HomeMy WebLinkAbout9 Cliffwood Drive - Building Plans & Dra RESIDENTIAL CARE HOME
9 CLI FFWOOD DRIVE
SOUTH WINDSOR, CT
Architect:
Blue Moon Design
168 Main Street
Terryville, CT 06786
860-582-2225
CODE INFORMATION GENERAL NOTES SCOPE OF WORK DRAWING INDEX
Applicable ReFerecnes: To lorovide a 5 person(exclud(ng employees) residential care A-1 LOWER PLANS
International Building Code 2003 horde. Construction classification of R-4 carries a similar hazard A-2 UPPER PLANS
Connecticut 2005/2009 Supplements classification as a one and two famlly use. No HCP acce6s(b(14 is
Connecticut 2003 International Fire Code required pper section 1007.1 existing buildings but is provided.
New handfalls shall be provided as noted on the plans.
2 USE GROUP CLASSIFICATION: R-4, Residential Care/Assisted Living. 6 person. Provide a new sprinkler system and alarm system. New fire alarm
305 9 p notification appliances must be visual and audible per NFPA 72
310.1 R 4: R-4 to follow R-3 construction requirements 5ec. 12. Provide shop drawings for sprinklers for Building
Department review.
503T HEIGHT/AREA LIMITATIONS: R-3: 4073st/ unlimited s.f. (allowed per 310.4)
20'/2stJ2,100 b.f. (actual)
WIT TYPES OF CONSTRUCTION: TYPE VB (unprotected)
Structural frame 01T.
Bearing wallsExter(or 0 hr.
Interior 0 hr.
Nonbearing Interior walls 0IT.
Floor construction 0 hr.
Roof construction 0 hr.
1012 SHAFT ENCLOSURES: 0 HR., Exc. "I Not required for openings w/In an Individual dwelling unit and
connecting 4 stories or less.
W35 INTERIOR FINISHES: (Sprinklered)
Vert.exit 4 passageways C
Exit access corridors 4 other exitwap C
Rooms and enclosed spaces G
9W32.1.1 AUTOMATIC SPRINKLERS: Required/provided.NFPA 13D allowed.
90(0.1 PORTABLE FIRE EXTINGUISHERS: Provided as shown on plans. r I
901.0 FIRE ALARM 4 DETECTION: Fire alarm not required but provided. Genera
IeI a NO lj�e5
9012.10 MULTIPLE-STATION SMOKE PET: Required and provided.
901.9.1 VISIBLE ALAW5 Not required but provided. 1.) Due to the nature of extst(nq�conditions, the General Contractor shall
field verify all dimensions anti exist. conditions and shall notify owner
912.1 CARBON MONOXIDE DETECTORS: Provided. of any discrepancies or new Information prior to start of
construction.
100(0.1 EMERGENCY LIGHTING: Exc. 03,not required for dwelling units and sleeping units In the R-3 2.) The contractor shall comply with all local, state and federal
use but provided. regulations.
1001.1 ACCESSIBLE MEANS OF EGRESS: Exc.h Accessible means of egress are not required in alterations to 3.) Contractor shall be responsible for securing all necessary permits
existing buildings but provided. and fees.
1009.11 HANDRAILS: Exc. +7 Stairways within a dwelling unit require one handrail_ Framing
1011.1 EXIT SIGNS: Not required per exc.03. 1 I I I It y�Iq Notes :
1019.1 VERTICAL OPENINGS: Not required per 1019.I,exc. M(occupant load less than 10), 03(R-3 use). 1.) All floor, ceiling 4 roof fram(n lumber to be Douglas Fir-Larch 02 or
better or HemFlf (North) 02 or-better
2.) All framing shall be spaced at iV' 04. unless noted otherwise.
3.) Provide cross bridging at V-0" o.c. maximum within all horizontal
framing.
4.) All connectors in contact w/ pressure treated shall be Simpson
connectors w/ 'Zmax' galvanl2ed finish
E0 Provide solid blocking at all columns and/or posts to transfer loads
to structure below.
a nth`:4-0 4
76�,";`4rU r
N
N
N
N
(^V J O
W
r i
W
n
U
LEGEND GN
O J a m 5
O C N
~ E °o
PB Indicates manual pull box
W`
fv
�
UindicatesI emergency strobe U
L 1— U
9
Q
O ht
detector AC/DC smoke
AP Annunciator Panel
• epprbxJnkler head (location � � �
Line or existing
deck above.
AC/DC Emergency light peck
Existing
O Fire extinguisher _+,I up Dn
Exterior
Ext. light emergency
Ilght.
Exterior Exist. Exist. Exist. Exist. Exist.
emergen
Ilght. cy
oil [7 a D O
o � 0
w
MO
/ O
Cxara e • ; U
0— Existing a O D 0
Ln
-070
0
Da
0 Existing t C
v \ U
• 2v
• • • tip0 .
QS
®• Ceara e
Existing
Famflu Rh
Block-In Existing • o L
Recreation exist. _°
f7replace.
U U_
ExistingW
❑s ® ® ) 3
t J
N
Mech
Existing Date: 6-27-11
PB Revisions:
m
Exterior
emergency
light.
LOUDER FLOOR PLAN
Drawn By: TC/CH
SCALE: 1/4
ll4
_0
1
1
2,100 -0. ..
y
4
N
N
N
N
N
UO
LEGEND
Q�
F,B Indicates manual pull box U o N
LIP
'O CO
Iii
Indicates emergency strobe O N FCG o c
light ` � °o
Indicates AC/DC smoke @j
detector b
� U
AP Annunciator Panel r u
U
Newsprinkler head (location i.
• approx.)
AC/PC Emergency tight Peck
Existing
pn
OFire extinguisher Dn
Deck
Exterior Existing
emergency
Provide new Ext. light Ight.
door In existing
Exist. Exist. Exist. opening. Exist. Exist. Exist. Exist.
��iiiiii7o&[
000
O Oa Meds I New eqress U
New a ress �f' m
`a°� t. Office p�°vide caeem�nt.
locks as
Remove ciao }� g_p x7_q req'd. I
stove.Provide
electric unit. xt edrm. 04
Bedrm. I XIT Existing (/)
Existing Exinin 30"
g Kitchen Remove
Existing up klisdienng
OS fixtures.
s ; u
Dn PB O po
O
• - - - - - - - - Dn •V V • O O
• 0 s • o U o
I
Block-I
exist. 3=am i
Bedrm. 02 I edrm. *33 ivin fireplace.
Existing Existing Existing Existing •
- - - Bedrm S
I
Existing
I New egqress o 0
casement. a O
I 0
Z*=Af I Exist. Q
v !Z
New egqress New eegqress N
casements. casements. Exterior
emergency
light.
Date: 6-27-11
UPPER FLOOR PLAN Porch Revisions:
Existing
5CALE: 1/4"=1'-0" 2,100 s.f. Dn
Drawn By: TC/CH
h
r
%%%,.hq 4 7e
,r
DF-52416:0•A3-20
MS-5UD )/MS-1OUD(E) Series FII'@•LITeALc'll'MS
no Fire Alarm Control Panel
Ten Zone Fire Alarm Control Panel by Honeywell
General
The MS-5UD-3(E) is a five-zone FACP (Fire Alarm Control
Panel)and the MS-10UD-7(E)is a ten-zone FACP.These con-
trol panels provide reliable fire signaling protection for small to
medium-sized commercial, industrial, and institutional build-
ings. Both panels include built-in communicators for Central
Station Service and remote upload/download. ui r
Each of these FACPs is compatible with System Sensor's f
microprocessor-based is series detectors.These conventional
smoke detectors can transmit a maintenance trouble signal to
the FACP indicating the need for cleaning and a supervisory
'freeze"signal when the ambient temperature falls below the
detector rating. Additionally, both the MS-5UD-3 and MS-
10UD-7 are compatible with conventional input devices such
as two-and four-wire smoke detectors,pull stations,waterflow,
devices, tamper switches, and other normally-open contact a
devices. Refer to the Fire-Lite Device Compatibility Document s
for a complete listing of compatible devices. '^
's
Outputs include four NACs (Notification Appliance Circuits), "
three programmable Form-C relays (fabtory programmed for
Alarm,Trouble,and Supervisory)and 24 VDC special applica-
tion resettable and nonresettable power outputs. The FACPs
supervise all wiring, AC voltage, battery level and telephone _Strobe Synchronization for System Sensor, Wheelock,
line integrity. Gentex,Faraday,or Amseco devices.
Activation of a compatible smoke detector or any normally- _Selective Silence(horn-strobe mute).
open fire alarm initiating device will activate audible and visual
signaling devices, illuminate an indicating LED, sound the —Temporal or Steady Signal.
piezo sounder at the FACP, activate the communicator and —Silenceable or Nonsilenceable.
FACP alarm relay, and operate an optional module used to - Optional CAC-5X Style Z (Class A) Converter Module for
notify a remote station or initiate an auxiliary control function. NACs and IDCs(2 required for MS-10UD-7).
New options include a UL listed printer,PRN-6F and Firel-ite's • Form-C Relays for Alarm, Trouble and Supervisory- Con-
IPDACT Internet Monitoring module. The Fire Watch Series tact Ratings 2.0 A@ 30 VDC or 0.5 A M 30 VAC(resistive).
internal monitoring modules IPDACT-2 and IPDACT-2UD per, - 3.0 A total system current for MS-5UD3.
mit monitoring of alarm signals over the Internet saving the - 7.0 A total system current for MS-10UD-7.
monthly cost of two telephone lines.Although not required,the
secondary telephone line may be retained providing backup • Optional Dress Panel DP-51050
communication over the public switched telephone line. • Optional Trim Ring TR-CE for semi-flush mounting.
NOTE. The MS-5UD3E and MS-f0UD-7E offers the same fee- - • 24 volt operation.
tunes as the MS.5UD-3 and MS-f0UD-7 but allow connection to • Low AC voltage sense.
240 VAC. Unless otherwise specified,the information in this data
sheet applies to both the 120 VAC and the 240 VAC versions of • Alarm Verification.
these panels • PAS(Positive Alarm Sequence).
NOTE.,For ULGlisted models,see DF-60440. • Automatic battery trickle charger.
• Up to eight ANN-BUS annunciators: -
Features —Optional 8 zone Relay Module ANWRLY.
• Listed to UL Standard 864,9th edition. —Optional LED Annunciator Module ANN-LED,
• Built-in DACT(Digital Alarm CommunicatoJiransmitter). —Optional Remote Annunciator ANN-80.
• Style B(Class B)IDC(Initiating Device Circuit) —Optional Remote Printer Gateway ANN-S/PG.
—MS-5UD-3-five IDCs. —Optional LED Annunciator Driver ANN-1/0.
—MS-10UD-7-ten IDCs. Optional 4XTMF module (conventional reverse polarity/city
• Style Y(Class B)NAC(Notification Appliance Circuit)-spe- box transmitter).
cial application power PROGRAMMING AND SOFTWARE.
—MS-5UD-3-four NACs. • Can be programmed at the panel with no special software
—MS-10UD-7-four NACs. or additional equipment.
• Notification Appliances may be programmed as • Programmable Make/Break Ratio.
—Silence Inhibit. • Upload/Download(local or remote)of program and data via
—Auto-Silence. integral DACT.
DF-52416:D-07/262010—Page 1 of 4
Fire alarm System
Community Residences Inc.
9 Cliffwood Drive
South Windsor, Ct. 06074
DIGITAL Communicator Inc.
4 Aarons Way
East Hampton, Ct. 06424
860-267-8069
FlreuTemarms MS-5UD-3 Battery Calculation
by Honeywell
Calculation in Total Sheet
24 Hours
Standby Load Current 0.11508 Am s x 24 1=1 2.762 AH
30 Minutes
Alarm Load Current Am 5.31000 Amps x 0.5 1= 0.155 AH
Total Current Load 2.917 AH
Multiply by the Derating Factor 1 1.2 1= x 1.20
Total Ampere Hours Required 3.50 AH
Recommended Batteries: BAT-1270-7AH Batteries
Battery Check
The batteries can be charged b the MS-5UD-3 Charger.
The batteries can be housed in the MS-5UD-3 Cabinet.
