Loading...
HomeMy WebLinkAboutWell Inspection 21 Saginaw Street Columbia Environmental Laboratory Drinking Water Analysis - Formaldehyde Testing National Property Inspection STATE OF CONNECTICUT 115 New London Turnpike CE DEPARTMENT OF HEALTH Glastonbury, CT 06033 CERTIFICATION NUMBER PH-0514 May 12, 1995 RE: Lab No. 950547, Inv. No. 95542 SAMPLING LOCATION: 21 Saginow, South Windsor, Connecticut SAMPLING/DELIVERY TIMES: Client Sampled 1800 5/8/95 1025 5/9/95 STANDARD WATER ANALYSIS STATE OF CONNECTICUT TEST RESULTS RECOMMENDED/MAXIMUM LEVELS RECOMMENDED pH UNITS 6.1 6.5-9.0 RANGE COLOR UNITS 15 RECOMMENDED <5 MAXIMUM ODOR 0-5 0(none) 3 MAXIMUMRECONDED TURBIDITY NTU 04 5 REACOIMMENDED UM ALKALINITY mg/L 35 NO RECOMMENDED LEVEL CHLORIDE mg/L 27 250 MAXIMUM ALLOWABLE HARDNESS mg/L 76 0-60 soft, 61-120 mod. hard 121-180 hard, >181 v. hard AMMONIA AS N mg/L <.05 .050 RECOMMENDED MAXIMUM NITRITE AS N mg/L <.005 1.0 MAXIMUM ALLOWABLE NITRATE AS N mg/L 3.8 10.0 MAXIMUM ALLOWABLE DETERGENTS mg/L <0 5 0.5 MAXIMUM ALLOWABLE IRON mg/L <0.10 0.3 RECOMMENDED MAXIMUM MANGANESE mg/L <.05 .050 RECOMMENDED MAXIMUM SODIUM mg/L 17 28 RECOMMENDED MAXIMUM COLIFORM BACTERIA 0/100 ml 0/100 ml MAXIMUM ALLOWABLE 1,2-Dibromoethane(EDB) ug/L <.05 .05 Max. Allow. Vorlox ug/L <0.10 Not Established For the parameters analyzed, this is a satisfactory potable drinking water supply. It may be objectionable due to the low pH/alkalinity, which may cause corrosion to plumbing fixtures. Treatment for neutralization may be warranted at this pH. A low pH is NOT a basis for the rejection of a drinking water supply. If you have any questions, please feel free to call. Very truly gun, 90�h�nc Burrell 2 Lakeview Park West . Columbia, CT 06237 9 Telephone: (203) 228-0329