HomeMy WebLinkAbout40 Kennedy Road - Life Safety System Tes (2) Contractor's Material and Test Certificate for Aboveground Piping
PROCEDURE
Upon completion of work,inspection and tests shall be made by the Contractor's representative and witnessed by an owner's representative. All defects
shalt be corrected and system left in service before contractor's personnel finally leave the job.
A certificate shall be filled out and signed by hnth representatives.Copies shall be pFepaFed for approving autho,ities,owi mrs,and contractor.it is
understood the owner's representative's signature in no way prejudices any claim against contractor for faulty material,poor workmanship,or failure to
comply with approving authority's requirements or local ordinances.
PROPERTY NAME FEDEX GROUND DATE NOVEMBER 1 2012
PROPERTY ADDRESS 40 KENNEDY ROAD,SOUTH WINDSOR,CT
ACCEPTED BY APPROVING AUTHORITIES(NAMES) TOWN OF SOUTH WINDSOR FIRE DEPARTMENT
ADDRESS 1175 ELLINGTON STREET SOUTH WINDSOR CT 06074
PLANS INSTALLATION CONFORMS TO ACCEPTED PLANS ®YES ❑ NO
EQUIPMENT USED IS APPROVED ®YES ❑ NO
IF NO,EXPLAIN DEVIATIONS
HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION ®YES ❑ NO
OF CONTROL VALVES AND CARE AND MAINTENANCE OF THEIS NEW EQUIPMENT?
IF NO,EXPLAIN
INSTRUCTIONS HAVE COPIES OF THE FOLLOWING BEEN LEFT ON THE PREMISES ®YES ❑ NO
1. SYSTEM COMPONENTS INSTRUCTIONS ®YES ❑ NO
2. CARE AND MAINTENANCE INSTRUCTIONS ®YES ❑ NO
3. NFPA 25
®YES ❑ NO
YEAR OF ORIFICE TEMPERATURE
MAKE MODEL MANUFACTURE SIZE QUANTITY RATING
SPRINKLERS VICTAULIC V3406 2012 3W' 155°F
VICTAULIC V3402 2012 314" 155°F
VICTAULIC V3401 2012 3/4" 286°F
VICTAULIC V3425 2012 314" 231 1 286'F
VICTAULIC V3608 2012 3/4" 165°F
PIPE AND TYPE OF PIPE BLACK SCHEDULE 10 AND SCHEDULE 40
FITTINGS TYPE OF FITTINGS GROOVED AND THREADED CAST IRON
ALARM VALVE MAXIMUM TIME TO OPERATE
ALARM DEVICE THROUGH TEST CONNECTION
OR TYPE FLOW MAKE MODEL MIN SEC
INDICATOR
MAKE MODEL SERIAL NO. MAKE MODEL SERIAL NO.
VICTAULIC NXT
TIME TO TRIP TIME WATER ALARM
DRY PIPE THROUGH TEST WATER AIR TRIP POINT REACHED OPERATED
OPERATING CONNECTION PRESSURE PRESSURE MR PRESSURE TEST OUTLET PROPERLY
TEST WITH MIN SEC PSI PSI PSI MIN I SEC YES NO
�
Q.O.D.
W/O
Q.O.D.
IF NO,EXPLAIN
OPERATION n PNEUMATIC n ELECTRIC 0 HYDRAULIC
PIPING SUPERVISED n YES rl NO DETECTING MEDIA SUPERVISED 1-1 YES fl NO
DOES THE VALVE OPERATE FROM THE MANUAL TRIP AND/OR REMOTE
DELUGE& CONTROL STATIONS YES NO
PREACTION IS THERE AN ACCESSIBLE FACILITY IN EACH CIRCUIT IF NO EXPLAIN
VALVES FOR TESTING? M YES r-1 NO ,
DOES EACH CIRCUIT OPERATE DOES EACH CIRCUIT MAXIMUM TIME TO
MAKE MODE SUPERVISION-LOSS ALARM OPERATE ALVE RELEASE OPERATE RELEASE
YES NO YES NO MIN I SEC
PRESSURE LOCATION MAKE& SETTING STATIC PRESSURE RESIDUAL PRESSURE FLOW RATE
REDUCING &FLOOR MODEL FLOWING
VALVE TEST INLET(PSI) OUTLET(PSI) INLET(PSI) OUTLET(PSI) FLOW(GPM)
HYDROSTATIC:Hydrostatic tests shall be made at not less than 200 psi(13.6 bars)for two hours or 50 psi(3.4 bars)above static
TEST pressure in excess of 150 psi(10.2 bars)for two hours.Differential dry-pipe valve clappers shall be left open during test to prevent
DESCRIPTION damage.All aboveground piping leakage shall be stopped.
PNEUMATIC:Establish 40 psi(2.7 bars)air pressure and measure drop,which shall not exceed 1 Y2 psi(0.1 bars)in 24 hours.Test
ressure tanks at normal water level and air pressure and measure air pressure dro which shall not exceed 1Y2 psi in 24 hours.