CUrrent Draw Check
NAC#1 current is within the limitations of the circuit.
NAC#2 current is within the limitations of the circuit.
NAC#3 current is within the limitations of the circuit.
NAC#4 current is within the limitations of the circuit.
MS-5UD-3 Control Panel:
The output current is within thepanel's limitations.
Fire-Lite Alarms Page 2 8/7/2011
eFire-ureAtar-ms MS-SUD-3 Battery Calculation
by Honeywell
Secondary Power Source Requirements
Secondary Non-Alarm CUrrent(amps) Secondary Alarm Current(amps)
Device Type QtY I Current Draw Total
1.System
Main Circuit Board 1 x 0.100000 1=1 0.100000 1 _lxl 0.235000 1=1 0.235000
4XTMF 0 x 0.005000 = 0 x 0.011000 =
CAC-5X 0 x 0.001000 = 0 ]XI 0,001000 =
IPDACT-2 0 x 0.093000 = 0 IxI 0.136000 =
IPDACT-2UD 0 x 0.098000 1 0 1XI 0.155000 =
2.Annunciators
ANN-80 1 IxI 0.015000 1=1 0.015000 1 1 lxl 0.040000 = 0.040000
ANWRLY I 00 = 0 x 0.075000 =
ANN-1/0 00 = 0 x 0.200020 =
ANN-I/O LEDs 00 = 0 x 0.010000 =
ANN-S/PG 00 = 0 x 0.045000 =
ANN-(R)LED 00 = 0 x 0.068000 =
3.Conventional Detection
Two-Wire Detector Heads 1 14 jxj 0.000006 1=1 0.000084
Four-Wire Detector Heads 1 0 1XI 0.000000 1=1
Number of IDC's Used Minus 1 0 jxj 0.040000 =
EOLR-1 1 0 IxI 0.020000 1=1 1 0 jxj 0.020000 =
4.Other Devices
Miscellaneous Device 1 0 x O.OD00o0 = 0 x 0.000000 =
Miscellaneous Device 2 0 x 0.000000 = 0 x 0.000000 =
Miscellaneous Device 3 0 X1 0.000000 1 0 XF 0. 000000 =
Miscellaneous Device 4 0 x 1 0.000000 = 0 x 0.000000 =
Miscellaneous Device 5 0 x 0.000000 = 1 0 x 0.000000 =
5.Notification Appliances
NAC 1 AOro
0.002500 = 0.005000
NAC 2 0.002500 = 0.005000
NAC 3 0.025000 0.025000
NAC q 0.000000 =
Current Draw from TB9(nonalam) 1 0 IxI 0.000000 1=1 1 0 1 x 0.000000 =
Total Standby Load 1 0.115084 Total Alarm Load 0.310000
Fire-Lite Alarms Page 1 8/7/2011
SpectrAlert Advance Specifications
General
SpectrAlert Advance horns,strobes,and horn strobes shall mount to a standard 4 x 4 x I/,-inch back box flinch octagon back box,or double-gang back
box.Two-wire products shall also mount to a single-gang 2 x 4 x 1t/a-inch back box A universal mounting plate shall be used for mounting ceiling and
wall product&The notification appliance circuit wiring shall terminate at the universal mounting plate.Also,SpectrAlert Advance products,when used with
the Sync-Circuit"Module accessory,shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts.
When used with the Sync-Circuit Module,12-volt rated notification appliance circuit outputs shall operate between 9 and 17.5 volts;24-volt-rated notification
appliance circuit outputs shall operate between 17 and 33 volts.Indoor SpearAlert Advance products shall operate between 32 and 120 degrees Fahrenheit
from a regulated DC or full-wave reatfied unfiltered power supply.Strobes_and horn strobes shall have field-selectable candela settings including 15,15175,30,
75,95,110,115,135,150,177,and 185.
Strobe
The strobe shall be a System Sensor SpectrAlert Advance Model_listed to UL 1971 and shall be approved for fire protective sew
wired strobe shall be
wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at
1 Hz over the strobes entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system.
Horn Strobe Combination
The horn strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and UL 464 and shall be approved for fire protective service.The
horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling
appliances,flashing at 1 Hz over the strobes entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector
system.The horn shall have three audibility options and an option to switch between a temporal three pattern and a non-temporal(continuous)pattern.These
options are set by a multiple position switch.On four-wire products,the strobe shall be powered independently of the sounder.The horn on horn strobe models
shall operate on a coded or non-coded power supply.
Synchronization Module
The module shall be a System Sensor Sync-Circuit model MDL listed to UL464 and shall be approved for fire protective service.The module shall synchronize
SpearAlert strobes at 1 Hz and horns at temporal three.Also,while operating the strobes,the module shall silence the homs on horn strobe models over a
single pair of whes.The module shall mount to a 411/16 x 411/16 x 21/rinch back box.The module shall also control two Style (class e)circuits or one Style Z
(class A)circuit.The module shall synchronize multiple zones.Daisy chaining two or more synchronization modules together Will synchronize all the zones they
control.The module shall not operate on a coded power supply.
Standard Operating Temperature 32°F to 120°F(0°C to 49°Q
Humidity Range 10 to 93%non-condensing
Strobe Flash Rate 1 flash per second
Nominal Voltage Regulated 12 OC/FWR or regulated 24 DC/FWR'
Operating Voltage Range2 8to 17.5 V p2 V nominal)or 16 to 33 V(24V nominal Input Terminal Wire Gauge 12 to 18 AWG
Wall-Mount Dimensions(including lens) 5.6"L x 4.7-W x 2.5'D(142 mm L x 119 mm W x 64 mm D)
Horn Dimensions 5.6"L x 4.7-W x 1.3-D T 42 mm L x 119 mm W x 33 mm D)
Wall-Mount Back Box Skirt Dlmensions(BBS-2,BBSW-2) 5.9-Lx5.0"W x2.2"D(151 mm L x 128 mm W x 56 mm D)
Wall-Mount Trim Ring Dimensions(sold as a 5 pack)(TR-HS,TRW-HS) 5.7-Lx4.8"W x0.35"D(145 mm L x 122 mm W x 9 mm D)
Notes:
1.Full Wave Rectified(FWR)voltage is a non-regulated,time-varying power source that is used on some power supply and panel outputs.
2.F.S,PC,and SC products will operate at 12 V nominal only for 15 and 15n5 cd.
nvowmao
SpectrAlert Advance Dimensions
�4.7" 5.05"� �2.23=►I
F
P5.6" 5.98" (OD;---7,
0
v 0
LC
Wall-mount horn strobes Wall back box skirt
SpectrAlert Advance Ordering information
Wall Horn Strobes Horns
P2R*t 2-Wre Horn Strobe,Standard cd*Red HR Horn,Red
P2RH* 2-Wire Horn Strobe,High cd,Red HW Hom,White
P2W* 2-Wre Horn Strobe,Standard cd,White Accessories
P2WH* 2-Wire Horn Strobe,High cd,White BBS-2 Back Box Skirt,Wall,Red
P4R* 4-Wre Horn Strobe,Standard cd,Red BBSW-2 Back Box Skirt,Wall,White
P4RH 4-Wire Horn Strobe,High cd,Red TR-HS Trim Ring,Wall,Red
MW 4-Wre Horn Strobe,Standard cd,White TRW-HS Trim Ring,Wall White
Wall Strobes
SR*t Strobe,Standard cd,Red
SRH*t Strobe,High cd,Red
SW* Strobe,Standard cd,White
SWH* Strobe,High cd,White
Notes:
Add'-P'to model number for plain housing(no'FIREmarking on cover),e.g.,P2R-P.
t Add'-SP'to model number forTUEGO'marking on cover,e.g.,P2R-5P.
#'Standard cd'mfersto strobes that include 15,15P5,30,75,95,110,and 115 candela settings.'High cd'refersto strobes that include 135,150,177,and 185 candela settings.
SYSTEM czanS ose w.
3825 Ohio Avenue•St.Charles,IL 60174 mdua:p ,*gmmdv�y�*mno,n*orcev� � ,cams
�� SENS®R° Phone-80o-SENSOR2•Fax 63(}377-6495 Wcr_wi.12M, vn°°"xmv a
RRS-MOD Specifications
Reversing relay/synchronization module shall be a System Sensor i' Series model number RRS-MOD,listed to Underwriters Laboratories as a smoke detector
accessory.The module shall allow all 2-wire and 4-wire P Series detectors equipped with a sounder on a loop to sound when one alarms The module shall
provide a switch to toggle between coded mode and continuous mode When in coded mode,the module shall synchronize the P sounders on the loop to
mirror the input signal.When in continuous mode,the module shall synchronize the P sounders on the loop to the ANSI S3.41 temporal coded pattern.In either
coded or continuous modes,the RRS-MOD module shall permit sounders to be silenced at the panel.The RRS-MOD module shall operate between 85 and 35
VDC,and shall provide 18 AWG stranded,tinned conductors connected toa quick-connect harness.
Physical Specifications
Dimensions 25 in H x 25 in W x 1 in D( 33 mm x 63 mm x 75 mm)
Operating Temperature Range 32°F to 131T(g°C to 55°Q
Wire Connections 18 AWG stranded,tinned,16 in length
Operating Humidity Range 5%to 85%non-condensing
Electrical Specifications
Operating Voltage Nominal:12/24V
Min:85V
Maz 35 V
Average Operating Current: 25 mA
Relay Contact Rating 2A@35VDC
Wiring Diagrams
NOTE:These diagrams represent two common wiring methods.Refer to the RRS-MOD installation manual for additional wiring configurations.
m�.+w
••• anuw anKxu _ � Amore
soioim o<"'°°n� °w°`m,w soioiao m'aaa,ox �.wwv'�
2-Wire SystemTriggered from Alarm/Bell Circuit 2-Wire System Triggered from Alarm Relay Contact
Ordering Information
Part Nci� Description
RRS-MOD Reversing relay/synchronization module fore Series smoke detectors
SYSTEM ommsnce�,se�«.
38250hio Avenue•St.Charles,IL60174 r�auam�v�vga,ma�se�n�rw�ermmremsem«.ca�m
�jY SENSOR' Phone:800-SENSOR2•Fax:630-377-6495 """" """d""q�Aa5MI.MI.116761pAmw:mowac
SYSTEM
SENSOR®
RRS-MOD
Reversing Relay/
Synchronization Module
The RRS-MOD reversing relay/synchronization module
enhances the operation of2-and 4-wire it Series
3
detectors equipped with a sounder.
Features Installation ease.The RRS-MOD reversing relay/synchronization
•is compatible with 2-and 4-wire i3 detectors equipped with a module includes a Velcro'attachment for easy installation into the
sounder fire alarm control panel cabinet.A quick-connect harness and color-
coded wires simplify connections.
•Activates all i3 sounders on a loop when one alarms
•Synchronizes all i3 sounders on the loop for a clear alarm signal Intelligence.The RRS-MOD module's design is flexible to
•Is usable with bell/alarm,alarm relay,or NAC outputs accommodate virtually any application.It is compatible with both l-
and 4-wire i3 Series detectors operating over 12 V and 24 V systems.
•Has a field-selectable switch to accommodate both coded and The module can be used with either bell/alarm,alarm relay,or NAC
continuous alarm signals outputs,and its field selectable switch accommodates both coded
•Allows i3 detector silencing from the panel or keypad and continuous alarm signals.
•Operates on 12 and 24 volt systems
Instant inspection.To meet fire alarm requirements,the RRS-MOD
•Simplifies connections with quick-connect harness and color-coded reversing relay/synchronization module activates all i3 sounders on a
wires loop when an individual sounder alarms.Additionally,it synchronizes
the output of the i3 sounders,regardless of whether the panel's alarm
signal is continuous or coded,to ensure a clear alarm signal
Agency Listings
@ <M > 0
LISTED
9M 1.1.9 13a 1c 3161
SYSTEM
SENSOR®
F'.,� ,'Fl c JS•Y
Smoke Detectors with
Sounder and Relay Option
ti
System Sensor P'sounder and relay smoke detectors Ws
apply the guiding principles of installation ease, .�
intelligence,and instant inspection in a series of
specialty conventional devices.
