Loading...
HomeMy WebLinkAboutWell Correspondence 00 Deming Street (2) 4 G STATE OF CONNECTICUT DEPARTMENT OF HEALTH SERVICES MEMORANDUM DATE: January 14, 1985 TO: Health Officials Working On EDB Investigations FROM: Paul Ritsick, Principal Sanitary Engineer Water Supplies Section SUBJECT: UPDATE, GRANULAR ACTIVATED CARBON FILTERS FOR EDB REMOVAL On June 4, 1984 you were sent a letter concerning granular activated carbon filters and the treatment of EDB in drinking water. Since that time we have compiled additional data and have discussed filter installations with various contractors and health officials. I wish to update you at this time with respect to filter media, contact time, filter sizes, and installation. Although this update is intended for single family residences it could also serve as a guidance for multi-family dwellings. Should you have any questions please contact this office. Thank you. Filter Media: GAC is still considered to be the most effective means of treating EDB. Virgin material is required. Manufacturers and specifi- cations are listed in the attached table. Contact Time: For EDB levels ranging from .1 ppb to less than 10 ppb a minimum empty bed contact time of 2 minutes is recommended. Example: For a flow rate of 5 gallons per 3minute (.67 cubic feet per Minute) the filter size would be: .67 Ft /Min. x 2 minutes - 1.34 Ft Design would be for a 1.5 Ft unit. Note: Flow restrictors may be installed in conjunction with the size of the filter unit to provide for a desired contact time. Filter Size: A minimum of 1 cubic foot is recommended. *If an installation requires 2 cubic feet, the installation of a single 2 cubic foot unit rather than 2-1 cubic foot units is recommended. This installation is less expensive to install and to maintain (media replace- ment and water quality testing). Both systems, however, will work. Installation: Attached is a schematic showing two installation options. Earlier this year only Option #2 which located the GAC filter before the water storage tank was recommended. New data indicates that Option #1 which locates the GAC unit after the water storage tank is also a viable installation. This b phone: 566-1253 150 Washington Street — Hartford, Connecticut 06106 An Equal Opportunity Employer is of interest since in many locations it may be easier and less expensive to install treatment following Option #1. Regardless of which option is followed the contact time provided is important. Flow restrictors can be installed in consideration of the filter size to ensure adequate contact time. Prefilter: A prefilter is recommended as a means of extending the life of the GAC media. The prefilter may be a cartridge type, media type or micro strainer depending upon the amount of particulate matter (iron or sediment) in the water. If a home already has a filter for iron removal the GAC unit should be installed after (down stream) that filter. PR/ch EDB TREATMENT - SINGLE HOUSEHOLD USE 12/20/8 GRANULAR ACTIVATED CARBON FILTERS Prepared by: hater Supplies Sectio Dept,- of Health Service OPTION #1 - GAC FILTER INSTALLED AFTER THE PRESSURE STORAGE TANK MINIMUM 1 FT3 OF MEDIA PRESSURE L OW STORAGE ` v RESTRICTOR GAC E FILTER TANK FLOW SERVI WELL SAMPLING METER SAMPLING TAP TAP MINIMUM 1 FT3 OF MEDIA OPTION #2 - GAC FILTER INSTALLED BEFORE THE PRESSURE STORAGE TANK FLOW GATE PRESSURE RESTRICTOR VALVE GAC STORAGE SERVI FLOW FILTER TANK METER SAMPLING WELL SAMPLING TAP AP NOTES: 1 . SAMPLING TAP ( 17 ) : TAPS ARE NECESSARY TO SAMPLE WATER BEFORE AND AFTER FILTER IN ORDER TO INSURE EFFECTIVE TREATMENT. 2. PREFILTER: 1T IS RECOMMENDED THAT A PREFILTER BE INSTALLED BEFORE THE GAC UNIT. IT IS USED TO REDUCE PARTICULATE MATTER BUILDUP ON THE GAC UNIT. A MEDIA TYPE PREFILTER REQUIRING BACKWASHING SHOULD NOT BE USED UNLESS THE SEPTIC SYSTEM IS ADEQUATE OR THE HOME IS ON PUBLIC SEWERS. 3. GATE VALVE: A GATE VALVE LOCATED BEFORE THE PRESSURE TANK IS SHOWN IN OPTION #2. THIS WOULD ALLOW WATER FROM THE PRESSURE TANK TO BE USED WHILE THE FILTER UNITS ARE REMOVED OR BEING REPAIRED. 