HomeMy WebLinkAbout100 Arnold Way (67) l Connecticut Engineers in Private Practice Structural Engin rs Coalition Statement of Special Inspections Project: Timothy Edwards Middle School (TEMS) Location: South Windsor, CT 06074 Owner: Town of South Windsor Own is Address: 1540 Sullivan Avenue South Windsor, CT 06074 Architect of Record: The S/UA/M Collaborative Structural Engineer of Record: The S/UA/M Collaborative This Statement of Special Inspections is submitted as a condition for permit issuance in accordance with the special inspection requirements of the BOCA National Building Code. It includes a Schedul of Sp cial Inspections applicable to this project as well as the name of the Special Inspector, and th id ntity of other approved agencies intended to be retained for conducting these inspections. The Special Inspector shall keep records of all inspections, and shall furnish inspection reports to the code official and to the structural engineer and architect of record. If such discrepancies are not corrected, the discrepancies shall be brought to the attention of the code official and the structural engineer and architect of record. The special inspection program does not relieve the contractor of his or her responsibilities. Interim reports shall be submitted to the code official, owner, structural engineer and architect of record. A schedule of interim reports shall be approved by the Code Official prior to permit issuance. A final report of inspections documenting completion of all required special inspections and correction of any discrepancies noted in the inspections shall be submitted prior to the issuance of a certificate of use and occupancy. Interim Report Frequency: monthly or O per attached schedul Prepared by Design Professional: •�.G 'G MORN Hamid Adib. P.E.. Ph.D. •��c°°� ,.L� �e$ (type or print name) ~��` v - <No. 14601 o�°° 4- Signature Date9 �FS:�En�s�v � @ S'/ON AL ENft �ra�mna�' Own s Authori io IBuilding Officialce t nce:c 1 ignature Date ure Date CEPP/SEC Form 101 •Statement of Special Inspections•©CEPP/SEC 1993 Connecticut Engineers in Private Practic Sheet-2_of 7 Structural Engineers Coalition Project: TEMS Schedule of Special Inspection Services The following sheets comprise the required schedule of special inspections for this specific project. The construction divisions which require special inspections for this project are as follows: ® Soils and Foundations ® Cast-in-Place Concrete ❑ Precast Concrete ® Masonry ® Structural Steel ❑ Wood ❑ Special Cases Inspection Agents Firm Address 1. Special Inspector The S/UA/M Collaborative 281 Farmington Avenue Farmington, CT 06032 2. Testing Laboratory Independent Materials Testing 57 N. Washington Street Laboratories, Inc. P.O. Box 745 Plainville, CT 06062 3. Testing Laboratory 4. Other Jan M. Reczek, Ph.D., P.E. 250 Briarwood Drive Geotechnical Engineer Recon Engineers Guilford, CT 06437 (203)458-9216 (203)458-2819 Fax Note: The qualifications of all personnel performing Special Inspection activities are subject to the approval of the Building Official. CEPP/SEC Form 101 •Statement of Special Inspections 9©CEPP/SEC 1993 c Schedul f Sp cial Insp cti n S rvices Sheet-1-of 2— Construction Division-Soils and Foundations Project: TEMS Item Agent Scope No. 1. Shallow Foundations4nsitu 4 Verify suitability of subgrade prior to start of backfilling operations,within the building footprint. Verify capacity of bearing stratum prior to placement of footings. 2. Controlled Structural Fill 2 For each subgrade,fill and backfill material. Perform one moisture-density relationship test for each 1,500 cubic yards of material or fraction thereof. Inplace Density Tests: One test per lift for every 1,500 SF. Minimum of 3 tests per lift Two tests per lift for backfilling of walls and trenches. 3. Deep Foundations N/A 4. Other N/A CEPP/SEC Form 101 9 Statement of Special Inspections 9 CCEPP/SEC 1993 Schedule f Sp cial Inspects In Services Sheet-A--of 7 Construction Division -Cast-In-Place Concrete Project: TEMS Item Agent Scope No. 1. Mix Design 1 Review concrete mix designs for footings, piers, walls, foundations, supported slabs, and slabs on grade for conformance with spec. requirements. 