HomeMy WebLinkAbout74 Andreis Trail - UST - Fire Marshal T RemovalTankworks . Replacement January 12, 2012 E C;E Ids Mark Millward APR 1 t 2012 1200 Strong Road South Windsor, CT 06074 BY- RE: Removal and Disposal of(1) 1,000 Gallon Underground Heating Oil Tank At: 74 Andreis Trail, South Windsor, CT 06074 Dear Mr. Millward: Thank you for the opportunity to service the removal of the buried oil tank at the above referenced address. The work was performed in accordance with E.P.A. Regulations and N.F.P.A. 30 and 30A Requirements. The building official from the town of Bolton was on site to witness the underground tank removal. The soil in the grave showed no signs of contamination and was backfilled. Before backfilling one final confirmation soil sample was collected and tested at an independent lab for CTETPH (extractable petroleum hydrocarbons). The recommended limit in a GA Ground Water Classification is 500 ppm (parts per million). These results are non- detectable. This letter, along with the attached soil sample results, should be stored safely with all legal documents pertaining to this property. This information, along with your Tankworks invoice and cancelled checks will serve as verification for future reference. Please feel free to call us if you have any further questions. It has been a pleasure working with you. We hope that you are pleased with our services and that you will recommend us to others. Very truly yours, Rosemar Viola Owner CC: Town of South Windsor Fire Marshal's Office, 1540 Sullivan Avenue, South Windsor, CT 06074 1-800-653-3140 Main Office 360 East Center s1t. Manchester, CT 06040 V PHOEIIt yr n Environmental Laboratories, Inc. ,�� act 587 East Middle Turnpike,P.O.Box 370, Manchester, CT 06045 Tel. (860)645-1102 Fax(860)645-0823 Analysis Report FOR: Attn: Mrs. Rose Rainville Tankworks Removal & Replacement, LLC January 11, 2012 360 East Center Street Manchester, CT 06040 Sample Information Custody Information Date Time Matrix: SOIL Collected by: 01/03/12 0:00 Location Code: TANKWKS Received by: LB 01/06/12 15:17 Rush Request: RUSH24 Analyzed by: see"By" below P.O.#: Laboratory Data SDG ID: GBB28557 Phoenix ID: BB28557 Project ID: 74 ANDREIS TRAIL Client ID: BOTTOM Parameter Result RL Units Date Time By Reference Percent Solid 87 % 01/06/12 JL El60.3 Extraction of CT ETPH Completed 01/06/12 SS/F 3545 TPH by GC (Extractable Products) Ext.Petroleum HC ND 11 mg/Kg 01/09/12 JRB CT ETPH/8015 Identification ND mg/Kg 01/09/12 JRB CT ETPH/8015 QA/QC Surrogates %n-Pentacosane 66 % 01/09/12 JRB 50-150% Comments: If there are any questions regarding this data, please call Phoenix Client Services at extension 200. ND=Not detected BDL=Below Detection Level RL=Reporting Level This report must not be reproduced except in full as defined by the attached chain of custody. Phyllis hiller,Laboratory Director January 11,2012 Page 1 of 1 Ver 1 k � s PHOENIX ' - Environmental Laboratories Inc. 587 East Middle Turnpike, P.O.Box 370, Manchester,CT 06045 NY.it 11301 QA/QC Report Tel.(860)645-1102 Fax(860)645-0823 January 11, 2012 QA/QC Data SDG I.D.: GBB28557 LCS LCSD LCS MS MSD MS Rec RPD Parameter Blank % % RPD % % RPD Limits Limits QA/QC Batch 192034,QC Sample No: BB28503(BB28557) TPH by GC (Extractable Products) - Soil Ext.Petroleum HC ND 61 68 10.9 62 58 6.7 50-150 30 %n-Pentacosane 73 74 81 9.0 74 80 7.8 50-150 30 If there are any questions regarding this data, please call Phoenix Client Services at extension 200. RPD-Relative Percent Difference LCS-Laboratory Control Sample LCSD-Laboratory Control Sample Duplicate MS-Matrix Spike MS Dup-Matrix Spike Duplicate Phyllie hiller, Laboratory Director NC- No Criteria Janua11,2012 Page 1 of 1