4. FLOW METER: THIS METER SHOULD BE CAPABLE OF MEASURING FLOW (GALLONS PER MINUTE) AND TOTAL GALLONS PUMPED. THE HOMEOWNER USES THIS INFORMATION TO DETERMINE MEDIA REPLACEMENT AND TESTING FREQUENCY. 5. FLOW RESTRICTOR: THIS RESTRICTOR SHOULD BE SIZED IN CONJUNCTION WITH THE SIZE OF THE GAC UNIT TO ENSURE A MINIMUM OF 2 MINUTES CONTACT TIME. SPECIFICATIONS OF SEVERAL COMMERCIALLY AVAILABLE CARBONS Cwgon Cslgon Westvaco: Filbuwb Filtrasorb physipl Properties 300 400 8x10 12x40 Surface Area,m�lg(BET) 950-1050 1000.1200 850 850 Apparent Density.9/cc OAS 0.44 26 25 Density, backwashed &drained,Iblcu ft 30 30 Real Density,glee 2.1 2.1 Particle Density,g/cc 1.3-1.4 1.3-1.4 1.4 1.4 Effective Size 0.8-0.9 0.55-0.65 0.90 0.65 Uniformity Coefficient 1.8 or less 1.9 or less 1_tl 1_6 Pore Volume,ce/g 0. - 0.9 Mean Particle Diameter,mm 1.51.7 0.9-1.1 Specificstions Sieve Sizc j U.S.Std.Serics) _ Larger than No. 8-Max. % 8 _ 2 Larger than No. 12-Max.%v S 2 5 I Smaller than No. 30-Max. % Smaller than No.40-Max.% 5 900 1000 850 850 Iodine No. Abrasion No., minimum 70 5 70 7�� g 8. 7 Ash, , 5 7 7 2 2 2 2 Moisture as packed,Max. % C VENDORS - GRANULAR ACTIVATED CARBON UNITS (WHOLE HOUSE UNITS) d Treatment Company Location Contact Person installSergi Media Disposal R.J.. Black b Son Watertown, CT Fred Black 274-8853 v v Yes Aqua Pump Services Stafford Springs, CT John Wittenzellner v v Possibly 684-5349 Zekes Pump Service Windsor Locks, CT Tom Kaplan v v 623-6843 Culligan Water Conditioning East Hartford, CT Rick Yaconiello v v Possibly 289-4355 Aqua Sentry Manchester, CT Daryl Angeloni v v Yes 643-8429 Bidwell Pump Co. Windsor Locks, CT Ray Antonacci v v Possibly 623-6910 Waterco Industries Exeter, N.H. M.L. Bunker v v Yes 603-778-7046 Environmental Ionics Norwalk, CT Pat Sherry v v Yes 853-3322 Dolphin Water Conditioning Norwich Charles Mulholland v v Yes 887-7385 PR/ch w 5/22/84 STATE OF CONNECTICUT # Thank You for Sharing Your Idea. Please send your ideas to: Employees' Suggestion Awards Program, 165 Capitol Ave., Hartford, 06106. nterdepartment Message SAFE TIME: Handwritten messages are acceptable. -)-201 RED'. 11/81 STATE OF CONNECTICUT Use carbon if you realhv need a copy. If typewrinen, ignore faint tines. Stock No. 6938-051-01 - DATE TITLE 8/6/84 SAW Assistant Director TO Beth Wienstein A KCY AQQR1S preventable Disease Division �l�shington St. - Hartford TITLE TELEPHONE NAME Assistant Director 2264 From Edward C. Parker AGENCY ADDRESS 9 - 122 Washington Street DEP/Haz. Waste Mngt. Section Room SUBJECT Disposal of Activated Carbon Contaminated with/EDB In response to your inquiry to Water Compliance I have attached a copy of the Department's position regarding the disposal of Activated Carbon contaminated with EDB. Should you have any questions, please contact me at 566-2264. Edward C. Parker ECP:et attachment C_ e A VT TI M E: If<onv enient, handwrite rep(- to sender on this same sheet. DISPOSAL OF ACTIVATED CARBON CONTAMINATED WITH EDB To treat water supplies contaminated with EDB, activated carbon filters are being installed in many homes and at several water companies. Activated carbon is a very effective media to remove EDB, however, the activated carbon has a finite capacity. Thus, the activated carbon media must be replaced periodically. The replacement interval is variable depending upon the concentration of EDB; and water consumption. For the individual home owner, the replacement interval is estimated to be every 8 to 10 months. The volume of contaminated activated carbon is 1 ft.3. The activated carbon treatment system is purchased through a vender who will periodically service the treatment system including the replacement of spent carbon with fresh carbon. The vendor who replaces the contaminated activated carbon is therefore responsible for ensuring that the waste carbon is properly disposed of or treated. Since EDB is a listed hazardous waste (40CFR Part 261.33) , it must be managed by the vendor in accordance with Sections 1-48 of Connecticut's Hazardous Waste Management Regulations. Of particular importance is the requirement that EDB must be transported to a licensed hazardous waste treatment, storage or disposal facility. Disposal at municipal landfills is prohibited. For the vendor who services activated carbon units, the waste carbon must be managed in accordance with the following requirements: 1. If the vendor generates less than 1000kg/month or accumulates on-site less than 1000kg, : the vendor is considered to be a small quantity generator. As a small quantity generator, the vendor is required to comply with all the requirements of Part I Section 2 and Part III, Section 9 of Connecticut's Hazardous Waste Management Regulations. 