Features Installation ease.Throughout the i3 series,installation is simple
•85 dB sounder with its installer-friendly base and plug-in design.The base
accommodates a broad range of back box and direct mounting
•Form C relay options and provides ample space for pre-wiring the device.To
•Isolated thermal sensor complete the installation,the P detector plugs into its base with a
simple Stop-Drop'N Lock action.
•Plug-in design(base included)
Intelligence.To reduce the likelihood of nuisance alarms,all
•In-line terminals i3 detectors are equipped with both drift compensation and
•Flexible mounting options smoothing algorithms.These capabilities minimize both short-and
long-term causes of nuisance alarms,such as RF interference and
•Stop-Drop Lock"attachment to the base dust accumulation.When connected to the 2W-MOD2 loop test/
•Removable cover and chamber maintenance module or an P Ready"panel,2-wire i3 detectors can
•Remote maintenance signaling generate a remote maintenance signal when in a maintenance or
freeze trouble condition.To measure the sensitivity of any i detector,
•Drift compensation and smoothing algorithms the SENS-RDR displays the reading,in terms of percent-per-foot
•Simplified sensitivity measurement obscuration,within seconds.
•Dual-color LEDs Instant inspection.i3 has red and green LEDs to simplify local
status indication during power-up,standby,alarm,maintenance,
and freeze trouble conditions.When in alarm,13 sounder models
generate an 85 dB temporal tone.If connected to the RRS-MOD
reversing relay/synchronization module,all i3 sounders on the loop
will activate when one detector is in alarm.The RRS-MOD also
synchronizes 13 sounder output to ensure a clear audible signal.
Agency Listings
Should the application call for differentiating between a local and
O a general alarm,the i3line offers an isolated thermal model,which
■�� ���aa initiates a local alarm when smoke is detected,and a general alarm
FM ® Ir A Irllfln
LISFED approved approved °(-)e when the thermal sensor is activated.
SM 3015195 nn-Mli& MR m 2133 31.g
ANN-BUS DEVICE ADDRESSING After calculating the total worst case current draw,the following
Each ANN-BUS device requires a unique address(ID Number) table specifies the maximum distance the modules can be
in order to communicate with the FACP.A maximum of 8 devices located from the FACP on a single wire run.The table ensures
can be connected to the FACP ANN-BUS communication circuit 6.0 volts of line drop maximum.In general,the wire length is lim-
See the FACP manual for more information. iced by resistance, but for heavier wire gauges, capacitance is
the limiting factor.
WIRE REQUIREMENTS.COMMUNICATIONS CIRCUIT These cases are marked in the chart with an asterisk('). Maxi-
The ANN-80 connects to the FACP ANN-BUS communications mum length can never be more than 6,000 feet (1,800 m),
circuit. To determine the type of wire and the maximum wiring regardless of gauge used. See table below.
distance that can be used with FACP ANN-BUS accessory mod- WIRE REQUIREMENTS:POWER CIRCUIT
ules, it is necessary to calculate the total worst case current
draw for all modules on a single 4-conductor bus.The total worst • 14 to 18 AWG(0.75-2.08 mm2)wire for 24 VDC power cir-
case current draw is calculated by adding the Individual worst cuit is acceptable. Power wire distance limitation is set by 1.2
case currents for each module. volt maximum line drop form source to end of circuit.
NOTE:For total worst case current draw on a single ANN-BUS • All connections are power-limited and supervised.
refer to appropriate FACP manual. • A maximum of eight ANN-80 modules may be connected to
this circuit.
Communication Pair Wiring Distance: FACP to Last ANN-BUS Module
Total Worst Case 22 Gauge 18 Gauge IS Gauge 14 Gauge
Current Draw(amps)
0.100 1,852 ft. 4,688 ft. '6,000 ft. -6,000 ft.
0.200 926 ft. 2,344 ft. 3,731 ft. 5,906 ft.
0.300 617 ft. 1,563 ft. 2,488 ft. 3,937 ft.
0,400 463 ft. 1,172 ft. 1,866 ft. 2,953 ft.
0.500 370 ft. 938 ft. 1,493 ft. 2,362 ft.
0.600 309 ft. 781 ft. 1,244 ft. 1,969 ft.
0.700 265 ft. 670 ft. 1,066 ft. 1,687 ft.
0.800 231 ft. 586 ft. 933 ft. 1,476 ft.
0.900 206 ft. 521 ft. 829 ft. 1,312 ft.
1.000(max.) 185 ft. 469 ft. 746 ft. 1,181 ft.
WIRING CONFIGURATION ORDERING OPTIONS.
The following figure illustrates the wiring between the FACP and ANN-80:Red 80 character LCD Annunciator.
ANN-BUS devices. ANN-80-W:White,80 character LCD Annunciator.
ANN-BUS and power ANNSB80KIT--R: Red surface mount backbox with angled
wiring are supervised wedge.
and power-limited. ANNSB80KIT-W: White surface mount backbox with angled
® jB j32
. - wedge.
t
ANN-BUS Device
O
MS-905OUD tea
1 2 3 6 5 6 7 9
FACP Wiring to ANN-BUS Device
FireLite®Alarms Is a registered trademark of Honeywell International Inc.
C2009 by Honeywell International Inc.All rights reserved.Unauthorized use
of this document is strictly prohibited.
'® This document is not coded i to be Lion for installation purposes
We try to keep our product information up-to-tlate and accurate.
We cannot cover all specific applications or anticipate all requirements.
GYBLIT IIFHI T SYSTEMS F MY T E MSS All specifications are subject to change without notice.
Made in the U.S.A.
For more information,contact Fire-Lite Alarms.Phone:(800)627-3473,FAX:W7)699-4105.
www.firelite.com
Page 2 of 2—df-52417:c•05/22/09
df-52417:c•B-90
ANN-80 FirelffeWarms
80-Character LCD by Honeywell
Serial Annunciator
General
The ANN-80 annunciator is a compact, backlit, 80-character
LCD fire annunciator that mimics the Fire Alarm Control Panel
(FACP) display. It provides system status indicators for AC
Power,Alarm,Trouble, Supervisory, and Alarm Silenced condi-
tions.The ANN-80 and the FACP communicate over a two-wire Y
serial interface employing the ANN-BUS communication format.
Connected devices are powered, via two additional wires, by
either the host FACP or a remote UL-listed,filtered power supply.
ANN-80 is red;for white,order ANN-80-W rat
The ANN-80 displays English-language text of system point
information including device type, zone, independent point
alarm, trouble or supervisory status, as well as any custom
alpha labels programmed into the control panel. It includes can- G
trol switches for remote control of critical system functions. (A
keyswitch prevents unauthorized operation of the control $
switches.)
Up to eight ANNAOs may be connected to the ANN-BUS of g _each FACP.No programming is required,which saves time dur-
ing system commissioning.
Features
• Listed to UL Standard 864,9th Edition.
• Backlit 80-character LCD display(20 characters x 4lines). • Supervisory
• Mimics all display information from the host panel. • Alarm Silenced
• Control switches for System Acknowledge, Signal Silence, SpecificationsDrill,and Reset.
• Control switches can be independently enabled or disabled • Operating voltage range: 18 VDC to 28 VDC.
at the FACP. • Current consumption @ 24 VDC nominal(filtered and non-
• Keyswitch enables/disables control switches and mechani- resettable):40 mA maximum.
cally locks annunciator enclosure • Ambient temperature:32°F to 120OF(0°C to 491C).
• Keyswitch can be enabled or disabled at the FACP. • Relative humidity:93%x 2/,RH(noncondensing)at 320C
• Enclosure supervised for tamper. t 20C(90°F x 3°F).
• System status LEDs for AC Power, Alarm,Trouble, Supervi- • 5.376' (13.65 cm.) high x 6.876'(17.46 cm.)wide x 1.376'
sory,and Alarm Silence. (3.49 cm.)deep.
• Local sounder can be enabled or disabled at the FACP. • For use indoors in a dry location.
• ANN-80 connects to the ANN-BUS terminal on the FACP and • All connections are power-limited and supervised.
requires minimal panel programming.
• Displays device type identifiers, individual point alarm,trou- Agency Listings and Approvals
ble,supervisory,zone,and custom alpha labels.
• Time-and date display field. The listings and approvals below apply to the ANN-80. In some
cases, certain modules may not be listed by certain approval
• Surface mount directly to wall or to single, double, or 4• agencies,or listing may be in process.Consult factory for latest
square electrical box. listing status.
• Semi-flush mount to single, double, or 4• square electrical • UL:S2424
box.Use ANN-SB80KIT for angled view mounting.
• Can be remotely located up to 6,000 feet(1,800 m)from the • FM approved
panel. • CSFM:7120-0075:211
• Backlight turns off during AC loss to conserve battery power • MEA:442-06-E
but will turn back on if an alarm condition occurs.
• May be powered by 24 VDC from the host FACP or by remote The ANN-BUS
power supply(requires 24 VDC).
• Up to eight ANN-80s can be connected on the ANN-BUS. POWERING THE DEVICES ON THE ANN-BUS FROM
AUXILIARY POWER SUPPLY
Controls and Indicators The ANN-BUS can be powered by an auxiliary power supply
when the maximum number of ANN-BUS devices exceeds the
• AC Power ANN-BUS power requirements.See the FACP manual for more
• Alarm information.
• Trouble
df-52417:c•05/27J09—Page 1 of 2
Specifications Agency Listings and Approvals
PHYSICAL SPECIFICATIONS: The listings and approvals below apply to the BG-12 Series pull
stations. In some cases,certain modules may not be listed by
certain approval agencies,or listing may be in process.Consult
pull station SB410 SB-10 factory for latest listing status.
Height 5.5 inches 5.601 inches 5.5 inches • C(UL)US:S711
(13.97 cm) (14.23 cm) If 3.97 cm) • FM Approved
Width 4.121 inches 4.222 inches 4.121 inches . CSFM:7150-0075:184
(10.47 cm) (10.72 cm) (10.47 cm) • MEA:67-02-E
Depth 1.39 inches 1.439 inches 1.375 inches . Patented: U.S. Patent No. D428,351; 6,380,846; 6,314,772;
(3.53 cm) (3.66 cm) (3.49 cm) 6,632,108.
51Si,Em.MI
ELECTRICAL SPECIFICATIONS: Product Line Information
Switch contact ratings:gold-plated;rating 0.25 A W 30 VAC or BG-12S: Single-action pull station with pigtail connections,hex
VDC. lock.
ENGINEERING(ARCHITECTURAL SPECIFICATIONS BG-12SL: Same as BG-12 with key lock.
Manual Fire Alarm Stations shall be non-code, with a key- or BG-12: Dual-action pull station with SPST WO switch, screw
hex-operated reset lock in order that they may be tested,and so terminal connections,hex lock.
designed that after actual Emergency Operation,they cannot be BG-12L: Same as BG-12 with key lock.
restored to normal except by use of a key or hex.An operated BG-12LSP: Same as BG-12L with English/Spanish (FIRE/
station shall automatically condition itself so as to be visually FUEGO)labeling.
detected as activated. Manual stations shall be constructed of BG-12LOB: Same as BG-12L with "outdoor use' listing.
red colored LEXAN (or polycarbonate equivalent) with Beady includes outdoor listed backbox,and sealing gasket.
visible operating instructions provided on the cover. The word
FIRE shall appear on the front of the stations in white letters, BG-12LO: Same as BG-12L with "outdoor use listing. Does
1.00 inches (2.54 cm) or larger. Stations shall be suitable for not include backbox.
surface mounting on matching backbox SB-10 or SB-I/O; or BG-12LA: Same as BG-12L with auxiliary contacts.
semi-flush mounting on a standard single-gang,double-gang,or 8G.12LPS: Dual-action pull station with pre-signal option.
4'(10.16 cm)square electrical box,and shall be installed within BG-12LPSP: Same as BG-12LPS with English/Spanish(FIRE/
the limits defined by the Americans with Disabilities Act(ADA)or FUEGO)labeling.
per nationaillocal requirements.Manual Stations shall be Under-
writers Laboratories listed. SB-10: Surface-mount backbox,metal.
NOTE.*The words FIRE/FUEGO"on the BG-12LSP shall appear SB-UO: Surface-mount backbox, plastic. (included with BG-
on the front of the station in while letters, approximatety 314' 12LOR.)
