Loading...
HomeMy WebLinkAboutScanned on 08/27/2010 at 10:10:47 SALAIVIONE & ASSOCIATES, P.C. Consulting Engineers CAP 1 TAL NEEDS ASSESSMENT FOR THE SOUTH WINDSOR TOWN HALL 1540 SULLIVAN AVENUE SOUTH WINDSOR, CONNECTICUT 06074 _ =f r t f ►1 � 1 i_ h' PREPARED FOR TOWN OF SOUTH WINDSOR Febrtmry, 2009 3035 Whitney Avenue Hamden Connecticut 06518 Phone (203) 281-6895 • Fax (203) 287-8728 1 Capital Needs Assessment for the South Windsor Town Hall Stamford, CT Project No. 791 2876.01 TABLE OF CONTENTS PAGES I. GENERAL PROJECT INFORMATION 3 II. INTRODUCTION 5 III. CAPITAL NEEDS ASSESSMENT A. ARCHITECTURAL 7 - 52 B. PLUMBING SYSTEMS 53 - 63 C. MECHANICAL SYSTEMS 64 - 97 D. ELECTRICAL SYSTEMS 98 - 148 IV. RECOMMENDATIONS FOR REPAIR/REPLACEMENT 150 - 163 V. LIFE SAFETY ITEM SPREADSHEET 164 - 165 VI. NON LIFE SAFETY CODE ITEM SPREADSHEET 166 - 168 VII. CRITICAL BUILDING SYSTEM SPREADSHEET 169 - 170 VIII. ENERGY EFFICIENTJOPERATING COST REDUCTION ITEM SPREADSHEET 171 - 173 IX. MISCELLANEOUS UPGRADES SPREADSHEET 174 - 180 X. COSMETIC UPGRADES SPREADSHEET 181 - 185 XI. SUMMARY SPREADSHEET 186 - 187 2 Capital Needs Assessment for the South Windsor Town Hall Stamford, CT Project No. 7912876.01 I. GENERAL PROJECT INFORMATION Development Name: South Windsor Town Hall Address: 1540 Sullivan Avenue, South Windsor, CT 06074 Construction Date: 1968 Occupancy Date: 1968 Number of Buildings: 1 Gross Sq. Ft of Building: 42,768 S.F. Construction Type (brief description): Town Hall Building: Three (3) story brick building with a main and upper flat roof. i 3 Capital Needs Assessment for the South Windsor Town Hall Stamford, CT Project No. 7912876.01 SECTION II: INTRODUCTION r �r r 1 Capital Needs Assessment for the South Windsor Town Hall Stamford, CT Project No. 791 2876.01 SECTION II—INTRODUCTION Salamone&Associates P.C. has been retained b the Town of South Windsor to provide a Y Capital Needs Assessment Report at the Town Hall located on 1540 Sullivan Avenue in South Windsor, Connecticut. The purpose of this Capital Needs Assessment is to review the existing conditions for the Town Hall Buildings, as well and provide recommendations as to future upgrades and replacement. The findings within this Assessment were based on feasibility, construction cost, and overall system performance. It is understood that Assessments of the existing conditions were limited to components accessible. A representative portion of the existing systems and assessment of the major equipment, components and conditions were reviewed. This Assessment is not intended to serve as a specification for remedial and/or construction of said components. South Windsor Town Hall Capital Needs Assessment Architectural CAPITAL NEEDS ASSESSMENT—ARCHITECTURAL A walkthrough of the facility was executed on January 6 & 8, 2009, to assess the architectural and site conditions of the existing facility. The architectural walkthrough was carried out by Brian Pulaski, Salamone &Associates,P.C. General • Please note recommendations are based on continuation of Note maintenance as recommended by respective manufacturers. 1 - Please note components and materials original to the building may contain hazardous materials and should be tested prior to implementation of any construction. This testing is beyond this ' reports scope of work. EXTERIOR: SITE DRIVES/PARKING & CURBS: -Main Entry Drive: Located directly off the main road is the main entry drive. The main entry drive is constructed of asphalt and appears to be in good condition. There was no significant damage noted in this area. Located around the perimeter of the main entry drive is the curbing. The curb is constructed of granite block and appears to be in good condition. No damaged or missing curbing was noted during our walk through. The main entry drive also contained striping to indicate driving direction, as well as lanes. The striping appeared to be in fair condition with some wear and fading noted. -Main Turn Around: Located at the Main Entrance to the building, connected to the entry drive, is the main turn around. This area is constructed of asphalt and appears to be in good condition. Some small areas of cracking were indicated, and one larger seam was noted to run along the southwest curb. The turn around also contains a parking area on its north side with eleven parking spaces. Located around the perimeter of the main turn around is the curbing. The curb is constructed of granite block and appears to be in good condition. No damaged or missing curbing was noted during our walk -"" through. The main turn around also contained striping to indicate driving direction, stop line,parking spaces and turn lanes. The striping appeared to be in fair condition with some wear and fading noted. South Windsor Town Hall Capital Needs Assessment Architectural -North Parking lots and drives: Located on the north side of the property is a pair of parking lots, with associated drives. The lot located closest to the building contains 44 parking spaces, 3 of which are handicapped. The lot located further from the building contains 46 parking spaces, none of which are handicapped. The parking lots and drives are constructed of asphalt and appear to be in fair condition. There was cracking noted in a few areas, including around the storm drains, as well as a major crack running half the length of the parking lot closer to the builder.No patching of the parking lot or drives was noted. Located around the perimeter of the north parking lots and .. drives is the curbing. The curb is constructed of asphalt and appears to be in fair condition. Some indications of damage were noted, but no large areas of missing curb were indicated. The north parking lots and drives also contained striping to indicate parking spaces, stop line and walkways. The striping appeared to be in fair condition with some wear and fading noted. -West Entry Drive: Located along the west side of the property is the west entry drive. The west entry drive is constructed of asphalt and appears to be in fair condition. The west entry drive contained areas of cracking throughout. There were no patches noted during the walkthrough. Located around the perimeter of the west entry drive is the curbing. The curb is constructed of asphalt and appears to be in fair condition. Some indications of damage were noted,but no large areas of missing curb were indicated. The west entry drive contained no striping. - Recommendation: • Patch all cracks. -- r • Repair damaged asphalt curbing. • Restripe all parking spaces. • Restripe all handicapped parking spaces per latest ADA codes. WALKS, PATIOS & STAIRS: -Lower Entry Walk: Located at the buildings lower north entrance is the lower entry walk. The lower entry walk is constructed of asphalt, as well as poured concrete and appears to be in good condition. The asphalt section runs from the parking lot to approximately 20 feet off the entry door. The asphalt shows no signs of cracking or poor drainage. Located in the 20 foot span in front of the entry is a 8 South Windsor Town Hall Capital Needs Assessment Architectural section of poured concrete. The concrete appears to be in good 7201 condition with no cracks or damage noted. Located along the east side of the walkway is concrete block curbing, which appears to be s, in good condition. Located along the west side of the walkway is asphalt curbing, which appears to be in good condition.No f' indication of damaged curbing was noted on either side of the walkway. -West Entry Walk: Located at the west entrance into stair B is the west entry walk. The west entry walk is constructed of asphalt, as well as poured concrete and appears to be in good condition. The asphalt section ;. runs from the main patio area to the corner of the stair tower. The asphalt shows no signs of cracking or poor drainage. Located directly in front of the stair entry is a section of poured concrete. The concrete appears to be in good condition with no cracks or damage noted. A small area of pooled water was indicated at the west corner where the concrete and asphalt meet.No curbing was indicated along the sides of the walk. Located on the north and west edge of the concrete section is a 30"tall brick wall with a ` stone top. The wall appears in fair condition. The wall contained a� areas of missing or damaged brick on its edge facing the asphalt g a walk, as well as the inner corner. Located between the two brick t walls, which flank the entry door, is a section of slate tile. This tile and associated grout appears to be in good condition. There was no indication of damaged or missing the or grout. -Main Lower Patio: Located directly off the main turn around is the buildings main lower patio. The main lower patio is constructed of brick pavers, which alternate octagon and square patterns. The exterior edges of the patio are constructed of rectangular shaped pavers. The pavers appear to be in good condition with no noted missing, cracked or damaged pieces.No heaving or uneven surfaces were noted during L the walkthrough. Located on the north side of the main lower patio is a 60"high retaining wall. The retaining wall is constructed of brick with a stone top and appears to be in fair condition. The retaining wall shows areas of damaged and missing grout, as well as cracked and broken bricks throughout. Located on the front of the wall are metal letters reading, "SOUTH WINDSOR TOWN HALL". The letters appear to be in good condition, with no damage indicated. 9 South Windsor Town Hall Capital Needs Assessment Architectural -Main Upper Patio: Located at the main entrance to the building, on its south fagade is the main upper patio. The main upper patio is constructed of a decorative poured concrete main area, with areas of concrete slabs III located on two sides. The area of poured concrete appears to be in good condition with no indication of damage or cracking, but some settling noted. The concrete slabs are located on the west side of j _ the poured concrete, as well as the south east corner. The concrete appears to be in fair condition with some sections of cracking and patchwork noted. The concrete appears to have settled and created some uneven surfaces. Located within these areas are drains, which - - appear to function properly. Located along all sides of the main upper patio is a brick wall, which creates the backside of the lower patios brick wall. This side of the brick wall appears to be in similar condition with areas of broken and cracked bricks, as well as damaged and missing grout. Located between the lower main patio and the upper main patio is a section of stairs. The stairs are constructed of concrete and appear to be in poor condition. There are significant cracks, spalling and rust staining throughout. There - is a metal handrail located up the center of the stair, which appears to be in fair condition. Some rust was indicated, especially at the junction with the stairs. Recommendation: • Power wash all walks,patios and brick walls. • Seal all brick walls with waterproof sealant. • Patch all cracks. • Re point areas of brick walls in need of re pointing. • Replace damaged and broken bricks at brick walls. 5 • Remove and replace areas of settling and damaged concrete at upper main patio. • Remove and replace stair located between upper main patio and lower main patio. • Prep,prime and paint handrail located on stair. VEGETATION: (Note, the ground was partially snow covered during our walk through.) -Main Entry and Turn Around: Located along the main entry drive is a row of trees. The trees in this area appeared to be in good condition with no signs of damage. Located within the center of the turn around is an area of grass with trees scattered about. The grass appeared well cared for and in good condition, and the same remains with the trees. Located adjacent to the lower main patio is a section of grass with some scattered vegetation. This area also appears to be in good condition with no damage noted during the walk through. 10 South Windsor Town Hall Capital Needs Assessment Architectural -North Parking lots and Island: Located on the outer edge of the north parking lots is a section of grass with associated vegetation. This area of vegetation appears to be in good condition with no damage noted. Located between the ;- two parking lots is a large island. The island contains small vegetation surrounded by dirt and mulch. The vegetation appeared to be in good condition and showed no signs of damage at the time of our visit. -Area Surrounding the Building: Located on all sides of the building, are sections of grass with associated trees and vegetation. The grass appears to be in good condition. The vegetation also appears to be in good condition and well cared for. Recommendation: 0 Seed areas of grass as needed. • Continue maintenance on all vegetation. SIGNAGE & FENCING: -Signs: Located throughout the property is the signage. Located at the head of the handicapped parking spaces are the signs indicating their use. These signs appear to be in good condition, and recently s replaced. The signs however do not meet the latest ADA code requirements for height. Located in the parking lot are signs indicating whom each space is dedicated for. These signs appear to be in good condition, and recently replaced. Also located on the property are stop signs. These signs appear to be also be recently replaced and in good condition. Located at the base of many of the trees on site, are signs indicating whom the tree is dedicated too. These signs are in poor condition with rot, mold and deterioration noted. The metal plate is rusted and tarnished. Holding all of the parking and stop signs up are wood posts. These posts are in fair } condition with wear and rot indicated at the base. There is paint missing from each. -Fencing: Located on the property are two sections of fencing. The first fence is located on the north wall of the building. This fence is constructed of round wood posts, with horizontal and vertical pieces between. This fence has a gate in its corner to allow access 4 r 5 inside. The fence appears to be in poor condition. The swinging ' 11 South Windsor Town Hall Capital Needs Assessment Architectural gate door was not attached and the fence showed signs of rot, staining and age. Located at the dumpster pad, in the north parking lot is another section of fence. This fence surrounds three sides of the dumpster pad and is constructed of wood posts with horizontal and vertical wood pieces between. This fence appears to be in fair condition. There is indication of the fence leaning and settling. The wood shows signs of age. Recommendation: • Replace all wood signposts. r • Replace handicapped signs and posts to meet ADA code complaince. • Replace wood on tree dedication signs. o Clean metal plaques on tree dedication signs. Remove and replace fence located adjacent to the building. • Remove and replace fence located around the back and sides of the dumpster pad. INTERIOR: LOWER LEVEL: 1 -Stairwell B: Located on the West side of the building is Stair B. The stair is constructed of a Steel Frame, on top of which is concrete. The floors are slate tile, grouted in place, as are the stair treads. The walls are constructed entirely of brick in a running bond style. The ceiling is constructed of concrete. The metal frame of the stairs appears in fair condition. There are signs of wear with paint missing, fading and rust beginning to form, especially near the exterior entrance. The slate tiles appear to be in good condition, including the stair treads. The concrete appears to be in good condition as well, with some areas of paint peeling. The walls appear to be in good condition with no signs of damage or destroyed brick or mortar. The ceiling is in good condition as well P with no signs of damage. Located along the edge of the stairs is the handrail. The handrail appears to be in good condition but does not meet latest code requirements. Located at the lower entrance of the stairwell is a door system consisting of a wood door with a window and sidelight. The frame is hollow metal and appears to be in fair condition. There are areas of missing and chipping paint. The door appears to be in good condition with some wear noted. The hardware appears to function properly. r12 South Windsor Town Hall Capital Needs Assessment Architectural Located at the landing between the lower and main floors, is an entry from the exterior. This door system is made of a wood door and sidelights on either side. The frame is hollow metal and appears in poor condition. There are signs of rust and rot on it's bottom edge, and paint chipped and missing. The door appears to be in fair condition. The door hardware appears to be in good condition and function properly. Located on the main floor is an entry door system, from the stairwell to the corridor, consisting of a hollow metal frame, with two wood doors. The door frame appears to be in good condition with some noted paint chipping and missing The doors appear to be in fair condition with wear noted but no significant damage. The door hardware appears to function as intended. Located on the second floor is an entry door system, from the stairwell into the corridor, consisting of a hollow metal frame, with two wood doors. The door frame appears to be in good condition with some noted paint chipping and missing The doors appear to be in fair condition with wear noted but no significant damage. The door hardware appears to function as intended. Recommendation: • Clean all brick walls in their entirety. • Clean all slate floors in their entirety. • Prep,prime and paint all metal stair frames, and metal at the base of the brick walls. • Prep,prime and paint all concrete. • Remove and Replace exterior doorframe. • Refinish all wood doors. • Replace handrail with new to meet current code requirements. -Elevator Lobby: F Located directly off Stair B is the lower elevator lobby. The elevator lobby is constructed of a concrete floor with carpet, brick walls, in a running bond style, and a 24"x 24"the suspended ceiling. Located around the perimeter of the room is a 4"vinyl base cove molding. The carpet in this location appears to be in good condition with no signs of damage or fraying, but does show wear. The walls appear to be in good condition with no signs of damage Mor destroyed brick or mortar. The ceiling tiles appear to be in good a condition with no damaged or broken tiles noted. Located on the lobby's east wall is a fire extinguisher box. The box is constructed of metal with a glass door surrounded by a copper frame. The box ' 13 South Windsor Town Hall Capital Needs Assessment Architectural appears to be in fair condition with signs of rust and missing paint. The door appears to function properly. Located on the North wall is an entrance door system from the exterior. The system is constructed of a hollow metal frame, with ►., two metal-framed glass doors. The metal doorframes are in poor condition with rust and rot indicated at the bottoms, as well as paint chipping and missing. The doors appear in fair condition with paint chipping and missing as well. The door hardware appears to function as intended. Located on the east wall is a doors stem leading to the common Y g corridor. The door system consists of a wood door with a window, in a hollow metal frame with a sidelight and toplight. The door appears to be in good condition with some wear noted. The metal frame appears to be in fair condition with some paint chipping and ' missing. Located on the West wall is the elevator with a hollow metal frame. The frame appears in good condition with some paint chipping and missing, but no damage noted. Recommendation: • Clean all brick walls in their entirety. • Replace any missing or damaged base cove molding. • Prep,prime and paint all metal doors and doorframes. • Remove and Replace exterior doorframe. 