2. If the vendor generates more than 1000kg per month of activated carbon contaminate;: with EDB, or if a vendor generates less than 1000kg per month, but accumulated more than 1000kg on-site, then the vendor is considered to be a generator. A generator is required to comply with all the applicable requirements of Parts II and III of Connecticut's Hazardous Waste Management Regulations. 2 _ 3. If the vendor accumulates on-site 1000kg or more of activated carbon contaminated Z with EDB and stores it for greater than 90 days, then the vendor is considered to be a storage facility. To be a storage facility, the-vendor must obtain a permit and comply with all the requirements of Part II, III, V, VI, and VII of Connecticut's Hazardous Waste Management Regulations. STATE OF CONNECTICUT 00 DEPARTMENT OF HEALTH SERVICES MEMORANDUM DATE: June 4, 1984 j Ctr N TO: Health Officials Working On EDB Investigations FROM: 0. Paul Ritsick, Principal Sanitary Engineer Water Supplies Section SUBJECT: GRANULAR ACTIVATED CARBON FILTERS FOR EDB REMOVAL During the past few months this office has been evaluating the use of granular activated carbon (GAC) filters as an effective means of removing EDB from drinking water. After discussions with officials at EPA, the State of Florida, the University of Connecticut and water treatment companies, the Depart- ment is recommending the use of GAC for the removal of EDB. We are recommending a filter containing a minimum of one cubic foot of GAC media. be used, although there may be instances where larger units or a second GAC filter will be necessary. Attached is a schematic showing the location of the GAC unit(s) relative to the water supply line and the water storage tank. Water sampling taps, flow meter and a prefilter (optional) are also shown as part of the installation. It should also be noted that the installation provides for the treatment of all water used in the home. To make this treatment effective, we are requiring that virgin GAC media be used in all installations; the use of reconditioned GAC media is not acceptable. For your information, a typical one cubic foot unit measures 10 inches in diameter and four feet in height. The Department of Environmental Protection (DEP) is issuing orders to parties believed to be responsible for EDB contamination. These orders require that the polluter provide affected residences with bottled water as a short term solution and also with a new source of water supply or a form of water treatment (including maintenance and monitoring) as a long term solution. Both you and the homeowner should realize, however, that if the homeowner wishes to install a GAC unit prior to an order being implemented, he is doing so at his own expense, since the orderee is under no legal obligation to reimburse affected parties for corrective action those parties have taken by themselves. Should the homeowner wish to proceed, we are recommending that the town conduct a sanitary survey at each well for which GAC treatment is to be installed. As part of the survey we ask that bacteriolo- gical, physical and chemical water samples be collected and analyzed. A review of that water quality will be useful in evaluating the need for a prefilter or disinfection. With respect to testing the GAC units for their effectiveness in removing EDB, the homeowner should be informed that periodic monitoring of the filter is necessary and that it is the homeowner's responsibility to have tests done at a private laboratory. By reading the