ALL PIPING HYDROSTATICALLY TESTED AT 200 PSI FOR 2 HOURS IF NO,STATE REASON
DRY PIPINGPNEUMATICALLY TESTED Lj YES N NO
EQUIPMENT OPERATES PROPERLY M YES n NO
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT ADDITIVES AND CORROSIVE CHEMICALS,SODIUM SILICATE
OR DERIVATIVES OF SODIUM SILICATE,BRINE,OR OTHER CORROSIVE CHEMICALS WERE NOT USED FOR TESTING
SYSTEMS OR STOPPING LEAKS? R YES ❑NO
DRAIN READING OF GAGE LOCATED NEAR WATER RESIDUAL PRESSURE WITH VALVE IN TEST
TESTS TEST SUPPLY TEST CONNECTION PSI CONNECTION OPEN WIDE PSI
UNDERGROUND MAINS AND LEAD-IN CONNECTIONS TO SYSTEM RISERS FLUSHED BEFORE
CONNECTION MADE TO SPRINKLER PIPING.
VERIFIED BY COPY OF THE U FORM NO.858 ❑YES ❑NO OTHER EXPLAIN
FLUSHED BY INSTALLER OF UNDERGROUND
SPRINKER PIPING n YES ❑NO
IF POWDER DRIVEN FASTENERS ARE USED IN CONCRETE IF NO,EXPLAIN
HAS REPRESENTATIVE SAMPLE TESTING BEEN COMPLETED? El YES n NO
BLANK TEST NUMBER USED LOCATIONS NUMBER REMOVED
GASKETS 0
WELDED PIPING M YES ❑NO
IF YES...
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT WELDING PROCEDURES COMPLY
WITH THE REQUIREMENTS OF AT LEAST AWS D10.9.LEVEL AR 3? ®YES ❑NO
DO YOU CERTIFY THAT THE WELDING WAS PERFORMED BY WELDERS QUALIFIED IN COMPLIANCE
WELDING WITH THE REQUIREMENTS OF AT LEAST AWS D10.9.LEVEL AR 3? ®YES ❑NO
DO YOU CERTIFY THAT WELDING WAS CARRIED OUT IN COMPLIANCE WITH A DOCUMENTED
QUALITY CONTROL PROCEDURE TO INSURE THAT ALL DISCS ARE RETRIEVED,THAT OPENINGS
1N PIPING ARE SMOOTH,THAT SLAG AND OTHER WELDING RESIDUE ARE REMOVED,AND THAT
THE INTERNAL DIAMETERS OF PIPING ARE NOT PENETRATED? M YES NO
CUTOUTS DO YOU CERTIFY THAT YOU HAVE A CONTROL FEATURE TO ENSURE THAT ALL CUTOUTS(DISCS)
DISCS ARE RETRIEVED? M YES n NO
HYDRAULIC NAMEPLATE PROVIDED IF NO,EXPLAIN
DATA ®YES ❑NO
NAMEPLATE
DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN.
REMARKS .00
NAME OF SPRINKER CONTRACTOR:
MACK FIRE PROTECTION LLC
SIGNATURES TESTS WITNESSED BY
FOR PROPERTY OWNER(SIGNED) TITLE DATE
A
FOR WRINKLE2f T (SIGNED) —TJ.T(.E� �- / DATE fr3 i
ADDITIONAL EXPLANAT! S ANDWOT S: 1—� �V Cl
I
Contractor's Material and Test Certificate for Aboveground Piping
PROCEDURE
Upon completion of work,inspection and tests shall be made by the Contractor's representative and witnessed by an owner's representative. All defects
shall be corrected and system left in service before contractor's personnel finally leave the job.
preparedA GeFtifiGate shall be filled eut and signed by both.eprese,itatives.Coples shall be r approving authorities,owners,and contractor.It is
understood the owner's representative's signature in no way prejudices any claim against contractor for faulty material,poor workmanship,or failure to
comply with approving authority's requirements or local ordinances..
PROPERTY NAME FEDEX GROUND DATE NOVEMBER 1 2012
PROPERTY ADDRESS 40 KENNEDY ROAD,SOUTH WINDSOR,CT
ACCEPTED BY APPROVING AUTHORITIES(NAMES) TOWN OF SOUTH WINDSOR FIRE DEPARTMENT
ADDRESS 1175 ELLINGTON STREET SOUTH WINDSOR CT 06074
PLANS INSTALLATION CONFORMS TO ACCEPTED PLANS ®YES ❑ NO
EQUIPMENT USED IS APPROVED ®YES ❑ NO
IF NO,EXPLAIN DEVIATIONS
HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION ®YES ❑ NO
OF CONTROL VALVES AND CARE AND MAINTENANCE OF THEIS NEW EQUIPMENT?
