February 19, 2015
Steve Palauskas
136 Trombley Road
East Windsor, CT 06088
RE: Connecticut Valley Brewing Co., 765 Sullivan Avenue - WPCA Approval
Dear Mr. Palauskas:
Motion was made to approve the application as presented for connection to the Town's
sewerage system for a proposed commercial building located at 765 Sullivan Avenue, South
Windsor, CT and as more specifically shown on plans entitled "Connecticut Valley
Brewing, Co., 765 Sullivan Avenue, South Windsor, CT"; prepared by JR Russo &
Associates, LLC.; Project No.: 2014-001; dated 11-17-14; Sheet 7 of 10 "Utility Plan" and
Sheet 9 of 10 "Detail Sheet". This approval is subject to the following conditions:
1. There will be a monitoring manhole on the outfall pipe installed within the street
right-of-way for the purpose of monitoring B.O.D. and solids;
2. A connection charge will be due in the amount of$11,433 for 3 acres at the time of
connection, the rates for which will be in effect until June 30, 2015;
3. Technical approval of the Town of South Windsor Department; and
4. Final Authority approval and acceptance of the sanitary sewerage connection will be
conditional upon the installed sewer line having been inspected by the Town staff,
and upon the written verification of the Town staff that said sanitary sewer line was
installed in substantial conformance with the design plans approved by the
Authority, and meeting all regulations and appropriate technical specifications
relating to sanitary sewer construction.
This approval letter must be superimposed on the final approval plans.
Very truly yours,
tRichar Aries, Chairman
Pollution Control Authority
cc: Michael J. Gantick, Director of Public Works
Jeff Doolittle, Town Engineer
Michele Lipe, Town Planner
Chris Dougan, Chief Building Inspector
TOWN OF SOUTH WINDSOR
WATER POLLUTION CONTROL AUTHORITY
APPLICATION FORM
Application No.:
Date Received
Date Scheduled F r 3
Applicant Connecticut Valley Brewing Co.
Address 765 Sullivan Ave
Telephone No.: 860 729-6408 -
Owner of Record on Land Records Town of South Windsor
Owner's Address
Property Description:
Assessor's Map# Parcel#_... _ Vol. 2015 Page 221
Project Title:
Inquiries to be Directed to: (Nate,Address,Telephone No.) Steve Palauskas
136 Trombiey Road East Windsor,CT 05088(860)729-6408
Approvals Previously Received (Check) IWA x P&.Z x ZBA
Purpose of Application: (Check all that apply)
1. Sewer Extension/Connection-- Residential Use
a. Subdivision
b. Single Unit
c. Other. .. ._...._ Explain
d. Type of Approval: Concept Final
2, Sewer Extension/Connection--Industrial/Commercial User
a. New Connection 'x
b. Request to Increase Flow Rate
c. Change in Nature of Waste Discharge
d. Other Explain
e. Type of Approval: Concept Final..._x
3. Appeal of Sewer User Charge
a. Residential
b, Industrial/Commercial
4. Sewer Assessment
a. Establish Sewer Assessment
b. Appeal of Sewer Assessment _
c. Change.in Use of Property_,____
5. Regulatory Appeal ,Explain
5. Other Explain
Z Lw
Applicant's Signature Date
Owner's Signature Date
"'S
1
3
r �.-,YF ry FF
t .
Proposal Prepared For:
Connecticut Valley Brewing Company
Attn: Steve Palauskas
765 Sullivan Ave
South Windsor, CT 06074
Woodard Curran
Attn: Michael J. Burns, P.E.
1699 King Street, Suite 406
Enfield, CT 06082
8,000 GPD HOOT MTS System
Based on the information provided to us by the owner, we have chosen to
recommend a 8,000 GPD Hoot MTS Series to Pre-Treat the wastewater to
better than residential levels for discharge into gravity sewer.
This facility is proposed to be a Brewery and the wastes generated from the
facility are estimated to be approximately 1,000 to 2,500 mg/L of BOD at
1,000 gallons per day for a total of 21.0 lbs. of BOD and pH Neutral (6-9).