(1.90.5 cm)high. BG12TR: Optional trim ring for semi-flush mounting.
17003:Keys,set of two.(Included with key-lock pull stations.)
17007:Hex lock,9/64".(Included with hex-lock pull stations.)
NOTE., For addressable BG-12LX models see data sheet DF-
52013.
I
II ••
I
I
Fire•Llte®Alarms, SpectrAlert® Advance, and System Sensor® are
registered trademarks of Honeywell International Inc.
@2008 by Honeywell International Inc.All rights reserved.Unauthorized use
of this document is strictly prohibited-
This try to keep
is not intended to be used for installation purposes
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
QUALITY SYSTEMS All specifications are subject to change without notice.
Made in the U.B.A.
For more information,contact Fre•Ute Alarms.Phone:(800)627-3473,FAX:(877)699,4105.
wwwfirelite.00m
Page 2 of 2—DF-52004:A1•04/22108
DF-52004:A1•F-050
13G-12 Series 'FIPG'•LITeALarmS
Manual Fire Alarm Pull Stations
by Honeywell
General
The Fire-Lite BG-12 Series is a cost-effective, feature-packed
series of non-coded manual fire alarm pull stations. It was
designed to meet multiple applications with the installer and
end-user in mind.The BG-12 Series features a variety of mod-
els including single-and dual-action versions.
The BG-12 Series provides Fire-Lite Alarm Control Panels
(FACPs),as well as other manufacturers'controls,with a man-
ual alarm initiating input signal. Its innovative design, durable •
construction, and multiple mounting options make the BG-12
Series simple to install,maintain,and operate. i
Features
• Aesthetically pleasing,highly visible design and color.
• Attractive contoured shape and light textured finish.
• Meets ADA 5 lb.maximum pull-force. R
• Meets UL 38,Standard for Manually Actuated Signaling Boxes.
• Easily operated(single-or dual-action), yet designed to pre- '8
vent false alarms when bumped,shaken,or jarred. '
• PUSH INIPULL DOWN handle latches in the down position to
clearly indicate the station has been operated. Construction
• The word "ACTIVATED" appears on top of the handle in • Cover, backplate and operation handle are all molded of
bright yellow,further indicating operation of the station. durable polycarbonate material.
• Operation handle features white arrows showing basic opera- • Cover features white lettering and trim.
tion direction for non-English-speaking persons. . Red color matches System Sensors popular SpectrAlerM
• Braille text included on finger-hold area of operation handle Advance horn/strobe series.
and across top of handle.
• Multiple hex-and key-lock models available. Operation
• U.S. patented hex-lock needs only a quarter-turn to lock/
unlock. The BG-12 manual pull stations provide a textured finger-hold
• Station can be opened for inspection and maintenance with- area that includes Braille text.In addition to PUSH IN and PULL
out initiating an alarm. DOWN text,there are arrows indicating how to operate the sta-
• Product ID label viewable by simply opening the cover;label tion,provided for non-English-speaking people.
is made of a durable long-life material. Pushing in and then pulling down on the handle activates the
• The words"NORMAL"and"ACTIVATED"are molded into the normally-open alarm switch.Once latched in the down position,
plastic adjacent to the alarm switch(located inside). the word"ACTIVATED"appears at the top in bright yellow,with a
• Four-position terminal strip molded into backplate. portion of the handle protruding at the bottom as a visible flag.
• Terminal strip includes Phillips combination-head captive 8132 Resetting the station is simple:insert the key,twist one quarter-
screws for easy connection to Initiating Device Circuit(IDC). turn, then open the station's front cover, causing the spring-
loaded operation handle to return to its original position. The
• Terminal screws backed-out at factory and shipped ready to alarm switch can then be reset to its normal(non-alarm)position
accept field wiring(up to 12 AWG/3.1 mm2). manually(by hand)or by closing the station's front cover,which
• Terminal numbers are molded into the backplate,eliminating automatically resets the switch.
the need for labels.
• Switch contacts are normally open.
• Can be surface-mounted (with SB-10 or SB-1/0) or semi-
flush mounted. Semi-flush mourn to a standard single-gang,
double-gang,or 4"(10.16 cm)square electrical box.
• Backplate is large enough to overlap a single-gang backbox
cutout by 1/2"(1.27 cm).
• Optional trim ring(BG12TR).
• Spanish versions(FUEGO)available(BG-12LSP,BG-121LPSP).
• Designed to replace the Fire-Lite legacy BG-10 Series.
• Models packaged in attractive, clear plastic (PVC), clam-
shelf-style, Pointof-Pumhase packages. Packaging includes
a cutaway dust/paint cover in shape of pull station.
DF-52004:A7•04/22/08—Page 1 of 2
USER INTERFACE: • SYSTEM RESET(lamp test)
• Built-in DACT(Digital Alarm Communicator/Transmitter). • DRILL
• Integral 80-character LCD display with backlighting and
keypad. Terminal Blocks
• Real-time clock/calendar with automatic daylight savings AC Power—TB1:
adjustments. • MS-5UD-3 (FLPS3 Power Supply): 120 VAC, 50/60 HZ,
• ANN-BUS for connection to remote annunciators. 1.00 A.
• Audible or silent walk test capabilities. • MS-5UD-3E (FLPS-3 Power Supply): 240 VAC, 50 HZ,
• Piezo sounder for alarm,trouble,and supervisory. 0.54 A.
• MS-10UD-7 (FLPS-7 Power Supply): 120 VAC, 50/60 HZ,
Controls and Indicators 3.80 A.
LED INDICATORS • MS-10UD-7E(FLPS-7 Power Supply):240 VAC,50/60 HZ,
2.20 A.
• FIRE ALARM(red) Wire size:minimum 14 AWG(2.00 mm2)with 600 V insulation.
• SUPERVISORY(yellow) Supervised,nonpower-limited.
• TROUBLE(yellow) Battery(sealed lead acid only)—J12:
• AC POWER(green) • Maximum Charging Circuit-Normal Flat Charge:27.6 VDC
• ALARM SILENCED(yellow) @ 1.4 A.Supervised,nonpower-limited.
CONTROL BUTTONS • Maximum Charger Capacity: 18 AH battery for MS-SUD-
• 3(E),and 26 AH battery for MS-10UD-7(E).[Two 18 Ah bat-
ACKNOWLEDGE
teries can be housed in the FACP cabinet.Larger batteries
• ALARM SILENCE require separate battery box such as the BB-26 or BB-55.1
Depth=5.207"(13.23 cm)
Top
Door=16.821"(42.73 cm) � 1 Depth=
~—Backbox=16.65"(42.29 cm) I�5.257"�I
(13.363 cm)
f iY
t < i
1 Door=19.26"(48.92 cm)
Backbox=19.0"(48.26 cm)
s y ,
e ~
Left Side " Right Side
Bottom
.(t
Cabinet Measurements
Page 2 of 4—DF52416:13•07/26/2010
SYSTEM SPECIFICATIONS
System Capacity Temperature and Humidity Ranges
• Annunciators......................................................................8 This system meets NFPA requirements for operation at 0 —
49°C/32 — 120°F and at a relative humidity 93% : 2% RH
Electrical Specifications (noncondensing) at 320C t 2°C (90°F x 3°F). However, the
useful life of the system's standby batteries and the electronic
• MS-5UD-3 (FLPS-3 Power Supply): 120 VAC, 60 HZ, components may be adversely affected by extreme tempera-
1.0 A ture ranges and humidity. Therefore,it is recommended that
• MS-1 DUD-7 (FLPS-7 Power Supply): 120 VAC, 60 HZ, this system and its peripherals be installed in an environment
3.90 A with a normal room temperature of 15—27IC160—80°F.
• MS-5UD3E (FLPS-3 Power Supply): 240 VAC, 50 HZ,
0.54 A. Agency Listings and Approvals
• MS-10UD-7E (FLPS-7 Power Supply): 240 VAC, 50 HZ, The listings and approvals below apply to the basic MS-51.0-3
2.20 A. and MS-10UD-7 control panels. In some cases, certain mod-
• Wire size: minimum 14 AWG(2.0 mm�with 600 V insula- ules or applications may not be listed by certain approval
tion,supervised,nonpower-limited agencies,or listing may be in process.Consult factory for lat-
est listing status.
Cabinet Specifications • UL Listed:File S624
Door: 19.26" (48.92 cm.) high x 16.82" (42.73 cm.) wide x • FM Approved
0.72" (1.82 cm.) deep. Backbox: 19.00' (48.26 cm.) high x • CSFM:7165-0075:0214
16.66" (42.29 cm.)wide x 5.25" (13.34 cm.)deep. Trim Ring • MEA: MEA:333-07-E
(TR-CE):22.00"(55.88 cm.)high x 19.65"(49.91 cm.)wide.
NOTE:For ULC-listed models,see OF-60440.
Shipping Specifications NFPA Standards
Dimensions: The MS-5UD-3(E) and MS-10UD-7(E) complies with the fol-
-20.00"(50.80 cm.)high lowing NFPA 72 Fire Alarm Systems requirements:
—22.5"(57.15 cm.)wide —LOCAL (Automatic, Manual, Waterflow and Sprinkler
—8.5"(21.59 cm.)deep. Supervisory).
Weight:271b(12.20 kg) —AUXILIARY(Automatic,Manual and Waterflow)(requires
4XTMF).
—REMOTE STATION (Automatic, Manual and Waterfiow)
(Where a DACT is not accepted, the alarm, trouble and
supervisory relays may be connected to UL 864 listed
transmitters. For reverse polarity signaling of alarm and
trouble,4XTMF is required.)
—PROPRIETARY(Automatic,Manual and Waterflow).
—CENTRAL STATION (Automatic, Manual and Waterflow,
and Sprinkler Supervised).
—OT, PSDN (Other Technologies, Packet-switched Data
Network)
PlreLlte® Alarms and System Sensor® are registered trademarks of
Honeywell International Inc.
@2010 by Honeywell International Inc.All rights reserved.Unauthorized use
of this document is strictly prohibited.
'® This document is not coded i to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
Kern! SNIIMfN.7RSi All specifications are subject to change without notice.
SiI LITY SYSTEMS Madeinthe U.S.A.
For more information,contact Fira•lite Alarms.Phone:(800)627-3473,FAX:(877)699-4105.
wwwArelke.00m
Page 4 014—DF52416:D•07/262010
• Minimum Battery Size:7 AH. MS-t0UD-7E:Same as above with 240 VAC FLPS-7.
Initiating Device Circuits—T84(and TB 6 on MS-10UD-7 IPDACT, IPDACT-212UD Internet Monitoring Module:
only): Mounts in bottom of enclosure with optional mounting kit(PN
• Alarm Zones 1 -5 on TB 4(MS5UD-3 and MS-10UD-7). IPBRKT). Connects to primary and secondary DACT tele-
phone output ports for internet communications over customer
provided ethernet internet connection. Requires compatible
• Supervised and power-limited circuitry. Teldat Visoralarm Central Station Receiver.Can use DHCP or
• Operation:All zones Style B(Class 8). static IF..(See data sheet DF-60407 for more information.)
• Normal Operating Voltage:Nominal 20 VDC. IPBRKT:Mounting kit for IPDACT in common enclosure.
• Alarm Current:15 mA minimum. IPSPLT: Y Adaptor option to allow connection of both panel
• Short Circuit Current:40 mA max. dialer outputs to one cable input to IPDACT(sold separately).
• Maximum Loop Resistance:100 ohms. OPTIONAL MODULES
• End-of-Line Resistor: 4.71K ohm, 112 watt (PM 71252 UL- CACSX:Optional(Class A)Converter Module.Converts Style
listed). B(Class B)Initiating Device Circuits to Style D(Class A);and
• Standby Current:2 mA. Style Y (Class B) Notification Appliance Circuits to Style Z
Refer to the Fire-Lite Device Compatibility Document for listed (Class A). Connects to J2 on the MS-51JD-3 and MS-10UD-
compatible devices. 7(E)main circuit board and to J7 on the MS-10UD-7(E).
Notification Appliance Circuits —TB5 (and TS 7 on MS- NOTE: Two Class A Converter Modules are required for the ten-
1OUD-7 only): zone panel.
