HomeMy WebLinkAboutWell Inspection 21 Saginaw Street Columbia Environmental Laboratory
Drinking Water Analysis - Formaldehyde Testing
National Property Inspection STATE OF CONNECTICUT
115 New London Turnpike CE DEPARTMENT OF HEALTH
Glastonbury, CT 06033 CERTIFICATION NUMBER
PH-0514
May 12, 1995
RE: Lab No. 950547, Inv. No. 95542
SAMPLING LOCATION: 21 Saginow, South Windsor, Connecticut
SAMPLING/DELIVERY TIMES: Client Sampled 1800 5/8/95 1025 5/9/95
STANDARD WATER ANALYSIS STATE OF CONNECTICUT
TEST RESULTS RECOMMENDED/MAXIMUM LEVELS
RECOMMENDED
pH UNITS 6.1 6.5-9.0 RANGE
COLOR UNITS 15 RECOMMENDED
<5 MAXIMUM
ODOR 0-5 0(none) 3 MAXIMUMRECONDED
TURBIDITY NTU 04 5 REACOIMMENDED
UM
ALKALINITY mg/L 35 NO RECOMMENDED LEVEL
CHLORIDE mg/L 27 250 MAXIMUM
ALLOWABLE
HARDNESS mg/L 76 0-60 soft, 61-120 mod. hard
121-180 hard, >181 v. hard
AMMONIA AS N mg/L <.05 .050 RECOMMENDED
MAXIMUM
NITRITE AS N mg/L <.005 1.0 MAXIMUM
ALLOWABLE
NITRATE AS N mg/L 3.8 10.0 MAXIMUM
ALLOWABLE
DETERGENTS mg/L <0 5 0.5 MAXIMUM
ALLOWABLE
IRON mg/L <0.10 0.3 RECOMMENDED
MAXIMUM
MANGANESE mg/L <.05 .050 RECOMMENDED
MAXIMUM
SODIUM mg/L 17 28 RECOMMENDED
MAXIMUM
COLIFORM BACTERIA 0/100 ml 0/100 ml MAXIMUM
ALLOWABLE
1,2-Dibromoethane(EDB) ug/L <.05 .05 Max. Allow.
Vorlox ug/L <0.10 Not Established
For the parameters analyzed, this is a satisfactory potable drinking water supply. It may be objectionable due to
the low pH/alkalinity, which may cause corrosion to plumbing fixtures. Treatment for neutralization may be
warranted at this pH. A low pH is NOT a basis for the rejection of a drinking water supply.
If you have any questions, please feel free to call. Very truly gun,
90�h�nc Burrell
2 Lakeview Park West . Columbia, CT 06237 9 Telephone: (203) 228-0329