0 Prep,prime and paint metal fire extinguisher box. -Mechanical Equipment Room: Located off the lower level elevator lobby is the mechanical equipment room. The room is constructed of concrete floors, concrete block walls and a plaster ceiling. The floors in this location appear to be in fair condition with some areas in poor condition. The floor shows signs of age with paint chipping and peeling, as well as holes from old machines mounted to it. There ' are floor drains located throughout the room,which appear to function properly. Located directly in front of you, upon entering, is a section of floor with a metal plate running straight towards the ' south wall, turning and running into the west wall. This metal section is approximately 16"wide and sits uneven with the floor. Located at the corner of this metal section is a crack, which extends # off at an angle to the south wall. Located near the east wall of the mechanical equipment room is a concrete pad,which is elevated 3 1/4" above the main floor. This pad measures 84"by 40"and 14 South Windsor Town Hall Capital Needs Assessment ' Architectural contains a round drain along one side. The pad is not painted but appears to be in good condition. Located in the northeast corner of _ the room, beginning underneath a mechanical device, extending towards the east wall, continuing adjacent to this wall, and then proceeding adjacent to the south wall for 3/4 of its run, is a concrete curb. This curb offers protection for vital piping located within this room. The curb appears to be in fair condition with some signs of wear and paint missing. The walls in the mechanical equipment room appear to be in fair condition with some signs of damage noted. Located on the north wall are some cracks above the entry door, as well as some damage around a metal sleeve, and where ductwork passes through the wall. There are cracks located in the corners of the room. Located on the south wall is a large area of damaged concrete where some piping extends through the wall. This same damage occurs in many locations throughout the mechanical equipment room. There are many areas of spalling, and missing paint throughout as well. The ceiling in this room is constructed of plaster on a metal grid. The ceiling appears to be in poor condition. There are many areas of missing and broken I plaster. Where metal hangers are mounted to the ceiling there are cracks and stress marks apparent. Areas of patching were noted during the walk through as well. There was staining evident in many areas of the ceiling. Located in the ceiling were metal access panels, which appeared to function properly. Some of the panels t. showed signs of wear and rust. Located on the north wall is the entry door system. The doors are constructed of wood with a hollow metal frame. The doors appear to be in fair condition with some damage noted. The metal frame appears to be in good condition with some paint missing or f, chipping. The hardware appears to function properly. r so V Recommendation: • Patch and repair all damage to concrete block walls. • Saw cut and level metal insert located on floor. • Patch and repair all damage to concrete floor. • Patch and repair existing plaster ceiling. • Prep,prime and paint all concrete flooring and walls. • Prep,prime and paint all metal access panels. • Prep,prime and paint all metal doorframes. ' 15 South Windsor Town Hall Capital Needs Assessment rArchitectural -Elevator Machine Room: Located directly to your right upon entering the mechanical equipment room is the elevator machine room. The elevator machine room is constructed of concrete floors, concrete and iconcrete block walls, and a plaster ceiling. The floor in this location appears to be in good condition with paint missing or chipping. The walls in this area appear to be in fair condition with ' some cracking noted, mainly in the corners, as well as some damage noted around the metal grille. The ceiling in this location is in good condition with a patch noted near the entry wall, as well as - some small damage indicated near around the electrical line pass through. Located on the west wall is the entry door. The door is constructed of wood with a hollow metal frame. The door appears to be in fair condition with some damage noted. The metal frame appears to be in good condition with some paint missing or chipping. The hardware appears to function properly. Recommendation: • Patch and repair all damage to concrete block walls. • Patch and repair all damage to the ceiling. ' • Prep,prime and paint all floors, walls and ceilings. • Prep,prime and paint metal doorframe. -Transformer Vault: Located in the center of the mechanical equipment room's west wall is the transformer vault. The vault was locked during our visit and no access was granted. -Communications Room: Located at the southwest corner of the mechanical equipment room is the communications room. The communications room is constructed of a concrete floor, concrete and concrete block walls, and the ceiling is open to the trusses. The floor in this room appears ' 1 to be in good condition with some wear noted to include missing 4 paint. Located on the floor, near the wall between the mechanical equipment room and the communications room is a metal plate. The plate appears to be in good condition. The walls of this room appear to be in fair condition with some cracking and damage noted in the areas where piping enters and exits. The trusses as viewed in this room as well as the metal floor framing appears to be in good condition with no signs of damage. ' 16 ' South Windsor Town Hall Capital Needs Assessment Architectural Located on the west wall is the entry door. The door is constructed of wood with a hollow metal frame. The door appears to be in fair condition with some damage noted. The metal frame appears to be in good condition with some paint missing or chipping. The hardware appears to function properly. Recommendation: - • Patch and repair all damage to concrete block walls. ' • Prep,prime and paint all walls and floors. • Prep,prime and paint metal doorframe. -IT Office: Located at the west end of the common corridor for stair B is the IT office. The IT office is constructed of a concrete floor with carpet, t: a concrete wall with wall coverings, and a 24"x 24"the suspended ceiling. Located around the perimeter of the room is a 4"vinyl base cove molding. The flooring in this location appears to be in poor condition. There is wear noted throughout the room, with areas of damage indicated in the direct walking paths. The walls in the IT office appear to be in good condition with no significant damage ' noted. The ceiling tiles appear to be in poor condition. There are many ceiling tiles missing or damaged, and it appears as though E some have been replaced, which did not match the existing. The x vinyl base cove molding appears to be in fair condition with some pieces pulling away from the wall. 71 Located on the south wall is the entry door system. The door is constructed of wood and glass with a hollow metal frame, which includes a sidelight. The door appears to be in fair condition with some damage noted. The metal frame appears to be in good condition with some paint missing or chipping. The hardware appears to function properly. Located at the no rthwest corner of the IT office is the server room. ._ The server room is constructed of a concrete floor with carpet, a ' concrete block wall with a fabric wall system on top of it, as well as sections of brick, and the ceiling is constructed of 24"x 24" suspended tiles. Located around the perimeter of the room is a 4" vinyl base cove molding. The floor appears to be in good condition = with some wear noted. The walls appear to be in good condition =a with no damage noted. The ceiling tiles appear to be in poor ' - condition with some tiles damaged and missing. The base cove molding appears to be in good condition with some sections pulling away from the wall. 17 South Windsor Town Hall Capital Needs Assessment Architectural Located on the south wall is the entry door. The door is constructed Iof wood with a hollow metal frame. The door appears to be in fair condition with some damage noted. The metal frame appears to be in good condition with some paint missing or chipping. The } hardware appears to function properly. Located on the north wall of the server room is a window. The window measures 44 1/8"wide by 64 1/4"tall, and is constructed of steel and glass on it's outer section and aluminum and glass on the ' inner section. The inner window appears to be in fair condition, and although dirty, appears to function properly. The outer window appears to be in poor condition with rust indicated. The window appears to function properly. The sill at this location is constructed of wood and appears to be in good condition. Also in this location is a metal grate over the window,which appears to be in fair condition. Located at the southeast corner of the IT office is the air handler v room. The air handler room is constructed of concrete floors, ' concrete block walls, and a 24" x 24"the suspended ceiling. The floors in this location are in fair condition with paint missing and wear noted during our walk through. The walls are in poor ' condition with many areas of damage noted. There are large holes, cracks, spalling and damage throughout this room. The ceiling is in ' poor condition as well,with missing and damaged tiles located throughout. Recommendation: • Clean all brick walls. • Remove and replace existing suspended ceiling. • Prep,prime and paint metal doorframes and inner window ' frames. • Patch and repair all concrete flooring. o Patch and repair all concrete walls. O Prep,prime and paint all concrete floors and walls. • Replace outer window. -Men's Lavatory: Located at the southwest corner of the common corridor for stair B ' is the men's lavatory. The men's lavatory is constructed of 1"x 1" ceramic tile floor, concrete block walls and a plaster ceiling. The floors in the men's lavatory appear to be in good condition with no cracked or broken tiles noted during our walk through. A section of floor approximately 12"by 12"has been replaced with pill mismatching colored tiles. The walls in the men's lavatory appear to be in good condition with no damage noted. The ceiling appears 18 South Windsor Town Hall Capital Needs Assessment ' Architectural to be in good condition as well with no damage noted. The lavatory does not meet current ADA requirements. _ Located on the north wall of the men's lavatory is the entry door. The door is constructed of wood with a hollow metal frame. The door appears to be in fair condition with some damage noted. The metal frame appears to be in good condition with some paint missing or chipping. The hardware appears to function properly. -Women's Lavatory: Located to the east of the men's lavatory is the women's lavatory. The women's lavatory is constructed of 1"x 1"ceramic tile floor, concrete block walls and a plaster ceiling. The floors in the women's lavatory appear to be in good condition with no cracked or broken tiles noted during our walk through. A section of floor approximately 12"by 12"has been replaced with mismatching colored tiles. The walls in the women's lavatory appear to be in good condition with no damage noted. Some staining was noted on the walls. The ceiling appears to be in good condition as well with no damage noted. Some staining was noted on the ceiling. The lavatory does not meet current ADA requirements. Located on the north wall of the women's lavatory is the entry ' door. The door is constructed of wood with a hollow metal frame. The door appears to be in fair condition with some damage noted. The metal frame appears to be in good condition with some paint missing or chipping. The hardware appears to function properly. Janitor's s, Closet: . Located just east of the men and women's lavatories is the janitor's closet. The janitor's closet is constructed of 1"x 1"ceramic tile floor, with a section of concrete located at the entrance. The walls are constructed of concrete block, with 3 walls having tile run up to approximately 48" and the ceiling is plaster. The concrete flooring appears to be in fair condition with staining, dirt and debris ' indicated. The tile flooring appears to be in poor condition with damaged tiles indicated. The tiles are dirty and stained. The walls z$ of the janitor's closet appear to be in fair condition with a small hole indicated on its south wall, near the ceiling. The ceiling appears to be in poor condition with a large hole located near the 1 t entry door, as well as damage located around the light. 19 rSouth Windsor Town Hall Capital Needs Assessment Architectural Located on the north wall of the janitor's closet is the entry door. The door is constructed of wood with a hollow metal frame. The door appears to be in fair condition with some damage noted. The metal frame appears to be in good condition with some paint missing or chipping. The hardware appears to function properly. Recommendation: • Replace sections of mismatching tile with those that match existing. • Patch and repair concrete walls where indicated. • Prep,prime and paint concrete walls. • Patch and repair plaster walls where indicated. • Prep,prime and plaster concrete walls. ' • Remove and replace tile located in janitor's closet. • Prep,prime and paint concrete floor in janitor's closet. • Possibly redo men and women's lavatories to meet current 4DA codes. -Madden Corridor: Located about halfway down the common corridor for stair B on its north side is the madden corridor. The madden corridor is ' m constructed of a concrete floor with carpet, fabric covered wall system, and a 24"x 24"the suspended ceiling. There is a 4"carpet base cove molding located throughout the corridor as well. The floors in the madden corridor appear to be in good condition with no signs of damage. The walls, and ceiling tiles appear to be in good condition as well. There is some staining noted on the ceiling ' tiles, but no damaged or missing tiles. The carpet base molding appears to be in good condition. Located at the entrance to the madden corridor from the common corridor is an entryway. The entry way is constructed of a steel header spanning between the brick walls. The entryway header appears to be in good condition with some paint chipping noted. -Sprenkel Room: 1 , Located at north end of the madden corridor lies the sprenkel room. k The sprenkel room is constructed of a concrete floor with carpet, a fabric covered wall system, along with brick walls and a 24"x 24" suspended ceiling. There is a 4"carpet base cove molding located ' throughout the sprenkel room as well. The floors in the sprenkel room appear to be in good condition with no signs of damage. The walls, and ceiling tiles appear to be in good condition as well. There is some staining noted on the ceiling tiles, but no damaged or ' 20 South Windsor Town Hall Capital Needs Assessment Architectural missing tiles. The brick walls appear to be in good condition with ' no damaged bricks or mortar. The carpet base molding appears to be in good condition. Located immediately to your left upon entering is a coat alcove. The alcove contains a wood shelf and ' - - coat rod. i-- Located on the south wall of the room is the entry door system. ' The door is constructed of wood and glass with a hollow metal frame,which includes a sidelight. The door appears to be in good condition with slight damage noted. The metal frame appears to be F: ; .� in good condition with some paint missing or chipping. The hardware appears to function properly. Located along the north wall of the sprenkel room is a series of windows. There are four windows each measuring 44 1/8"wide by 641/4"tall, and are constructed of steel and glass on their outer section and aluminum and glass on the inner section. The inner windows appear to be in fair condition, and although dirty, appear to function properly. The outer windows appear to be in poor condition with rust indicated. The windows appear to function properly, although very tough to operate. The sills at these ' locations are constructed of wood and appear to be in good condition. A large amount of caulk was noted around these windows. Madden Room: Located along the east wall of the madden corridor lies the madden IN room. The madden room is constructed of a concrete floor with carpet, a fabric covered wall system, along with brick walls and a 24"x 24" suspended ceiling. There is a 4" carpet base cove molding located throughout the madden room as well. The floors in the madden room appear to be in good condition with no signs of ' damage. The walls,and ceiling tiles appear to be in good condition as well. There is some staining noted on the ceiling tiles, but no damaged or missing tiles. One section of tiles located in front of the closets on the west wall appears to hang low, and the closet door scrapes these. The brick walls appear to be in good condition with no damaged bricks or mortar. The carpet base molding ' appears to be in good condition. Located immediately to your left upon entering on the entry wall are two closets. The closets are constructed of concrete block walls, carpet floors, and 24"x 24" ' the suspended ceiling. The floor and walls appear to be in good condition. The ceiling tiles appear to be in poor condition with mismatched tiles indicated. 21 South Windsor Town Hall Capital Needs Assessment ' Architectural Located on the west all of the room is the entry door system. The ' door is constructed of wood and glass with a hollow metal frame, which includes a sidelight. The door appears to be in good } condition with slight damage noted. The metal frame appears to be in good condition with some paint missing or chipping. The r- hardware appears to function properly. ' Located along the north wall of the sprenkel room is a series of windows. There are three windows each measuring 44 1/8"wide by 641/4"tall, and are constructed of steel and glass on their outer section and aluminum and glass on the inner section. The inner windows appear to be in fair condition and although dirty, appear to fu nction n oproperly. Th e outer windows ap pear to i be poor ' pP condition with rust indicated. The windows appear to function properly, although very tough to operate. The sills at these locations are constructed of wood and appear to be in good ' condition. A large amount of caulk was noted around these windows. Recommendation: ' • Clean all brick walls. • Replace existing ceiling tiles. • Replace outer window. • Prep,prime and paint all metal door and window frames. • Replace existing ceiling tiles in closets. -Lounge: Located at the far end of the common corridor for stair A is the lounge. The lounge is constructed of a concrete floor with 9"x 9" VCT tiles, the walls are constructed of a sheetrock system as well as sections of brick, and the ceiling is 24"x 24"the suspended. There is a 6"vinyl base cove molding located throughout the room .r as well. The floors appear to be in fair condition with dirt and staining noted. The walls appear to be in fair condition with evidence of damage where the base cove molding is missing. The brick sections appear to be in good condition with no damage noted. The ceiling tiles appear to be in fair condition with staining evident throughout. There were some areas of damage noted on the tile as well. The base cove molding is missing along one wall. Also ' located in this room is a kitchenette. The kitchenette contains a set of lower cabinets, a counter with a sink, and a set of upper cabinets with a shelf for a microwave. The cabinets and counters appear to be in good condition, and the hardware appears to function properly. ' 22 ' South Windsor Town Hall Capital Needs Assessment Architectural Located on the south wall of the lounge is the entry door. The door is constructed of wood and glass with a hollow metal frame. The door appears to be in fair condition with some damage noted. The metal frame appears to be in good condition with some paint missing or chipping. The hardware appears to function properly. Located along the north wall of the lounge is a pair of windows. There are two windows each measuring 44 1/8"wide by 64 1/4" t tall, and are constructed of steel and glass on their outer section and aluminum and glass on the inner section. The inner windows appear to be in fair condition, and although dirty, appear to ' function properly. The outer windows appear to be in poor condition with rust indicated. The windows appear to function properly, although very tough to operate. The sills at these locations are constructed of wood and appear to be in good condition. A large amount of caulk was noted around these windows. Recommendation: • Remove and replace existing VCT flooring. • Clean all brick walls. • Remove and replace existing suspended ceiling. • Replace outer window. • Prep,prime and paint all metal door and window frames. q� • Remove and replace base cove molding. • Prep,prime and paint walls. t ' -Vault: Located at the northeast corner of the building is the vault. The vault is constructed of concrete floor with 9"x 9" VCT tiles, ' concrete block walls, and 24"x 24"the suspended ceiling. The floor in the vault appears to be in good condition with staining and r� dirt indicated. The walls appear to be in fair condition with cracks and areas of damage noted. The ceiling tiles appear to be in fair condition with staining and some damaged tiles noted. ' Located on the west and south walls are entry doors into the vault. There are two doors per opening. The opening dimension is 47 3/8"wide by 80 %"high. The doors are 4-hour fire rated and ' insulated and appear to be in good condition. There was some evidence of paint missing or pealing on the doors and doorframes. Recommendation: • Remove and replace existing VCT flooring. • Remove and replace existing suspended ceiling. • Patch and repair concrete block walls. 