• Four NACs 4XTMF:Transmitter module. Provides a supervised output for
• Operation:Style Y(Class B) local energy municipal box transmitter and alarm and trouble
reverse polarity. Includes a disable switch and disable trouble
• Special Application power LED.A module jumper option allows the reverse polarity circuit
• Supervised and power-limited circuitry to open with a system trouble condition if no alarm conditions
• Normal Operating Voltage:Nominal 24 VDC exists.Mounts to the main circuit board connectors J4 and J5.
• Maximum Signaling Current: 3.0 A for MS51JD-3, 2.5 A COMPA77BLEANNUNCIATORS
maximum per NAC; 7.0 A for MS-10UD-7(E), 3.0 A maxi- ANN-80: Remote LCD Annunciator. Mimics the information
mum per NAC. displayed on the FACP's LCD. Red. (For white, order: ANN-
• End-of-Line Resistor:4.71K ohm,1/2 watt(Part#71252) 60-W)
• Max.Wiring Voltage Drop:2 VDC ANN-LED: LED Annunciator with three LEDs for each zone:
Refer to the Fire-Lite Device Compatibility Document for com- Alarm,Trouble, and Supervisory. Mounts in the DP-51050(B)
patible listed devices. dress panel.Red.(For white,order ANN-LED-W.)
Form C Relays—TB6: ANN-RLED: LED Annunciator with three alarm (red) indica-
• Relay 1(factory default programmed as Alarm Relay) tors for up to 30 input zones or addressable points.(Red. For
• Relay 2 (factory default programmed as fail-safe Trouble white,order ANN-LED-W.)(See DF-60241).
Relay) ANN-RLY.Relay module.Mounts inside the cabinet.Provides
• Relay 3(factory default programmed as Supervisory Relay) ten Form C relays.
Special Application Resettable Power—TB9: ANN-S/PG:Seriallparallel printer gateway.Provides a connec-
• Jumper selectable by JP31 for resettable or nonresettable tion for a serial or parallel printer.
power. ANN-1/O: Driver module. Provides connections to a user-sup-
Operating voltage:24 VDC nominal. plied graphic annunciator.
• Maximum available current:500 mA-appropriate for pow- ACCESSORIES
ering four-wire smoke detectors. DP-51050:Optional dress panel. Restricts access to the sys-
• Power-limited circuit. tem wiring while allowing access to the membrane switch
Refer to the Fire-Lite Device Compatibility Document for listed panel.
compatible devices. 88-26: Battery backbox,holds up to two 25 AH batteries and
Remote Sync Output-T82: Remote power supply synchro- CHG-75.
nization output,only required for the MS-51JD-3.24 VDC nom- BB-55:Battery backbox,holds up to two 25 AH batteries.
inal special application power. Maximum current is 40 mA.
Endof-Line Resistor: 4.71K ohm. Supervised and power-lim- TR-CE:Optional trim-ring for semi-flush mounted cabinets.
tied circuit. PRN-6F:UL listed printer.
Product Line Information
MS-SUD-3: Five-zone, 24-volt Fire Alarm Control Panel
(includes backbox, FLPS-3 power supply, technical manual,
and a frame & post operating instruction sheet). 120 VAC
operation.
MS-5UD-3E: Same as MS-51JD-3 except for 240 VAC opera-
tion.
MS-10UD-7: Ten-zone, 24-volt Fire Alarm Control Panel
(includes backbox, FLPS-7 power supply, technical manual,
and a frame&post operating instruction sheet).
DF32416:D•07Mf2010—Page 3 of 4
DF-52416:0•A3-20
MS-5UD )/MS-1OUD(E) Series FII'@•LITeALc'll'MS
no Fire Alarm Control Panel
Ten Zone Fire Alarm Control Panel by Honeywell
General
The MS-5UD-3(E) is a five-zone FACP (Fire Alarm Control
Panel)and the MS-10UD-7(E)is a ten-zone FACP.These con-
trol panels provide reliable fire signaling protection for small to
medium-sized commercial, industrial, and institutional build-
ings. Both panels include built-in communicators for Central
Station Service and remote upload/download. ui r
Each of these FACPs is compatible with System Sensor's f
microprocessor-based is series detectors.These conventional
smoke detectors can transmit a maintenance trouble signal to
the FACP indicating the need for cleaning and a supervisory
'freeze"signal when the ambient temperature falls below the
detector rating. Additionally, both the MS-5UD-3 and MS-
10UD-7 are compatible with conventional input devices such
as two-and four-wire smoke detectors,pull stations,waterflow,
devices, tamper switches, and other normally-open contact a
devices. Refer to the Fire-Lite Device Compatibility Document s
for a complete listing of compatible devices. '^
's
Outputs include four NACs (Notification Appliance Circuits), "
three programmable Form-C relays (fabtory programmed for
Alarm,Trouble,and Supervisory)and 24 VDC special applica-
tion resettable and nonresettable power outputs. The FACPs
supervise all wiring, AC voltage, battery level and telephone _Strobe Synchronization for System Sensor, Wheelock,
line integrity. Gentex,Faraday,or Amseco devices.
Activation of a compatible smoke detector or any normally- _Selective Silence(horn-strobe mute).
open fire alarm initiating device will activate audible and visual
signaling devices, illuminate an indicating LED, sound the —Temporal or Steady Signal.
piezo sounder at the FACP, activate the communicator and —Silenceable or Nonsilenceable.
FACP alarm relay, and operate an optional module used to - Optional CAC-5X Style Z (Class A) Converter Module for
notify a remote station or initiate an auxiliary control function. NACs and IDCs(2 required for MS-10UD-7).
New options include a UL listed printer,PRN-6F and Firel-ite's • Form-C Relays for Alarm, Trouble and Supervisory- Con-
IPDACT Internet Monitoring module. The Fire Watch Series tact Ratings 2.0 A@ 30 VDC or 0.5 A M 30 VAC(resistive).
internal monitoring modules IPDACT-2 and IPDACT-2UD per, - 3.0 A total system current for MS-5UD3.
mit monitoring of alarm signals over the Internet saving the - 7.0 A total system current for MS-10UD-7.
monthly cost of two telephone lines.Although not required,the
secondary telephone line may be retained providing backup • Optional Dress Panel DP-51050
communication over the public switched telephone line. • Optional Trim Ring TR-CE for semi-flush mounting.
NOTE. The MS-5UD3E and MS-f0UD-7E offers the same fee- - • 24 volt operation.
tunes as the MS.5UD-3 and MS-f0UD-7 but allow connection to • Low AC voltage sense.
240 VAC. Unless otherwise specified,the information in this data
sheet applies to both the 120 VAC and the 240 VAC versions of • Alarm Verification.
these panels • PAS(Positive Alarm Sequence).
NOTE.,For ULGlisted models,see DF-60440. • Automatic battery trickle charger.
• Up to eight ANN-BUS annunciators: -
Features —Optional 8 zone Relay Module ANWRLY.
• Listed to UL Standard 864,9th edition. —Optional LED Annunciator Module ANN-LED,
• Built-in DACT(Digital Alarm CommunicatoJiransmitter). —Optional Remote Annunciator ANN-80.
• Style B(Class B)IDC(Initiating Device Circuit) —Optional Remote Printer Gateway ANN-S/PG.
—MS-5UD-3-five IDCs. —Optional LED Annunciator Driver ANN-1/0.
—MS-10UD-7-ten IDCs. Optional 4XTMF module (conventional reverse polarity/city
• Style Y(Class B)NAC(Notification Appliance Circuit)-spe- box transmitter).
cial application power PROGRAMMING AND SOFTWARE.
—MS-5UD-3-four NACs. • Can be programmed at the panel with no special software
—MS-10UD-7-four NACs. or additional equipment.
• Notification Appliances may be programmed as • Programmable Make/Break Ratio.
—Silence Inhibit. • Upload/Download(local or remote)of program and data via
—Auto-Silence. integral DACT.
DF-52416:D-07/262010—Page 1 of 4
Fire alarm System
Community Residences Inc.
9 Cliffwood Drive
South Windsor, Ct. 06074
DIGITAL Communicator Inc.
4 Aarons Way
East Hampton, Ct. 06424
860-267-8069
FlreuTemarms MS-5UD-3 Battery Calculation
by Honeywell
Calculation in Total Sheet
24 Hours
Standby Load Current 0.11508 Am s x 24 1=1 2.762 AH
30 Minutes
Alarm Load Current Am 5.31000 Amps x 0.5 1= 0.155 AH
Total Current Load 2.917 AH
Multiply by the Derating Factor 1 1.2 1= x 1.20
Total Ampere Hours Required 3.50 AH
Recommended Batteries: BAT-1270-7AH Batteries
Battery Check
The batteries can be charged b the MS-5UD-3 Charger.
The batteries can be housed in the MS-5UD-3 Cabinet.
CUrrent Draw Check
NAC#1 current is within the limitations of the circuit.
NAC#2 current is within the limitations of the circuit.
NAC#3 current is within the limitations of the circuit.
NAC#4 current is within the limitations of the circuit.
MS-5UD-3 Control Panel:
The output current is within thepanel's limitations.
Fire-Lite Alarms Page 2 8/7/2011
eFire-ureAtar-ms MS-SUD-3 Battery Calculation
by Honeywell
Secondary Power Source Requirements
Secondary Non-Alarm CUrrent(amps) Secondary Alarm Current(amps)
Device Type QtY I Current Draw Total
1.System
Main Circuit Board 1 x 0.100000 1=1 0.100000 1 _lxl 0.235000 1=1 0.235000
4XTMF 0 x 0.005000 = 0 x 0.011000 =
CAC-5X 0 x 0.001000 = 0 ]XI 0,001000 =
IPDACT-2 0 x 0.093000 = 0 IxI 0.136000 =
IPDACT-2UD 0 x 0.098000 1 0 1XI 0.155000 =
2.Annunciators
ANN-80 1 IxI 0.015000 1=1 0.015000 1 1 lxl 0.040000 = 0.040000
ANWRLY I 00 = 0 x 0.075000 =
ANN-1/0 00 = 0 x 0.200020 =
ANN-I/O LEDs 00 = 0 x 0.010000 =
ANN-S/PG 00 = 0 x 0.045000 =
ANN-(R)LED 00 = 0 x 0.068000 =
3.Conventional Detection
Two-Wire Detector Heads 1 14 jxj 0.000006 1=1 0.000084
Four-Wire Detector Heads 1 0 1XI 0.000000 1=1
Number of IDC's Used Minus 1 0 jxj 0.040000 =
EOLR-1 1 0 IxI 0.020000 1=1 1 0 jxj 0.020000 =
4.Other Devices
Miscellaneous Device 1 0 x O.OD00o0 = 0 x 0.000000 =
Miscellaneous Device 2 0 x 0.000000 = 0 x 0.000000 =
Miscellaneous Device 3 0 X1 0.000000 1 0 XF 0. 000000 =
Miscellaneous Device 4 0 x 1 0.000000 = 0 x 0.000000 =
Miscellaneous Device 5 0 x 0.000000 = 1 0 x 0.000000 =
5.Notification Appliances
NAC 1 AOro
0.002500 = 0.005000
NAC 2 0.002500 = 0.005000
NAC 3 0.025000 0.025000
NAC q 0.000000 =
Current Draw from TB9(nonalam) 1 0 IxI 0.000000 1=1 1 0 1 x 0.000000 =
Total Standby Load 1 0.115084 Total Alarm Load 0.310000
Fire-Lite Alarms Page 1 8/7/2011
SpectrAlert Advance Specifications
General
SpectrAlert Advance horns,strobes,and horn strobes shall mount to a standard 4 x 4 x I/,-inch back box flinch octagon back box,or double-gang back
box.Two-wire products shall also mount to a single-gang 2 x 4 x 1t/a-inch back box A universal mounting plate shall be used for mounting ceiling and
wall product&The notification appliance circuit wiring shall terminate at the universal mounting plate.Also,SpectrAlert Advance products,when used with
the Sync-Circuit"Module accessory,shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts.
