24 HOURS.
ALL PIPING HYDROSTATICALLY TESTED AT F PSI FOR 2 HRS. IF NO,STATE REASON
DRY PIPING PNEUMATICALLY TESTED eYES eNO
EQUIPMENT OPERATED PROPERLY YES NO
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT ADDITIVES AND CORROSIVE CHEMICALS,SODIUM SILICATE OR
DERIVATIVES OF SODIUM SILICATE,BRINE,OR OTHER CORROSIVE CHEMICALS WERE NOT USED FOR TESTING SYSTEMS OR
TESTS STOPPING LEAKS? ®YES F 1NO
DRAIN I STATIC PRESSURE READING OF GAGE LOCATED NEAR WATER RESIDUAL PRESSURE WITH VALVE IN TEST
TEST SUPPLY TEST CONNECTION PSI CONNECTION OPEN WIDE PSI
UNDERGROUND MAINS AND LEAD IN CONNECTION TO SYSTEM RISERS FLUSHED BEFORE CONNECTION MADE TO SPRINKLER PIPING,
AND VERIFIED BY COPY OF FORM NO.13U YES El NO OTHER EXPLAIN
FLUSHED BY INSTALLER OF UNDERGROUND
SPRINKLER PIPING YES 1:1NO
IF POWDER-DRIVEN FASTENERS ARE USED IN
CONCRETE,HAS REPRESENTATIVE SAMPLE YES 1:1NO NA
TESTING BEEN SATISFACTORILY COMPLETED?
BLANK TESTING Number Used Locations Number Removed
GASKETS 0 0
WELDED PIPE ®YES 1:1NO
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT WELDING PROCEDURES COMPLY WITH THE
REQUIREMENTS OF AT LEAST AWS D10,9,LEVEL AR-3 ®YES El NO
WELDING DO YOU CERTIFY THAT THE WELDING WAS PERFORMED BY WELDERS QUALIFIED IN COMPLIANCE WITH THE
REQUIREMENTS OF AT LEAST AWS D10,9,LEVEL AR-3 ®YES F-1NO
DO YOU CERTIFY THAT WELDING WAS CARRIED OUT IN COMPLIANCE WITH A DOCUMENTED QUALITY CONTROL
PROCEDURE TO INSURE THAT ALL DISC ARE RETRIEVED,THAT OPENINGS IN PIPING ARE SMOOTH,THAT SLAG AND
OTHER WELDING RESIDUE ARE REMOVED,AND THAT THE INTERNAL DIAMETERS OF PIPING ARE NOT PENETRATED. ®YES [:]NO
CUTOUTS(DISKS) DO YOU CERTIFY THAT YOU HAVE A CONTROL FEATURE THAT INSURES THAT ALL
CUTOUTS(DISCS)ARE RETRIEVED? ®YES 1:1NO
HYDRAULIC DATA NAME PLATE PROVIDED IF NO,EXPLAIN
NAMEPLATE ®YES 1:1NO
DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN:
REMARKS
NAME OF SPRINKLER CONTRACTOR
F.E. Moran Fire Protection, 3001 Research Road,Suite A,Champaign, Illinois 61822
TEST WITNESS BY
SIGNATURES FOR PRO ERT NER(SIGNED) TITLE DATE
+, /' 'a/moo/lb
K E T TOR SI ) TITLE, — 0 DATE
J d�✓�-�ar7 l —f�,ZOl(v
ADDITIONAL EXPLANATION17 NOTES
CONTRACTOR'S MATERIAL & TEST CERTIFICATE FOR ABOVEGROUND PIPING
PROCEDURE
UPON COMPLETION OF WORK,INSPECTION&TESTS SHALL BE MADE BY THE CONTRACTOR'S REP.AND WITNESSED BY AN OWNER'S REP.
ALL DEFECTS SHALL BE CORRECTED AND SYSTEM LEFT IN SERVICE BEFORE CONTRACTOR'S PERSONNEL LEAVE THE JOB.