All human wastes will be diverted around the system and directly drain into
the city sewer. The system has been designed to deliver the amount of air
necessary to complete digestion in %Z of the day (running 720 of 1440
minutes), and the Aeration can be increased to 100% and essentially double
either the flow or the strength, or a combination there of.
We assume residential strength of wastewater, which is not to exceed on
average 238 on BOD5i 200 on TSS and maintain a pH of 6-9. pH adjustment,
via the addition of chemicals in the main drain along with Anti-Foaming
agents or microbes to encourage digestion may be required, and are in
addition to this proposal, if necessary.
Hoot Systems, LLC. 2885 Highway 14 East Lake Charles, LA 70607
Hoot/CT Valley Brewing
January 20, 2015
Page 2 of 4
Grease Trap/Trash Trap:
• The first compartment (1,000 gallons) of a Heavy Duty 2,000 Gallon
tank will be used for settling of Solids, and provide for separation of
Grease as the first compartment of the Pre-Treatment tank.
• A PL-625 Solids Filter from Polylok of Wallingford, CT with High Water
Alarm Package.
Equalization Tank:
• 1,000 Gallon Pre-Cast Tank as the 2nd compartment of the 2
compartment tank
• Troy Air H-820 Blower and coarse air diffuser bar to deliver air to mix
the waste and begin the treatment process.
• Blower Control Panel —
o 96 pin Cycle timer will be provided to time EQ air delivery
• All piping for Simplex Aeration and Duplex Meter Dosed Pumping.
• Charcoal Filtered Vent Cover.
• Cast Iron Ring and covers brought to grade on Concrete Risers over
the openings (24" on Inlet and Filter, 30" over the pumps.)
• Stilling Well for Float switches
• Two, 2" Solids Transfer pumps (Gould's WW511) for duplex
equalization.
• Rhombus IFS Meter Dosing Pump Control Panel —
o NEMA U Duplex Control Panel, Single Phase, 120 Volt
• 3" Sleeve for Electrical Pass Through and 8"x8" junction Box
Aeration Chamber Packages Includes:
• 3,000, 5,000 or 8,000 Gallons of Aeration Chambers, in 2 Castings.
The Second casting (MTS 1) will contain the clarifier.
• 60"x60" Aluminum Pedestrian Rated (300 lbs. per square foot) to
cover openings on treatment plant.
• Fine Air Diffuser assembly package.
Hoot Systems, LLC. 2885 Highway 14 East Lake Charles, LA 70607
Hoot/CT Valley Brewing
January 20, 2015
Page 3 of 4
Aeration Chamber Packages (Continued):
• Polylok Charcoal Filtered Vent Cover
• Miscellaneous mounting hardware, boots and clamps kit.
• Blower Package Includes
o Duplex URAI-24 blowers with 1.5 HP motors
o Blower Frame with S.S. Hardware with Aluminum housing.
o NEMA 4 X, duplex control panel, Single phase, 230 volt.
• Blower & Systems Controls Include
o NEMA 4 X, Duplex Control Panel, Single Phase, 230 volt.
Clarifier
• 5,000 GPD Rated Clarifier.
• Aluminum Double Weir Trough & Baffle.
• Aluminum Baffled Stilling Well.
• 30"x72" Aluminum Pedestrian Rated (300 lbs. per square foot)
• 3" Air Lift Return Activated Sludge Line.
• 2" Air Lift Adjustable Surface Skimmer and Return Line.
• Valving to control return flow rate and air delivery.
Other Items
• Aluminum and Galvanized Panel Rack and with load Center
• 3 Days factory trained professional time for assistance (providing
direction for install) is included in the purchase price of the system.
Estimated Projected Total (Excluding any Taxes): $60,000.00
Refundable Deposit Due to complete design and drawings:
$6,000.00
Hoot Systems, LLC. 2885 Highway 14 East Lake Charles, LA 70607
Hoot/CT Valley Brewing
January 20, 2015
Page 4of4
From this Bid, if accepted, a full contract will be developed. Prior to release
of final submittal documents and drawings to the DEP for approval, a
deposit of 10% ($6,000) of the projected cost is required to complete the
work. The final price will be determined by any additional components that
are required to obtain the permit, as required by either the engineer or the
local or State Health Department/DEP. From that final price, a contract will
be developed.