23 South Windsor Town Hall Capital Needs Assessment ' Architectural • Prep,prime and paint concrete block walls. • Prep,prime and paint fire-rated doors and frames. -Probate Office: Located at the intersection of the common corridor for stairs A and B is the probate office. The probate office is constructed of a ' concrete floor with carpet, and a section of 9"x 9"VCT tile at the - entrance to the vault, a gypsum wall system, and 24"x 24"the suspended ceiling. There is also 4"vinyl base cove molding located on all the walls of the probate office. The floors appear to be in good condition with no damage noted. The walls appeared to be in good condition with no damage noted, and the ceiling tiles also appear to be in good condition with no damage or staining noted. Located on the west wall of the probate office is the entry door ' system. The door is constructed of wood and glass with a hollow metal frame, which includes a sidelight. The door appears to be in good condition with slight damage noted. The metal frame appears ' to be in good condition with some paint missing or chipping. The hardware appears to function properly. ' -Hearing Room: Located within the probate office is the hearing room. The hearing room is constructed of a concrete floor with carpet, a gypsum wall system, as well as brick sections along its east-facing wall, and a 24"x 24"tile suspended ceiling. There is also 4"vinyl base cove molding located on all the walls of the hearing room. The floor appears to be in good condition with no damage noted. The walls appear to be in good condition and the ceiling appears to be in ' -"T good condition as well, with no damage or staining noted. One ceiling tile showed signs of wear. Located on the west wall of the hearing room are two entry doors. One entry door, which leads directly into the probate office, and the other, which leads into the judge's quarters. These doors are constructed of wood with a metal frame. The doors appear to be in good condition with no damage noted, and the hardware appears to function properly. Located along the east wall of the hearing room is a series of windows. There are three windows each measuring 44 1/8"wide .. by 64 1/4"tall, and are constructed of steel and glass on their outer section and aluminum and glass on the inner section. The inner windows appear to be in fair condition, and although dirty, appear to function properly. The outer windows appear to be in poor 1 24 South Windsor Town Hall Capital Needs Assessment Architectural condition with rust indicated. The windows appear to function ' properly, although very tough to operate. The sills at these locations are constructed of wood and appear to be in good condition. A large amount of caulk was noted around these windows. -Judge's Quarters: Located within the probate office are the judge's quarters. The judge's quarters are constructed of a concrete floor with carpet, a gypsum wall system, and 24"x 24"the suspended ceiling. There is a 4"vinyl base cove molding located on all the walls of the judge's rl: V F quarters. The floors appear to be in good condition with no damage noted. The walls appear to be in good condition with damage noted. The ceiling tiles appear to be in good condition with no = 1 damaged or stained tiles noted. Located on the west wall of the judge's quarters is a door to the probate office. This door is constructed of wood with a metal frame. The door appears to be in good condition with no damage noted. The doors hardware appears to also be in good condition and appears to function properly. Recommendation: • Replace damaged ceiling tile to match existing. • Replace outer windows. ' • Prep,prime and paint all metal door and window frames. -Registrar's Office: Located adjacent to the probate office is the registrar's office. The registrar's office is constructed of a concrete floor with carpet, a ' gypsum wall system, and 24"x 24"the suspended ceiling. There is also 4"vinyl base cove molding located on all the walls of the registrar's office. The floors appear to be in fair condition with some areas of damage noted. The walls appeared to be in fair condition with some staining and paint damage noted. The ceiling tiles also appear to be in fair condition with some damage and ' staining noted during our walk through. Located on the west wall of the registrar's office is the entry door system. The door is constructed of wood and glass with a hollow ' metal frame, which includes a sidelight. The door appears to be in good condition with slight damage noted. The metal frame appears to be in good condition with some paint missing or chipping. The hardware appears to function properly. ' 25 South Windsor Town Hall Capital Needs Assessment Architectural -Back Office: _ Located within the registrar's office is the back office area. This back office is constructed of a concrete floor with carpet,� a gypsum wall system as well as sections of brick, and 24"x 24"the suspended ceiling. There is also 4"vinyl base cove molding located on all the walls of the registrar's office. The floors appear to be in fair condition with some areas of damage noted. The walls appeared to be in fair condition with some staining and paint damage noted. There were areas noted of missing and crumbling gypsum at the wall corners. The brick sections appeared to be in good condition with no damage noted. The ceiling tiles also appear to be in fair condition with some damage and staining noted during our walk through. Located within the back office is a small closet. ` The closet is constructed of a concrete floor with 9" x 9"VCT tile, which appear to be in good condition. The walls are constructed of gypsum and appear to be in good condition. The ceiling is constructed of 24"x 24"the suspended ceiling, and appears to be '< t in fair condition with some staining noted. Located on the west wall of the back office is a door to the registrar's office. Also located into the closet is a similar door. These doors are constructed of wood with metal frames. The doors := appear to be in good condition with no damage noted. The door , j hardware appears to also be in good condition and appears to function properly. ' Located along the east wall of the back office is a series of windows. There are three windows each measuring 44 1/8"wide by 64 1/4"tall, and are constructed of steel and glass on their outer section and aluminum and glass on the inner section. The inner g z . windows appear to be in fair condition, and although dirty, appear _ to function properly. The outer windows appear to be in poor condition with rust indicated. The windows appear to function a properly, although very tough to operate. The sills at these locations are constructed of wood and appear to be in good ' condition. A large amount of caulk was noted around these windows. 1 -Lavatory: �19 I Located on the south wall, between the registrar's office and the back office is a lavatory. The lavatory is constructed of a concrete floor with 9"x 9"VCT tiles, gypsum walls, and 24"x 24"the suspended ceiling. The floors appear to be in good condition with All 11 some wear and dirt noted. The walls appear to be in good condition with no damage, but areas of missing paint noted. The ceiling tiles appear to be in fair condition with some staining noted. 26 South Windsor Town Hall Capital Needs Assessment Architectural Located on the north wall of the lavatory is the entry door. This door is constructed of wood with a metal frame. The door appears to be in good condition with no damage noted. The doors hardware appears to also be in good condition and appears to function properly. Recommendation: • Remove and replace all existing carpet. • Replace damaged ceiling tiles to match existing. • Patch and repair damaged gypsum wall. • Prep,prime and paint all walls. • Replace outer windows. • Prep,prime and paint all metal door and window frames. -Common Corridor for Stair B: Located in the center of the building, spanning from the elevator lobby to the probate office is the common corridor for stair B. the common corridor for stair B runs east and west and is constructed of a concrete floor with 9"x 9"VCT tile flooring, brick walls in a running bond pattern, and 24"x 24"the suspended ceiling. The floors through the corridor appear to be in good condition with an area outside the IT office where the tiles appear to have shifted, creating an uneven surface. The walls appear to be in good condition with no damaged or broken bricks or mortar noted. The ceiling tiles appear to be in good condition with some staining noted during our walk through. -Common Corridor for Stair A: Located in the center of the building, spanning from stair A to the lounge is the common corridor for stair A. the common corridor for stair A runs north and south and is constructed of a concrete floor with 9" x 9"VCT tile flooring, brick walls in a running bond pattern, and 24"x 24"the suspended ceiling. The floors through the corridor appear to be in good condition with no damage noted. The walls appear to be in good condition with no damaged or broken bricks or mortar noted. The ceiling tiles appear to be in good condition with some staining noted during our walk through. Recommendation: • Replace damaged section of VCT outside of IT office. • Clean VCT tiles in both corridors. • Clean all ceiling tiles. • Clean all brick walls in their entirety. 27 South Windsor Town Hall Capital Needs Assessment Architectural -Maintenance Office: Located at the intersection of both common corridors is the maintenance office. The maintenance office is constructed of a I concrete floor with 9"x 9"VCT tile flooring, concrete block outer walls with gypsum inner walls, and 24"x 48"the suspended } . ceiling. The floor in the maintenance office appears to be in poor condition. There were many missing and broken tiles, which revealed damage to the concrete below. The tiles that remain are dirty, worn and damaged. The concrete block walls appear to be in fair condition with some damage noted. The gypsum walls appear to be in fair condition with areas of paint missing. The ceiling tiles appear to be in poor condition. There are many missing and broken tiles, and the remaining tiles appear stained. Located on the north wall of the maintenance office is the entry door. This door is constructed of wood with a metal frame. The Pn door appears to be in fair condition with some damage noted. The door hardware appears to be in good condition and appears to function properly. -Storage Room: Located on within the maintenance office, on its south side, is the storage room. The storage room is constructed of a concrete floor, concrete block exterior walls, with a gypsum wall between it and the maintenance office, and no ceiling. The concrete floors appear to be in fair condition with some cracks noted, as well as many areas of missing, cracked and chipped paint. The concrete walls appear to be in poor condition with many areas of cracking, damage, and staining. The gypsum wall appears to be in poor condition as well. There are many sections of missing gypsum, and the gypsum in place is unfinished with insulation exposed. The ceiling is not in place, giving direct view to the trusses and floor supports above. The trusses appear to be severely rusted along the south wall of the storage room. The trusses appear to be in good condition in all areas besides the one indicated. Located on the north wall between the storage room and the maintenance office is the entry door. This door is constructed of wood with a wood frame. The door appears to be in fair condition with some damage noted. The frame appears to be in fair condition with some damaged noted as well. The door hardware appears to be in good condition and appears to function properly. it Recommendation: ��� �''�� ` r' • Replace complete VCT flooring in maintenance office. `" i- 28 South Windsor Town Hall Capital Needs Assessment Architectural • Patch and repair damaged concrete under flooring and within storage room. • Patch and repair all damaged areas of concrete block walls. li • Remove and replace suspended ceiling in maintenance office. • Finish gypsum wall between maintenance office and storage room. • Prep,prime and paint all gypsum walls. • Prep,prime and paint all concrete walls. • Prep,prime and paint all exposed concrete flooring. ' • Repair any rusted or rotted trusses and main floor supports. • Prep,prime and paint all trusses and main floor supports. -Stairwell A: Located on the south side of the building is Stair A. The stair is constructed of a Steel Frame, on top of which is concrete. The floors are slate tile, grouted in place, as are the stair treads. The walls are constructed entirely of brick in a running bond style. The ceiling is constructed of plaster. The metal frame of the stairs appears in fair condition. There are signs of wear with paint missing, fading and rust beginning to form, especially near the exterior entrance. The slate tiles appear to be in good condition, including the stair treads. The concrete appears to be in good condition as well, with some areas of paint peeling. The walls appear to be in good condition with no signs of damage or destroyed brick or mortar. The ceiling is in fair condition as well with some signs of damage. Located along the edge of the stairs is the handrail. The handrail appears to be in fair condition but does not meet latest code requirements. Located at the lower entrance of the stairwell is a door system consisting of two wood doors with a windows. The frame is hollow metal and appears to be in fair condition. There are areas of missing and chipping paint. The doors appear to be in good condition with some wear noted. The hardware appears to function properly. Located on the main floor is an entry door system, from the stairwell to the foyer, consisting of a hollow metal frame, with two wood doors. The frame is hollow metal and appears in fair condition. There are signs of wear and missing paint. The doors j appear to be in fair condition. The door hardware appears to be in good condition and function properly. Located on the main floor is an entry door, from the stairwell to the lobby, consisting of a hollow metal frame, with a wood door and window. The door frame appears to be in good condition with some noted paint chipping and missing The door appears to be in 29 South Windsor Town Hall Capital Needs Assessment Architectural fair condition with wear noted but no significant damage. The door hardware appears to function as intended. Located on the second floor is an entry door, from the stairwell to the upper lobby, consisting of a hollow metal frame, with a wood door and window. The door frame appears to be in good condition with some noted paint chipping and missing The door appears to be x in fair condition with wear noted but no significant damage. The _ door hardware appears to function as intended. ' Located on the second floor is an entry door, from the stairwell to building department reception area, consisting of a hollow metal ;a frame, with a wood door. The door frame appears to be in good condition with some noted paint chipping and missing The door appears to be in fair condition with wear noted but no significant damage. The door hardware appears to function as intended. Located at the landing between the upper floor and the roof, is an entry from the exterior. This door system is made of a wood door and sidelights on either side. The frame is hollow metal and appears in poor condition, especially on the outside. There are signs of rust and rot on it's bottom edge, and paint chipped and missing. The door appears to be in fair condition with a lot of weathering on its exterior. The door hardware appears to be in 1 good condition and function properly. --------------------- _ g Located at the roof, is an entry from the exterior. This door system is made of a metal door and frame. The frame is hollow metal and appears in fair condition. There are signs of chipping and missing paint. The door appears to be in fair condition, with signs of ' chipping and missing paint. The door hardware appears to be in good condition and function properly. Recommendation: • Clean all brick walls in their entirety. • Clean all slate floors in their entirety. • Prep,prime and paint all metal stair frames, and metal at the base of the brick walls. • Prep,prime and paint all concrete. • Patch and repair ceiling damage. • Remove and Replace exterior doorframe between upper floor tand roof. ' • Refinish all wood doors. • Prep,prime and paint all metal doorframes and doors. • Replace handrail with new to meet current code requirements. 30 South Windsor Town Hall Capital Needs Assessment Architectural MAIN LEVEL: -Elevator Lobby: Located directly off Stair B is the main floor elevator lobby. The elevator lobby is constructed of a concrete floor with carpet, brick walls, in a running bond style, and a 24"x 24"the suspended ceiling. The carpet in this location appears to be in good condition with no signs of damage or fraying,but does show wear. The walls appear to be in good condition with no signs of damage or NO destroyed brick or mortar. The ceiling tiles appear to be in good condition with no damaged or broken tiles noted. Located on the lobby's east wall is a fire extinguisher box. The box is constructed of metal with a glass door surrounded by a copper frame. The box appears to be in fair condition with signs of rust and missing paint. The door appears to function properly. Located on the West wall is the elevator with a hollow metal frame. The frame appears in good condition with some paint chipping and missing, but no damage noted. The hardware appears to be in good condition and appears to function properly. Located on the east wall is a door system leading to the common corridor. The door system consists of two wood doors with windows, in a hollow metal frame. The doors appear to be in good .' condition with some wear noted. The metal frame appears to be in t fair condition with some paint chipping and missing. The hardware appears to be in good condition and appears to function properly. L Located on the North wall is a window. The window measures 76" wide by 84"tall. The window is constructed of a hollow metal frame and has no movable function. The window appears to be in good condition with no damage noted. Recommendation: • Clean all brick walls in their entirety. • Prep,prime and paint all metal doors, doorframes and window frames. • Prep,prime and paint metal fire extinguisher box. -Council Chamber: x Located directly off the elevator lobby, to its south side is the s- council chamber. The council chamber is constructed of concrete floors with carpet, brick walls on the north and south, and plaster walls on the west and east end. The ceiling is constructed of plaster, with an oriental stucco section made of three angled pieces. The carpet in the council chamber appears to be in fair condition with indications of damage located throughout the room. The brick walls appear to be in good condition with no noted damaged. The plaster walls appear to be in good condition with the west wall 31 South Windsor Town Hall Capital Needs Assessment Architectural being angled upwards, and the east wall being perpendicular to the ground.No damage was noted at the time of the walk through. The ceiling appears to be in good condition was well, with no indications of damage. Located on the north wall is a door system leading to the elevator lobby. The door system consists of two wood doors with a hollow metal frame. The doors appear to be in good condition with some wear noted. The metal frame appears to be in fair condition with some paint chipping and missing. The hardware appears to be in good condition and appears to function properly. Located on the east wall is a door system leading to the lobby. The p, door system consists of four wood doors with a hollow metal frame. The doors appear to be in good condition with some wear noted. The metal frame appears to be in fair condition with some paint chipping and missing. The hardware appears to be in good condition and appears to function properly. Located along the south wall of the council chamber is a series of windows. There are five windows each measuring 24"wide by 194 1/2"tall, and are constructed of steel and. The windows appear to be in fair condition, and although dirty, no drafts were indicated at the time of the walk through. The windows had no movable function to them. A large amount of caulk was noted around the windows. him Recommendation: • Clean all brick walls in their entirety. • Remove and replace carpet in its entirety. • Prep,prime and paint all metal door and window frames. • Prep,prime and paint all plaster walls. • Remove and re-caulk around all windows. -Men's Lavatory: Located at the southwest corner of the common corridor is the men's lavatory. The men's lavatory is constructed of 1"x 1" ceramic tile floor, concrete block walls and a plaster ceiling. The floors in the men's lavatory appear to be in good condition with no cracked or broken tiles noted during our walk through. The walls in the men's lavatory appear to be in good condition with no damage noted. The ceiling appears to be in good condition as well with no damage noted. The lavatory does not meet current ADA requirements. Located on the north wall of the men's lavatory is the entry door. The door is constructed of wood with a hollow metal frame. The door appears to be in fair condition with some damage noted. The metal frame appears to be in good condition with some paint missing or chipping. The hardware appears to function properly. 