IF NO,EXPLAIN
INSTRUCTIONS HAVE COPIES OF THE FOLLOWING BEEN LEFT ON THE PREMISES ®YES ❑ NO
1. SYSTEM COMPONENTS INSTRUCTIONS ®YES ❑ NO
2. CARE AND MAINTENANCE INSTRUCTIONS ®YES ❑ NO
3. NFPA 25 ®YES ❑ NO
SUPPLIESLOCATION
YEAR OF ORIFICE TEMPERATURE_
MAKE MODEL MANUFACTURE SIZE QUANTITY RATING
SPRINKLERS VICTAULIC V3406 2012 314" 155°F
VICTAULIC V3402 2012 3/4" 155°F
VICTAULIC V3401 2012 3/4" 286*F
VICTAULIC V3426 2012 3/4" 217 286°F
VICTAULIC V3608 2012 314" 165°F
PIPE AND TYPE OF PIPE BLACK SCHEDULE 10 AND SCHEDULE 40
FITTINGS TYPE OF FITTINGS GROOVED AND THREADED CAST IRON
MAXIMUM TIME TO OPERATE
ALARM VALVE ALARM DEVICE THROUGH TEST CONNECTION
OR TYPE MAKE MODEL MIN SEC
FLOW
INDICATOR
MAKE MODEL SERIAL NO. MAKE MODEL SERIAL NO.
VICTAULIC NXT
TIME TO TRIP TIME WATER ALARM
DRY PIPE THROUGH TEST WATER AIR TRIP POINT REACHED OPERATED
OPERATING CONNECTION PRESSURE PRESSURE LIR PRESSURE TEST OUTLET PROPERLY
TEST MIN SEC PSI PSI PSI MIN SEC YES NO
WITH -7 I }
Q.O.D.
W/O
Q.O.D.
IF NO,EXPLAIN
OPERATION PNEUMATIC n ELECTRIC El HYDRAULIC
PIPING SUPERVISED 1-1 YES 11 NO DETECTING MEDIA SUPERVISED n YES rl NO
DOES THE VALVE OPERATE FROM THE MANUAL TRIP AND/OR REMOTE
DELUGE& CONTROL STATIONS YES NO
PREACTION 1S THERE AN ACCESSIBLE FACILITY IN EACH CIRCUIT IF NO,EXPLAIN
VALVES FOR TESTING? n YES [1 NO
DOES EACH CIRCUIT OPERATE DOES EACH CIRCUIT MAXIMUM TIME TO
MAKE MODEI SUPERVISION LOSS ALARM OPERATE VALVE RELEASE OPERATE RELEASE
YES NO YES I NO MIN SEC
PRESSURE LOCATION MAKE& SETTING STATIC PRESSURE RESIDUAL PRESSURE FLOW RATE
REDUCING &FLOOR MODEL FLOWING
VALVE TEST INLET(PSI) OUTLET(PSI) INLET(PSI) OUTLET(PSI) FLOW(GPM)
HYDROSTATIC:Hydrostatic tests shall be made at not less than 200 psi(13.6 bars)for two hours or 50 psi(3.4 bars)above static
TEST pressure in excess of 150 psi(10.2 bars)for two hours.Differential dry-pipe valve clappers shall be left open during test to prevent
DESCRIPTION damage.All aboveground piping leakage shall be stopped.
PNEUMATIC:Establish 40 psi(2.7 bars)air pressure and measure drop,which shall not exceed 1 Y psi(0.1 bars)in 24 hours.Test
ressure tanks at normal water level and air oressure and measure air pressure drop which shall not exceed V/2 psi in 24 hours.
ALL PIPING HYDROSTATICALLY TESTED AT 200PAIFOR21-101-IRS IF NO,STATE REASON
DRY PIPING PNEUMATICALLY TESTED ❑YES ®NO
EQUIPMENT OPERATES PROPERLY ®YES ❑NO
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT ADDITIVES AND CORROSIVE CHEMICALS,SODIUM SILICATE
OR DERIVATIVES OF SODIUM SILICATE,BRINE,OR OTHER CORROSIVE CHEMICALS WERE NOT USED FOR TESTING
SYSTEMS OR STOPPING LEAKS? ®YES ❑NO
DRAIN READING OF GAGE LOCATED NEAR WATER RESIDUAL PRESSURE WITH VALVE IN TEST
TESTS TEST SUPPLY TEST CONNECTION PSI CONNECTION OPEN WIDE PSI
UNDERGROUND MAINS AND LEAD-IN CONNECTIONS TO SYSTEM RISERS FLUSHED BEFORE
CONNECTION MADE TO SPRINKLER PIPING.
VERIFIED BY COPY OF THE U FORM NO.858 ❑YES ❑NO OTHER EXPLAIN
FLUSHED BY INSTALLER OF UNDERGROUND
SPRINKER PIPING ❑YES I-lNO
IF POWDER DRIVEN FASTENERS ARE USED IN CONCRETE IF NO,EXPLAIN
HAS REPRESENTATIVE SAMPLE TESTING BEEN COMPLETED? n YES n NO
BLANK TEST NUMBER USED LOCATIONS NUMBER REMOVED
GASKETS 0
WELDED PIPING M YES ❑NO
IF YES...