Please Note:
• You will need to provide a CT licensed Installer to complete this
project. They will need to be present, onsite, each day that
construction takes place and be responsible for the installation. They
will be responsible for the excavation, setting of tanks including
crane, installation, hook-up of drain lines to the first tank and from
the Clarifier of the Hoot Tanks to the city sewer line.
• Any watertight testing required and the lines to and from the system
are the responsibility of the owner.
• You will need to employ a licensed Maintenance provider for the
lifetime of the treatment system.
• We will work with your engineer to provide the required drawings,
documents and any additional information required, and attend
meetings with them or the State or L.H. Department, if needed.
• No excavation work is included with this bid.
• No setting of tanks by a crane is included, only delivered in Full truck
load quantities to the site. (Crane rental responsibility of Installer)
• No electrical work or supply is included, other than supply of
components listed above (listed pumps, motors, load center, etc.)
• Plumbing to the system from the structures and between final tank
and the city drain line is not included.
• No permit (s) (construction, impact, environmental or otherwise) are
included.
• We recommend a fence around the system, but it is not included.
Hoot Systems, LLC. 2885 Highway 14 East Lake Charles, LA 70607
South Windsor Calculations @ 1,000 GPD
CFM Calculatio
ns
ppm Gallons Rate Lbs
Lbs of BODs/D 2,500 1,000 0.00000834 20.9
OZ rate per Total Lbs
Lb Lbs Needed
02 Needed per lb of BOD 1.8 20.9 37.5
lbs of 02 Needed 37.5
Cubic Feet of Air Needed (58.2 CF= 1 lb of 02) 2,184.2
CFM Needed @ 100% uptake at 720 min 3.0
effiency of uptake with Fine Air Diffusion (20%) 15.2
Additional Air Needed for Air Lift 10.0
Total CFM Needed 25.2
Basin Sizing Calculations
VA= (BOD x Q x 8.34)/BLF
VA=Volume of Aeration Basin in 1000 ft 3
BOD Loading in ppm
Q= Influent Flow in MGD
BLF= BOD Loading Factor of 20
ppm of BOD 2,500
Gallons 1,000
Cubic Feet Needed at 20 BLF 1,042.5
7,797.9
Recommended Basin Size in Gallons 8,000
Diffuser Requirement Calculations
CFM 15.2
Rate Per Diffuser 2.5
Total Diffusers 6
..��lulrs .us i
■ . , �7�
�� 1111 'ala ''����1••u,:;r:iiGii�lnl�uj .I
--
nwXn
III
I
I
* i -
�u
•��r I II
-- - it •
• [a�il�u: �•
��� ci1,111
- l
:� 1 ..
........................ .
HOOT SYSTEMS
STEMS LLC
- -
................::::......... .
WNAINYM.11 1.D U A 0 1 Z 1 j Eo ..
CT
_ . .
CT—
HOOT . . ..
3"SCH 40
COUPLING
I I I I �_ 8.00
0 I
6.00
I 5.00 �
I I
I II I I
I I I II I II I III I
I LJ I I II I III
I I I I I II LJII I
I I I I n n I I I I I 79.00
I
61.00 I I I I I I I
I I I I 6a.00 I I I
I I I I II II
I I I I I I I I
i I I I kAAA AA
L-------- I
I II I I I
I II I I I
L-- ----J �--— ----------J -- — J
�600
FRONT VIEW
SIDE VIEW
121.00
1 s.00
14.00 I —_ -__ ___ —
16.00
O O INLET II I
OUTLETS
16.00 TO + LET 4'IN
AERATION r
TANK I
•{}• II I
024.00 I I
030.00 I I I
85.00 I II II I
II 3'CONDIUT 030.00 II I
I II II I
I I6'0 I I I
II II I O O HOOT SYSTEMS LLC
I II II I
36.00 I I I
OLYLOK II I
I I I 22.00 EFFLUEENf I I I
Fl-= THIS DRAWING IS THE PROPRIETARY PROPERTY OF HOOT SYSTEMS LLC. REPRODUCTION,
DISCLOSURE OR USE OF ANY PART OF THIS DRAWING OR ANY INFORMATION THEREIN IS
—— ———— ———————————— EXPRESSLY PROHIBITED WITHOUT PRIOR WRITTEN CONSENT OF HOOT SYSTEMS LLC.
