Loading...
HomeMy WebLinkAbout467 Oakland Road UAquatek Labs 3 Research Drive-Woodbridge, CT 06525 Water Analysis Report TEST ID: A040918043 DATE SAMPLED: 4/9/2018 TO: PRIME HOME INSPECTIING, LLC 597 SAMPLE POINT: KITCHEN NO TREATMENT SAMPLED BY: ARTHUR ANNECHARIO PROPERTY LOCATION: 467 OAKLAND ROAD - SOUTH WINDSOR , CT BACTERIA ABSENT PRESENT LIMITS REF METHOD Coliform(Total) G ❑ ABSENT P SM 9223 E.Coli(Fecal) G ❑ ABSENT P SM 9223 Chlorine(Total) G ❑ ABSENT SM 4500-CI G PHYSICAL PARAMETERS RESULT UNITS LIMITS MRL REF METHOD pH 7.3 SU 6.4-10 S 0 SM 4500-H B Turbidity 0.60 NTU 5 0.10 SM 2130 B Color ND CU 15 S 5 SM 2120 B Odor 1 TON 2 S 0 SM 2150 CHEMICALS RESULT UNITS LIMITS MRL REF METHOD Fluoride ND mg/L 4 P 0.3 EPA 300.0 Chloride 24 mg/L 250 P 3 EPA 300.0 Nitrite Nitrogen ND mg/L 1 P 0.1 EPA 300.0 Nitrate Nitrogen 3.9 mg/L 10 P 1 EPA 300.0 Sulfate 13 mg/L 250 S 4 EPA 300.0 Calcium 29 mg/L NONE 0.5 EPA 200.7 Magnesium 9 mg/L NONE 0.5 EPA 200.7 Hardness 111 mg/L 200 S 4 SM 2340 B Sodium 9.7 mg/L 100 S 0.5 EPA 200.7 Copper ND mg/L 1.3 S 0.04 EPA 200.7 Iron ND mg/L 0.3 S 0.04 EPA 200.7 Manganese ND mg/L 0.05 S 0.04 EPA 200.7 RADON WATER SINGLE RESULT UNITS LIMITS MRL REF METHOD Radon Water Single 3214 pCi/L 5000 S 51 SM 7500-RN CONCLUSION: Based on the above results, this water was safe for drinking purposes at the time of collection. P=Primary limit,used to judge potability S=Secondary limit,recommended but not required MRL=Minimum Reportable Level /�� a�•� e�n?ar� *Limit exceeded Michael F. Berman, Ph.D. ND=None Detected Laboratory Director CT License#PH-0466,Aquatek Labs R=Reference Lab Work Page 1 of 1 for test#A040918043