32 South Windsor Town Hall Capital Needs Assessment Architectural -Women's Lavatory: Located to the east of the men's lavatory is the women's lavatory. The women's lavatory is constructed of 1"x 1"ceramic tile floor, concrete block walls and a plaster ceiling. The floors in the women's lavatory appear to be in good condition with no cracked or broken tiles noted during our walk through. The walls in the women's lavatory appear to be in good condition with no damage noted. The ceiling appears to be in good condition as well with no damage noted. The lavatory does not meet current ADA requirements. Located on the north wall of the women's lavatory is the entry door. The door is constructed of wood with a hollow metal frame. The door appears to be in fair condition with some damage noted. The metal frame appears to be in good condition with some paint missing or chipping. The hardware appears to function properly. -Janitor's Closet: Located just east of the men and women's lavatories is the janitor's closet. The janitor's closet is constructed of 1"x 1"ceramic tile ` -- � floor,with a section of concrete located at the entrance. The walls are constructed of concrete block, with 3 walls having tile run up to approximately 48" and the ceiling is plaster. The concrete flooring appears to be in fair condition with staining, dirt and debris indicated. The tile flooring appears to be in poor condition with damaged and missing tiles indicated. The tiles are dirty and stained. The walls of the janitor's closet appear to be in fair condition with dirt and missing paint noted. The ceiling appears to be in poor t condition with large holes located where conduit enters and exits, as well as damage located around the light. Located on the north wall of the janitor's closet is the entry door. The door is constructed of wood with a hollow metal frame. The door appears to be in fair condition with some damage noted. The metal frame appears to be in good condition with some paint missing or chipping. The hardware appears to function properly. Recommendation: • Patch and repair concrete walls where indicated. • Prep,prime and paint concrete walls. • Prep,prime and paint concrete walls. • Repair damage to janitor's closet ceiling. .. • Prep,prime and paint ceiling in janitor's closet. • Remove and replace tile located in janitor's closet. • Prep,prime and paint concrete floor in janitor's closet. • Possibly redo men and women's lavatories to meet current ADA codes. 33 South Windsor Town Hall Capital Needs Assessment Architectural -Common Corridor: Located in the center of the building, spanning from the elevator lobby to the lobby is the common corridor. The common corridor runs east and west and is constructed of a concrete floor with carpet, brick walls in a running bond pattern, and 24"x 24"the suspended ceiling. The floors through the corridor appear to be in good condition with no damage noted, but some wear evident. The walls appear to be in good condition with no damaged or broken bricks or mortar noted. The ceiling tiles appear to be in good condition with some staining noted during our walk through. Recommendation: • Clean all brick walls in their entirety. -Caucus Room: Located on the west end of the common corridor,to its north, is the caucus room. The caucus room is constructed of concrete floors with carpet, gypsum walls, and 24"x 24"the suspended ceilings. There is a 4"vinyl base cove molding located on all walls. The carpet appears to be in good condition with no noted damage,but some wear apparent. The walls appear to be in good condition with one area of damage noted. The ceiling tiles appear to be in fair condition with some staining noted. The vinyl base cove molding appears to be in good condition with no missing or damaged >� pieces. n Located on the south wall is the entry door system. The door is constructed of wood and glass with a hollow metal frame, which includes a sidelight. The door appears to be in fair condition with some damage noted. The metal frame appears to be in good condition with some paint missing or chipping. The hardware appears to function properly. -Caucus Lobby, Office and Break Room: Located through the caucus room, along the north wall of the building are the lobby, office and break room. These rooms are constructed of concrete floors with carpet, gypsum walls with brick sections along the north wall, and 24"x 24"the suspended ceilings. There is a 4"vinyl base cove molding located on all 1 walls. The carpet appears to be in good condition with no noted damage, but some wear apparent. The walls appear to be in good condition with some areas of damage noted. The ceiling tiles appear to be in fair condition with some staining noted as well as some small holes. The vinyl base cove molding appears to be in good condition with no missing or damaged pieces. 34 South Windsor Town Hall Capital Needs Assessment Architectural 3 Located between the caucus lobby and the caucus room is a door, which is constructed of wood with a metal frame. The door appears to be in good condition with no damage noted. The doors hardware appears to also be in good condition and appears to function properly. Located within the lobby between the office and break room are doors, which are constructed of wood, with wood frames. The doors appear to be in good condition with some wear noted. The frames appear to be in good condition with some wear noted. Located along this wall above the doors is a section of glass. The glass runs the length of this wall and appears to be in good condition. Located between the caucus lobby and the human resources office is the caucus copy room. This room is in the same condition as noted above, using the same materials. Located in this area is another door. This door is constructed of wood with a window inside a hollow metal frame. The door appears to be in good condition with some wear noted. The metal frame appears to be in good condition with some wear and paint missing noted. Located above the door are windows, looking between the central office 45 f and the human resources office. Located along the north wall of the finance offices are a group of windows. There is one window in the west office and two windows in the east office, each measuring 44 1/8"wide by 64 '/4"tall, and are constructed of steel and glass on their outer section and aluminum and glass on the inner section. The inner windows appear to be in fair condition, and although dirty, appear to function properly. The outer windows appear to be in poor condition with rust indicated. The windows appear to function - --- properly, although very tough to operate. The sills at these locations are constructed of wood and appear to be in good condition. A large amount of caulk was noted around these windows. Recommendation: • Patch sections of damaged walls. i�■�r • Prep,prime and paint patched walls to match existing. • Prep,prime and paint metal doorframes. • Replace outer window. • Clean all brick walls. 35 South Windsor Town Hall Capital Needs Assessment Architectural -Human Resources Main Office: Located along the common corridor directly east of the finance offices and the meeting room is the human resources main office. The human resources main office is constructed of concrete floors with carpet, gypsum walls, and 24"x 24"the suspended ceilings. There is a 4"vinyl base cove molding located on all walls. The carpet appears to be in good condition with no noted damage, but s some wear apparent. The walls appear to be in good condition with no areas of damage noted. The ceiling tiles appear to be in fair condition with some staining noted. The vinyl base cove molding appears to be in good condition with no missing or damaged pieces. Located on the south wall is the entry door system. The door is constructed of wood and glass with a hollow metal frame, which includes a sidelight. The door appears to be in fair condition with I some damage noted. The metal frame appears to be in good condition with some paint missing or chipping. The hardware appears to function properly. -Human Resources Offices: Located within the human resources area are two offices. The offices are located along the north wall of the building and are constructed of concrete floors with carpet, gypsum walls with brick sections along the north wall, and 24" x 24" the suspended ceilings. There is a 4" vinyl base cove molding located on all walls. The carpet appears to be in good condition with no noted damage, but some wear apparent. The walls appear to be in good condition with no areas of damage noted. The ceiling tiles appear to be in fair condition with some staining noted. The vinyl base cove molding appears to be in good condition with no missing or damaged pieces. Located on the south wall of each office is an entry door. The doors are constructed of wood with metal frames. The doors appear to be in good condition with no damage noted. The door hardware appears to also be in good condition and appears to function properly. Located between the two rear offices is a wood door with a wood frame. This door appears to be in good condition, with one panel showing signs of wear and paint missing. The frame also appears to be in good condition. The hardware on the door appears to be in u.z good condition and function properly. Located along the north wall of the human resource offices are a group of windows. There are two windows in each office, measuring 44 1/8"wide by 64 1/4"tall, and are constructed of steel 36 South Windsor Town Hall Capital Needs Assessment Architectural and glass on their outer section and aluminum and glass on the inner section. The inner windows appear to be in fair condition, and although dirty, appear to function properly. The outer windows appear to be in poor condition with rust indicated. The windows --- _ appear to function properly, although very tough to operate. The sills at these locations are constructed of wood and appear to be in good condition. A large amount of caulk was noted around these windows. Recommendation: • Patch sections of damaged walls. o Prep,prime and paint patched walls to match existing. • Prep,prime and paint metal door frames. o Replace outer window. o Clean all brick walls. -Town Clerk Main Office: Located along the common corridor directly west of the human resource offices is the town clerks main office. The town clerks main office is constructed of concrete floors with carpet, gypsum walls, and 24"x 24"the suspended ceilings. There is carpet base cove molding located on all walls. The carpet appears to be in good condition with no noted damage, but some wear apparent. The walls appear to be in good condition with no areas of damage noted. The ceiling tiles appear to be in fair condition with some staining noted as well as some damage. The carpet base cove molding appears to be in good condition. Located on the south wall is the entry door system. The door is constructed of wood and glass with a hollow metal frame, which includes a sidelight. The door appears to be in fair condition with some damage noted. The metal frame appears to be in good condition with some paint missing or chipping. The hardware appears to function properly. -Town Clerk Offices: Located to the north of the town clerks main office are two smaller town clerk offices. The town clerk offices are constructed of concrete floors with carpet, gypsum walls, and 24"x 24"the suspended ceilings. There is a 4"vinyl base cove molding located on all walls. The carpet appears to be in good condition with no noted damage, but some wear apparent. The walls appear to be in good condition with no areas of damage noted. The ceiling tiles I appear to be in fair condition with some staining noted as well as i 37 South Windsor Town Hall al Capital Needs Assessment Architectural some damage. The vinyl base cove molding appears to be in good condition with no missing sections or damage noted. Located on the south wall of each office is an entry door. The doors are constructed of wood with metal frames. The doors appear to be in fair condition with some damage noted along the bottom edges. The door hardware appears to also be in good condition and appears to function properly. Located along the north wall of the town clerk offices are a group of windows. There are two windows in the west office and one window in the east office, each measuring 44 1/8"wide by 64 1/4" r tall, and are constructed of steel and glass on their outer section and aluminum and glass on the inner section. The inner windows appear to be in fair condition, and although dirty, appear to function properly. The outer windows appear to be in poor condition with rust indicated. The windows appear to function properly, although very tough to operate. The sills at these locations are constructed of wood and appear to be in good condition. A large amount of caulk was noted around these windows. Recommendation: • Replace damaged ceiling tiles with new to match existing. • Prep,prime and paint metal doorframes. g �.i , F'jII Replace outer window.. .4 0 Clean all brick walls. • Replace damaged doors. -Vault: Located at the northeast corner of the building is the vault. The vault is constructed of concrete floor with 9"x 9"VCT tiles, 1 concrete block walls, and 24"x 24"the suspended ceiling. The floor in the vault appears to be in good condition with staining and dirt indicated. The walls appear to be in fair condition with cracks and areas of damage noted. The ceiling tiles appear to be in fair condition with staining and some damaged tiles noted. Located on the west and south walls are entry doors into the vault. d There are two doors per opening. The opening dimension is 47 3/8"wide by 80 1/4"high. The doors are 4-hour fire rated and insulated and appear to be in good condition. There was some evidence of paint missing or pealing on the doors and doorframes. Recommendation: • Remove and replace existing VCT flooring. • Remove and replace existing suspended ceiling. r�9 • Patch and repair concrete block walls. av»s sraaa • Prep,prime and paint concrete block walls. 38 South Windsor Town Hall Capital Needs Assessment Architectural • Prep,prime and paint fire-rated doors and frames. -Lobby: Located at the main entrance to the town hall is the lobby. The lobby is constructed of slate tiled floor, with carpet running along the outside, brick walls, with concrete located at the balcony faces and plaster above the doors to the council chamber, and 24"x 24" tile suspended ceiling located at the lower section as well as the vaulted section. The slate floor appears to be in good condition with no noted cracks or damage. The carpet appears to be in good condition as well with no damage noted. The brick walls appear to be in good condition with no damaged brick or mortar. The plaster walls appear to be in fair condition with some staining noted. The ceiling tiles show wear and staining. Located at the south wall of the lobby are the entrance doors. The entrance doors are constructed of glass doors with metal frames at the top and bottom, and no doorframe. The hinges are set into metal plates on the floor and ceiling. The glass appears to be in good shape. The metal frames appear to be in good shape and the hinges appear to function properly. The metal plates appear to be in fair condition with wear and some dirt and staining noted. -Foyer: Located directly inside the main entrance to the town hall is the foyer. The foyer is constructed of slate tile flooring, brick walls, and a plaster ceiling. The floor appears to be in good condition with no damage noted. The walls appear to be in good condition as well with no damage noted. The ceiling appears to be in good condition with no damage noted, but some staining and dirt apparent. Located at the main entrance are the entry doors. These doors are constructed of wood with a metal frame containing sidelights. The doors appear to be in fair condition with some damage and wear noted. The frames appear to be in poor condition with significant rust apparent,notably on the exterior. The glass in the sidelights appears to be in good condition with no damage noted. Recommendation: .R. • Clean all slate floors. • Patch and repair any damage to plaster walls. " • Prep,prime and repaintplaster walls. • Prep,prime and paint all metal doorframes. • Remove and replace metal door and sidelight frame at entrance. • Refinish wood doors at entrance. 39 1 South Windsor Town Hall Capital Needs Assessment Architectural -Assessors Main Office: Located on the east end of the building between the vault and the tax collectors office is the assessors main office. The assessors main office is constructed of concrete with carpet, the walls are constructed of gypsum and the ceiling is constructed of 24"x 24" tile suspended ceiling. There is a 4"vinyl base cove molding located within the assessors main office. The floors appear to be in fair condition with a lot of wear indicated. The walls appear to be in fair condition with no damage noted but paint missing. The ceiling appears to be in fair condition with some staining noted. The vinyl base cove molding appears to be intact and in good condition. Located on the west wall of the assessors main office is the entry door system. The door is constructed of wood and glass with a hollow metal frame, which includes a sidelight. The door appears to be in good condition with slight damage noted. The metal frame appears to be in good condition with some paint missing or chipping. The hardware appears to function properly. -Assessors Back Offices: Located within the assessors main office are two assessors offices. These offices are constructed of concrete with carpet, the walls are constructed of gypsum and the ceiling is constructed of 24"x 24" the suspended ceiling. There is a 4"vinyl base cove molding located within the assessors main office. The floors appear to be in fair condition with a lot of wear indicated. The walls appear to be in fair condition with no damage noted but paint missing. The ceiling appears to be in fair condition with some staining noted. The vinyl base cove molding appears to be intact and in good condition. Located on the west wall of the assessors offices are two entry doors. One entry door, which leads into each office. These doors are constructed of wood with a metal frame. The doors appear to be in good condition with no damage noted, and the hardware appears to function properly. Located along the east wall of the assessors offices are a series of windows. There is one window in the north office, and two windows in the south office, each measuring 44 1/8"wide by 64 1/4"tall, and are constructed of steel and glass on their outer section and aluminum and glass on the inner section. The inner windows appear to be in fair condition, and although dirty, appear to function properly. The outer windows appear to be in poor condition with rust indicated. The windows appear to function properly, although very tough to operate. The sills at these 40 South Windsor Town Hall Capital Needs Assessment Architectural locations are constructed of wood and appear to be in good condition. A large amount of caulk was noted around these windows. Recommendation: • Remove and replace worn carpet throughout assessors offices. • Clean all brick walls. • Prep,prime and paint all walls. • Replace outer windows. • Prep,prime and paint all metal door and window frames. -Tax Collectors Offices: Located just northeast of stair A is the tax collectors offices. The tax collectors offices are constructed of concrete with carpet, the walls are constructed of gypsum and the ceiling is constructed of 24"x 24"tile suspended ceiling. There is a 4"vinyl base cove molding located within the tax collectors office. The floors appear to be in fair condition with some wear indicated. The walls appear to be in fair condition with no damage noted but paint missing. The ceiling appears to be in fair condition with some staining noted. The vinyl base cove molding appears to be intact and in good condition. Located within the front office is a safe. The safe appears to be in good condition and appears to function properly. Located in the southeast corner of the tax collectors rear office is a storage closet. The storage closet is constructed of a concrete floor with 9"x 9"VCT tile flooring, gypsum walls, and a 24"x 24"the suspended ceiling. The floors appear to be in good condition with ! some dirt and staining noted, but no damage. The walls appeared to be in good condition with no damage noted. The ceiling tiles appeared to be in good condition with some staining noted. Located on the west wall of the tax collectors office is the entry door system. The door is constructed of wood and glass with a L Now" hollow metal frame, which includes a sidelight. The door appears to be in good condition with slight damage noted. The metal frame appears to be in good condition with some paint missing or chipping. The hardware appears to function properly. Located between the main office and the back office is a door. The door is constructed of wood with a metal frame. The doors appear to be in good condition with no damage noted, and the hardware appears to function properly. Located along the east wall of the tax collectors back office is a group of windows. There are three windows each measuring 44 1/8"wide by 641/4"tall, and are constructed of steel and glass on their outer section and aluminum and glass on the inner section. 