A CERTIFICATE SHALL BE FILLED OUT AND SIGNED BY BOTH THE REPRESENTATIVES. COPIES SHALL BE PREPARED FOR APPROVING AUTHORITIES,OWNERS AND
CONTRACTOR. IT IS UNDERSTOOD THE OWNER'S REPRESENTATIVE'S SIGNATURE IN NO WAY PREJUDICES ANY CLAIM AGAINST CONTRACTOR FOR FAULTY
MATERIAL,POOR WORKMANSHIP,OR FAILURE TO COMPLY WITH APPROVING AUTHORITY'S REQUIREMENTS OR LOCAL ORDINANCES.
PROPERTY NAME JOB NO. DATE
NEW DISTRIBUTION CENTER FOR VISTAR 201000
PROPERTY ADDRESS
LOT 3 175 SULLIVAN AVE.,SOUTH WINDSOR,CONNECTICUT 06074
ACCEPTED BY APPROVING AUTHORITIES(NAMES)
SOUTH WINDSOR,CT
ADDRESS
PLANS 1540 SULLIVAN AVE.,SOUTH WINDSOR,CT
INSTALLATION CONFORMS TO ACCEPTED PLANS X YES ONO
EQUIPMENT USED IS APPROVED YES LJNO
IF NO,EXPLAIN DEVIATIONS
HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION MYES 1:1NO
OF CONTROL VALVES AND CARE AND MAINTENANCE OF THIS NEW EQUIPMENT? IF NO,EXPLAIN
INSTRUCTIONS HAVE COPIES OF THE FOLLOWING BEEN LEFT ON THE PREMISES:
1. SYSTEM COMPONENTS INSTRUCTIONS X YES NO
2. CARE AND MAINTENANCE INSTRUCTIONS X YES NO
3. NFPA 25 X YES NO
LOCATION PRE-ACTION SYSTEM
MAKE MODEL YEAR OF MFG. ORIFICE SIZE QUANTITY TEMP.
VIKING VK595 2015 K=25.2 238 200
SPRINKLERS
PIPE AND TYPE OF PIPE SCHEDULE 7
FITTINGS TYPE OF FITTINGS GROOVED
ALARM DEVICE MAX.TIME TO OPERATE THROUGH TEST CONN.
ALARM VALVE OR TYPE MAKE MODEL MIN. SEC.
FLOW INDICATOF FLOW SWICTH POTTER VSR
DRY VALVE Q.O.D.
MAKE MODEL SERIAL NO. MAKE MODEL SERIAL NO.
TIME TO TRIP TIME WATER ALARM
THRU TEST WATER AIR TRIP POINT REACHED OPERATED
DRY PIPE CONNECTION` PRES. PRES. AIR PRESSURE TEST OUTLET* PROPERLY
OPERATING IN. SEC. PSI PSI PSI MIN. SEC. YES NO
TEST WITHOUT Q.O.D.
WITH Q.O.D.
MEASURED FROM THE TIME INSPECTOR'S TEST CONNECTION IS OPENED
OPERATION PNEUMATIC ®ELECTRIC El HYDRAULIC
PIPING SUPERVISED ®YES 1:1NO DETECTING MEDIA SUPERVISED YES El NO
DELUGE& DOES VALVE OPERATE FROM THE MANUAL TRIP AND/OR REMOTE CONTROLS STATIONS YES 1:1NO
PREACTION IS THERE AN ACCESSIBLE FACILITY IN EACH CIRCUIT FOR TESTING IF NO,EXPLAIN
VALVES YES FJNO
DOES EACH CIRCUIT OPERATE DOES EACH CIRCUIT OPERATE MAXIMUM TIME TO
MAKE MODEL SUPERVISION LOSS ALARM VALVE RELEASE OPERATE RELEASE
YES NO YES NO MIN. SEC.
(OVER)
LOCATION MAKE& STATIC PRESSURE RESIDUAL PRESSURE(FLOWING) FLOW RATE
PRESSURE &FLOOR MODEL SETTING INLET(PSI) OUTLET(PSI) INLET(PSI) OUTLET(PSI) FLOW(GPM)
REDUCING
VALVE TEST
TEST PRESSURE IN EXCESS OF 150 PSI(10.2 BARS)FOR TWO HOURS. DIFFERENTIAL DRY PIPE VALVE CLAPPERS SHALL BE LEFT OPEN
DESCRIPTION DURING TEST TO PREVENT DAMAGE. ALL ABOVEGROUND PIPING LEAKAGE SHALL BE STOPPED.
