Loading...
HomeMy WebLinkAbout376 Deming Street UAquatek Labs 3 Research Drive-Woodbridge, CT 06525 Water Analysis Report TEST ID: D011118021 DATE SAMPLED: 1/10/2018 TO: HOME QUALITY HQ 538 SAMPLE POINT: KITCHEN NO TREATMENT SAMPLED BY: LARRY WILLETTE PROPERTY LOCATION: 376 DEMING STREET - SOUTH WINDSOR , CT BACTERIA ABSENT PRESENT LIMITS REF METHOD Coliform(Total) G ❑ ABSENT P SM 9223 E.Coli(Fecal) G ❑ ABSENT P SM 9223 Chlorine(Total) G ❑ ABSENT SM 4500-CI G PHYSICAL PARAMETERS RESULT UNITS LIMITS MRL REF METHOD pH 7.4 SU 6.4-10 S 0 SM 4500-H B Turbidity 0.40 NTU 5 0.10 SM 2130 B Color ND CU 15 S 5 SM 2120 B Odor 0 TON 2 S 0 SM 2150 CHEMICALS RESULT UNITS LIMITS MRL REF METHOD Fluoride ND mg/L 4 P 0.3 EPA 300.0 Chloride 9 mg/L 250 P 3 EPA 300.0 Nitrite Nitrogen ND mg/L 1 P 0.1 EPA 300.0 Nitrate Nitrogen 4.3 mg/L 10 P 1 EPA 300.0 Sulfate 24 mg/L 250 S 4 EPA 300.0 Calcium 35 mg/L NONE 0.5 EPA 200.7 Magnesium 7 mg/L NONE 0.5 EPA 200.7 Hardness 115 mg/L 200 S 4 SM 2340 B Sodium 8.9 mg/L 100 S 0.5 EPA 200.7 Copper ND mg/L 1.3 S 0.04 EPA 200.7 Iron ND mg/L 0.3 S 0.04 EPA 200.7 Manganese ND mg/L 0.05 S 0.04 EPA 200.7 CONCLUSION: Based on the above results, this water was safe for drinking purposes at the time of collection. P=Primary limit,used to judge potability S=Secondary limit,recommended but not required MRL=Minimum Reportable Level' Limit exceeded Michael F. Berman, Ph.D. ND=None Detected Laboratory Director CT License#PH-0466,Aquatek Labs R=Reference Lab Work Page 1 of 1 for test# D011118021