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT WELDING PROCEDURES COMPLY
WITH THE REQUIREMENTS OF AT LEAST AWS D10.9.LEVEL AR 3? ®YES ❑NO
DO YOU CERTIFY THAT THE WELDING WAS PERFORMED BY WELDERS QUALIFIED IN COMPLIANCE
WELDING WITH THE REQUIREMENTS OF AT LEAST AWS D10.9.LEVEL AR 3? ®YES ❑NO
DO YOU CERTIFY THAT WELDING WAS CARRIED OUT IN COMPLIANCE WITH A DOCUMENTED
QUALITY CONTROL PROCEDURE TO INSURE THAT ALL DISCS ARE RETRIEVED,THAT OPENINGS
IN PIPING ARE SMOOTH,THAT SLAG AND OTHER WELDING RESIDUE ARE REMOVED,AND THAT
THE INTERNAL DIAMETERS OF PIPING ARE NOT PENETRATED? YES NO
CUTOUTS DO YOU CERTIFY THAT YOU HAVE A CONTROL FEATURE TO ENSURE THAT ALL CUTOUTS(DISCS)
DISCS ARE RETRIEVED? YES NO
HYDRAULIC NAMEPLATE PROVIDED IF NO,EXPLAIN
DATA ®YES ❑NO
NAMEPLATE
DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN.
REMARKS
NAME OF SPRINKER CONTRACTOR:
MACK FIRE PROTECTION LLC �� t
SIGNATURES TES119WITNESSED BY
FOR PROP!�WN I ) TITLE a DATE i N Z
FOR SPRI LER N T (SIGN TITLE DATE / f
Oet&A / 01
ADDITIONAL EXPLANATIONS 1AND NOTES:
Contractor's Material and Test Certificate for Aboveground Piping
PROCEDURE
I Innn completion of work,inspection and tests shall be made by the Contractor's representative and witnessed by an owner's representative. All defects
shall be corrected and system left in service before contractor's personnel finally eave a to .
A certificate shall be filled out and signed by both representatives.Copies shall be prepared for approving authorities,owners,and contractor.It is
understood the owner's representative's signature in no way prejudices any claim against contractor for faulty material,poor workmanship,or failure to
comply with approving authority's requirements or local ordinances.
PROPERTY NAME FEDEX GROUND I DATE NOVEMBER 1 2012
PROPERTY ADDRESS 40 KENNEDY ROAD,SOUTH WINDSOR,CT
ACCEPTED BY APPROVING AUTHORITIES(NAMES) TOWN OF SOUTH WINDSOR FIRE DEPARTMENT
ADDRESS 1176 ELLINGTON STREET SOUTH WINDSOR CT 06074
PLANS INSTALLATION CONFORMS TO ACCEPTED PLANS 0 YES ONO
®YES ❑ NO
EQUIPMENT USED IS APPROVED
IF NO,EXPLAIN DEVIATIONS
HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION ®YES ❑ NO
OF CONTROL VALVES AND CARE AND MAINTENANCE OF THEIS NEW EQUIPMENT?
IF NO,EXPLAIN
INSTRUCTIONS HAVE COPIES OF THE FOLLOWING BEEN LEFT ON THE PREMISES ®YES ❑ NO
1. SYSTEM COMPONENTS INSTRUCTIONS ®YES ❑ NO
2. CARE AND MAINTENANCE INSTRUCTIONS ®YES ❑ NO
3. NFPA 25 ®YES ❑ NO
LOCATION SUPPLIES BUILDINGS ZOI IF 93 YEAR OF ORIFICE TEMPERATURE
MAKE MODEL MANUFACTURE SIZE QUANTITY RATING
SPRINKLERS VICTAULIC V3406 2012 3/4" 83 155"F
VICTAULIC V3402 2012 3/4" 155°F
VICTAULIC V3401 2012 314" 38 286'F
VICTAULIC I V3426 2012 3WI 81 286'F
VICTAULIC I V3608 2012 3/4" 1 165"F
PIPE AND TYPE OF PIPE BLACK SCHEDULE 10 AND SCHEDULE 40
FITTINGS TYPE OF FITTINGS GROOVED AND THREADED CAST IRON
MAXIMUM TIME TO OPERATE
ALARM VALVE ALARM DEVICE THROUGH TEST CONNECTION
OR TYPE MAKE MODEL MIN SEC
FLOW
INDICATOR
MAKE MODEL SERIAL NO. MAKE I MODEL SERIAL NO.
VICTAULIC NXT
TIME TO TRIP TIME WATER ALARM
DRY PIPE THROUGH TEST WATER AIR TRIP POINT REACHED OPERATED
OPERATING CONNECTION PRESSURE PRESSURE AIR PRESSURE TEST OUTLET PROPERLY
TEST MIN I SEC I PSI PSI PSI MIN SEC YES JNO
WITH I
Q.O.D. t L L.
W/O
Q.O.D.
IF NO,EXPLAIN
OPERATION ❑PNEUMATIC ❑ELECTRIC ❑HYDRAULIC
PIPING SUPERVISED ❑YES ❑NO DETECTING MEDIA SUPERVISED ❑YES ❑NO
DOES THE VALVE OPERATE FROM THE MANUAL TRIP AND/OR REMOTE ❑YES ❑NO
DELUGE& CONTROL STATIONS
PREACTION IS THERE AN ACCESSIBLE FACILITY IN EACH CIRCUIT IF NO,EXPLAIN
VALVES FOR TESTING? ❑YES ❑NO
DOES EACH CIRCUIT OPERATE DOES EACH CIRCUIT MAXIMUM TIME TO
MAKE MODE SUPERVISION LOSS ALARM OPERATE VALVE RELEASE OPERATE RELEASE
YES NO YES NO MIN 1 SEC
PRESSURE LOCATION MAKE& SETTING STATIC PRESSURE RESIDUAL OWINGSSURE FLOW RATE
REDUCING &FLOOR MODEL
VALVE TEST INLET(PSI) OUTLET(PSI) INLET(PSI) OUTLET(PSI) FLOW(GPM)
r
HYDROSTATIC:Hydrostatic tests shall be made at not less than 200 psi(13.6 bars)for two hours or 50 psi(3.4 bars)above static
TEST pressure in excess of 150 psi(10.2 bars)for two hours.Differential dry-pipe valve clappers shall be left open during test to prevent
DESCRIPTION damage.All aboveground piping leakage shall be stopped.