flow meter over a period of time and testing for the presence of EDB, the homeowner should have a good feel for when the media needs to be replaced. With respect to the disposal of exhausted GAC media, we v Phone: 566-1253 ISO Washington Street — Hartford, Connecticut 06106 An Equal Opportunity Employer prefer to leave that responsibility with the filter installer (see attached vendor list). We will be working with DEP to arrive at a policy relative to the disposal of GAC media containing EDB. The Water Supplies Section will provide you with additional information con- cerning filters and EDB as that information becomes available. Should you have any questions please feel free to contact this office. Thank you. PR/ch Enclosure (2) cc: Peter Galbraith, Director Beth Weinstein, Assistant Director DEP, Water Compliance 'REPARED BY: PAUL RITSICK HOUSEHOLD FILTER SYSTEM FOR EDB REMOVAL WATER SUPPLIES SECT. DEPT. OF HEALTH SERV. STORAGE TANK N1 GAC #2 GAC FILTER FILTER (OPTIONAL GRANULAR rGRANULAR� ACTIVATED IACTIVATE9 CARBON CARBON 1 CUBIC I CUBIC I � FLOW REGULATING VALVE 'OR FOOT FOOT I GATE VALVE WITH FLOW MINIMUM) I RESTRICTOR WATER PIPE I FLOW TOTALIZING METER FROM WELL PRESSURE GAUGE 1 GATE HOUSE I I VALVE USE SAMPLING SAMPLING SAMPLING FAUCET FAUCET FAUCET ( IF #2 FILTER USED) PRE FILTER (OPTIONAL) CARTRIDGE TYPE OR OTHER AS NEEDED NOTES: 1. Prefilter: If water quality warrants this filter would be used to reduce particulate matter buildup on the GAC unit(s). A media type unit requiring backwashing is not shown and should not be installed unless the septic system is adequate or the home is on sewer. 2. Faucets: Faucets are necessary to evaluate water quality before and after filtration. 3. Gate Valves These valves would provide for the removal of filter units or flow meter for repair or maintenance And Bypass: purposes. We do not recommend the installation of filter bypass plumbing. 4. Flow Totalizing Meter: This meter should be capable of measuring flow in terms of gallons per minute and total gallons pumped. Meter readings accompanied with water quality data will provide the homeowner with useful information as to when the GAC filter media or prefilter media would require replacement. 5. Flow Regulating Valve or Flow Restrictor: This device would regulate the flow across the filters and provide for a uniform loading rate. This should be considered for wells with high pumping rdtes so that an adequate contact time can be provided with the GAC media. ay STATE OF CONNECTICUT DEPARTMENT OF HEALTH SERVICES MEMORANDUM DATE: June 4, 1984 TO: Health Officials Working On EDB Investigations FROM: Paul Ritsick, Principal Sanitary Engineer Water Supplies Section SUBJECT: GRANULAR ACTIVATED CARBON FILTERS FOR EDB REMOVAL During the past few months this office has been evaluating the use of granular activated carbon (GAC) filters as an effective means of removing EDB from drinking water. After discussions with officials at EPA, the State of Florida, the University of Connecticut and water treatment companies, the Depart- ment is recommending the use of GAC for the removal of EDB. We are recommending a filter containing a minimum of one cubic foot of GAC media be used, although there may be instances where larger units or a second GAC filter will be necessary. Attached is a schematic showing the location of the GAC unit(s) relative to the water supply line and the water storage tank. Water sampling taps, flow meter and a prefilter (optional) are also shown as part of the installation. It should also be noted that the installation provides for the treatment of all water used in the home. To make this treatment effective, we are requiring that virgin GAC media be used in all installations; the use of reconditioned GAC media is not acceptable. For your information, a typical one cubic foot unit measures 10 inches in diameter and four feet in height. The Department of Environmental Protection (DEP) is issuing orders to parties believed to be responsible for EDB contamination. These orders require that the polluter provide affected residences with