2. Material Certification 1 Review mill certificates for conformance with spec. requirements. 3. Reinforcement Installation 1 Inspect all reinforcing steel for conformance with requirements. 4. Post-Tensioning Operations NA 5. Batching Plant 1 Review batching operations prior to start of project and once a month during the concreting operations for this project. 6 Formwork Geometry 1 Review for conformance. 7. Concrete Placement 2 Verify conformance with slump, air content and temperature requirements for each strength test and as required to assure conformance. 8. Evaluation of Concrete 2 One set of cylinders per 50 cubic yards or portion thereof. Strength One set of cylinders per 3,500 SF of floor or wall area or portion thereof. 9. Curing and Protection 1 Verify conformance of curing and protection requirements for all concrete. 10. Other CEPP/SEC Form 101 •Statement of Special Inspections •CCEPP/SEC 1993 Sch dul f Sp cial Inspecti n S rvic s Sheet—5_of Z Construction Division -Masonry Project: TEMS It m Agent Scope No. 1. Material Certification 1 Verify conformance of all block, rein., and grout/mortar with approved materials. 2. Mixing of Mortar and Grout 1 *Verify conformance with spec. requirements. 3. Installation of Masonry 1 *Verify conformance of laying and mortaring procedures with spec. requirements. 4. Reinforcement Installation 1 *Verify conformance of grade, size, type, spacing, and placement of ties, rein., anchors, and insert with spec. requirements. 5. Grouting Operations 1 *Verify conformance with low-lift grouting procedures. 6 Weather Protection 1 *Verify conformance with spec. requirements. 7. Evaluation of Masonry 2 Grouted and ungrouted prism tests for each 5,000 SF of Strength each wall type. Three cube tests for each 30 yards grout or fraction thereof for each type of grout being placed each day. B. Other NA • Indicates that item is to be performed on a full time basis at the onset of the work and will be adjusted by the Engine r of R cord in writing after a review of the quality and consistency of th completed work. CEPP/SEC Form 101 9 Statem nt of Special Inspections*QCEPP/SEC 1993 Schedul of Special Inspection Services Sheet--6__of 7 Construction Division-Structural Steel Project: TEMS Item Agent Scope No. 1. Fabricator Certification/ 1 Review quality control procedures and AISC certifications. Quality Control Procedures 2. Material Certification 1 Review mill certificates and bolts for conformance. 3. Open Web Steel Joists 2 Field inspection of erection, bridging and field connections for all joist. 4. Bolting 2 Comply with testing and verification procedures per AISC for all field bolts. 5. Welding 2 Field Fillet Welds- 100%visual, 25% magnetic particle; 15%witness Shop Fillet Welds 100%visual, 25% magnetic particle: 15%witness Full Penetration - 100% ultrasonic 6 Shear Connectors 2 Inspect and test all field shear connectors. 7. Structural Details 2 Verify column plumbness and conformance of erected steel. 8. Other 2 Visually inspect approximately 10%of welds to steel supports. Metal Deck CEPP/SEC Form 101 •Statement of Special Inspections•©CEPP/SEC 1993 CONNECTICUT ENGINEERS IN PRIVATE PRACTICE Sh t 7 of L STRUCTURAL ENGINEERS COALITION FINAL REPORT OF SPECIAL INSPECTIONS PROJECT: Timothy Edwards Middle School (TEMS) LOCATION: South Windsor, CT 06074 PERMIT APPLICANT: Town of South Windsor APPLICANT'S ADDRESS: 1540 Sullivan Avenue, South Windsor, CT 06074 ARCHITECT OF RECORD: The S/L/A/M Collaborative STRUCTURAL ENGINEER OF RECORD: The S/L/A/M Collaborative To the best of my information, knowledge, and belief,the special inspections required for this proj ct, and itemized in the statement of special inspections submitted for permit, have been completed. The following discrepancies that were outstanding since the last interim report dated , hav been corrected: (Attach 8 112 x 11 continuation sheets(s)if required to complete the description of corrections) Interim reports submitted prior to this final report, and numbered _ to ,form a basis for, and are to be considered an integral part of this final report. R spectfully submitted, Special Inspector Signature Date Type or print name Date