41 South Windsor Town Hall Capital Needs Assessment Architectural The inner windows appear to be in fair condition, and although dirty, appear to function properly. The outer windows appear to be in poor condition with rust indicated. The windows appear to F. function properly, although very tough to operate. The sills at these locations are constructed of wood and appear to be in good condition. A large amount of caulk was noted around these windows. During the walk through it was noted that plastic had been placed over the windows. Located between the tax collectors main office and the rear office is a small pass through window. The window is constructed of a wood frame with glass. The window appears to be in good condition with no damage noted. Recommendation: Y • Remove and replace all VCT flooring. • Clean all brick walls. • Prep,prime and paint all walls. • Replace outer windows. • Prep,prime and paint all metal door and window frames. UPPER LEVEL: -Elevator Lobby: Located directly off Stair B is the upper floor elevator lobby. The elevator lobby is constructed of a concrete floor with carpet, brick walls, in a running bond style, and a 24"x 24"the suspended ceiling. The carpet in this location appears to be in good condition with no signs of damage or fraying, but does show wear. The walls appear to be in good condition with no signs of damage or destroyed brick or mortar. The ceiling tiles appear to be in good condition with no damaged or broken tiles noted. Located on the lobby's east wall is a fire extinguisher box. The box is constructed of metal with a glass door surrounded by a copper frame. The box appears to be in fair condition with signs of rust and missing paint. The door appears to function properly. Located on the West wall is the elevator with a hollow metal frames The frame appears in good condition with some paint chipping and missing, but no damage noted. The hardware appears to be in good condition and appears to function properly. Located on the east wall is a door system leading to the common corridor. The door system consists of two wood doors with windows, in a hollow metal frame. The doors appear to be in good condition with some wear noted. The metal frame appears to be in r _ fair condition with some paint chipping and missing. The hardware appears to be in good condition and appears to function properly. 42 South Windsor Town Hall Capital Needs Assessment Architectural Located on the North wall is a window. The window measures 76" wide by 84"tall. The window is constructed of a hollow metal frame and has no movable function. The window appears to be in good condition with no damage noted. Recommendation: • Clean all brick walls in their entirety. • Prep,prime and paint all metal doors, doorframes and window frames. • Prep,prime and paint metal fire extinguisher box. -Men's Lavatory: Located at the southwest corner of the common corridor is the men's lavatory. The men's lavatory is constructed of P x F ceramic tile floor, concrete block walls and a plaster ceiling. The floors in the men's lavatory appear to be in fair condition with some cracked or broken tiles noted during our walk through. The walls in the men's lavatory appear to be in good condition with no damage noted. The ceiling appears to be in fair condition as well with some damage noted. The lavatory does not meet current ADA requirements. Located on the north wall of the men's lavatory is the entry door. The door is constructed of wood with a hollow metal frame. The "= door appears to be in fair condition with some damage noted. The ' j _ metal frame appears to be in good condition with some paint i missing or chipping. The hardware appears to function properly. -Women's Lavatory: Located to the east of the men's lavatory is the women's lavatory. The women's lavatory is constructed of 1"x 1"ceramic tile floor, concrete block walls and a plaster ceiling. The floors in the women's lavatory appear to be in fair condition with some cracked or broken tiles noted during our walk through. The walls in the women's lavatory appear to be in good condition with no damage noted. The ceiling appears to be in fair condition with some damage noted. The lavatory does not meet current ADA requirements. Located on the north wall of the women's lavatory is the entry door. The door is constructed of wood with a hollow metal frame. The door appears to be in fair condition with some damage noted. The metal frame appears to be in good condition with some paint missing or chipping. The hardware appears to function properly. i 43 South Windsor Town Hall Capital Needs Assessment Architectural -Janitor's Closet: Located just east of the men and women's lavatories is the janitor's closet. The janitor's closet is constructed of 1"x 1" ceramic tile floor,with a section of concrete located at the entrance. The walls are constructed of concrete block, with 3 walls having tile run up to approximately 48"and the ceiling is plaster. The concrete flooring 1 appears to be in fair condition with staining, dirt and debris indicated. The tile flooring appears to be in poor condition with damaged and missing tiles indicated. The tiles are dirty and stained. The walls of the janitor's closet appear to be in fair condition with dirt and missing paint noted. The ceiling appears to be in poor condition with damage noted during our walk through. Located on the north wall of the janitor's closet is the entry door. The door is constructed of wood with a hollow metal frame. The door appears to be in fair condition with some damage noted. The metal frame appears to be in good condition with some paint missing or chipping. The hardware appears to function properly. Recommendation: - ,'°, • Replace broken or damaged tiles to match existing. ' • Patch and repair concrete walls where indicated. • Prep,prime and paint concrete walls. 1 • Prep,prime and paint concrete walls. • Repair damage to ceilings. • Prep,prime and paint ceilings. • Prep,prime and paint concrete floor in janitor's closet. • Possibly redo men and women's lavatories to meet current ADA codes. -Common Corridor: Located in the center of the building, spanning from the elevator lobby to the balcony is the common corridor. The common corridor runs east and west and is constructed of a concrete floor with carpet, brick walls in a running bond pattern, and 24"x 24" tile suspended ceiling. The floors through the corridor appear to be in good condition with no damage noted, but some wear evident. r The walls appear to be in good condition with no damaged or broken bricks or mortar noted. The ceiling tiles appear to be in good condition with some staining noted during our walk through. Recommendation: • Clean all brick walls in their entirety. 44 South Windsor Town Hall Capital Needs Assessment Architectural -Finance Offices: Located on the west end of the common corridor are the finance offices. These offices are constructed of concrete floors with carpet, gypsum walls with brick sections along the north wall, and 24"x 24"tile suspended ceilings. There is a 4"vinyl base cove molding located on all walls. The carpet appears to be in good condition with no noted damage, but some wear apparent. The walls appear to be in good condition with some areas of damage noted. The ceiling tiles appear to be in fair condition with some staining noted as well as some small holes. The vinyl base cove molding appears to be in good condition with no missing or damaged pieces. Located at the northwest corner of the main area is a small office. The office is constructed in the same way the main are is, using the same materials and appears to be in the same condition. Located between the back office and the main area is a door, which is constructed of wood, with a metal frame. The door appears to be in good condition with some wear noted. The frame appears to be in good condition with some wear noted. The hardware on the door appears to be in good condition and function properly. Located on the south wall is the entry door system. The door is constructed of wood and glass with a hollow metal frame, which includes a sidelight. The door appears to be in fair condition with some damage noted. The metal frame appears to be in good condition with some paint missing or chipping. The hardware appears to function properly. Located along the north wall of the finance offices are a group of windows. There is one window in the west office and two windows in the east office, each measuring 44 1/8"wide by 641/4"tall, and are constructed of steel and glass on their outer section and aluminum and glass on the inner section. The inner windows appear to be in fair condition, and although dirty, appear to function properly. The outer windows appear to be in poor condition with rust indicated. The windows appear to function f� properly, although very tough to operate. The sills at these 4: locations are constructed of wood and appear to be in good condition. A large amount of caulk was noted around these windows. Recommendation: • Patch sections of damaged walls. • Prep,prime and paint patched walls to match existing. o Prep,prime and paint metal door frames. JN ' Replace outer window. �:� ■ ` ' o Clean all brick walls. a _ 45 South Windsor Town Hall Capital Needs Assessment Architectural e Public Works Offices: Located to the east of the finance offices are the public works offices. These offices are constructed of concrete floors with carpet, gypsum walls with brick sections along the north wall, and 24"x 24"tile suspended ceilings. There is a 4"vinyl base cove molding located on all walls. The carpet appears to be in good condition with no noted damage, but some wear apparent. The walls appear to be in good condition with some areas of damage noted. The ceiling tiles appear to be in fair condition with some staining noted as well as some small holes. The vinyl base cove molding appears to be in good condition with no missing or v damaged pieces. Located at the north and west end of the works main area are 4 offices. The offices are constructed in the same way the main are is,using the same materials and appear to be in the same condition. Located between the main area and the offices are wood doors _. with metal doorframes. The doors appear to be in good condition with some wear noted. The frames appear to be in good condition with some wear noted. The hardware on the doors appears to be in good condition and function properly. Located on the south wall is the entry door system to the main area. The door is constructed of wood and glass with a hollow metal frame, which includes a sidelight. The door appears to be in fair condition with some damage noted. The metal frame appears to be in good condition with some paint missing or chipping. The hardware appears to function properly. Located along the north wall of the offices are a group of windows. 1 There are two windows in the west most office,two windows in the east office, and three windows behind the cubicles, each a measuring 44 1/8"wide by 641/4"tall, and are constructed of steel y and glass on their outer section and aluminum and glass on the inner section. The inner windows appear to be in fair condition, and although dirty, appear to function properly. The outer windows i appear to be in poor condition with rust indicated. The windows appear to function properly, although very tough to operate. The sills at these locations are constructed of wood and appear to be in good condition. A large amount of caulk was noted around these windows. Recommendation: Patch sections of damaged walls. o Prep,prime and paint patched walls to match existing. Prep,prime and paint metal doorframes. O Replace outer window. ® Clean all brick walls. 46 South Windsor Town Hall Capital Needs Assessment Architectural -Balcony: Located between the common corridor and stair A is the balcony. The balcony is constructed of a concrete floor with carpet, brick walls, and a 24"x 24"the suspended ceiling. The floors in the ° = balcony appear to be in good condition with no damage noted, but some wear evident. The walls appear to be in good condition with no damaged or broken bricks or mortar noted. The ceiling tiles appear to be in good condition with some staining noted during our walk through. Located around the opening to the main floor is a handrail. The handrail is constructed of metal and wood and appears to be in good condition. the handrail does not meet latest codes. Recommendation.- Replace suspended ceiling in its entirety. • Clean all brick walls in their entirety. ""ry • Possibly remove and replace handrail located along opening p g to the main floor. -Engineering Department Offices: ' Located within the same area as the town clerk offices are the engineering department offices. These offices are also constructed _ of concrete floors with carpet, gypsum walls with brick sections n . " along the north wall, and 24"x 24"the suspended ceilings. There is a 4"vinyl base cove molding located on all walls. The carpet appears to be in good condition with no noted damage, but some wear apparent. The walls appear to be in good condition with some areas of damage noted. The ceiling tiles appear to be in fair " - _ condition with some staining noted as well as some small holes. t ,. The vinyl base cove molding appears to be in good condition with a - no missing or damaged pieces. Located at the northeast corner of the engineering department area --- _ is a small office. The office is constructed in the same way the main area is, using the same materials, and appears to be in the same condition. This office has 7-foot tall walls, which do not extend to the ceiling. Pa Located between the main area and the office is a wood door with 4 +' a metal doorframe. The door appears to be in good condition with some wear noted. The frame appears to be in good condition with some wear noted. The hardware on the door appears to be in good condition and function properly. There is no entry door system as the town clerks office and the building department office, with no separations, access this area. 47 South Windsor Town Hall Capital Needs Assessment Architectural Located along the north and east wall of the offices are groups of windows. There are five windows on the north wall,two of which are located within the corner office, and five windows on the east wall,two of which are located within the corner office. Each window measures 24"wide by 64 1/4"tall, and are constructed of steel and glass on their outer section and aluminum and glass on ' the inner section. The inner windows appear to be in fair condition, and although dirty, appear to function properly. The outer windows appear to be in poor condition with rust indicated. The windows appear to function properly, although very tough to operate. The sills at these locations are constructed of wood and appear to be in good condition. A large amount of caulk was noted around these windows. ' Recommendation: mV • Patch sections of damaged walls. a • Prep,prime and paint patched walls to match existing. • Prep,prime and paint metal door frames. '= • Replace outer window. • Clean all brick walls. ' Building Department Offices: Located within the same area as the town clerk offices and engineering department offices are the building department offices. These offices are also constructed of concrete floors with carpet, i GIRITIFT I Fh gypsum walls with brick sections along the north wall, and 24"x 24 the suspended ceilings. There is a 4 vinyl base cove molding :3 located on all walls. The carpet appears to be in good condition with no noted damage,but some wear apparent. The walls appear to be in good condition with some areas of damage noted. The ceiling tiles appear to be in fair condition with some staining noted as well as some small holes. The vinyl base cove molding appears to be in good condition with no missing or damaged pieces. ' Located at the east wall building department area are two small offices. The offices are constructed in the same way the main area is, using the same materials, and appears to be in the same condition. Located between the main area and the offices are wood doors +.