When used with the Sync-Circuit Module,12-volt rated notification appliance circuit outputs shall operate between 9 and 17.5 volts;24-volt-rated notification
appliance circuit outputs shall operate between 17 and 33 volts.Indoor SpearAlert Advance products shall operate between 32 and 120 degrees Fahrenheit
from a regulated DC or full-wave reatfied unfiltered power supply.Strobes_and horn strobes shall have field-selectable candela settings including 15,15175,30,
75,95,110,115,135,150,177,and 185.
Strobe
The strobe shall be a System Sensor SpectrAlert Advance Model_listed to UL 1971 and shall be approved for fire protective sew
wired strobe shall be
wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at
1 Hz over the strobes entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system.
Horn Strobe Combination
The horn strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and UL 464 and shall be approved for fire protective service.The
horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling
appliances,flashing at 1 Hz over the strobes entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector
system.The horn shall have three audibility options and an option to switch between a temporal three pattern and a non-temporal(continuous)pattern.These
options are set by a multiple position switch.On four-wire products,the strobe shall be powered independently of the sounder.The horn on horn strobe models
shall operate on a coded or non-coded power supply.
Synchronization Module
The module shall be a System Sensor Sync-Circuit model MDL listed to UL464 and shall be approved for fire protective service.The module shall synchronize
SpearAlert strobes at 1 Hz and horns at temporal three.Also,while operating the strobes,the module shall silence the homs on horn strobe models over a
single pair of whes.The module shall mount to a 411/16 x 411/16 x 21/rinch back box.The module shall also control two Style (class e)circuits or one Style Z
(class A)circuit.The module shall synchronize multiple zones.Daisy chaining two or more synchronization modules together Will synchronize all the zones they
control.The module shall not operate on a coded power supply.
Standard Operating Temperature 32°F to 120°F(0°C to 49°Q
Humidity Range 10 to 93%non-condensing
Strobe Flash Rate 1 flash per second
Nominal Voltage Regulated 12 OC/FWR or regulated 24 DC/FWR'
Operating Voltage Range2 8to 17.5 V p2 V nominal)or 16 to 33 V(24V nominal Input Terminal Wire Gauge 12 to 18 AWG
Wall-Mount Dimensions(including lens) 5.6"L x 4.7-W x 2.5'D(142 mm L x 119 mm W x 64 mm D)
Horn Dimensions 5.6"L x 4.7-W x 1.3-D T 42 mm L x 119 mm W x 33 mm D)
Wall-Mount Back Box Skirt Dlmensions(BBS-2,BBSW-2) 5.9-Lx5.0"W x2.2"D(151 mm L x 128 mm W x 56 mm D)
Wall-Mount Trim Ring Dimensions(sold as a 5 pack)(TR-HS,TRW-HS) 5.7-Lx4.8"W x0.35"D(145 mm L x 122 mm W x 9 mm D)
Notes:
1.Full Wave Rectified(FWR)voltage is a non-regulated,time-varying power source that is used on some power supply and panel outputs.
2.F.S,PC,and SC products will operate at 12 V nominal only for 15 and 15n5 cd.
nvowmao
SpectrAlert Advance Dimensions
�4.7" 5.05"� �2.23=►I
F
P5.6" 5.98" (OD;---7,
0
v 0
LC
Wall-mount horn strobes Wall back box skirt
SpectrAlert Advance Ordering information
Wall Horn Strobes Horns
P2R*t 2-Wre Horn Strobe,Standard cd*Red HR Horn,Red
P2RH* 2-Wire Horn Strobe,High cd,Red HW Hom,White
P2W* 2-Wre Horn Strobe,Standard cd,White Accessories
P2WH* 2-Wire Horn Strobe,High cd,White BBS-2 Back Box Skirt,Wall,Red
P4R* 4-Wre Horn Strobe,Standard cd,Red BBSW-2 Back Box Skirt,Wall,White
P4RH 4-Wire Horn Strobe,High cd,Red TR-HS Trim Ring,Wall,Red
MW 4-Wre Horn Strobe,Standard cd,White TRW-HS Trim Ring,Wall White
Wall Strobes
SR*t Strobe,Standard cd,Red
SRH*t Strobe,High cd,Red
SW* Strobe,Standard cd,White
SWH* Strobe,High cd,White
Notes:
Add'-P'to model number for plain housing(no'FIREmarking on cover),e.g.,P2R-P.
t Add'-SP'to model number forTUEGO'marking on cover,e.g.,P2R-5P.
#'Standard cd'mfersto strobes that include 15,15P5,30,75,95,110,and 115 candela settings.'High cd'refersto strobes that include 135,150,177,and 185 candela settings.
SYSTEM czanS ose w.
3825 Ohio Avenue•St.Charles,IL 60174 mdua:p ,*gmmdv�y�*mno,n*orcev� � ,cams
�� SENS®R° Phone-80o-SENSOR2•Fax 63(}377-6495 Wcr_wi.12M, vn°°"xmv a
RRS-MOD Specifications
Reversing relay/synchronization module shall be a System Sensor i' Series model number RRS-MOD,listed to Underwriters Laboratories as a smoke detector
accessory.The module shall allow all 2-wire and 4-wire P Series detectors equipped with a sounder on a loop to sound when one alarms The module shall
provide a switch to toggle between coded mode and continuous mode When in coded mode,the module shall synchronize the P sounders on the loop to
mirror the input signal.When in continuous mode,the module shall synchronize the P sounders on the loop to the ANSI S3.41 temporal coded pattern.In either
coded or continuous modes,the RRS-MOD module shall permit sounders to be silenced at the panel.The RRS-MOD module shall operate between 85 and 35
VDC,and shall provide 18 AWG stranded,tinned conductors connected toa quick-connect harness.
Physical Specifications
Dimensions 25 in H x 25 in W x 1 in D( 33 mm x 63 mm x 75 mm)
Operating Temperature Range 32°F to 131T(g°C to 55°Q
Wire Connections 18 AWG stranded,tinned,16 in length
Operating Humidity Range 5%to 85%non-condensing
Electrical Specifications
Operating Voltage Nominal:12/24V
Min:85V
Maz 35 V
Average Operating Current: 25 mA
Relay Contact Rating 2A@35VDC
Wiring Diagrams
NOTE:These diagrams represent two common wiring methods.Refer to the RRS-MOD installation manual for additional wiring configurations.
m�.+w
••• anuw anKxu _ � Amore
soioim o<"'°°n� °w°`m,w soioiao m'aaa,ox �.wwv'�
2-Wire SystemTriggered from Alarm/Bell Circuit 2-Wire System Triggered from Alarm Relay Contact
Ordering Information
Part Nci� Description
RRS-MOD Reversing relay/synchronization module fore Series smoke detectors
SYSTEM ommsnce�,se�«.
38250hio Avenue•St.Charles,IL60174 r�auam�v�vga,ma�se�n�rw�ermmremsem«.ca�m
�jY SENSOR' Phone:800-SENSOR2•Fax:630-377-6495 """" """d""q�Aa5MI.MI.116761pAmw:mowac
SYSTEM
SENSOR®
RRS-MOD
Reversing Relay/
Synchronization Module
The RRS-MOD reversing relay/synchronization module
enhances the operation of2-and 4-wire it Series
3
detectors equipped with a sounder.
Features Installation ease.The RRS-MOD reversing relay/synchronization
•is compatible with 2-and 4-wire i3 detectors equipped with a module includes a Velcro'attachment for easy installation into the
sounder fire alarm control panel cabinet.A quick-connect harness and color-
coded wires simplify connections.
•Activates all i3 sounders on a loop when one alarms
•Synchronizes all i3 sounders on the loop for a clear alarm signal Intelligence.The RRS-MOD module's design is flexible to
•Is usable with bell/alarm,alarm relay,or NAC outputs accommodate virtually any application.It is compatible with both l-
and 4-wire i3 Series detectors operating over 12 V and 24 V systems.
•Has a field-selectable switch to accommodate both coded and The module can be used with either bell/alarm,alarm relay,or NAC
continuous alarm signals outputs,and its field selectable switch accommodates both coded
•Allows i3 detector silencing from the panel or keypad and continuous alarm signals.
•Operates on 12 and 24 volt systems
Instant inspection.To meet fire alarm requirements,the RRS-MOD
•Simplifies connections with quick-connect harness and color-coded reversing relay/synchronization module activates all i3 sounders on a
wires loop when an individual sounder alarms.Additionally,it synchronizes
the output of the i3 sounders,regardless of whether the panel's alarm
signal is continuous or coded,to ensure a clear alarm signal
Agency Listings
@ <M > 0
LISTED
9M 1.1.9 13a 1c 3161
SYSTEM
SENSOR®
F'.,� ,'Fl c JS•Y
Smoke Detectors with
Sounder and Relay Option
ti
System Sensor P'sounder and relay smoke detectors Ws
apply the guiding principles of installation ease, .�
intelligence,and instant inspection in a series of
specialty conventional devices.
Features Installation ease.Throughout the i3 series,installation is simple
•85 dB sounder with its installer-friendly base and plug-in design.The base
accommodates a broad range of back box and direct mounting
•Form C relay options and provides ample space for pre-wiring the device.To
•Isolated thermal sensor complete the installation,the P detector plugs into its base with a
simple Stop-Drop'N Lock action.
•Plug-in design(base included)
Intelligence.To reduce the likelihood of nuisance alarms,all
•In-line terminals i3 detectors are equipped with both drift compensation and
•Flexible mounting options smoothing algorithms.These capabilities minimize both short-and
long-term causes of nuisance alarms,such as RF interference and
•Stop-Drop Lock"attachment to the base dust accumulation.When connected to the 2W-MOD2 loop test/
•Removable cover and chamber maintenance module or an P Ready"panel,2-wire i3 detectors can
•Remote maintenance signaling generate a remote maintenance signal when in a maintenance or
freeze trouble condition.To measure the sensitivity of any i detector,
•Drift compensation and smoothing algorithms the SENS-RDR displays the reading,in terms of percent-per-foot
•Simplified sensitivity measurement obscuration,within seconds.
•Dual-color LEDs Instant inspection.i3 has red and green LEDs to simplify local
status indication during power-up,standby,alarm,maintenance,
and freeze trouble conditions.When in alarm,13 sounder models
generate an 85 dB temporal tone.If connected to the RRS-MOD
reversing relay/synchronization module,all i3 sounders on the loop
will activate when one detector is in alarm.The RRS-MOD also
synchronizes 13 sounder output to ensure a clear audible signal.
Agency Listings
Should the application call for differentiating between a local and
O a general alarm,the i3line offers an isolated thermal model,which
■�� ���aa initiates a local alarm when smoke is detected,and a general alarm
FM ® Ir A Irllfln
LISFED approved approved °(-)e when the thermal sensor is activated.
SM 3015195 nn-Mli& MR m 2133 31.g
ANN-BUS DEVICE ADDRESSING After calculating the total worst case current draw,the following
Each ANN-BUS device requires a unique address(ID Number) table specifies the maximum distance the modules can be
in order to communicate with the FACP.A maximum of 8 devices located from the FACP on a single wire run.The table ensures
can be connected to the FACP ANN-BUS communication circuit 6.0 volts of line drop maximum.In general,the wire length is lim-
See the FACP manual for more information. iced by resistance, but for heavier wire gauges, capacitance is
the limiting factor.
WIRE REQUIREMENTS.COMMUNICATIONS CIRCUIT These cases are marked in the chart with an asterisk('). Maxi-
The ANN-80 connects to the FACP ANN-BUS communications mum length can never be more than 6,000 feet (1,800 m),
circuit. To determine the type of wire and the maximum wiring regardless of gauge used. See table below.
distance that can be used with FACP ANN-BUS accessory mod- WIRE REQUIREMENTS:POWER CIRCUIT
ules, it is necessary to calculate the total worst case current
draw for all modules on a single 4-conductor bus.The total worst • 14 to 18 AWG(0.75-2.08 mm2)wire for 24 VDC power cir-
case current draw is calculated by adding the Individual worst cuit is acceptable. Power wire distance limitation is set by 1.2
case currents for each module. volt maximum line drop form source to end of circuit.
NOTE:For total worst case current draw on a single ANN-BUS • All connections are power-limited and supervised.
refer to appropriate FACP manual. • A maximum of eight ANN-80 modules may be connected to
this circuit.
