HomeMy WebLinkAbout720 Graham Road UAquatek Labs
3 Research Drive-Woodbridge, CT 06525
Water Analysis Report
TEST ID: C121416303
DATE SAMPLED: 12/14/2016
TO: OASIS INSPECTION SERVICES, LLC 747 SAMPLE POINT: BATHROOM
NO TREATMENT
SAMPLED BY: ERIC ROWE
PROPERTY LOCATION: 720 GRAHAM ROAD -SOUTH WINDSOR , CT
BACTERIA ABSENT PRESENT LIMITS REF METHOD
Coliform(Total) G ❑ ABSENT P SM 9223
E.Coli(Fecal) G ❑ ABSENT P SM 9223
Chlorine(Total) G ❑ ABSENT SM 4500-CI G
PHYSICAL PARAMETERS RESULT UNITS LIMITS MRL REF METHOD
pH 7.3 SU 6.4-10 S 0 SM 4500-H B
Turbidity 0.25 NTU 5 0.10 SM 2130 B
Color ND CU 15 S 5 SM 2120 B
Odor 1 TON 2 S 0 SM 2150
CHEMICALS RESULT UNITS LIMITS MRL REF METHOD
Flouride ND mg/L 4 P 0.3 EPA 300.0
Chloride 103 mg/L 250 P 3 EPA 300.0
Nitrite Nitrogen ND mg/L 1 P 0.1 EPA 300.0
Nitrate Nitrogen 4.9 mg/L 10 P 1 EPA 300.0
Sulfate 17 mg/L 250 S 4 EPA 300.0
Calcium 52 mg/L NONE 0.5 EPA 200.7
Magnesium 7 mg/L NONE 0.5 EPA 200.7
Hardness 159 mg/L 200 S 4 SM 2340 B
Sodium 33.6 mg/L 100 S 0.5 EPA 200.7
Copper 0.07 mg/L 1.3 S 0.04 EPA 200.7
Iron ND mg/L 0.3 S 0.04 EPA 200.7
Manganese ND mg/L 0.05 S 0.04 EPA 200.7
Lead ND mg/L 0.015 P 0.005 SM 3113 B
RADON WATER SINGLE RESULT UNITS LIMITS MRL REF METHOD
Radon Water Single 1284 pCi/L 5000 S 51 SM 7500-RN
CONCLUSION: Based on the above results, this water was safe for drinking purposes at the time of collection.
P=Primary limit,used to judge potability
S=Secondary limit,recommended but not required
MRL=Minimum Reportable Level Li� a�•� e�n?ar�
*Limit exceeded Michael F. Berman, Ph.D.
ND=None Detected Laboratory Director
CT License#PH-0466,Aquatek Labs
R=Reference Lab Work
Page 1 of 1 for test#C121416303