`. with metal doorframes. The doors appear to be in good condition _ with some wear noted. The frames appear to be in good condition with some wear noted. The hardware on the doors appears to be in good condition and function properly. Located on the west wall is the entry door system to the main area. The door is constructed of wood and glass with a hollow metal frame, which includes a sidelight. The door appears to be in fair A48 South Windsor Town Hall Capital Needs Assessment Architectural condition with some damage noted. The metal frame appears to be in good condition with some paint missing or chipping. The hardware appears to function properly. Located along the east wall of the offices are groups of windows. There are six windows in total, one in each office and four in the open main area. Each window measures 44 1/8"wide by 64 '/4" ' tall, and are constructed of steel and glass on their outer section and aluminum and glass on the inner section. The inner windows appear to be in fair condition, and although dirty, appear to function properly. The outer windows appear to be in poor condition with rust indicated. The windows appear to function properly, although very tough to operate. The sills at these locations are constructed of wood and appear to be in good ' condition. A large amount of caulk was noted around these windows. One window was cracked and damaged during our walkthrough. Recommendation: :_ • Patch sections of damaged walls. • Prep,prime and paint patched walls to match existing. • Prep,prime and paint metal door frames. • Replace outer window. i, • Clean all brick walls. Mechanical Room: Located directly above the foyer is a mechanical room. The mechanical room is constructed of concrete floors, concrete block ' walls, no ceiling tiles and a gypsum soffit alone the east wall. The floors in this location appeared to be in fair condition with no damage noted, but paint peeling and chipping. The walls appeared to be in fair condition with some cracks and damage noted. The soffit appeared to be in good condition as well. The roof beams are visible in this location and appear to be in good condition with ' paint chipping and peeling and some slight rust showing. Located on the east wall of the mechanical room is the entrance door. The door is constructed of wood with a metal doorframe. The door appears to be in good condition with some wear noted. The frame appears to be in good condition with some chipping and missing paint noted. Recommendation: • Patch and repair all damage to concrete block walls. ' • Prep,prime and paint all roof trusses. • Prep,prime and paint all floors and walls. • Prep,prime and paint metal doorframe. ' 49 South Windsor Town Hall Capital Needs Assessment Architectural • Remove and replace any and all Firestop at wall,floor and ceiling penetrations. ROOF: -Main Roof: Located above the building is the roof. The roof is accessed solely by stair A. As you exit the stair you come out on the lower roof section. The roof is a built up design, with a steel deck, coated felt material and a gravel top course. There is a V —9"tall parapet located along all sides at the facade. The parapet has a copper cap along its top edge, as well as copper termination strips where the roof meets the brick fagade. There are roof drains located along the center of the roof running east to west. The built up roof appears to be in fair condition with cracking noted at many areas of coated felt on the parapet. The copper cap and termination strips appear to be weathered and damaged and in poor condition. Located at the brick facades within the lower roof was caulk, which appears to have been added due to leaking. The roof drains located on the lower roof appeared to be functioning properly. There were areas of standing water and ice located throughout the roof. -Upper Roof: Located above the council chamber is the upper roof. This roof is accessed by the lower roof. The roof is a built up design, with a steel deck, coated felt material and a gravel top course. There is a V —9"tall parapet located along all sides at the fagade. The parapet has a copper cap along its top edge, as well as copper termination strips where the roof meets the brick fagade. There are roof drains located along the north edge of the roof running east to west. The built up roof appears to be in fair condition with cracking noted at many areas of coated felt on the parapet. The ' copper cap and termination strips appear to be weathered and damaged and in poor condition. The roof drains located on the upper roof appeared to be functioning properly, although one drain appears to be flowing water directly below a roof top unit. There were areas of standing water and ice located throughout this roof as well. 50 South Windsor Town Hall Capital Needs Assessment ' Architectural -Stair Roof. Located above stair A is the roof. This roof is constructed in the same manner as the previous roofs. There is a parapet located on all sides with the same construction as the lower roof sections. The condition of this roof appears the same as the previously mentioned roofs. -Slate Roofs: Located above the main entrance, the north entrance,the balcony, t and the north and east section of windows is a slate shingled roof. This roof is constructed of wood gussets and sheathing, a plaster soffit and slate shingles. These roofs appear to be in fair condition. P. The slate shingles appear to be weathered with some damage and cracking, but no missing shingles were noted. The plaster soffits appear to be in fair condition as well with some staining and slight damage noted. There were no signs of sheathing damage that could be seen, noted. -Balconies: ' Located between the upper floor and the roof along stair A was the balcony. The balcony is constructed of a slate floor, with a metal handrail, and walls consisting of the brick fagade. The floor ' appears to be in fair condition with some cracking noted. The handrail appears to be in fair condition with rust evident and paint peeling. ' Recommendation: • Remove and replace existing membrane. • Remove and replace all copper caps. ' • Remove all caulk at brick fagade and copper edges. • Clean all roof drains. • Repoint areas of brick located within the roof. BUILDING EXTERIOR: -Exterior: Located at the face of the entire building is the exterior fagade. The fagade is constructed of a concrete foundation, brick in a running bond pattern, and slate tiles above the doorways. The bricks also create a sill and header at each window, as well as a decorative shadow feature between the windows along the north and east walls. The concrete foundation appears to be in fair condition with cracking and damage noted, especially along the southeast corner. ' The brick fagade, including the headers, sills and decorative areas ' 51 ' South Windsor Town Hall Capital Needs Assessment ' Architectural appears to be in good condition with some small sections of damage noted. The mortar located between the brick appears to be in fair condition with some damage and broken areas noted. Many areas of heavy staining were noted on the lower half of the building. Located above the windows was also a steel header. This header appears to be in fair condition with some rust and missing ' paint noted. Recommendation: • Power wash complete exterior fagade. • Replace all damaged and broken bricks. • Repoint all areas of damaged mortar. i, • Remove and replace all caulk around windows. • Prep,prime and paint all steel headers. • Apply waterproof sealant complete exterior fagade. ' 52 ' South Windsor Town Hall Capital Needs Assessment ' Plumbing ' CAPITAL NEEDS ASSESSMENT—PL UMBING A walkthrough of the facility was executed on January 6th and 9th,2009,to assess the plumbing system condition of the existing facility. The plumbing system assessment was carried out by Sherman Taylor, Salamone&Associates,P.C. General • Please note recommendations are based on continuation of Note maintenance as recommended by respective manufacturers. • Please note components and materials original to the building may contain hazardous materials and should be tested prior to implementation of any construction. This testing is beyond this ' reports scope of work. See Architectural report for roof drains section. EXTERIOR: ' Hose bibs are located on the building's exteriors and provide a convenience for the use of domestic cold water. Each hose bib is connected to a 1/4" domestic cold water branch pipe located within the existing wall cavity. All the fixtures appear to be in fair condition with minor signs of deterioration and original to the building. Branch piping located in the central shaft was not visible ' during our site visit. Recommendation: ' • Replacement of the Hose Bibs and associated accessories due to the respective age of the fixture. On the buildings Southern exterior a 3000 gallon underground fuel ' storage tank is found. The tank measures at 64'-0"x18'x0"long and sits on a 20'-0"x7'-4"x24" concrete pad. Above grade on the buildings exterior the leak detection system alarm and associated accessories are present. The leak detection control panel is located in the Mechanical Equipment Room. The tank is connected to two (2) sets of fuel oil supply and return piping which feeds the hot ' water boiler and domestic water heater. No access to the tank was available during our offices site visit. ' Recommendation: • Refer to manufacturer's maintenance requirements and ' coordinate with service contractor. ' 53 South Windsor Town Hall ' Capital Needs Assessment Plumbing INTERIOR SYSTEMS: ' SANITARY DRAINAGE SYSTEM: ' The building's cast iron sanitary drainage system consists of one (1) 6" sanitary building drain pipe routed from the street. The 6" main serves the plumbing fixtures located throughout the building's levels. The sanitary system ventilation is provided through two (2)vent pipes measuring at 1-1/2" and 2". Each pipe is routed to the main roof through the buildings central shaft. The overall appearance of the system appeared to be fair with minor sign of deterioration on the cast-iron main located in the mechanical room. Several revisions have been made to this system over recent years, with the remainder being original to the building. Recommendation: i_ _ • Regular inspections to be provided by onsite maintenance. • Replacement of the following items at the year 9 mark: Sanitary main and vent system piping due to the respective age of the components. ' STORM DRAINAGE SYSTEM: The building's storm storm drainage system consists of a under slab 8"main under slab which is routed to the central shaft and ' Picture then down to the eastern shaft. Prior to entering the shafts the 8" main transitions down to 3" and 4"branch mains. These branch Unavailable mains are then routed to the various roof drains. During our offices ' site visit a secondary storm system was not visble. The primary system has strom leaders routed to the roof drains lcoated throughout the main and upper roof. The piping appeared to be ' original to the building and in fair condition. Recommendation: ' • Replacement of the following items at the year 9 mark: Storm main piping due and associated accessories due to the respective age of the components. ' 54 So uth Windsor Town Hall ' Capital Needs Assessment Plumbing ' DOMESTIC SYSTEM: Domestic cold water service for the building enters at 1 1/4" and is routed to the city meter located in the mechanical room. From the ' meter the main splits to feed the Domestic Water Heater, Cast Iron Boiler and the various plumbing fixtures located throughout the building. The overall appearance of the piping and fiberglass ' insulation appeared to be fair with deterioration around the various shutoff valves. Branch mains located in the mechanical rooms appeared to over ten (10)years old and in good condition. Branch piping located in the central shaft was not visible during our site visit. Recommendation: u • Replacement of the following items at the year 9 mark: Domestic Cold Water main piping and associated accessories ' due to the respective age of the components. • Replacement of the Domestic Cold Water branch mains associated with fixture replacement. • Contact the Local Water Authority regarding a water meter inspection due to the condition and respective age. 1 ' The Domestic Hot Water for the building is provided by a thirty two (32) gallon oil-fired water heater. Located within the mechanical room the Water Heater is manufactured by the Bock S, Company(model 32E) and provides 102 gallons per hour ' recovery. The water heater is equipped with a Carlin oil burner and a separate hot water recirculation pump. The pump is manufactured by the Bell and Gossett Company (model 389034) ' and appeared to be in good condition. The 3/4"piping leaving the water heater is routed to the central bathrooms located on each level and the small restroom located in the registers office. Fiberglass insulation was found throughout the system and -, appeared to have minor signs of deterioration. Branch piping located in the central shaft was not visible during our site visit. Proving Natural gas to the building can create energy/maintenance savings for the Domestic Water Heater. ' Recommendation: • Replacement of the following items at the year 9 mark: ' Domestic Hot Water main piping and associated accessories due to the respective age of the components. • Replacement of the Domestic Cold Water branch mains ' associated with fixture replacement. • Refer to the Water Heater's maintenance manual for required scheduled maintenance. ' 55 South Windsor Town Ha ll Capital Needs Assessment Plumbing • Addition of natural gas to the building. Yankee Gas has indicated availability. • Replacement of the recirculation pump and associated accessories at ten (10)year mark. LOWER LEVEL LOUNGE: The lounge located on the lower level of the building is equipped with a kitchen sink and a small instant-flow water heater. This unit only provides hot water for the sink. The instant-flow water heater is manufactured by Chromomite Laboratories (Model SR- 20L/208). This unit appears to be in good condition and newer to ' the site. However, the sink in the lounge area appears to be in newer condition, the associated faucet appears to have been updated recently. Branch piping for the sink also appeared to be good condition with no signs of deterioration i Recommendation: ' • Refer to the Water Heater's maintenance manual for required scheduled maintenance. i LOWER LEVEL CORRIDOR: ' A wall mounted drinkingfountain is located in-between the two bathrooms. The fixture is in working condition, appears to be ' original to the building. It also appears that the current spout height of the fixture is not in current ADA code requirements. The associated branch piping for the fixture was not visible during our ' offices site visit. Recommendations: • Replacement of drinking fountain due to the respective age of ' the fixture and current mounting height not being in ADA compliance. 56 South Windsor Town Hall ' Capital Needs Assessment Plumbing LOWER LEVEL RESTROOMS: There are three (3)restrooms in the lower level of the Town Hall ' building; one a men's room and ones women's room and one is a unisex. Within the men's room the fixtures consist of two (2) water closets, one (1)urinal and two (2) wall hung lavatories. The water closets and urinals are manufactured by the Kolher Company and are 1.6 Gallons per flush. Each fixture is equipped with an automatic flush valve that is manufactured by the Sloan Company. The water closets, urinal and associated accessories have been recently replaced and appear to be in good condition. The water closets may not be in compliance with the current mounting ' heights as specified in the ADA code. The associated branch piping for the fixtures was not visible during our offices site visit. Recommendation: • Replacement of one (1) Water Closet due to the respective age of the fixture and current mounting height not being in ADA compliance. The two (2) lavatories are side by side and have several areas of hard water around the drain area. The faucet and drain are original and the faucet is equipped with an aerator. Underneath the fixture the associated branch piping appears to have been replaced in .� recent years. Each fixture appears to be in fair condition with minor signs of deterioration. Due to the respective age of the fixture and the overall condition, the estimated water consumption exceeds a current low consumption fixture. It also appears that the current fixture does not meet the current ADA code requirements of bowl depth and mounting height. The associated branch piping within the shaft for the fixture was not visible during our offices site visit. Recommendations: • Replacement of one (1) Water Closet due to the respective age of the fixture and current mounting height not being in ADA compliance. • Replace with low-consumption aerators for energy savings. ' 57 South Windsor Town Hall Capital Needs Assessment Plumbing Within the women's room the fixtures consist of two (2)water closets and two (2) wall hung lavatories. The water closets and urinals are manufactured by the Kolher Company and are 1.6 Gallons per flush. Each fixture is equipped with an automatic flush valve that is manufactured by the Sloan Company. The water closets, urinal and associated accessories have been recently replaced and appear to be in good condition. The water closets may not be in compliance with the current mounting heights as specified in the ADA code. The associated branch piping for the fixtures was not visible during our offices site visit. Recommendation: ' • Replacement of one (1) Water Closet due to the respective age of the fixture and current mounting height not being in ADA compliance. The two (2) lavatories are side by side and have several areas of hard water around the drain area. The faucet and drain are original and the faucet is equipped with an aerator. Underneath the fixture the associated branch piping appears to have been replaced in recent years. Each fixture appears to be in fair condition with minor signs of deterioration. Due to the respective age of the fixture and the overall condition, the estimated water consumption ' exceeds a current low consumption fixture. It also appears that the 4 r current fixture does not meet the current ADA code requirements of bowl depth and mounting height. The associated branch piping within the shaft for the fixture was not visible during our offices site visit. rRecommendations: • Replacement of the lavatories due to the respective age of the fixture and current bowl depth/mounting height not being in ADA compliance. • Replace with low-consumption aerator for energy savings. Adjacent to the women's restroom a janitor's closet and sink reside. The mop sink is in a tiled area with a large faucet and floor drain. The mop sink and faucet appear to be in working condition, original to the building. Due to the respective age of the fixture and the overall condition, the estimated water consumption exceeds a current low consumption fixture. Recommendations: • Replace with low-consumption model for energy savings. ' 58 South Windsor Town Hall ' Capital Needs Assessment Plumbing The unisex restroom located within the Registrar's offices is equipped with a water closet and a lavatory. The water closet is a flush valve type and is manufactured by the Church Company. The fixture appeared to be in good condition with no signs of deterioration. The water closet may not be in compliance with the current mounting heights as specified in the ADA code. The associated branch piping for the fixtures was not visible during our offices site visit. Recommendations: • Replacement of the water closet and associated accessories and replace with a automatic flush fixture to match the remaining existing water closets The faucet and drain are original and the faucet is equipped with an aerator. Underneath the fixture the associated branch piping appears to have been replaced in recent years. Each fixture appears to be in fair condition with minor signs of deterioration. Due to the respective age of the fixture and the overall condition, the estimated water consumption exceeds a current low consumption fixture. It also appears that the current fixture does not meet the current ADA code requirements of bowl depth and mounting height. The associated branch piping within the shaft for the fixture was not visible during our offices site visit. Recommendations: • Replacement of the lavatories due to the respective age of the fixture and current bowl depth/mounting height not being in ADA compliance. • Replace with low-consumption model for energy savings. j 59 South Windsor Town Hall Capital Needs Assessment Plumbing MAIN LEVEL LAVATORIES: a There are two (2)restrooms in the main level of the Town Hall building; a men's room and women's room. Within the men's room the fixtures consist of two (2)water closets, one (1)urinal and two (2)wall hung lavatories. The water closets and urinals are manufactured by the Kolher Company and are 1.6 Gallons per flush. Each fixture is equipped with an automatic flush valve that is manufactured by the Sloan Company. The water closets, urinal and 41..; associated accessories have been recently replaced and appear to be in good condition. The water closets may not be in compliance 7t with the current mounting heights as specified in the ADA code. The associated branch piping for the fixtures was not visible during our offices site visit. Recommendation: • Replacement of one (1) Water Closet due to the respective age of the fixture and current mounting height not being in ADA compliance. The two (2) lavatories are side b side and have several areas eas of hard water around the drain area. The faucet and drain are original and the faucet is equipped with an aerator. Underneath the fixture the associated branch piping appears to have been replaced in - recent years. Each fixture appears to be in fair condition with minor signs of deterioration. Due to the respective age of the fixture and the overall condition,the estimated water consumption exceeds a current low consumption fixture. It also appears that the current fixture does not meet the current ADA code requirements of bowl depth and mounting height. The associated branch piping within the shaft for the fixture was not visible during our offices site visit. Recommendations: • Replacement of the lavatories due to the respective age of the fixture and current bowl depth/mounting height not being in ADA compliance. • Replace with low-consumption aerators for energy savings. 