DESCRIPTION. PART$
TOP VIEW CT VALLEY BREWING CO. - S WINDSOR, CT
HOOT GREASE TRAP/ TT/EQ TANK
DATE: DRAWN BY. CNECIL BY: MILE: GREASE & TRAS H
01-20-2015 AY RS N.T.S. TRAP & EQ
8.
------------- '
----------�aII6'.sa ( 9.38
/ ----
54.00
54.00 i 43.00
I I I
I
-------- I I I
I
82.00 I 82.00
'Z°°
arHaHaararioarraoraioiarai raiararoaaaHrHiHiaiaiaiHi ��o����o�om�n�o��ooaoo���� I rHHr./////Il/raHa/ai/II!/HHr HmHmruHrHHr/H//aHr �v���� ���----��o�u 1200
.50 I
,w/war µwTa.q I
20.00
a00
J_ 8.00
FRONT VIEW —�
600 204.00 SIDE VIEW
192.00
12.00 90.00
,z.o0
3.00
72.00
84.00
HOOT SYSTEMS LLC
I I I 024.00 '
_-
______ Moo THIS DRAWING IS THE PROPRIETARY PROPERTY OF HOOT SYSTEMS LLC. REPRODUCTION,
L ————————————————— _ J DISCLOSURE OR USE OF ANY PART OF THIS DRAWING OR ANY INFORMATION THEREIN IS
fioo EXPRESSLY PROHIBITED WITHOUT PRIOR WRITTEN CONSENT OF HOOT SYSTEMS LLC.
DESCRIPTION: PART#
16.00 CT VALLEY BREWING CO. — S WINDSOR, CT
PLAN VIEW HOOT 8K MTS — AERATION 2
DATE: DR DW BY. CHECK BY. SCALE. AERATION
01-20-2015 1 AY IRS N.T.S. 2
i
6Oo 6es
14.00 8.869.38
11 18.42 0.50
I
54.00
I 19.00 I I I I
I I I FROM
O IFROMI I
8200 I
// /////////// ///////////// 1 T- /
moo
FIRE 606PA.E DPFusERs w 54.50 /
11T// I `'i 24.00
rk-
6.00
L
FRONT VIEW
204.00
RIGHT SIDE
1 iz.00 192.00
3 00
84.75 12.00 6.O0
Y'�� Y AIR ME
fROM CLARIFIER 6'DNMEIER
———————— ° T 1RASFER PPE
7.25 -------
24.00 --
30.00 I 16.00
/ I aw
91fMIMER k P-1ItM I I
r/6ERNCE PORT
72.00 3,SLUDGE
84.DO FROM
\ I CE
24k7Y I
wxFss Fum
\ • . HOOT SY STEMS LLC
6.00
6.00
33.00
THIS DRAWING IS THE PROPRIETARY PROPERTY OF HOOT SYSTEMS LLC. REPRODUCTION,
DISCLOSURE OR USE OF ANY PART OF THIS DRAWING OR ANY INFORMATION THEREIN IS
PLAN VIEW EXPRESSLY PROHIBITED WITHOUT PRIOR WRITTEN CONSENT OF HOOT SYSTEMS LLC.
DESCRIPTION. PART M
CT VALLEY BREWING CO. - S WINDSOR, CT
MTS AERATION 1 + CLARIFIER
DATE. DRAAN BY. CHECK BY. SCALE: MTS 1
1-20-2015 AY IRS N.T.S. CLARIFIER