HomeMy WebLinkAboutWell Inspection 1043 Foster Street Exten STATE OF CONNECTICUT
DEPARTMENT OF ENVIRONMENTAL PROTECTION
W/ SVy1�Nt{ -
tl1�Nb)y!I -
f
August 31, 2006
Mr. Albert Ohlhof
1043 Foster Street Ext.
South Windsor, CT 06074
RE: Water Sampling Results for 1043 Foster Street Ext., South Windsor, CT
Dear Mr. Ohlhof:
Enclosed please find a copy of the laboratory results for the water samples that were collected
from your home on August 15, 2000. The water sample was analyzed for the presence of volatile
organic compounds(VOCs).
The chemical compound trichloroethene was identified at a concentration of 1.8 micrograms per
liter(ug/1).
The Department of Public Health's (DPH)has established the action level for trichloroethene in
drinking water at a concentration of 5 ug/l. Based on the laboratory results,the drinking water at
your home is potable with respect to the constituents tested.
Please be apprised that an environmental consulting firm contracted by the Town of South
Windsor will be monitoring your drinking water supply in the future.
If you have any questions regarding the above,please call me at(860)-424-3782.
Sincerely,
Michael P. Senyk
Environmental Analyst
Permitting, Enforcement and Remediation Division
cc: Robert Deptula, Sanitarian, Town of South Windsor
(Printed on Recycled Paper)
79 Elm Street • Hartford, CT 06106-5127
http://dep.state.ct.us
An Equal Opportunity Employer
�le\brating`Connecticut Coastal Resource Management.1980-2000
STATE OF CONNECTICUT •
Department of Public Health
Division of Laboratory Services 1NR!!,. 1 04371116125427 IA00 142
10 Clinton St. = :�7 7
P.O.Box 1689 INFORMATION
Hartford,CT 06144
TELEPHONE:(860)509-8500 132SOUTH WINDSOR
OHLHOF
F 1043 FOSTER ST
SOUTH WINDSOR CT
DEP—P.E.R.D. POTABLE WATER
79 ELM ST. 08/15/00 08/16/00 08/24/00
L HARTFORD CT 06106 14,' 15 11 '.38 13:28
FINAL REPORT
SAMPLING POINT; RAW
COLLECTOR: SENYKr MICHAEL TITLE.' ANALYST
PRIVATE WELL TREATMENT:
ATE ANALYZED 8/18/oo
--------------------------------------------------------
ANALYTICAL METHOD; EPA METHOD 524.2
MEASUREMENT OF ORGANIC COMPOUNDS IN WATER BY
CAPILLARY COLUMN GAS CHROMATOGRAPHY/MASS SPECTROMETRY.
--------------------------------------------------------
'A 524.2 FINAL RESULT;
COMPOUND QUANTITY (UG/L)
ENZ ENE ND
3ROMOBENZENE ND
3ROMOCHLOROMETHANE ND
3ROMODICHLOROMETHANE ND
3ROMOFORM ND
3ROMOMETHANE ND
4—BUTYLBENZENE ND
3EC—BUTYLBENZENE ND
rERT—BUTYLBENZENE ND
'ARBON TETRACHLORIDE ND
"HLOROBENZENE ND
:HLOROETHANE ND
,HLOROFORM ND
3HLOROMETHANE ND
nt" —CHLOROTOLUENE ND
—CHLOROTOLUENE ND
IBROMOCHLOROMETHANE ND
Z-DIBROMO-3-CHLOROPROPANE ND
2-DIBROMOETHANE ND
IBROMOMETHANE ND
2—DICHLOROBENZENE ND
,3—DICHLOROBENZENE ND
Y4—DICHLOROBENZENE ND
ICHLORODIFLUOROMETHANE ND
yl-DICHLOROETHANE ND
CONTI UED
RM NO.OL-6A REV.10-99
STATE OF CONNECTICUT •
-T 110�16
Department of Public Health
Division of Laboratory Services 7NR-:' 1043 16125427 A00 1427
10 Clinton St.
P.O.Box 1689 INFORMATION
Hartford,CT 06144
TELEPHONE:(860)509-8500 132SOUTH- WINDSOR
OHLHOF
1043 FOSTER ST
SOUTH WINDSOR CT
DEP—P.E.R.D. POTABLE WATER
'*
79 ELM ST. 08, ot
L HARTFORD CT 06106 14:
'INAL REPORT
r2—DICHLOROETHANE ND
. yl—DICHLOROETHENE ND
CIS-1 ,2—DICHLOROETHENE ND
ND
. ,2-DICHLOROPROPANE ND
,3—DICHLOROPROPANE ND
r2—DICHLOROPROPANE ND
yl—DICHLOROPROPENE ND
IS-1 ,3—DICHLOROPROPENE ND
RANS-1 ,3—DICHLOROPROPENE ND
THYLBENZENE ND
EXACHLOROBUTADIENE ND
SOPROPYLBENZENE ND
—ISOPROPYLTOLUENE ND
ETHYLENE CHLORIDE ND
ETHYL T—BUTYL ETHER ND
APHTHALENE ND
ROPYLBENZENE ND
TYRENE ND
. , 1 , 1 ,2—TETRACHLOROETHANE ND
" 1 ,2,2—TETRACHLOROETHANE ND
ETRACHLOROETHENE ND
OLUENE ND
. ,2,3-TRICHLOROBENZENE ND
1,2,4—TRICHLOROBENZENE ND
171—TRICHLOROETHANE ND
, 1 ,2—TRICHLORDETHANE ND
RICHLOROETHENE 1 .8
RICHLOROFLUOROMETHANE ND
2,3—TRICHLOROPROPANE ND
,2,4—TRIMETHYLBENZENE ND
. ,3,5-TRIMETHYLBENZENE ND
INYL CHLORIDE ND
two
P,P—XYLENES (TOTAL) ND
NJTE.1 ND = NONE DETECTED
MrTHOD DETECTION LIMIT IS 0.5 UG/L FOR ABOVE
CIMPOUNDS.
------ END OF REPORT
ARM NO.OL-6A REV.10-99