PNEUMATIC:Establish 40 psi(2.7 bars)air pressure and measure drop,which shall not exceed 1'/psi(0.1 bars)in 24 hours.Test
ressure tanks at normal water level and air twessure and measure air messure drop which shall not exceed 1% si in 24 hours.
Al I PIPING ALLY TESTED AT 200 PSI FOR 2 HOURS IF NO,STATE REASON
DRY PIPING PNEUMATICALLY TESTED ❑YES ®NO
EQUIPMENT OPERATES PROPERLY ®YES ❑NO
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT ADDITIVES AND CORROSIVE CHEMICALS,SODIUM SILICATE
OR DERIVATIVES OF SODIUM SILICATE,BRINE,OR OTHER CORROSIVE CHEMICALS WERE NOT USED FOR TESTING
SYSTEMS OR STOPPING LEAKS? M YES rl NO
DRAIN READING OF GAGE LOCATED NEAR WATER RESIDUAL PRESSURE WITH VALVE IN TEST
TESTS TEST SUPPLY TEST CONNECTION PSI CONNECTION OPEN WIDE PSI
UNDERGROUND MAINS AND LEAD-IN CONNECTIONS TO SYSTEM RISERS FLUSHED BEFORE
CONNECTION MADE TO SPRINKLER PIPING.
VERIFIED BY COPY OF THE U FORM NO.858 ❑YES ❑NO OTHER EXPLAIN
FLUSHED BY INSTALLER OF UNDERGROUND
SPRINKER PIPING ❑YES ❑NO
IF POWDER DRIVEN FASTENERS ARE USED IN CONCRETE IF NO,EXPLAIN
HAS REPRESENTATIVE SAMPLE TESTING BEEN COMPLETED? YES F1NO
BLANK TEST NUMBER USED LOCATIONS NUMBER REMOVED
GASKETS 0
WELDED PIPING M YES ❑NO
IF YES...
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT WELDING PROCEDURES COMPLY
WITH THE REQUIREMENTS OF AT LEAST AWS D10.9.LEVEL AR 3? ®YES ❑NO
DO YOU CERTIFY THAT THE WELDING WAS PERFORMED BY WELDERS QUALIFIED IN COMPLIANCE
WELDING WITH THE REQUIREMENTS OF AT LEAST AWS D10.9.LEVEL AR 3? ®YES ❑NO
DO YOU CERTIFY THAT WELDING WAS CARRIED OUT IN COMPLIANCE WITH A DOCUMENTED
QUALITY CONTROL PROCEDURE TO INSURE THAT ALL DISCS ARE RETRIEVED,THAT OPENINGS
IN PIPING ARE SMOOTH,THAT SLAG AND OTHER WELDING RESIDUE ARE REMOVED,AND THAT
THE INTERNAL DIAMETERS OF PIPING ARE NOT PENETRATED? M YES n NO
CUTOUTS DO YOU CERTIFY THAT YOU HAVE A CONTROL FEATURE TO ENSURE THAT ALL CUTOUTS(DISCS)
DISCS ARE RETRIEVED? YES NO
HYDRAULIC NAMEPLATE PROVIDED IF NO,EXPLAIN
DATA ®YES ❑NO
NAMEPLATE
DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN.
REMARKS
NAME OF SPRINKER CONTRACTOR: f �Z
MACK FIRE PROTECTION LLC
SIGNATURES TESTS WPtNFSSED B
FOR PROP RT R TITLE DATE !� J
FOR SPRI_, LE R(. D} DATE
I
ADDITIONAL EXPLANATIONS AND NOTES:
r -
i -
Contractor's Material and Test Certificate for Aboveground Piping
PROCEDURE
Upon completion of work,inspection and tests shall be made by the Contractors representative and witnessed by an owner's representative. All defects
shall be corrected and system left in service before contractor's personnel finally leave the job. sand contractor.It is
certificate shall
understood the owner's representative's signature in no way prejudices any claim against contractor for faulty material,poor workmanship,or failure to
comply with approving authority's requirements or local ordinances.
PROPERTY NAME FEDEX GROUND DATE NOVEMBER 1 2012
PROPERTY ADDRESS 40 KENNEDY ROAD,SOUTH WINDSOR,CT
ACCEPTED BY APPROVING AUTHORITIES(NAMES) TOWN OF SOUTH WINDSOR FIRE DEPARTMENT
ADDRESS 1175 ELLINGTON STREET SOUTH WINDSOR CT 06074
PLANS INSTALLATION CONFORMS TO ACCEPTED PLANS ®YES ❑ NO
EQUIPMENT USED IS APPROVED
IF NO,EXPLAIN DEVIATIONS
HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION ®YES ❑ NO
OF CONTROL VALVES AND CARE AND MAINTENANCE OF THEIS NEW EQUIPMENT?