bottled water as a short term solution and also with a new source of water supply or a form of water treatment (including maintenance and monitoring) as a long term solution. Both you and the homeowner should realize, however, that if the homeowner wishes to install a GAC unit prior to an order being implemented, he is doing so at his own expense, since the orderee is under no legal obligation to reimburse affected parties for corrective action those parties have taken by themselves. Should the homeowner wish to proceed, we are recommending that the town conduct a sanitary survey at each well for which GAC treatment is to be installed. As part of the survey we ask that bacteriolo- gical, physical and chemical water samples be collected and analyzed. A review of that water quality will be useful in evaluating the need for a prefilter or disinfection. With respect to testing the GAC units for their effectiveness in removing EDB, the homeowner should be informed that periodic monitoring of the filter is necessary and that it is the homeowner's responsibility to have tests done at a private laboratory. By reading the flow meter over a period of time and testing for the presence of EDB, the homeowner should have a good feel for when the media needs to be replaced. With respect to the disposal of exhausted GAC media, we v Phone: 566-1253 150 Washington Street — Hartford, Connecticut 06106 An Equal Opportunity Employer prefer to leave that responsibility with the filter installer (see attached vendor list). We will be working with DEP to arrive at a policy relative to the disposal of GAC media containing EDB. The Water Supplies Section will provide you with additional information con- cerning filters and EDB as that information becomes available. Should you have any questions please feel free to contact this office. Thank you. PR/ch Enclosure (2) cc: Peter Galbraith, Director Beth Weinstein, Assistant Director DEP, Water Compliance 'REPARED BY: PAUL RITSICK HOUSEHOLD FILTER SYSTEM FOR EDB REMOVAL WATER SUPPLIES SECT. DEPT. OF HEALTH SERV. STORAGE TANK N1 GAC #2 GAC FILTER FILTER (OPTIONAL GRANULAR GRANULAR' ACTIVATED IACTIVATE9 CARBON CARBON 1 CUBIC 1 CUBIC I ( FLOW REGULATING VALVE OR FOOT FOOT I GATE VALVE WITH FLOW MINIMUM) RESTRICTOR WATER PIPE I FLOW TOTALIZING METER FROM WELL PRESSURE GAUGE I GATE HOUSE I 1 VALVE USE SAMPLING SAMPLING SAMPLING FAUCET FAUCET FAUCET ( IF #2 FILTER USED) PRE FILTER (OPTIONAL) CARTRIDGE TYPE OR OTHER AS NEEDED NOTES: 1. Prefilter: If water quality warrants this filter would be used to reduce particulate matter buildup on the GAC unit(s). A media type unit requiring backwashing is not shown and should not be installed unless the septic system is adequate or the home is on sewer. 2. Faucets: Faucets are necessary to evaluate water quality before and after filtration. 3. Gate Valves These valves would provide for the removal of filter units or flow meter for repair or maintenance And Bypass: purposes. We do not recommend the installation of filter bypass plumbing. 4. Flow Totalizing Meter: This meter should be capable of measuring flow in terms of gallons per minute and total gallons pumped. Meter readings accompanied with water quality data will provide the homeowner with useful information as to when the GAC filter media or prefilter media would require replacement. 5. Flow Regulating Valve or Flow Restrictor: This device would regulate the flow across the filters and provide for a uniform loading rate. This should be considered for wells with high pumping rdtes so that an adequate contact time can be provided with the GAC media. VENDORS - GRANULAR ACTIVATED CARBON UNITS (WHOLE HOUSE UNITS) Treatment Company Location Contact Person Install Service Media Disposal R.J. Black & Son Watertown, CT Fred Black 274-8853 v v Yes Aqua Pump Services Stafford Springs, CT John Wittenzellner v v Possibly 684-5349 Zekes Pump Service Windsor Locks, CT Tom Kaplan v v 623-6843 Culligan Water Conditioning East Hartford, CT Rick Yaconiello v v Possibly 289-4355 Aqua Sentry Manchester, CT Daryl Angeloni v v Yes 643-8429 Bidwell Pump Co. Windsor Locks, CT Ray Antonacci v v Possibly 623-6910 Waterco Industries Exeter, N.H. M.L. Bunker v v Yes 603-778-7046 Environmental Ionics Norwalk, CT Pat Sherry v v Yes 853-3322 Dolphin Water Conditioning Norwich Charles Mulholland v v Yes 887-7385 PR/ch w 5/22/84 STATE OF CONNECTICUT DEPARTMENT OF HEALTH SERVICES MEMORANDUM DATE: June 4, 1984 TO: Health Officials Working On EDB Investigations FROM: K. Paul Ritsick, Principal Sanitary Engineer Water Supplies Section SUBJECT: GRANULAR ACTIVATED CARBON FILTERS FOR EDB REMOVAL During the past few months this office has been evaluating the use of granular activated carbon (GAC) filters as an effective means of removing EDB from drinking water. After discussions with officials at EPA, the State of Florida, the University of Connecticut and water treatment companies, the Depart- ment is recommending the use of GAC for the removal of EDB. We are recommending a filter containing a minimum of one cubic foot of GAC media be used, although there may be instances where larger units or a second GAC filter will be necessary. Attached is a schematic showing the location of the GAC unit(s) relative to the water supply line and the water storage tank. Water sampling taps, flow meter and a prefilter (optional) are also shown as part of the installation. It should also be noted that the installation provides for the treatment of all water used in the home. To make this treatment effective, we are requiring that virgin GAC media be used in all installations; the use of reconditioned GAC media is not acceptable. For your information, a typical one cubic foot unit measures 10 inches in diameter and four feet in height. The Department of Environmental Protection (DEP) is issuing orders to parties believed to be responsible for EDB contamination. These orders require that the polluter provide affected residences with bottled water as a short term solution and also with a new source of water supply or a form of water treatment (including maintenance and monitoring) as a long term solution. Both you and the homeowner should realize, however, that if the homeowner wishes to install a GAC unit prior to an order being implemented, he is doing so at his own expense, since the orderee is under no legal obligation to reimburse affected parties for corrective action those parties have taken by themselves. Should the homeowner wish to proceed, we are recommending that the town conduct a sanitary survey at each well for which GAC treatment is to be installed. As part of the survey we ask that bacteriolo- gical, physical and chemical water samples be collected and analyzed. A review of that water quality will be useful in evaluating the need for a prefilter or disinfection. With respect to testing the GAC units for their effectiveness in removing EDB, the homeowner should be informed that periodic monitoring of the filter is necessary and that it is the homeowner's responsibility to have tests done at a private laboratory. By reading the flow meter over a period of time and testing for the presence of EDB, the homeowner should have a good feel for when the media needs to be repladed. With respect to the disposal of exhausted GAC media, we v Phone: 566-1253 150 Washington Street — Hartford, Connecticut 06106 An Equal Opportunity Employer prefer to leave that responsibility with the filter installer (see attached vendor list). We will be working with DEP to arrive at a policy relative to the disposal of GAC media containing EDB. The Water Supplies Section will provide you with additional information con- cerning filters and EDB as that information becomes available. Should you have any questions please feel free to contact this office. Thank you. PR/ch Enclosure (2) cc: Peter Galbraith, Director Beth Weinstein, Assistant-Director DEP, Water Compliance (EPARED BY: PAUL RITSICK HOUSEHOLD FILTER SYSTEM FOR EDB REMOVAL WATER SUPPLIES SECT. STORAGE TANK DEPT. OF HEALTH SERV. //1 GAC N2 GAC FILTER FILTER (OPTIONAL RANULAR GRANULAR ACTIVATED IACTIVATE9 CARBON CARBON 1 CUBIC 1 CUBIC I � � FLOW REGULATING VALVE OR FOOT FOOT GATE VALVE WITH FLOW MINIMUM) RESTRICTOR 1 WATER PIPE � FLOW TOTALIZING METER PRESSURE FROM WELL ?- GAUGE war GATE HOUSE I 1 VALVE USE SAMPLING SAMPLING SAMPLING FAUCET FAUCET FAUCET ( IF #2 FILTER USED) U PRE FILTER (OPTIONAL) CARTRIDGE TYPE OR OTHER AS NEEDED NOTES: 1. Prefilter: If water quality warrants this filter would be used to reduce particulate matter buildup on the GAC unit(s) . A media type unit requiring backwashing is not shown and should not be installed unless the septic system is adequate or the home is on sewer. 2. Faucets: Faucets are necessary to evaluate water quality before and after filtration. 3. Gate Valves These valves would provide for the removal of filter units or flow meter for repair or maintenance And Bypass: purposes. We do not recommend the installation of filter bypass plumbing. 4. Flow Totalizing Meter: This meter should be capable of measuring flow in terms of gallons per minute and total gallons pumped. Meter readings accompanied with water quality data will provide the homeowner with useful information as to when the GAC filter media or prefilter media would require replacement. S. Flow Regulating Valve or Flow Restrictor: This device would regulate the flow across the filters and provide for a uniform loading rate. This should be considered for wells with high pumping rates so that an adequate contact time can be provided with the GAC media. ... .. ... ... .. ... .. .. . . .... VENDORS - GRANULAR ACTIVATED CARBON UNITS (WHOLE HOUSE UNITS) Treatment Company Location Contact Person Install Service Media Disposal K.J. Black & Son Watertown, CT Fred Black 274-8853 v v Yes Aqua Pump Services Stafford Springs, CT John Wittenzellner v v Possibly 684-5349 Zekes Pump Service Windsor Locks, CT Tom Kaplan v v 623-6843 Culligan Water Conditioning East Hartford, CT Rick Yaconiello v v Possibly 289-4355 Aqua Sentry Manchester, CT Daryl Angeloni v v Yes 643-8429 Bidwell Pump Co. Windsor Locks, CT Ray Antonacci v v Possibly 623-6910 Waterco Industries Exeter, N.H. M.L. Bunker v v Yes 603-778-7046 Environmental Ionics Norwalk, CT Pat Sherry v v Yes 853-3322 Dolphin Water Conditioning Norwich Charles Mulholland v v Yes 887-7385 PR/ch w 5/22/84 b STATE OF CONNECTICUT DEPARTMENT OF HEALTH SERVICES MEMORANDUM DATE: June 4, 1984 TO: Health Officials Working On EDB Investigations FROM: � Paul Ritsick, Principal Sanitary Engineer Water Supplies Section SUBJECT: GRANULAR ACTIVATED CARBON FILTERS FOR EDB REMOVAL During the past few months this office has been evaluating the use of granular activated carbon (GAC) filters as an effective means of removing EDB from drinking water. After discussions with officials at EPA, the State of Florida, the University of Connecticut and water treatment companies, the Depart- ment is recommending the use of GAC for the removal of EDB. We are recommending a filter containing a minimum of one cubic foot of GAC media be used, although there may be instances where larger units or a second GAC filter will be necessary. Attached is a schematic showing the location of the GAC unit(s) relative to the water supply line and the water storage tank. Water sampling taps, flow meter and a prefilter (optional) are also shown as part of the installation. It should also - - be noted that the installation provides for the treatment of all water used in the home. To make this treatment effective, we are requiring that virgin GAC media be used in all installations; the use of reconditioned GAC media is not acceptable. For your information, a typical one cubic foot unit measures 10 inches in diameter and four feet in height. The Department of Environmental Protection (DEP) is issuing orders to parties believed to be responsible for EDB contamination. These orders require that the polluter provide affected residences with bottled water as a short term solution and also with a new source of water supply or a form of water treatment (including maintenance and monitoring) as a long term solution. Both you and the homeowner should realize, however, that if the homeowner wishes to install a GAC unit prior to an order being implemented, he is doing so at his own expense, since the orderee is under no legal obligation to reimburse affected parties for corrective action those parties have taken by themselves. Should the homeowner wish to proceed, we are recommending that the town conduct a sanitary survey at each well for which GAC treatment is to be installed. As part of the survey we ask that bacteriolo- gical, physical and chemical water samples be collected and analyzed. A review of that water quality will be useful in evaluating the need for a prefilter or disinfection. With respect to testing the GAC units for their effectiveness in removing EDB, the homeowner should be informed that periodic monitoring of the filter is necessary and that it is the homeowner's responsibility to have tests done at a private laboratory. By reading the flow meter over a period of time and testing for the presence of EDB, the homeowner should have a good feel for when the media needs to be replaced. With respect to the disposal of exhausted GAC media, we v phone: 566-1253 ISO Washington Street — Hartford, Connecticut 06106 An Equal Opportunity Employer prefer to leave that responsibility with the filter installer (see attached vendor list) .• We will be working with DEP to arrive at a policy relative to the disposal of GAC media containing EDB. The Water Supplies Section will ,provide you with additional information con- cerning filters and EDB as that 'information becomes available. Should you have any questions please feel free to contact this office. Thank you. PR/ch Enclosure (2) cc: Peter Galbraith, Director Beth Weinstein, Assistant Director DEP, Water Compliance REPARED BY: PAUL RITSICK HOUSEHOLD FILTER SYSTEM FOR EDO REMOVAL WATER SUPPLIES SECT. STORAGE TANK DEPT. OF HEALTH SERV. #1 GAC N2 GAC FILTER FILTER (OPTIONAL GRANULAR GRANULAR ACTIVATED IACTIVATE4 CARBON CARBON 1 CUBIC ( 1 CUBIC � FLOW REGULATING VALVE OR FOOT FOOT II GATE VALVE WITH FLOW MINIMUM) RESTRICTOR i WATER PIPE � FLOW TOTALIZING METER FROM WELL PRESSURE GAUGE GATE HOUSE I VALVE USE SAMPLING SAMPLING SAMPLING FAUCET FAUCET FAUCET ( IF N2 FILTER USED) U PRE FILTER (OPTIONAL) CARTRIDGE TYPE OR OTHER AS NEEDED NOTES: 1. Prefilter: If water quality warrants this filter would be used to reduce particulate matter buildup on the GAC unit(s). A media type unit requiring backwashing is not shown and should not be installed unless the septic system is adequate or the home is on sewer. 2. Faucets: Faucets are necessary to evaluate water quality before and after filtration. 3. Gate Valves These valves would provide for the removal of filter units or flow meter for repair or maintenance And Bypass: purposes. We do not recommend the installation of filter bypass plumbing. 4. Flow Totalizing Meter: This meter should be capable of measuring flow in terms of gallons per minute and total gallons pumped. Meter readings accompanied with water quality data will provide the homeowner with useful information as to when the GAC filter media or prefilter media would require replacement. S. Flow Regulating Valve or Flow Restrictor: This device would regulate the flow across the filters and provide for a uniform loading rate. This should be considered for wells with high pumping rapes so that an adequate contact time can be provided with the GAC media. t VENDORS - GRANULAR ACTIVATED CARBON UNITS (WHOLE HOUSE UNITS) r Treatment Company Location Contact Person Install Service Media Disposal R.J. Black & Son Watertown, CT Fred Black 274-8853 v v Yes Aqua Pump Services Stafford Springs, CT John Wittenzellner v v Possibly 684-5349 Zekes Pump Service Windsor Locks, CT Tom Kaplan v v 623-6843 Culligan Water Conditioning East Hartford, CT Rick Yaconiello v v Possibly 289-4355 Aqua Sentry Manchester, CT Daryl Angeloni v v Yes 643-8429 Bidwell Pump Co. Windsor Locks, CT Ray Antonacci v v Possibly 623-6910 Waterco Industries Exeter, N.H. M.L. Bunker v v Yes 603-778-7046 Environmental Ionics Norwalk, CT Pat Sherry v v Yes 853-3322 Dolphin Water Conditioning Norwich Charles Mulholland v v Yes 887-7385 PR/ch w 5/22/84