HomeMy WebLinkAboutDrain Layers Permit Rosemary Lane (5) MEMORANDUM December 6, 1977
To: Allan Young
Re: T.V. viewing and air testing two (2) sections of
Rosemary Lane
On Monday, December 5, air testing, T.V. viewing and sealing
was conducted on Rosemary Lane.
Present during the operations were:
Mr. Bill Dobbins, D.E.P.
Mr. Dave Tomey, State Health Dept.
Mr. Daniel Savino, State Health Dept.
The work was done by the Wethersfield Sweeping Service. Results
were as follows: From M.H. Sta. 5 + 0 to (8 + 35 = 2 + 95)
(E. to W. )
134' from M.H. - water bubbling in at bottom of pipe joint this was sealed.
284' from M.H. - Lateral to "Parcel G" leaks excessively - has
to be repaired.
285'. from M.H. - broken pipe - water pouring in - has to be repaired.
From M.H. 5 + 40 to 2 + 95 = 8 + 35 (W. to E. )
192' from M.H. (Bloom lateral) leaking more now than last July has to be repaired. Also, broken piece of pipe at 3 o'clock
opposite lateral.
These findings are of a nature that have to be taken care of
immediately. See enclosed approximate costs.
One. other note, the manhold cover was removed on Rosemary at
.Sta. 5 + 0 to 2 + 0 (end) and initially, very little running
water was observed. However, later during operations, water
build-up moved plug at M.H. Sta.. 5 + 0 and water came to top
of brick invert work.
No time was taken today to determine the cause, but this should
be looked into. There was only one house in this area that could
have introduced water, so it seems that conditions may be more
involved.
The State also wants the easement Section (442' ) to be T.V. ,
but with no laterals here, an air to would be fficient.
Frank/ C. Messenger
/