IF NO,EXPLAIN
INSTRUCTIONS HAVE COPIES OF THE FOLLOWING BEEN LEFT ON THE PREMISES ®YES ❑ NO
1. SYSTEM COMPONENTS INSTRUCTIONS ®YES ❑ NO
2. CARE AND MAINTENANCE INSTRUCTIONS ®YES ❑ NO
3. NFPA 25 ®YES ❑ NO
LOCATION SUPPLIES BUILDINGS
YEAR OF ORIFICE TEMPERATURE
MAKE MODEL MANUFACTURE SIZE QUANTITY RATING
SPRINKLERS VICTAULIC V3406 2012 3/4" 21 155"F
VICTAULIC V3402 2012 3/4" 1 155°F
VICTAULIC V3401 2012 3/4" 286`F
VICTAULIC V3426 2012 3/4" 192 165°F
VICTAULIC V3608 2012 3/4'
PIPE AND TYPE OF PIPE BLACK SCHEDULE 10 AND SCHEDULE 40
FITTINGS TYPE OF FITTINGS GROOVED AND THREADED CAST IRON
MAXIMUM TIME TO OPERATE
ALARM VALVE ALARM DEVICE THROUGH TEST CONNECTION
OR TYPE MAKE MODEL MIN SEC
FLOW
INDICATOR MAKE- MODEL SERIAL NO. MAKE MODE SERIAL NO.
VICTAULIC NXT TIME WATER ALARM
TIME TO TRIP
DRY PIPE THROUGH TEST WATER AIR RIP POINT REACHED OPERATED
OPERATING CONNECTION PRESSURE PRESSURE IR PRESSURE TEST OUTLET PROPERLY
TEST MIN SEC PSI PSI PSI MIN SEC YES NO
WITH ` r r
Q.O.D.
W/O
Q.O.D.
IF NO,EXPLAIN
OPERATION ❑PNEUMATIC ❑ELECTRIC ❑HYDRAULIC
PIPING SUPERVISED ❑YES ❑NO DETECTING MEDIA SUPERVISED ❑YES ❑NO
DOES THE VALVE OPERATE FROM THE MANUAL TRIP AND/OR REMOTE ❑YES ❑NO
DELUGE& CONTROL STATIONS
PREACTION IS THERE AN ACCESSIBLE FACILITY IN EACH CIRCUIT IF NO,EXPLAIN
VALVES FOR TESTING? ❑YES ❑NO
DOES EACH CIRCUIT OPERATE DOES EACH CIRCUIT MAXIMUM TIME TO
MAKE MODE SUPERVSSEO LOSS ALARM OPERATE ALVE RELEASE OPERATE RELEASE
YES NO YES NO MIN SEC
PRESSURE LOCATION MAKE& SETTING STATIC PRESSURE RESIDUAL L R�SSURE FLOW RATE
REDUCING &FLOOR MODEL
VALVE TEST INLET(PSI) OUTLET(PSI) INLET(PSI) OUTLET(PSI) FLOW(GPM)
HYDROSTATIC:Hydrostatic tests shall be made at not less than 200 psi(13.6 bars)for two hours or 50 psi(3.4 bars)above static
TEST pressure in excess of 150 psi(10.2 bars)for two hours.Differential dry-pipe valve clappers shall be left open during test to prevent
DESCRIPTION damage.All aboveground piping leakage shall be stopped.
PNEUMATIC:Establish 40 psi(2.7 bars)air pressure and measure drop,which shall not exceed 1'/psi(0.1 bars)in 24 hours.Test
pressure tanks at normal water level and air oressure and measure air pressure droo which shall not exceed 1'/z psi in 24 hours.
1DROSTATICALLY TESTED AT 200 PSI FOR 2 HOURS IF NO,STATE REASON
DRY PIPING PNEUMATICALLY TESTED YES N NO
EQUIPMENT OPERATES PROPERLY ®YES ❑NO
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT ADDITIVES AND CORROSIVE CHEMICALS,SODIUM SILICATE
OR DERIVATIVES OF SODIUM SILICATE,BRINE,OR OTHER CORROSIVE CHEMICALS WERE NOT USED FOR TESTING
SYSTEMS OR STOPPING LEAKS? ®YES ❑NO
DRAIN READING OF GAGE LOCATED NEAR WATER RESIDUAL PRESSURE WITH VALVE IN TEST
TESTS TEST SUPPLY TEST CONNECTION PSI CONNECTION OPEN WIDE PSI
UNDERGROUND MAINS AND LEAD-IN CONNECTIONS TO SYSTEM RISERS FLUSHED BEFORE
CONNECTION MADE TO SPRINKLER PIPING.
