HomeMy WebLinkAbout637 Deming Street UAquatek Labs 3 Research Drive-Woodbridge, CT 06525 Water Analysis Report TEST ID: B030618302 DATE SAMPLED: 3/5/2018 TO: PRIME HOME INSPECTIING, LLC 597 SAMPLE POINT: KITCHEN AFTER TREATMENT SAMPLED BY: JASON LIMA PROPERTY LOCATION: 637 DEMING STREET- SOUTH WINDSOR , CT BACTERIA ABSENT PRESENT LIMITS REF METHOD Coliform(Total) G ❑ ABSENT P SM 9223 E.Coli(Fecal) G ❑ ABSENT P SM 9223 Chlorine(Total) G ❑ ABSENT SM 4500-CI G PHYSICAL PARAMETERS RESULT UNITS LIMITS MRL REF METHOD pH 7.2 SU 6.4-10 S 0 SM 4500-H B Turbidity 3.80 NTU 5 0.10 SM 2130 B Color 9 CU 15 S 5 SM 2120 B Odor 0 TON 2 S 0 SM 2150 CHEMICALS RESULT UNITS LIMITS MRL REF METHOD Fluoride ND mg/L 4 P 0.3 EPA 300.0 Chloride 37 mg/L 250 P 3 EPA 300.0 Nitrite Nitrogen ND mg/L 1 P 0.1 EPA 300.0 Nitrate Nitrogen ND mg/L 10 P 1 EPA 300.0 Sulfate 5 mg/L 250 S 4 EPA 300.0 Calcium 67 mg/L NONE 0.5 EPA 200.7 Magnesium 14 mg/L NONE 0.5 EPA 200.7 * Hardness 224 mg/L 200 S 4 SM 2340 B Sodium 10.0 mg/L 100 S 0.5 EPA 200.7 Copper ND mg/L 1.3 S 0.04 EPA 200.7 * Iron 1.91 mg/L 0.3 S 0.04 EPA 200.7 * Manganese 0.88 mg/L 0.05 S 0.04 EPA 200.7 RADON WATER SINGLE RESULT UNITS LIMITS MRL REF METHOD Radon Water Single 1276 pCi/L 5000 S 51 SM 7500-RN CONCLUSION: Based on the above results, this water was safe for drinking purposes at the time of collection. COMMENTS:* Filtration and/or conditioning are recommended. P=Primary limit,used to judge potability S=Secondary limit,recommended but not required MRL=Minimum Reportable Level �� 3e� Limit exceeded Michael F. Berman, Ph.D. ND=None Detected Laboratory Director CT License#PH-0466,Aquatek Labs R=Reference Lab Work Page 1 of 1 for test# B030618302