Well Correspondence 369 Oakland Road
l quatek Labs 131 Bradley Road-Woodbridge, CT 06525 Water Analysis Report WATER SOURCE: 369 OAKLAND ROAD - SOUTH WINDSOR, CT NO TREATMENT, TANK TAP TO: SHAWS PUMP COMPANY DATE: 04/03/2008 20 LYONS STREET TEST# : D0403810 ELLINGTON, CT 06029 BACTERIOLOGICAL EXAMINATION Total Coliforms Present Absent X Fecal Coliforms Present Absent X RESULT AL UNITS PHYSICAL/CHEMICAL EXAMINATION * Turbidity 10 5 . 0 NTU * Color 25 15 --- Odor N.D. 2 --- pH 6 . 5 10 . 0 - 6 . 4 --- Calcium 29 . 6 None mg/L Magnesium 7 . 2 None mg/L Hardness - 103 . 5 200 mg/L Nitrate Nitrogen 2 . 7 10 . 0** mg/L Nitrite Nitrogen N.D. 1 . 00** mg/L Sulfate 12 . 2 250 . 0 mg/L Sodium 22 . 1 28 . 0 mg/L Chloride 55 . 4 250 . 0 mg/L Copper 0 . 22 1 . 30** mg/L * Iron 2 . 18 0 . 30 mg/L Manganese N.D. 0 . 05 mg/L CONCLUSIONS : Based on the above results, this water was safe for drinking purposes at the time the sample was collected. Sampled By: Michael Bessette under the direction of Aquatek Labs . AL = Advisory Level = EPA Maximum Contaminant Level (MCL) or State enforceable standard when value followed by ** . N.D. = None Detected * = exceeds AL, see attached sheet = below AL, see attached sheet David M. Graham, Ph.D. Laboratory Director CT License #PH-0466 Woodbridge ■ Old Saybrook 0 Glastonbury