VERIFIED BY COPY OF THE U FORM NO.858 ❑YES ❑NO OTHER EXPLAIN
FLUSHED BY INSTALLER OF UNDERGROUND
SPRINKER PIPING ❑YES ❑NO
IF POWDER DRIVEN FASTENERS ARE USED IN CONCRETE IF NO,EXPLAIN
HAS REPRESENTATIVE SAMPLE TESTING BEEN COMPLETED? n YES n NO
BLANK TEST NUMBER USED LOCATIONS NUMBER REMOVED
GASKETS 0
WELDED PIPING ®YES ❑NO
IF YES...
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT WELDING PROCEDURES COMPLY
WITH THE REQUIREMENTS OF AT LEAST AWS D10.9.LEVEL AR 3? ®YES ❑NO
DO YOU CERTIFY THAT THE WELDING WAS PERFORMED BY WELDERS QUALIFIED IN COMPLIANCE
WELDING WITH THE REQUIREMENTS OF AT LEAST AWS D10.9.LEVEL AR 3? ®YES El NO
DO YOU CERTIFY THAT WELDING WAS CARRIED OUT IN COMPLIANCE WITH A DOCUMENTED
QUALITY CONTROL PROCEDURE TO INSURE THAT ALL DISCS ARE RETRIEVED,THAT OPENINGS
IN PIPING ARE SMOOTH,THAT SLAG AND OTHER WELDING RESIDUE ARE REMOVED,AND THAT YES n NO
THE INTERNAL DIAMETERS OF PIPING ARE NOT PENETRATED?
CUTOUTS DO YOU CERTIFY THAT YOU HAVE A CONTROL FEATURE TO ENSURE THAT ALL CUTOUTS(DISCS) YES NO
DISCS ARE RETRIEVED? IF NO,EXPLAIN
HYDRAULIC NAMEPLATE PROVIDED ®YES ❑NO
DATA
NAMEPLATE
DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN.
REMARKS
NAME OF SPRINKER CONTRACTOR-
MACK FIRE PROTECTION LLC
SIGNATURES STS TNESSED BY
FOR PROP R SI ' D) TITLE/ DATE
n
FOR SPR1 L R R TITLE _ DATE
ADDITIONAL EXPLANATIONS AND NOTES: t�
a
Contractor's Material and Test Certificate for Aboveground Piping
PROCEDURE
Upon completion of work,inspection and tests shall be made by the Contractor's representative and witnessed by an owner's representative. All defects
shall be corrected and system left in service before contractor's personnel finally leave the job.
A GeFtifiGate shall be filled out and signed by both representatives Copies shall hp prep;ired for appmving authoriflt-q,owners and contractor,It
understood the owner's representative's signature in no way prejudices any claim against contractor for faulty material,poor workmanship,or failure to
comply with approving authority's requirements or local ordinances.
PROPERTY NAME FEDEX GROUND DATE NOVEMBER 1,2012
PROPERTY ADDRESS 40 KENNEDY ROAD,SOUTH WINDSOR,CT
ACCEPTED BY APPROVING AUTHORITIES(NAMES) TOWN OF SOUTH WINDSOR FIRE DEPARTMENT
ADDRESS 1175 ELLINGTON STREET, SOUTH WINDSOR CT 06074
PLANS INSTALLATION CONFORMS TO ACCEPTED PLANS ®YES ❑ NO
EQUIPMENT USED IS APPROVED ®YES ❑ NO
IF NO,EXPLAIN DEVIATIONS
HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION ®YES ❑ NO
OF CONTROL VALVES AND CARE AND MAINTENANCE OF THEIS NEW EQUIPMENT?
IF NO,EXPLAIN
INSTRUCTIONS HAVE COPIES OF THE FOLLOWING BEEN LEFT ON THE PREMISES ®YES ❑ NO
1. SYSTEM COMPONENTS INSTRUCTIONS ®YES ❑ NO
2. CARE AND MAINTENANCE INSTRUCTIONS ®YES ❑ NO
3. NFPA 25 ®YES ❑ NO
LOCATIONL
YEAR OF ORIFICE TEMPERATURE
MAKE MODEL MANUFACTURE SIZE QUANTITY RATING
SPRINKLERS VICTAULIC V3406 2012 3W- 155°F
VICTAULIC V3402 2012 3/4" 155°F
VICTAULIC V3401 2012 3/4" 286"F
VICTAULIC V3426 2012 3/4" 231 286°F
VICTAULIC V3608 2012 3/4" 4 165°F
PIPE AND TYPE OF PIPE BLACK SCHEDULE 10 AND SCHEDULE 40
FITTINGS TYPE OF FITTINGS GROOVED AND THREADED CAST IRON
MAXIMUM TIME TO OPERATE
ALARM VALVE ALARM DEVICE THROUGH TEST CONNECTION
OR TYPE MAKE MODEL MIN SEC
FLOW
INDICATOR --4-
MAKE MODEL SERIAL NO. MAKE MODE SERIAL NO.
VICTAULIC NXT
TIME TO TRIP TIME WATER ALARM
DRY PIPE THROUGH TEST WATER AIR TRIP POINT REACHED OPERATED
OPERATING CONNECTION PRESSURE PRESSURE AIR PRESSURE TEST OUTLET PROPER
TEST MIN I SEC - PSI PSI PSI MIN SEC YES NO
WITH L
Q.O.D.