PNEUMATIU: ESTABLISH 40 P.51(2.7 BARS)AIR PRESSURE AND MEASURE DROP WHICH SHALL NUT z
-PSr(U.7MRS)IN
24 HOURS. TEST PRESSURE TANKS AT NORMAL WATER LEVEL AND AIR PRESSURE AND MEASURE AIR PRESSURE DROP WHICH
SHALL NOT EXCEED 1'/2 PSI(0.1 BARS)IN 24 HOURS.
ALL PIPING HYDROSTATICALLY TESTED AT ry 3W PSI FOR 2 HRS. IF NO,STATE REASON
DRY PIPING PNEUMATICALLY TESTED O_ H
YES BNO
EQUIPMENT OPERATED PROPERLY YES NO
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT ADDITIVES AND CORROSIVE CHEMICALS,SODIUM SILICATE OR
DERIVATIVES OF SODIUM SILICATE,BRINE,OR OTHER CORROSIVE CHEMICALS WERE NOT USED FOR TESTING SYSTEMS OR
TESTS STOPPING LEAKS? ®YES 1:1NO
DRAIN I STATIC PRESSURE READING OF GAGE LOCATED NEAR WATER RESIDUAL PRESSURE WITH VALVE IN TEST
TEST SUPPLY TEST CONNECTION PSI CONNECTION OPEN WIDE PSI
UNDERGROUND MAINS AND LEAD IN CONNECTION TO SYSTEM RISERS FLUSHED BEFORE CONNECTION MADE TO SPRINKLER PIPING,
AND VERIFIED BY COPY OF FORM NO.13U YES 1:1NO OTHER EXPLAIN
FLUSHED BY INSTALLER OF UNDERGROUND
SPRINKLER PIPING YES 1:1NO
IF POWDER-DRIVEN FASTENERS ARE USED IN
CONCRETE,HAS REPRESENTATIVE SAMPLE YES El NO NA
TESTING BEEN SATISFACTORILY COMPLETED?
BLANK TESTING Number Used ns Number Removed
Locatio
GASKETS 0 0
WELDED PIPE ®YES El NO
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT WELDING PROCEDURES COMPLY WITH THE
REQUIREMENTS OF AT LEAST AWS D10,9,LEVEL AR-3 ®YES 1:1NO
WELDING DO YOU CERTIFY THAT THE WELDING WAS PERFORMED BY WELDERS QUALIFIED IN COMPLIANCE WITH THE
REQUIREMENTS OF AT LEAST AWS D10,9,LEVEL AR-3 ®YES F_1NO
DO YOU CERTIFY THAT WELDING WAS CARRIED OUT IN COMPLIANCE WITH A DOCUMENTED QUALITY CONTROL
PROCEDURE TO INSURE THAT ALL DISC ARE RETRIEVED,THAT OPENINGS IN PIPING ARE SMOOTH,THAT SLAG AND
OTHER WELDING RESIDUE ARE REMOVED,AND THAT THE INTERNAL DIAMETERS OF PIPING ARE NOT PENETRATED. ®YES ONO
CUTOUTS(DISKS) DO YOU CERTIFY THAT YOU HAVE A CONTROL FEATURE THAT INSURES THAT ALL
CUTOUTS(DISCS)ARE RETRIEVED? ®YES 1-1 NO
HYDRAULIC DATA NAME PLATE PROVIDED IF NO,EXPLAIN
NAMEPLATE ®YES 1:1NO
DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN:
REMARKS
NAME OF SPRINKLER CONTRACTOR
F.E. Moran Fire Protection,3001 Research Road, Suite A, Champaign, Illinois 61822
TEST WITNESS BY
SIGNATURES FOR PR ER OWNER(SIGNED) TITLE v e t(C/2 DATE
F, S CO (SIGNED.) TITLE DAT
�
ADDITIONAL EXP A A I- D NO]ES