HomeMy WebLinkAbout74 Andreis Trail - UST - Fire Marshal T
RemovalTankworks
. Replacement
January 12, 2012 E C;E Ids
Mark Millward APR 1 t 2012
1200 Strong Road
South Windsor, CT 06074 BY-
RE: Removal and Disposal of(1) 1,000 Gallon Underground Heating Oil Tank
At: 74 Andreis Trail, South Windsor, CT 06074
Dear Mr. Millward:
Thank you for the opportunity to service the removal of the buried oil tank at the above
referenced address. The work was performed in accordance with E.P.A. Regulations and
N.F.P.A. 30 and 30A Requirements. The building official from the town of Bolton was
on site to witness the underground tank removal.
The soil in the grave showed no signs of contamination and was backfilled. Before
backfilling one final confirmation soil sample was collected and tested at an independent
lab for CTETPH (extractable petroleum hydrocarbons). The recommended limit in a GA
Ground Water Classification is 500 ppm (parts per million). These results are non-
detectable.
This letter, along with the attached soil sample results, should be stored safely with all
legal documents pertaining to this property. This information, along with your
Tankworks invoice and cancelled checks will serve as verification for future reference.
Please feel free to call us if you have any further questions. It has been a pleasure
working with you. We hope that you are pleased with our services and that you will
recommend us to others.
Very truly yours,
Rosemar Viola
Owner
CC: Town of South Windsor Fire Marshal's Office, 1540 Sullivan Avenue, South
Windsor, CT 06074
1-800-653-3140 Main Office 360 East Center s1t. Manchester, CT 06040
V
PHOEIIt yr n
Environmental Laboratories, Inc. ,�� act
587 East Middle Turnpike,P.O.Box 370, Manchester, CT 06045
Tel. (860)645-1102 Fax(860)645-0823
Analysis Report FOR: Attn: Mrs. Rose Rainville
Tankworks Removal & Replacement, LLC
January 11, 2012 360 East Center Street
Manchester, CT 06040
Sample Information Custody Information Date Time
Matrix: SOIL Collected by: 01/03/12 0:00
Location Code: TANKWKS Received by: LB 01/06/12 15:17
Rush Request: RUSH24 Analyzed by: see"By" below
P.O.#:
Laboratory Data SDG ID: GBB28557
Phoenix ID: BB28557
Project ID: 74 ANDREIS TRAIL
Client ID: BOTTOM
Parameter Result RL Units Date Time By Reference
Percent Solid 87 % 01/06/12 JL El60.3
Extraction of CT ETPH Completed 01/06/12 SS/F 3545
TPH by GC (Extractable Products)
Ext.Petroleum HC ND 11 mg/Kg 01/09/12 JRB CT ETPH/8015
Identification ND mg/Kg 01/09/12 JRB CT ETPH/8015
QA/QC Surrogates
%n-Pentacosane 66 % 01/09/12 JRB 50-150%
Comments:
If there are any questions regarding this data, please call Phoenix Client Services at extension 200.
ND=Not detected BDL=Below Detection Level RL=Reporting Level
This report must not be reproduced except in full as defined by the attached chain of custody.
Phyllis hiller,Laboratory Director
January 11,2012
Page 1 of 1 Ver 1
k
� s
PHOENIX ' -
Environmental Laboratories Inc.
587 East Middle Turnpike, P.O.Box 370, Manchester,CT 06045 NY.it 11301
QA/QC Report Tel.(860)645-1102 Fax(860)645-0823
January 11, 2012 QA/QC Data SDG I.D.: GBB28557
LCS LCSD LCS MS MSD MS Rec RPD
Parameter Blank % % RPD % % RPD Limits Limits
QA/QC Batch 192034,QC Sample No: BB28503(BB28557)
TPH by GC (Extractable Products) - Soil
Ext.Petroleum HC ND 61 68 10.9 62 58 6.7 50-150 30
%n-Pentacosane 73 74 81 9.0 74 80 7.8 50-150 30
If there are any questions regarding this data, please call Phoenix Client Services at extension 200.
RPD-Relative Percent Difference
LCS-Laboratory Control Sample
LCSD-Laboratory Control Sample Duplicate
MS-Matrix Spike
MS Dup-Matrix Spike Duplicate Phyllie
hiller, Laboratory Director
NC- No Criteria Janua11,2012