Communication Pair Wiring Distance: FACP to Last ANN-BUS Module
Total Worst Case 22 Gauge 18 Gauge IS Gauge 14 Gauge
Current Draw(amps)
0.100 1,852 ft. 4,688 ft. '6,000 ft. -6,000 ft.
0.200 926 ft. 2,344 ft. 3,731 ft. 5,906 ft.
0.300 617 ft. 1,563 ft. 2,488 ft. 3,937 ft.
0,400 463 ft. 1,172 ft. 1,866 ft. 2,953 ft.
0.500 370 ft. 938 ft. 1,493 ft. 2,362 ft.
0.600 309 ft. 781 ft. 1,244 ft. 1,969 ft.
0.700 265 ft. 670 ft. 1,066 ft. 1,687 ft.
0.800 231 ft. 586 ft. 933 ft. 1,476 ft.
0.900 206 ft. 521 ft. 829 ft. 1,312 ft.
1.000(max.) 185 ft. 469 ft. 746 ft. 1,181 ft.
WIRING CONFIGURATION ORDERING OPTIONS.
The following figure illustrates the wiring between the FACP and ANN-80:Red 80 character LCD Annunciator.
ANN-BUS devices. ANN-80-W:White,80 character LCD Annunciator.
ANN-BUS and power ANNSB80KIT--R: Red surface mount backbox with angled
wiring are supervised wedge.
and power-limited. ANNSB80KIT-W: White surface mount backbox with angled
® jB j32
. - wedge.
t
ANN-BUS Device
O
MS-905OUD tea
1 2 3 6 5 6 7 9
FACP Wiring to ANN-BUS Device
FireLite®Alarms Is a registered trademark of Honeywell International Inc.
C2009 by Honeywell International Inc.All rights reserved.Unauthorized use
of this document is strictly prohibited.
'® This document is not coded i to be Lion for installation purposes
We try to keep our product information up-to-tlate and accurate.
We cannot cover all specific applications or anticipate all requirements.
GYBLIT IIFHI T SYSTEMS F MY T E MSS All specifications are subject to change without notice.
Made in the U.S.A.
For more information,contact Fire-Lite Alarms.Phone:(800)627-3473,FAX:W7)699-4105.
www.firelite.com
Page 2 of 2—df-52417:c•05/22/09
df-52417:c•B-90
ANN-80 FirelffeWarms
80-Character LCD by Honeywell
Serial Annunciator
General
The ANN-80 annunciator is a compact, backlit, 80-character
LCD fire annunciator that mimics the Fire Alarm Control Panel
(FACP) display. It provides system status indicators for AC
Power,Alarm,Trouble, Supervisory, and Alarm Silenced condi-
tions.The ANN-80 and the FACP communicate over a two-wire Y
serial interface employing the ANN-BUS communication format.
Connected devices are powered, via two additional wires, by
either the host FACP or a remote UL-listed,filtered power supply.
ANN-80 is red;for white,order ANN-80-W rat
The ANN-80 displays English-language text of system point
information including device type, zone, independent point
alarm, trouble or supervisory status, as well as any custom
alpha labels programmed into the control panel. It includes can- G
trol switches for remote control of critical system functions. (A
keyswitch prevents unauthorized operation of the control $
switches.)
Up to eight ANNAOs may be connected to the ANN-BUS of g _each FACP.No programming is required,which saves time dur-
ing system commissioning.
Features
• Listed to UL Standard 864,9th Edition.
• Backlit 80-character LCD display(20 characters x 4lines). • Supervisory
• Mimics all display information from the host panel. • Alarm Silenced
• Control switches for System Acknowledge, Signal Silence, SpecificationsDrill,and Reset.
• Control switches can be independently enabled or disabled • Operating voltage range: 18 VDC to 28 VDC.
at the FACP. • Current consumption @ 24 VDC nominal(filtered and non-
• Keyswitch enables/disables control switches and mechani- resettable):40 mA maximum.
cally locks annunciator enclosure • Ambient temperature:32°F to 120OF(0°C to 491C).
• Keyswitch can be enabled or disabled at the FACP. • Relative humidity:93%x 2/,RH(noncondensing)at 320C
• Enclosure supervised for tamper. t 20C(90°F x 3°F).
• System status LEDs for AC Power, Alarm,Trouble, Supervi- • 5.376' (13.65 cm.) high x 6.876'(17.46 cm.)wide x 1.376'
sory,and Alarm Silence. (3.49 cm.)deep.
• Local sounder can be enabled or disabled at the FACP. • For use indoors in a dry location.
• ANN-80 connects to the ANN-BUS terminal on the FACP and • All connections are power-limited and supervised.
requires minimal panel programming.
• Displays device type identifiers, individual point alarm,trou- Agency Listings and Approvals
ble,supervisory,zone,and custom alpha labels.
• Time-and date display field. The listings and approvals below apply to the ANN-80. In some
cases, certain modules may not be listed by certain approval
• Surface mount directly to wall or to single, double, or 4• agencies,or listing may be in process.Consult factory for latest
square electrical box. listing status.
• Semi-flush mount to single, double, or 4• square electrical • UL:S2424
box.Use ANN-SB80KIT for angled view mounting.
• Can be remotely located up to 6,000 feet(1,800 m)from the • FM approved
panel. • CSFM:7120-0075:211
• Backlight turns off during AC loss to conserve battery power • MEA:442-06-E
but will turn back on if an alarm condition occurs.
• May be powered by 24 VDC from the host FACP or by remote The ANN-BUS
power supply(requires 24 VDC).
• Up to eight ANN-80s can be connected on the ANN-BUS. POWERING THE DEVICES ON THE ANN-BUS FROM
AUXILIARY POWER SUPPLY
Controls and Indicators The ANN-BUS can be powered by an auxiliary power supply
when the maximum number of ANN-BUS devices exceeds the
• AC Power ANN-BUS power requirements.See the FACP manual for more
• Alarm information.
• Trouble
df-52417:c•05/27J09—Page 1 of 2
Specifications Agency Listings and Approvals
PHYSICAL SPECIFICATIONS: The listings and approvals below apply to the BG-12 Series pull
stations. In some cases,certain modules may not be listed by
certain approval agencies,or listing may be in process.Consult
pull station SB410 SB-10 factory for latest listing status.
Height 5.5 inches 5.601 inches 5.5 inches • C(UL)US:S711
(13.97 cm) (14.23 cm) If 3.97 cm) • FM Approved
Width 4.121 inches 4.222 inches 4.121 inches . CSFM:7150-0075:184
(10.47 cm) (10.72 cm) (10.47 cm) • MEA:67-02-E
Depth 1.39 inches 1.439 inches 1.375 inches . Patented: U.S. Patent No. D428,351; 6,380,846; 6,314,772;
(3.53 cm) (3.66 cm) (3.49 cm) 6,632,108.
51Si,Em.MI
ELECTRICAL SPECIFICATIONS: Product Line Information
Switch contact ratings:gold-plated;rating 0.25 A W 30 VAC or BG-12S: Single-action pull station with pigtail connections,hex
VDC. lock.
ENGINEERING(ARCHITECTURAL SPECIFICATIONS BG-12SL: Same as BG-12 with key lock.
Manual Fire Alarm Stations shall be non-code, with a key- or BG-12: Dual-action pull station with SPST WO switch, screw
hex-operated reset lock in order that they may be tested,and so terminal connections,hex lock.
designed that after actual Emergency Operation,they cannot be BG-12L: Same as BG-12 with key lock.
restored to normal except by use of a key or hex.An operated BG-12LSP: Same as BG-12L with English/Spanish (FIRE/
station shall automatically condition itself so as to be visually FUEGO)labeling.
detected as activated. Manual stations shall be constructed of BG-12LOB: Same as BG-12L with "outdoor use' listing.
red colored LEXAN (or polycarbonate equivalent) with Beady includes outdoor listed backbox,and sealing gasket.
visible operating instructions provided on the cover. The word
FIRE shall appear on the front of the stations in white letters, BG-12LO: Same as BG-12L with "outdoor use listing. Does
1.00 inches (2.54 cm) or larger. Stations shall be suitable for not include backbox.
surface mounting on matching backbox SB-10 or SB-I/O; or BG-12LA: Same as BG-12L with auxiliary contacts.
semi-flush mounting on a standard single-gang,double-gang,or 8G.12LPS: Dual-action pull station with pre-signal option.
4'(10.16 cm)square electrical box,and shall be installed within BG-12LPSP: Same as BG-12LPS with English/Spanish(FIRE/
the limits defined by the Americans with Disabilities Act(ADA)or FUEGO)labeling.
per nationaillocal requirements.Manual Stations shall be Under-
writers Laboratories listed. SB-10: Surface-mount backbox,metal.
NOTE.*The words FIRE/FUEGO"on the BG-12LSP shall appear SB-UO: Surface-mount backbox, plastic. (included with BG-
on the front of the station in while letters, approximatety 314' 12LOR.)
(1.90.5 cm)high. BG12TR: Optional trim ring for semi-flush mounting.
17003:Keys,set of two.(Included with key-lock pull stations.)
17007:Hex lock,9/64".(Included with hex-lock pull stations.)
NOTE., For addressable BG-12LX models see data sheet DF-
52013.
I
II ••
I
I
Fire•Llte®Alarms, SpectrAlert® Advance, and System Sensor® are
registered trademarks of Honeywell International Inc.
@2008 by Honeywell International Inc.All rights reserved.Unauthorized use
of this document is strictly prohibited-
This try to keep
is not intended to be used for installation purposes
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
QUALITY SYSTEMS All specifications are subject to change without notice.
Made in the U.B.A.
For more information,contact Fre•Ute Alarms.Phone:(800)627-3473,FAX:(877)699,4105.
wwwfirelite.00m
Page 2 of 2—DF-52004:A1•04/22108
DF-52004:A1•F-050
13G-12 Series 'FIPG'•LITeALarmS
Manual Fire Alarm Pull Stations
by Honeywell
General
The Fire-Lite BG-12 Series is a cost-effective, feature-packed
series of non-coded manual fire alarm pull stations. It was
designed to meet multiple applications with the installer and
end-user in mind.The BG-12 Series features a variety of mod-
els including single-and dual-action versions.
The BG-12 Series provides Fire-Lite Alarm Control Panels
(FACPs),as well as other manufacturers'controls,with a man-
ual alarm initiating input signal. Its innovative design, durable •
construction, and multiple mounting options make the BG-12
Series simple to install,maintain,and operate. i
Features
• Aesthetically pleasing,highly visible design and color.
• Attractive contoured shape and light textured finish.
• Meets ADA 5 lb.maximum pull-force. R
• Meets UL 38,Standard for Manually Actuated Signaling Boxes.
• Easily operated(single-or dual-action), yet designed to pre- '8
vent false alarms when bumped,shaken,or jarred. '
• PUSH INIPULL DOWN handle latches in the down position to
clearly indicate the station has been operated. Construction
• The word "ACTIVATED" appears on top of the handle in • Cover, backplate and operation handle are all molded of
bright yellow,further indicating operation of the station. durable polycarbonate material.
• Operation handle features white arrows showing basic opera- • Cover features white lettering and trim.
tion direction for non-English-speaking persons. . Red color matches System Sensors popular SpectrAlerM
• Braille text included on finger-hold area of operation handle Advance horn/strobe series.
and across top of handle.
• Multiple hex-and key-lock models available. Operation
• U.S. patented hex-lock needs only a quarter-turn to lock/
unlock. The BG-12 manual pull stations provide a textured finger-hold
• Station can be opened for inspection and maintenance with- area that includes Braille text.In addition to PUSH IN and PULL
out initiating an alarm. DOWN text,there are arrows indicating how to operate the sta-
• Product ID label viewable by simply opening the cover;label tion,provided for non-English-speaking people.
is made of a durable long-life material. Pushing in and then pulling down on the handle activates the
• The words"NORMAL"and"ACTIVATED"are molded into the normally-open alarm switch.Once latched in the down position,
plastic adjacent to the alarm switch(located inside). the word"ACTIVATED"appears at the top in bright yellow,with a
• Four-position terminal strip molded into backplate. portion of the handle protruding at the bottom as a visible flag.