W/O
Q.O.D.
IF NO,EXPLAIN
OPERATION F1 PNEUMATIC M ELECTRIC Fl HYDRAULIC
PIPING SUPERVISED n YES ❑NO DETECTING MEDIA SUPERVISED Fl YES ❑NO
DOES THE VALVE OPERATE FROM THE MANUAL TRIP AND/OR REMOTE
DELUGE& CONTROL STATIONS ❑YES ❑NO
PREACTION IS THERE AN ACCESSIBLE FACILITY IN EACH CIRCUIT IF NO,EXPLAIN
VALVES FOR TESTING? ❑YES F I NO
DOES EACH CIRCUIT OPERATE DOES EACH CIRCUIT MAXIMUM TIME TO
MAKE MODE SUPERVSSEO LOSS ALARM OPERATE ALVE RELEASE OPERATE RELEASE
YES NO YES NO MIN I SEC
PRESSURE LOCATION MAKE& SETTING STATIC PRESSURE RESIDUAL PRESSURE FLOW RATE
REDUCING &FLOOR MODEL (FLOWING)
VALVE TEST INLET(PSI) OUTLET(PSI) INLET(PSI) OUTLET(PSI) FLOW(GPM)
1
HYDROSTATIC:Hydrostatic tests shall be made at not less than 200 psi(13.6 bars)for two hours or 50 psi(3.4 bars)above static
TEST pressure in excess of 150 psi(10.2 bars)for two hours.Differential dry-pipe valve clappers shall be left open during test to prevent
DESCRIPTION damage.All aboveground piping leakage shall be stopped.
PNEUMATIC:Establish 40 psi(2.7 bars)air pressure and measure drop,which shall not exceed 1%psi(0.1 bars)in 24 flours.Test
ressure tanks at normal water level and air vessure and measure air pressure drop which shall not exceed IY2 psi in 24 hours.
ALL PIPING HYDROSTATICALLY TESTED AT 200 PSI FOR 2 HOURS IF NO,STATE REASON
DRY PIPING PNEUMATICALLY TESTED
EQUIPMENT OPERATES PROPERLY ®YES ❑NO
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT ADDITIVES AND CORROSIVE CHEMICALS,SODIUM SILICATE
OR DERIVATIVES OF SODIUM SILICATE,BRINE,OR OTHER CORROSIVE CHEMICALS WERE NOT USED FOR TESTING
SYSTEMS OR STOPPING LEAKS? ®YES ❑NO
DRAIN READING OF GAGE LOCATED NEAR WATER RESIDUAL PRESSURE WITH VALVE IN TEST
TESTS TEST SUPPLY TEST CONNECTION PSI CONNECTION OPEN WIDE PSI
UNDERGROUND MAINS AND LEAD-IN CONNECTIONS TO SYSTEM RISERS FLUSHED BEFORE
CONNECTION MADE TO SPRINKLER PIPING.
VERIFIED BY COPY OF THE U FORM NO.858 ❑YES ❑NO OTHER EXPLAIN
FLUSHED BY INSTALLER OF UNDERGROUND
SPRINKER PIPING ❑YES FIND
IF POWDER DRIVEN FASTENERS ARE USED IN CONCRETE IF NO,EXPLAIN
HAS REPRESENTATIVE SAMPLE TESTING BEEN COMPLETED? YES n NO
BLANK TEST NUMBER USED LOCATIONS NUMBER REMOVED
GASKETS 0
WELDED PIPING YES NO
IF YES...
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT WELDING PROCEDURES COMPLY
WITH THE REQUIREMENTS OF AT LEAST AWS D10.9.LEVEL AR 3? ®YES ❑NO
DO YOU CERTIFY THAT THE WELDING WAS PERFORMED BY WELDERS QUALIFIED IN COMPLIANCE
WELDING WITH THE REQUIREMENTS OF AT LEAST AWS D10.9.LEVEL AR 3? ®YES NO
DO YOU CERTIFY THAT WELDING WAS CARRIED OUT IN COMPLIANCE WITH A DOCUMENTED
QUALITY CONTROL PROCEDURE TO INSURE THAT ALL DISCS ARE RETRIEVED,THAT OPENINGS
IN PIPING ARE SMOOTH,THAT SLAG AND OTHER WELDING RESIDUE ARE REMOVED,AND THAT YES n NO
THE INTERNAL DIAMETERS OF PIPING ARE NOT PENETRATED?
CUTOUTS DO YOU CERTIFY THAT YOU HAVE A CONTROL FEATURE TO ENSURE THAT ALL CUTOUTS(DISCS) YES n NO
DISCS ARE RETRIEVED? IF NO,EXPLAIN
HYDRAULIC NAMEPLATE PROVIDED ®YES ❑NO
DATA
NAMEPLATE
DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN.
REMARKS
NAME OF SPRINKER CONTRACTOR: pr0! Z
MACK FIRE PROTECTION LLC
SIGNATURES TES S WITNESSED BY
FOR PROPERTY 0 {R(SIG ED TITLE DATE
FOR LrjP,,I C (SIGNE
ADDITIONAL EXPLANATIONS NDGG�'NOTES: