May 29, 1997
Jeff and Mary Mattis
4 fen Ct.
Wallingford, Ct. 06492
Dear Jeff and Mary,
We have the fallowing to report on the samples submitted to
this laboratory on May 21 , 1997.
Sample Number: 38103
Mark: water sample collected 5/20/97 by Tony Rinaldi from
Lot No. 848, Stron Rd. , South Windsor, Ct.
Results, mg/L MCL, mg/L
Odor 0 no MCL
Turbidity 350 no MCL
Color > 100 no MCL
Turbidity-treated 0 no MCL.
Color -treated 0 no MCL
PH 7.73 no MCL
Nitrite Nitrogen < 0.001 1 .0
Nitrate Nitrogen < 1 .00 10.0
Chloride (as Cl ) i8 250
Hardness (as CaCO3) 160 no MCL
Iron (as Fe) 5.85 no MCL
Mangenese 0.115 no MCL
Sodium 1€3 no MCL
Sulfate 67.5 no MCL
VOC' BDL see next pages
BACTERIOLOGICAL EXAMINATION
Number- of Co 1 iform Bacteria
per 100 mLs (membrane filter ) O O
All parameters analyzed are below Maximum Contamination
Levels (MCL) for potable water. However the turbidity,
color- , iron and mangenese contents .are extremely high.
Levels this high will cause staining. We recommond that only
treated water be used for drinking. If there are any
questions we would be pleased to discuss them with you.
Very truly yours,
Envir h Laboratory
Ma,rye UiLuzio
PH0464, PHO514
w
PHYSICAL PARAMETERS
ODOR; MCL = 2 - Scale O = none, l = very faint, 2 = faint
3 = distinct,_ 4 = decided, 5 = strong. Good well
water should be free of odor.
TURBIDITY; MCL 5 - A measure of particles in the water, '
usually an indication of the presence of iron.
pH; MCL 6.4 - 10.0 - pH ranges from 0 - 14. A pH of 7 is
neurtal, C 7 is acidic, > 7 is basic. A pH less than
6.4 is considered acidic and may be corrosive to
piping.
COLOR; MCL 15 - High color usually indicates the presence
of iron.
INORGANIC PARAMETERS
NIRITE NITROGEN; MCL 1.0 mg/L - An intermediate breakdown
product of organic matter. See nitrate comment.
NITRATE NITROGEN; MCL 10.0 mg/L - The final completely
oxidized stage of nitrogen. Levels •above 10 are known
to be harmful to infants. Pregnant/nursing mothers
and parents of infants should consult with a physican.
CHLORIDE; MCL 250 mg/L - The non-metallic portion of common
salt. Levels above 50 mg/L may indicate undesirably
high sodium levels and it also may appreciably
increase corrosion rates. Levels above 250 mg/L inpart
a salty taste noticeable to most people.
HARDNESS; MCL none - A measure of the total calcium and
magnesium in water. Waters over 100 mg/L are described
as hard and levels over 250 mg/L are considered very
hard. The effect of hardness is to increase the amount
of soap necessary to form suds with water. High levels
may also increase scaling on the inside of water pipes.
IRON; MCL none - Above 0.3 mg/L iron may cause staining to
laundry and fixtures. Iron is naturally occurring
water mineral due to the geology of the area.
MANGENESE; MCL none - Above 0.05 mg/L mangense may cause
staining to laundry and fixtures. See iron comment
SULFATE; MCL none - A naturally occuring substance in
water, levels above 250 mg/L may inpart a bitter taste
and render a laxative effect.
SODIUM; MCL none - A notification level of 28 mg/L has been
established for people on low salt diets, high levels
may increase the corrosive effect.
ORGANIC CHEMICALS
VOLATILE ORGANIC CHEMICALS (VOC) - see report for a listing
of the individual chemical MCL. VOC's are a gas chro-
matographic scan of 58 compounds. This list was de-
termined by the Conneticut State Department of Health.
These compounds include some of the more commonly found
ground water contaminates.
ENVIROTECA LABORATORY
TESTING & CONSULTING
77 COOK HILL ROAD • WINDSOR, CONNECTICUT 06095
MARYELLEN DiLUZ10 TELEPHONE
(203) 688-7249
4ti ( t.
De at' Ja?f it aid " a:-Y�
1� halve th-p -Fol 4"wiful to Y°f pof-1, 1•!1 the 4a'ampjf—s aw.A.ml, w tf.4 + t.`,
Lh i rm Pier 21 )r9f .
Simp II o futimb ov t M3 1 t2 }
f1 ,4v- 2 watwv ca slu- S/20/97 by 1olvt ' fUnald st�kn
No. U48 o :I-1 v ov i R41- 9, f4oiLl Ut 44 j ktlsr:,e C t;
ORGAINIC CHEMICALS BY EPA 502.2
Results NCL
MDL in ug/L in ug/L
Benzene 0.5 BDL 5
Bromobenzene 0.5 BDL
Bromomethane 0.5 BDL
n-Butylbenzene 0.5 BDL
Carbon Tetrachloride 0.5 BDL 5
Chlorobenzene 0.5 BDL 100
Chloroethane 0.5 BDL
Chloromethane 0.5 BDL
2-Chlorotoluene 0.5 BDL �
4-Chlorotoiuene 0.5 BDL
Dibromomethane 0.5 BDL
1 ,2-Dichlorobenzene 0.5 BDL 600
1 ,3-Dichlorobenzene 0.5 BDL iE
1,44-1)ichlorobenzene 0.5 BDL 75
1 ,1-Dichloroethane 0.5 BDL �
1 ,2-Dichloroethane (EDC) 0.5 BDL 5
1 ,1-Dichloroethylene 0.5 BDL 7
cis-1 ,2-Dichloroethylene 0.5 BDL 70
Trans-1 ,2-Dichloroethylene 0.5 BDL 100
1,2-Dichloropropane 0.5 BDL 5
1 ,3-Dichloropropane 0.5 BDL �€
2,2-Dichloropropane 0.5 BDL
1 , 1-Dichloropropylene 0.5 - BDL �
cis-1 ,3-Dichloropropylene 0.5 BDL �
trans-1 ,3-Dichloropropylene 0.5 BDL
Ethylbenzene 0.5 BDL 700
Methylene Chloride 0.5 BDL 5
EPA Method 502.2 Results MCL
MDL in ug/L in ug/L
MethylTertButylEther (MTBE) 2.0 BDL
Naphthalene 0.5 BDL
n-Propylbenzene 0.5 BDL
Styrene 0.5 BDL 110
1,1 , 1,2-Tetrachloroethane 0.5 BDL
1 , 1 ,2,2-Tetrachloroethane 0.5 BDL
Tetrachloroethylene 0.5 BDL 5
Toluene 0.5 BDL 1000
Total Trihalomethanes (TTHM) BDL 100
Bromodichloromethane 0.5 BDL
Bromoform 0.5 BDL
Chlorodibromomethane 0.5 BDL
Chloroform 0.5 BDL
1,2,4-Trichlorobenzene 0.5 BDL 5
1, 1 , 1-Trichloroethane 0.5 BDL 200
1, 1 ,2-Trichloroethane 0.5 BDL 5
Trichloroethylene 0.5 BDL 5
1,2,3-Trichloropropane 0.5 BDL
112,4-Trimethylbenzene 0.5 BDL
1,3,5-Trimethylbenzene 0.5 BDL
Vinyl Chloride 0.5 BDL 2
Xylenes (total ) 10000
o-Xylene 0.5 BDL
p/m Xylene 0.5 BDL
MDL = minimum detectable level BDL = below MDL
MCL = maximum contaminant level * = no MCL established
= MCL is for the combined four TTHWs
= MCL is for the combined three Xylene
If there are any questions we would be pleased to discuss
them with you.
Very truly yours,
E4§ii s h Laboratory
Maryellen DiLuzio
cc: one enclosed
PH-0464 & PH-0547