60 South Windsor Town Hall Capital Needs Assessment Plumbing Within the women's room the fixtures consist of two (2)water closets and two (2)wall hung lavatories. The water closets and urinals are manufactured by the Kolher Company and are 1.6 Gallons per flush. Each fixture is equipped with an automatic flush 1 valve that is manufactured by the Sloan Company. The water k closets, urinal and associated accessories have been recently w replaced and appear to be in good condition. The water closets may ' not be in compliance with the current mounting heights as specified in the ADA code. The associated branch piping for the fixtures was not visible during our offices site visit. Recommendation: • Replacement of one (1) Water Closet due to the respective age of the fixture and current mounting height not being in ADA compliance. The two (2) lavatories are side by side and have several areas of hard water around the drain area. The faucet and drain are original and the faucet is equipped with an aerator. Underneath the fixture the associated branch piping appears to have been replaced in recent years. Each fixture appears to be in fair condition with -.mom minor signs of deterioration. Due to the respective age of the fixture and the overall condition, the estimated water consumption 4 exceeds a current low consumption fixture. It also appears that the current fixture does not meet the current ADA code requirements of bowl depth and mounting height. The associated branch piping within the shaft for the fixture was not visible during our offices site visit. Recommendations: • Replacement of the lavatories due to the respective age of the fixture and current bowl depth/mounting height not being in ADA compliance. • Replace with low-consumption model for energy savings. Adjacent to the women's restroom a janitor's closet and sink reside. The mop sink is in a tiled area with a large faucet and floor drain. The mop sink and faucet appear to be in working condition, original to the building. Due to the respective age of the fixture and ' the overall condition, the estimated water consumption exceeds a current low consumption fixture. Recommendations: • Replace with low-consumption model for energy savings. 61 j South Windsor Town Hall Capital Needs Assessment Plumbing UPPER LEVEL RESTROOMS: There are two (2)restrooms in the main level of the Town Hall building; a men's room and women's room. Within the men's room the fixtures consist of two (2) water closets, one (1)urinal and two (2) wall hung lavatories. The water closets and urinals are manufactured by the Kolher Company and are 1.6 Gallons per flush. Each fixture is equipped with an automatic flush valve that is manufactured by the Sloan Company. The water closets, urinal and associated accessories have been recently replaced and appear to be in good condition with the exception of one of the water closets base has a large crack. The water closets may not be in compliance with the current mounting heights as specified in the ADA code. The associated branch piping for the fixtures was not visible during our offices site visit. Recommendation: • Replacement of one (1) Water Closet due to the respective age of the fixture and current mounting height not being in ADA compliance. • Repair crack at water closet base. The two (2) lavatories are side by side and have several areas of hard water around the drain area. The faucet and drain are original and the faucet is equipped with an aerator. Underneath the fixture the associated branch piping appears to have been replaced in recent years. Each fixture appears to be in fair condition with minor signs of deterioration. Due to the respective age of the fixture and the overall condition, the estimated water consumption exceeds a current low consumption fixture. It also appears that the current fixture does not meet the current ADA code requirements of bowl depth and mounting height. The associated branch piping i within the shaft for the fixture was not visible during our offices site visit. Recommendations: • Replacement of one (1) Water Closet due to the respective age I of the fixture and current mounting height not being in ADA compliance. • Replace with low-consumption aerators for energy savings. 62 South Windsor Town Hall Capital Needs Assessment Plumbing Within the women's room the fixtures consist of two (2)water closets and two (2)wall hung lavatories. The water closets and urinals are manufactured by the Kolher Company and are 1.6 Gallons per flush. Each fixture is equipped with an automatic flush valve that is manufactured by the Sloan Company. The water closets, urinal and associated accessories have been recently replaced and appear to be in good condition. The water closets may not be in compliance with the current mounting heights as specified in the ADA code. The associated branch piping for the fixtures was not visible during our offices site visit. Recommendation: • Replacement of one (1) Water Closet due to the respective age of the fixture and current mounting height not being in ADA compliance. The two (2) lavatories are side by side and have several areas of hard water around the drain area. The faucet and drain are original and the faucet is equipped with an aerator. Underneath the fixture 7 the associated branch piping appears to have been replaced in recent years. Each fixture appears to be in fair condition with minor signs of deterioration. Due to the respective age of the fixture and the overall condition,the estimated water consumption exceeds a current low consumption fixture. It also appears that the current fixture does not meet the current ADA code requirements of bowl depth and mounting height. The associated branch piping within the shaft for the fixture was not visible during our offices site visit. Recommendations: • Replacement of one (1) Water Closet due to the respective age of the fixture and current mounting height not being in ADA compliance. • Replace with low-consumption model for energy savings. Adjacent to the women's restroom a janitor's closet and sink reside. The mop sink is in a tiled area with a large faucet and floor drain. The mop sink and faucet appear to be in working condition, original to the building. Due to the respective age of the fixture and the overall condition, the estimated water consumption exceeds a current low consumption fixture. Recommendations: • Replace with low-consumption aerators for energy savings. 63 South Windsor Town Hall Capital Needs Assessment Mechanical(HVAC) CAPITAL NEEDS ASSESSMENT—MECHANICAL (HVAC) A walkthrough of the facility was executed on January 6th and 9 h,2009,to assess the mechanical system condition of the existing facility. The mechanical assessment was carried out by Sherman Taylor, Salamone&Associates,P.C. General • Please note recommendations are based on continuation of Note maintenance as recommended by respective manufacturers. • Please note components and materials original to the building may contain hazardous materials and should be tested prior to implementation of any construction. This testing is beyond this reports scope of work. EXTERIOR The building's exterior western face has four(4) fresh air intake �= x louvers located in an areaway beneath grade. The louvers are aluminum fixed blade with bird screens. Each louver provides r fresh air to the following areas: A 32"06"louver is connected to a 32"xl2"duct routed to the transformer vault. A 24"06" louver is connected to a 24"x 12" duct routed to the elevator machine room. A 36"x36" louver is connected to a 36"x24" duct routed to the air `.`` handling unit. A 24"x36" louver is connected to a 24"x24"duct routed to the mechanical room. Each louver appeared to be original to the building with minor dirt/debris on the exterior faces. € The weatherproofing caulking around each louver also appeared to be failing. Recommendation • Clean louvers and associated ductwork. • Remove and replace weatherproof caulking. Located in the buildings northeast corner behind a fenced area an air cooled condensing unit sit on a 6" concrete pad and provides cooling to an air handling unit located on the lower level. The unit is manufactured by the Carrier Company and provides eight(8) and a half tons of cooling. One (1) set of refrigerated and suction lines are routed into the building to the cooling coil located within ' s the air handling unit. The unit appears to be over twenty(20)years old with deterioration(rust) found on the casing and fan guards. The insulation around the refrigerant pipe appears to have mold covering the lower portion. The estimated Seasonal Energy Efficiency Ratio is 10 SEER, current replacement units can range f` from 11-13 SEER. 64 ISouth Windsor Town Hall Capital Needs Assessment Mechanical (HVAC) `( Recommendation: • Replacement of unit and associated accessories due to the estimated life span, deterioration level and current energy consumption. A current replacement can provide Higher efficiency, thus creating energy savings. • Heating Ventilation and Air Conditioning rebates are currently available from Connecticut Light and Power. Coordinate selection of equipment with CL&P prior to installation. INTERIOR LOWER FLOOR: STAIRWELL B: The lower landing of Stairwell B is conditioned by an 12"xl2" supply diffuser and provides 200 CFM of heating and cooling. The diffuser is connected to an 12"x15"which connects to an 10"0 branch main duct, which in turn is connected to an 12"O main duct from the Mechanical Room. The diffuser is manufactured by the Titus Company(Model TMD-S 1) and appeared to be original to be original to the building with minor signs of deterioration. During our offices site visit it was noted that this area appeared to have an insufficient amount of airflow. MRecommendation: • Clean existing diffuser and associated ductwork. ELEVATOR LOBBY: Over the main rear entrance to the building a two (2) foot linear diffuser provides 150 CFM of heating and cooling to this area. The diffuser is connected to an 6"0 duct which connects to an 10"0 branch main duct, which in turn is connected to an 12"0 - 11 main duct from the mechanical room. The diffuser is manufactured by the Titus Company(Model MU500) and appeared to be original to the building with minor signs of debris (dust) on the units face. Recommendation: I • Clean existing diffuser and associated ductwork. 65 South ut Windsor Town Hall Capital Needs Assessment Mechanical (HVAC) Supplemental heat for the elevator lobby is provided through a wall mounted electric unit heater. The Dayton Company manufacturers the heater and is controlled by an integral thermostat. The unit appeared to be over twenty(20)years old with debris (dust) on the unit casing. Recommendation: • Due to the respective age of the unit replacement is warranted. ELEVATOR MACHINE ROOM: rFresh air for the elevator is provided through a 24"x12" fresh air grille that is connected to a 24"x 12"duct with a full size fire damper. The grille is mounted at the shared wall of the Communications Room. The Titus Company(Model RH 55) manufacturers the grille and it appeared to be original to the building with minor deterioration present. Recommendation.- 0 Remove and replace fresh air grille. • Clean all ductwork associated with grille. TRANSFORMER VAULT: During our office's site visit access to this areas was not available due to it being controlled by the local electrical company. After Picture reviewing the existing plans, a 12"02"fresh air grille provides Unavailable ventilation to this area through a 12"02"duct with a full size fire damper. The Titus Company(Model RH 55)manufacturers the grille and it would appear to be original to the building. Recommendation: • Replace grille if deterioration is present. • Clean all ductwork associated with grille. 66 j South Windsor Town Hall Capital Needs Assessment Mechanical (HVAC) COMMUNICATION ROOM: This room has several fresh air ducts that originate from the exterior louvers located inside the areaway. The ductwork is routed to the various areas and pieces of equipment to which they serve. The fiberglass insulation for the ductwork appeared to be loose and faulty in some areas. The ductwork and insulation appear to be original to the building and in fair condition. Recommendation: 7777 • Replace faulty areas of fiberglass insulation. r MECHANICAL EQUIPMENT ROOM: This room is home to various pieces of equipment which provide the main heating and cooling for the building. The following paragraphs are separated by specific system and the associated components within. The main source for the buildings hot water is rod oil- fired produced by an oil _ fired cast-iron boiler. The HB Smith Company manufacturers the ' 350 mills boiler and provides 1,374,600 BTU's/HR of hydronic g water. The boiler is constructed of eight (8) cast-iron sections with an oil-fired burner manufactured by the Carlin Company. The fuel-oil supply and return lines are routed under poured concrete and located in front of the burner. The boiler appeared to be original to the building with major signs of leakage around the casing and drums. Due to the current age, condition and lack of a secondary system, removal and replacement is a critical item. The boiler's exhaust is provided through breeching located behind the boiler. A 16"0 main vent is routed to the chimney and is also connected to the domestic water heater. Combustion air for the burner is provided by a 24"x24"duct routed to the building's exterior. The grille is manufactured by the Titus Company(Model RH 55) and appeared to have debris on the face. Both the boiler breeching and combustion air grille appeared to be original to the building and in fair condition. L 67 South Windsor Town Hall Capital Needs Assessment Mechanical (HVAC) Proving Natural gas to the building can create energy/maintenance savings for the Hot Water Boiler. The estimated Annual Fuel Utilization Efficiency is 70 AFUE, current replacement units can range from 85-95 AFUE. Depending on which fuel type is utilized and operating conditions.Natural Gas can provide the highest AFUE. Recommendation: • Due to the age, energy consumption and overall condition replacement of the boiler is warranted. • Addition of natural gas to the building. Yankee Gas has indicated availability and current rebates may be available. 0 Replace existing boiler with two (2) high efficiency boilers to create redundancy and produce energy savings. Piping for the hot water supply and return originate at the boilers AP Y supply and return drums at 3". The HWS/HWR piping are apart of 1 4� a four(4)pipe system with the chilled water supply and return. Off the 3"main piping, a circulator pump manufactured by the Leland Furadey Company(Model M251A) and is designed for 80 GPM @ 15 H.D. and %HP motor. Water expansion for the system is provided by a floor mounted expansion tank that appears to be newer to the facility. A 2"HWS/HWR is routed to the heating coil r �r located inside the central station air handling unit located in the Mechanical Equipment Room. Another set of HWS/HWR pipes come off the main at 4"end and is routed to the lower/upper level fan coil units located in the Vault. A 1 %" HWS/HWR branch main is routed off the main shaft to the upper levels air handling units heating coil. The last branch main is routed to the IT Room ! closet fan coil units heating coil. Full size shutoff valves throughout the system appear to original to the building with the exception of the first valve on the main supply which appears to have been replaced within recent years. Minor deterioration at the original valve stems and fiberglass insulation were witnessed during our office's site visit. All the supply and return piping is well insulated with fiberglass wrapped insulation throughout. The overall appearance was poor considering the insulation is stained,torn, and loose. The circulator pump appeared to be over ten(10)years old and in fair condition. ' 68 South Windsor Town Hall Capital Needs Assessment Mechanical (HVAC) Recommendation: • Remove and replace existing valves due to age and deterioration level. • Due to the age and condition of the circulator pump replacement is warranted. • Remove and replace fiberglass insulation in faulty areas. The main source for the buildings chilled water is provided by an s indoor reciprocating chiller manufactured by the Carrier Company (Model 30HJO45400). The chiller provides forty (40)tons of cooling to the various cooling coils located throughout the facility. The condenser piping from the roof unit is routed down to the chiller through a central shaft. The piping includes two (2) liquid suction lines at 1 3/8"and one (1) at 1 1/8". The hot gas lines have a total of three (3) sized at 7/8". The indoor chiller and associated liquid section and gas lines appear to be original to the building and in fair condition. The estimated Seasonal Energy Efficiency Ratio is 10 SEER, current replacement units can range from 11-13 SEER, thus creating energy savings. Recommendation: • Replacement of unit and associated accessories due to the estimated life span, deterioration level and current energy consumption. A current replacement can provide Higher efficiency, thus creating energy savings. • Heating Ventilation and Air Conditioning rebates are currently available from Connecticut Light and Power. Coordinate selection of equipment with CL&P prior to installation. 69 B South Windsor Town Hall Capital Needs Assessment Mechanical (HVAC) j Piping for the chilled water system originates at the chiller at 4" and is route through winter/summer shutoff valves to a circulator ' pump. During our office's site visit the nameplate for the chilled I water pump is non-legible, after reviewing the existing drawings it _s is indicated as an Taco (Model CC-3-49) %Hp, 160 GPM at 16' ( H.D. Piping for the hot water supply and return originate at the $' boilers supply and return drains at 3". The CWS/CWR pipes are apart of a four(4)pipe system with chilled water supply and return f of the 3"main piping,An 3" CWS/CWR is routed to the AHU coil located inside the central station air handling unit located in the Mechanical Equipment Room. Another set of CWS/CWR pipes f come off the main at 4" and is routed to the lower/upper level fan + coil units located in the Vaults. A 1 '14" CWS/CWR branch main is °y routed off the main shaft to the upper levels air handling units heating coil. The last branch main is routed to the IT Room closet i _ fan coil unit heating coil. Full size shutoff valves throughout the system appear to original to the building with the exception of the first valve on the main supply pipe appears to have been replaced within recent years. Minor deterioration at the original valve stems were witnessed during our office's site visit. _ The chilled water piping is insulated with fiberglass wrapped insulation throughout. In some areas the insulation is stained, torn, ' and loose. The overall appearance was fair considering the piping and insulation are original to the building. The circulator pump appeared to be over ten(10)years old and in poor condition. Recommendation: S • Remove and replace chilled water shutoff valves due to deterioration. j y • Remove and replace circulator pump due to the respective age A of the unit. ;�'� 1 r ;, • Remove and replace fiberglass insulation in faulty areas. Forced air heating and cooling is provided to the building through a blow-thru central station air handling unit. The unit is manufactured by the Carrier Company(Model 39CA100_129) and is located in the center of the mechanical room. The unit has two (2) integral coils, one (1) for heating and one (1) for cooling. Supply ductwork for the unit begins at the end of the unit and is routed to the various zones located throughout the building. Three (3) existing ducts have been capped, due to the addition of the fan 70 South Windsor To wn Hall Capital Needs Assessment Mechanical (HVAC) --- '' coil unit located in the IT closet. The sizes range from 8"0 to 24"x 12" and has fiberglass insulation throughout. Return air for the system is provided by a 47"x14"return duct routed to a separate return fan located in the adjacent supply room. The Air Handler is currently controlled by the Metasys control ' panel which sets the operation defaults and monitoring. Control dampers within the units supply main are interconnected to the five (5) zones located throughout each level. Thermostats and sensors located within the zones control the corresponding damper. The entire system appeared to be original to the building and in fair condition with minor deterioration at the unit and faulty insulation on the ductwork. The current zone configuration is limited to five " (5) zones, a replacement unit can introduce supplemental zones for additional comfort. The estimated Energy Efficiency Ratio is 10 EER, current replacement units can range from 11-13 EER, thus creating energy savings. Recommendation: • Replacement of unit and associated accessories due to the estimated life span, deterioration level and current energy consumption. A current replacement can provide Higher efficiency, thus creating energy savings. 0 Heating Ventilation and Air Conditioning rebates are currently available from Connecticut Light and Power. Coordinate selection of equipment with CL&P prior to installation. • Clean associated ductwork and filters. • Remove and replace fiberglass insulation in faulty areas. The buildings control system consists of two (2) Honeywell pneumatic panels and one (1) Johnston Controls Metasys Panel. The pneumatic panel appeared to be reading system temperatures while the Metasys system provides the overall system control. - Outdoor set points control the circulator pumps, boiler burner, chiller, air cooled condensing unit, control valves and the central station air handler. The pneumatic compressor which serves the components throughout the building is located beneath the central panels and is equipped with an external dryer. The compressor appears to be ten (10)years old and in bad condition. The dryer appears to be over five (5)years old and in good condition. 