• Terminal strip includes Phillips combination-head captive 8132 Resetting the station is simple:insert the key,twist one quarter-
screws for easy connection to Initiating Device Circuit(IDC). turn, then open the station's front cover, causing the spring-
loaded operation handle to return to its original position. The
• Terminal screws backed-out at factory and shipped ready to alarm switch can then be reset to its normal(non-alarm)position
accept field wiring(up to 12 AWG/3.1 mm2). manually(by hand)or by closing the station's front cover,which
• Terminal numbers are molded into the backplate,eliminating automatically resets the switch.
the need for labels.
• Switch contacts are normally open.
• Can be surface-mounted (with SB-10 or SB-1/0) or semi-
flush mounted. Semi-flush mourn to a standard single-gang,
double-gang,or 4"(10.16 cm)square electrical box.
• Backplate is large enough to overlap a single-gang backbox
cutout by 1/2"(1.27 cm).
• Optional trim ring(BG12TR).
• Spanish versions(FUEGO)available(BG-12LSP,BG-121LPSP).
• Designed to replace the Fire-Lite legacy BG-10 Series.
• Models packaged in attractive, clear plastic (PVC), clam-
shelf-style, Pointof-Pumhase packages. Packaging includes
a cutaway dust/paint cover in shape of pull station.
DF-52004:A7•04/22/08—Page 1 of 2
USER INTERFACE: • SYSTEM RESET(lamp test)
• Built-in DACT(Digital Alarm Communicator/Transmitter). • DRILL
• Integral 80-character LCD display with backlighting and
keypad. Terminal Blocks
• Real-time clock/calendar with automatic daylight savings AC Power—TB1:
adjustments. • MS-5UD-3 (FLPS3 Power Supply): 120 VAC, 50/60 HZ,
• ANN-BUS for connection to remote annunciators. 1.00 A.
• Audible or silent walk test capabilities. • MS-5UD-3E (FLPS-3 Power Supply): 240 VAC, 50 HZ,
• Piezo sounder for alarm,trouble,and supervisory. 0.54 A.
• MS-10UD-7 (FLPS-7 Power Supply): 120 VAC, 50/60 HZ,
Controls and Indicators 3.80 A.
LED INDICATORS • MS-10UD-7E(FLPS-7 Power Supply):240 VAC,50/60 HZ,
2.20 A.
• FIRE ALARM(red) Wire size:minimum 14 AWG(2.00 mm2)with 600 V insulation.
• SUPERVISORY(yellow) Supervised,nonpower-limited.
• TROUBLE(yellow) Battery(sealed lead acid only)—J12:
• AC POWER(green) • Maximum Charging Circuit-Normal Flat Charge:27.6 VDC
• ALARM SILENCED(yellow) @ 1.4 A.Supervised,nonpower-limited.
CONTROL BUTTONS • Maximum Charger Capacity: 18 AH battery for MS-SUD-
• 3(E),and 26 AH battery for MS-10UD-7(E).[Two 18 Ah bat-
ACKNOWLEDGE
teries can be housed in the FACP cabinet.Larger batteries
• ALARM SILENCE require separate battery box such as the BB-26 or BB-55.1
Depth=5.207"(13.23 cm)
Top
Door=16.821"(42.73 cm) � 1 Depth=
~—Backbox=16.65"(42.29 cm) I�5.257"�I
(13.363 cm)
f iY
t < i
1 Door=19.26"(48.92 cm)
Backbox=19.0"(48.26 cm)
s y ,
e ~
Left Side " Right Side
Bottom
.(t
Cabinet Measurements
Page 2 of 4—DF52416:13•07/26/2010
SYSTEM SPECIFICATIONS
System Capacity Temperature and Humidity Ranges
• Annunciators......................................................................8 This system meets NFPA requirements for operation at 0 —
49°C/32 — 120°F and at a relative humidity 93% : 2% RH
Electrical Specifications (noncondensing) at 320C t 2°C (90°F x 3°F). However, the
useful life of the system's standby batteries and the electronic
• MS-5UD-3 (FLPS-3 Power Supply): 120 VAC, 60 HZ, components may be adversely affected by extreme tempera-
1.0 A ture ranges and humidity. Therefore,it is recommended that
• MS-1 DUD-7 (FLPS-7 Power Supply): 120 VAC, 60 HZ, this system and its peripherals be installed in an environment
3.90 A with a normal room temperature of 15—27IC160—80°F.
• MS-5UD3E (FLPS-3 Power Supply): 240 VAC, 50 HZ,
0.54 A. Agency Listings and Approvals
• MS-10UD-7E (FLPS-7 Power Supply): 240 VAC, 50 HZ, The listings and approvals below apply to the basic MS-51.0-3
2.20 A. and MS-10UD-7 control panels. In some cases, certain mod-
• Wire size: minimum 14 AWG(2.0 mm�with 600 V insula- ules or applications may not be listed by certain approval
tion,supervised,nonpower-limited agencies,or listing may be in process.Consult factory for lat-
est listing status.
Cabinet Specifications • UL Listed:File S624
Door: 19.26" (48.92 cm.) high x 16.82" (42.73 cm.) wide x • FM Approved
0.72" (1.82 cm.) deep. Backbox: 19.00' (48.26 cm.) high x • CSFM:7165-0075:0214
16.66" (42.29 cm.)wide x 5.25" (13.34 cm.)deep. Trim Ring • MEA: MEA:333-07-E
(TR-CE):22.00"(55.88 cm.)high x 19.65"(49.91 cm.)wide.
NOTE:For ULC-listed models,see OF-60440.
Shipping Specifications NFPA Standards
Dimensions: The MS-5UD-3(E) and MS-10UD-7(E) complies with the fol-
-20.00"(50.80 cm.)high lowing NFPA 72 Fire Alarm Systems requirements:
—22.5"(57.15 cm.)wide —LOCAL (Automatic, Manual, Waterflow and Sprinkler
—8.5"(21.59 cm.)deep. Supervisory).
Weight:271b(12.20 kg) —AUXILIARY(Automatic,Manual and Waterflow)(requires
4XTMF).
—REMOTE STATION (Automatic, Manual and Waterfiow)
(Where a DACT is not accepted, the alarm, trouble and
supervisory relays may be connected to UL 864 listed
transmitters. For reverse polarity signaling of alarm and
trouble,4XTMF is required.)
—PROPRIETARY(Automatic,Manual and Waterflow).
—CENTRAL STATION (Automatic, Manual and Waterflow,
and Sprinkler Supervised).
—OT, PSDN (Other Technologies, Packet-switched Data
Network)
PlreLlte® Alarms and System Sensor® are registered trademarks of
Honeywell International Inc.
@2010 by Honeywell International Inc.All rights reserved.Unauthorized use
of this document is strictly prohibited.
'® This document is not coded i to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
Kern! SNIIMfN.7RSi All specifications are subject to change without notice.
SiI LITY SYSTEMS Madeinthe U.S.A.
For more information,contact Fira•lite Alarms.Phone:(800)627-3473,FAX:(877)699-4105.
wwwArelke.00m
Page 4 014—DF52416:D•07/262010
• Minimum Battery Size:7 AH. MS-t0UD-7E:Same as above with 240 VAC FLPS-7.
Initiating Device Circuits—T84(and TB 6 on MS-10UD-7 IPDACT, IPDACT-212UD Internet Monitoring Module:
only): Mounts in bottom of enclosure with optional mounting kit(PN
• Alarm Zones 1 -5 on TB 4(MS5UD-3 and MS-10UD-7). IPBRKT). Connects to primary and secondary DACT tele-
phone output ports for internet communications over customer
provided ethernet internet connection. Requires compatible
• Supervised and power-limited circuitry. Teldat Visoralarm Central Station Receiver.Can use DHCP or
• Operation:All zones Style B(Class 8). static IF..(See data sheet DF-60407 for more information.)
• Normal Operating Voltage:Nominal 20 VDC. IPBRKT:Mounting kit for IPDACT in common enclosure.
• Alarm Current:15 mA minimum. IPSPLT: Y Adaptor option to allow connection of both panel
• Short Circuit Current:40 mA max. dialer outputs to one cable input to IPDACT(sold separately).
• Maximum Loop Resistance:100 ohms. OPTIONAL MODULES
• End-of-Line Resistor: 4.71K ohm, 112 watt (PM 71252 UL- CACSX:Optional(Class A)Converter Module.Converts Style
listed). B(Class B)Initiating Device Circuits to Style D(Class A);and
• Standby Current:2 mA. Style Y (Class B) Notification Appliance Circuits to Style Z
Refer to the Fire-Lite Device Compatibility Document for listed (Class A). Connects to J2 on the MS-51JD-3 and MS-10UD-
compatible devices. 7(E)main circuit board and to J7 on the MS-10UD-7(E).
Notification Appliance Circuits —TB5 (and TS 7 on MS- NOTE: Two Class A Converter Modules are required for the ten-
1OUD-7 only): zone panel.
• Four NACs 4XTMF:Transmitter module. Provides a supervised output for
• Operation:Style Y(Class B) local energy municipal box transmitter and alarm and trouble
reverse polarity. Includes a disable switch and disable trouble
• Special Application power LED.A module jumper option allows the reverse polarity circuit
• Supervised and power-limited circuitry to open with a system trouble condition if no alarm conditions
• Normal Operating Voltage:Nominal 24 VDC exists.Mounts to the main circuit board connectors J4 and J5.
• Maximum Signaling Current: 3.0 A for MS51JD-3, 2.5 A COMPA77BLEANNUNCIATORS
maximum per NAC; 7.0 A for MS-10UD-7(E), 3.0 A maxi- ANN-80: Remote LCD Annunciator. Mimics the information
mum per NAC. displayed on the FACP's LCD. Red. (For white, order: ANN-
• End-of-Line Resistor:4.71K ohm,1/2 watt(Part#71252) 60-W)
• Max.Wiring Voltage Drop:2 VDC ANN-LED: LED Annunciator with three LEDs for each zone:
Refer to the Fire-Lite Device Compatibility Document for com- Alarm,Trouble, and Supervisory. Mounts in the DP-51050(B)
patible listed devices. dress panel.Red.(For white,order ANN-LED-W.)
Form C Relays—TB6: ANN-RLED: LED Annunciator with three alarm (red) indica-
• Relay 1(factory default programmed as Alarm Relay) tors for up to 30 input zones or addressable points.(Red. For
• Relay 2 (factory default programmed as fail-safe Trouble white,order ANN-LED-W.)(See DF-60241).
Relay) ANN-RLY.Relay module.Mounts inside the cabinet.Provides
• Relay 3(factory default programmed as Supervisory Relay) ten Form C relays.
Special Application Resettable Power—TB9: ANN-S/PG:Seriallparallel printer gateway.Provides a connec-
• Jumper selectable by JP31 for resettable or nonresettable tion for a serial or parallel printer.
power. ANN-1/O: Driver module. Provides connections to a user-sup-
Operating voltage:24 VDC nominal. plied graphic annunciator.
• Maximum available current:500 mA-appropriate for pow- ACCESSORIES
ering four-wire smoke detectors. DP-51050:Optional dress panel. Restricts access to the sys-
• Power-limited circuit. tem wiring while allowing access to the membrane switch
Refer to the Fire-Lite Device Compatibility Document for listed panel.
compatible devices. 88-26: Battery backbox,holds up to two 25 AH batteries and
Remote Sync Output-T82: Remote power supply synchro- CHG-75.
nization output,only required for the MS-51JD-3.24 VDC nom- BB-55:Battery backbox,holds up to two 25 AH batteries.
inal special application power. Maximum current is 40 mA.
Endof-Line Resistor: 4.71K ohm. Supervised and power-lim- TR-CE:Optional trim-ring for semi-flush mounted cabinets.
tied circuit. PRN-6F:UL listed printer.
Product Line Information
MS-SUD-3: Five-zone, 24-volt Fire Alarm Control Panel
(includes backbox, FLPS-3 power supply, technical manual,
and a frame & post operating instruction sheet). 120 VAC
operation.
MS-5UD-3E: Same as MS-51JD-3 except for 240 VAC opera-
tion.
MS-10UD-7: Ten-zone, 24-volt Fire Alarm Control Panel
(includes backbox, FLPS-7 power supply, technical manual,
and a frame&post operating instruction sheet).
DF32416:D•07Mf2010—Page 3 of 4