71 South Windsor To wn Hall Capital Needs Assessment Mechanical (HVAC) N m — The Honeywell panels appear to be original to the building and in fair condition. In the year 2007,the Metasys panel was installed and it appears to be in good condition. Recommendation: • Maintain scheduled maintenance as required by the manufacturer. • Remove compressor and associated accessories. • Provide a full Direct Digital Control system. I.T. OFFICE: The open office area is conditioned by a separate direct expansion fan coil unit located in an adjacent closet. The unit is manufactured by the Carrier Company(Model 40 BA009300) and provides a nominal 3,900 CFM. Supply and return ductwork for the units is also routed to the various diffusers in the conference rooms and lounge. The unit zones are locally controlled by a wall mounted thermostat manufactured by the Honeywell Company. Heating for the unit is provided by an integral heating coil that is connected to a 1"hot water supply and return piping stemming from the boiler room. Cooling for the unit is provided through a integral coil that is connected to the exterior air cooled condensing unit via refrigerant lines. The estimated Energy Efficiency Ratio is 10 EER, current replacement units can range from 11-13 EER, thus creating energy savings. Condensate for the unit is provided by a 2"PVC pipe to a capped r floor drain located within the closet. All the supply and return ductwork is insulated with fiberglass insulation throughout. The = unit appears to be over twenty(20)years old and in good z, condition. The supply diffuser and return grille within the space appeared to have debris (dust) located on the component faces. Recommendation: • Replacement of unit and associated accessories due to the estimated life span, deterioration level and current energy consumption. A current replacement can provide Higher efficiency, thus creating energy savings. • Heating Ventilation and Air Conditioning rebates are currently available from Connecticut Light and Power. Coordinate selection of equipment with CL&P prior to installation. • Clean diffusers, grilles and associated ductwork. ' 72 South Windsor Town Hall Capital Needs Assessment Mechanical (HVAC) Cooling for the server room located behind the IT office is provided by two (2) air conditioning units. The first unit located near the entrance is manufactured by the Koldwave Company (Model 4WK26AGAIAAAO) and provides 26,000 BTU/HR of cooling to the area. Chilled water supply and return lines measure at 1"and is routed to the integral coil within the unit. Condensate is removed by an integral pump within the unit. Condensate from the unit is removed with piping routed to a local drain. The unit's control system is integral and also provided through the Johnston control panel located within the room. According to the noted located on the manual the unit was installed in 2006 and appeared to be in good condition. Recommendation: • Perform regularly scheduled maintenance as required by manufacturer. Located toward the back of the server room a second cooling unit �j- is mounted on a drain pan. The unit is manufactured by the Koldwave Company(Model K14Df) and provides 14,000 BTU/HR of cooling to the area. Chilled water supply and return lines measure at 1" and is routed to the non-integral coil within the unit. Condensate is removed by a non-integral pump located outside of the unit and routed to a local drain. The unit's control system is integral and also provided through the Johnston control panel located within the room. The unit appeared to be over twenty (20) years and in poor condition. The estimated Seasonal Energy Efficiency Ratio is 10 SEER, current replacement units can range from 11-13 SEER,thus creating energy savings. Recommendation: • Replacement of unit and associated accessories due to the estimated life span, deterioration level and current energy consumption. A current replacement can provide Higher efficiency, thus creating energy savings. The server room also has a single supply diffuser located within the room's center. During our office's site visit, it was observed that no air flow control was found and warm air was flowing out of the diffuser. Leftover tape was found on the diffusers face indicating prior blockage to the diffuser. Recommendation: • Provide volume damper in existing supply ductwork. ' 73 South Windsor Tow n Hall Capital Needs Assessment Mechanical (HVAC) MENS AND WOMEN'S RESTROOMS: >l Exhaust for each toilet room is provided through an 8"x8" exhaust grille. Each grille provides 100 CFM of exhaust and is manufactured by the Titus Company(Model TMD-51). The grille ' is connected to a 8"x4" duct which is routed to the 8"0" open ended main located in the central shaft. Each grille appeared in fair condition, original to the building and with minor amounts of :u debris located on the grilles face. Recommendation: • Clean grilles and associated ductwork SPRINKLER, MADDEN ROOM AND LOUNGE: #" These three (3) areas are conditioned by the fan coil unit located in the IT rooms supply closet. Each room has a supply and return grilles and are connected by fiberglass insulated ductwork routed to and from the fan coil unit. Room is considered to be a zone and is controlled by a separate wall mounted thermostat manufactured i by the Honeywell Company. In many areas the fiberglass insulation is loose, torn, missing and the ceiling tiles near the grilles are dirty. All the components appear to be over twenty(20) , t years old and in fair condition. ' Recommendation: • Clean diffusers, grilles and associated ductwork. • Replace faulty areas offiberglass insulation. MAINTENACE OFFICE: No heating and cooling supply diffusers where observed in the area. The central station air handler's return air is routed through this area to a ceiling mounted return fan. The fan is manufactured by the Carrier Company(model 3913080) and provides 7840 CFM of return air. Originating from the central station air handler a 74 South Windsor s Town Hall Capital Needs Assessment Mechanical (HVAC) 47"x 14"return duct is routed to the inline fan. After the fan a 24"x20"main duct is routed to the areas perimeter wall. From that ' point, five (5) 14" 0 open ended return ducts are routed to the various shafts located in the building. Each duct is equipped with a fire damper and provides the return air back to the system through the plenum returns. The estimated Energy Efficiency Ratio is 10 EER, current replacement units can range from 11-13 EER,thus creating energy savings. Recommendation: • Replacement of unit and associated accessories due to the estimated life span, deterioration level and current energy consumption. A current replacement can provide Higher efficiency, thus creating energy savings. VAULT: ' Heating and cooling for the vault are provided through two (2) may. ceiling mounted fan coil units. The units are manufactured by the gill Trane Company (model D, coil type Q. An integral coil is fed from two (2) insulated%" supply and return lines. The coil is rated for both heating and cooling and is controlled by a valve ' located within the mechanical room. The control valve is installed between the hot/chilled water supply and return piping and depending on the season the valve will open to the appropriate ' water supply. Condensate for the units is drained through a%" pipe that is routed to a lower level drain. The integral fan is controlled by a wall mounted thermostat manufactured by the Honeywell Company. A second thermostat was found underneath one of the units. The Dayton company manufactured this unit and it appeared to be newer to the building. The units and thermostat = L appeared to be in fair condition with minor deterioration on the casing. All the units appeared to be original to the building with _ the exception of the Dayton thermostat. The estimated Energy Efficiency Ratio is 10 EER, current replacement units can range from 11-13 EER, thus creating energy savings. �> Recommendation: -, taon: • Replacement of unit and associated accessories due to the estimated life span, deterioration level and current energy consumption. A current replacement can provide Higher efficiency, thus creating energy savings. • Heating Ventilation and Air Conditioning rebates are - currently available from Connecticut Light and Power. i 75 South Winds or Town Hall Capital Needs Assessment Mechanical (HVAC) Coordinate selection of equipment with CL&P prior to installation. • Remove and replace thermostat due to the respective age of the unit. iVentilation for the vault is provided by a ceiling mounted inline exhaust fan located above the drop ceiling. The fan is manufactured by the Fan Tech Company(model FX 12XL) and J =^ provides 730 CFM of ventilation to the area. Ductwork for the fan is mounted on each side of the unit at 24"x6". One side of duct is connected to a 24"x24"return grille rated for 720 CFM and is 41, manufactured by the Titus Company(model ML3400). The remaining duct is routed to a 24"x 12" supply diffuser rated for 720 CFM and is also manufactured by the Titus Company(model TMD-51). No insulation was found on the existing ductwork. Controls for the fan are located on a wall mounted switch located near the main entry and on the fan itself. Debris was found on the grilles face and the remaining components appeared to be in fair condition and original to the building. Recommendation: • Clean associated grille, diffuser and associated ductwork PROBATE OFFICES: ' Heating and cooling for the open n area office is provided by three a= (3) linear diffusers. Located adjacent to the four(4) foot light fixtures each measures at four(4) feet and provide 50 CFM each. The diffusers are connected to a 5" 0 duct which connects to a 9"0 main duct then to a pressure reducing box. The pressure reducing box is manufactured by the Buensod Company and is rated for 250 CFM. An 11" 0 high pressure duct is connected to the other side of the box and originated from the air handler in the Mechanical room. All ductwork is insulated by fiberglass insulation throughout. All the components appeared in fair condition and original to the building. Recommendation: • Option of adding Terminal Re-heat, due to respective age of pressure box and existing conditions. • Clean diffusers and associated ductwork. ' 76 South Windsor Town Hall Capital Needs Assessment Mechanical (HVAC) Conditioning for the Judges quarters is provided by two (2) four - - -:-_= (4) foot linear diffusers that provide 50 CFM each. The linears are ' mounted adjacent to the light fixtures and are connected to a 5" 0 duct which connects to the same 9" 0 main duct and pressure reducing box as the open area. All ductwork is insulated by fiberglass insulation throughout. All the components appeared in fair condition and original to the building. Recommendation: • Option of adding Terminal Re-heat, due to respective age of pressure box and existing conditions. ' • Clean diffusers and associated ductwork. The hearing area's heating and cooling is generated from two (2) four(4) foot linear diffusers located over the existing windows. Each diffuser is rated at 50 CFM each and is manufactured by the ' Titus Company(model ML 5400). The linear is and connected to a 5 O branch duct which connects to a 9"0 main duct then to a pressure reducing box. The pressure reducing box is manufactured ' by the Buensod Company and is rated for 250 CFM. An I O high pressure duct is connected to the other side of the box and originated from the air handler in the Mechanical room. A local wall mounted sensor is monitoring the area temperature. All ductwork is insulated by fiberglass insulation throughout. All the 7, V components appeared in fair condition and original to the building. Recommendation: • Option of adding Terminal Re-heat, due to respective age of pressure box and existing conditions. �` + LL= • Clean diffusers and associated ductwork. ' REGISTARS OFFICES: Heating and cooling for the open area office is provided by four(4) ' linear diffusers. Located near the office entrance two linears "�••� ,;;,,, measure at four(4) feet and provide 75 CFM each. The diffusers are connected to a 5" O duct which connects to a 7" O main duct t then to a pressure reducing box. The pressure reducing box is ' 77 South Windsor Town Hall Capital Needs Assessment Mechanical (HVAC) manufactured by the Buensod Company(model type HS) and is ' rated for 150 CFM. An I 0 high pressure duct is connected to the other side of the box and originated from the air handler in the Mechanical room. The remaining linears are located on the perimeter wall and measure at two (2) feet and provide 75 CFM. Each diffuser is connected to a 5" 0 duct which connects to a 12"x8"main duct then to a pressure reducing box. The pressure reducing box is manufactured by the Buensod Company(model type HS) and is rated for 470 CFM. A 12" 0 high pressure duct is connected to the other side of the box and originated from the air handler in the Mechanical room. A local wall mounted sensor is monitoring the area temperature and is manufactured by the Johnston Control Company. All ductwork is insulated by fiberglass insulation L throughout. All the components appeared in fair condition and original to the building. Recommendation: • Option of adding Terminal Re-heat, due to respective age of pressure box and existing conditions. • Clean diffusers and associated ductwork. This office area also has an internal bathroom which is equipped with a single linear diffuser measuring at one (1) foot and providing 75 CFM of heating and cooling. The diffuser is connected to a 5" 0 duct which connects to a 12"x8"main duct then to the same pressure reducing box as the perimeter diffusers. The associated ductwork is insulated by fiberglass insulation throughout. All the components appeared in fair condition and original to the building. Recommendation: 0 Clean diffusers and associated ductwork. ' The rear office's heating and cooling for the perimeter area under the windows is provided by three (3) linear diffusers. Each linear ' measure at four(4) feet and provide 50 CFM. The diffusers are connected to a 5" 0 duct which connects to an 8" 0 main duct then to a pressure reducing box. The pressure reducing box is manufactured by the Buensod Company(model type HS) and is ' 78 South Windsor Town Hall Capital Needs Assessment Mechanical (HVAC) rated for 200 CFM. An 11" O high pressure duct is connected to the other side of the box and originated from the air handler in the Mechanical room. All the components appeared in fair condition and original to the building. Recommendation: • Option of adding Terminal Re-heat, due to respective age of pressure box and existing conditions. • Clean diffusers and associated ductwork. MAIN LEVEL: STAIRWELL B: Conditioning for the stairwells landing is provided by a 12"x12" supply diffuser manufactured by the Titus Company (model TMD-51). The diffuser provides 200 CFM of heating and cooling fto this area by a 12"x5"duct that originates at a pressure reducing 4 box. Deterioration (rust) is found on the blades of the diffuser and it appeared to be original to the building. 1 Recommendation: • Clean diffusers and associated ductwork. ELEVATOR LOBBY: µ Over the existing window near a two (2) foot linear diffuser which provides 150 CFM heating and cooling to this area. The diffuser is --- — connected to a 6" 0 duct which connects to a 13" 0 main duct to a pressure reducing box. The diffuser is manufactured by the Titus Company (Model ML3500) and appeared to be original to the building with minor signs of debris (dust) on the units face. ' Recommendation: • Option of adding Terminal Re-heat, due to respective age of pressure box and existing conditions. • Clean diffusers and associated ductwork. CONSOLE CHAMBER: See upper level description for this area. ' 79 South Windsor Town Ha ll Capital Needs Assessment Mechanical (HVAC) MENS AND WOMEN'S RESTROOMS: Exhaust for each toilet room is provided through an 8"x8"exhaust grille. Each grille provides 100 CFM of exhaust and is �Win manufactured by the Titus Company(Model TMD-51). The grille is connected to a 8"x4" duct which is routed to the 8"x7" open ended main located in the central shaft. Each grille appeared in fair condition, original to the building and with minor amounts of debris located on the grilles face. Recommendation: • Clean grilles and associated ductwork. COMMON CORRIDOR/ MAIN LOBBY: The ceilings interior perimeter has a full size linear duct with eight (8) four(4) foot linears rated for 100 CFM each. Manufactured by the Titus Company(Model ML 3400 1-A-1). Each diffuser is connected by a 5" 0 branch duct back to the 12" 0 main. A pressure reducing box manufactured by the Buensod Company (model type HS) and is rated for 800 CFM. This zone is controlled by a wall mounted thermostat by the Honeywell Company. An 8" O high pressure duct is connected to the other side of the box and originated from the 10" 0 main riser in the central shaft. All " ductwork is insulated by fiberglass insulation. All the components appear to be in fair condition and original to the building. ' Recommendation: • Option of adding Terminal Re-heat, due to respective age of pressure box and existing conditions. • Remove and replace thermostats due to the respective age of ' the unit • Clean diffusers and associated ductwork. FRONT ENTRY: VA Heating and cooling for the front entry is provided by three (3) ' linear diffusers providing 100 CFM each. Each diffuser is connected to a 5" O duct which connects to a 9" O main duct then to a pressure reducing box. The pressure reducing box is manufactured by the Buensod Company(model type HS) and is rated for 300 CFM. A 6" 0 high pressure duct is connected to the ' other side of the box and originated from the 8" 0 main riser in the ' 80 South Windsor Town Hall Capital Needs Assessment ' Mechanical (HVAC) southeastern shaft. All ductwork is insulated by fiberglass insulation. Deterioration was found on the linears face along with paint failure. With the exception of the linears the remaining components appeared to be in fair condition and original to the building. Recommendation: • Option of adding Terminal Re-heat, due to respective age of pressure box and existing conditions. • Clean diffusers and associated ductwork. ' • Clean and repaint linear face. ' CAUCUS MEETING ROOM: The meeting room for this department is conditioned by two (2) linear diffusers located on the perimeter wall. The linears are two (2) feet long and provide 85 CFM of heating and cooling. Each ' diffuser is connected to a 5"0 branch duct which is routed to the 13"O main off the pressure reducing box. The box is manufactured by the Buensod Company (model type HS) and is fed from an 8" 0 ' high pressure duct that originates from the south western shaft. The box is rated for 670 FPM and all the associated ductwork for the area is insulated with fiberglass insulation. A wall mounted ' thermostat controls the zones and is manufactured by the Honeywell Company. The ductwork's insulation appeared to have `' kx deterioration in several areas and debris was found on the linears ' face. All the components appeared in fair condition and original to the building. The offices located behind the meeting room are conditioned by five (5) linear diffusers located on the perimeter wall. Two (2) of i f ; the linears are (2) feet long and provide 75 CFM of heating and cooling. Each diffuser is connected to a 5"0 branch duct which is routed to the 13" 0 main off the same pressure reducing box as the meeting room. The remaining three (3) linears are four(4) foot long and provide 50 CFM of heating and cooling. Each diffuser is connected to a 5"0 branch duct which is routed to the 9"O main off the pressure reducing box. The box is manufactured by the Buensod Company(model type HS) and is fed from a 6"0 high ' pressure duct that originates from the south western shaft. All the ' 81 South Windsor Town Hall Capital Needs Assessment Mechanical (HVAC) associated ductwork for the area is insulated with fiberglass insulation. The box is rated for 250 CFM and a wall mounted thermostat controls the pressure reducing box and it is manufactured by the Honeywell Company. All the components ' appeared in fair condition and original to the building. Recommendation.- Option of adding Terminal Re-heat, due to respective age of pressure box and existing conditions. • Remove and replace thermostats due to the respective age of the unit • Remove and replace faulty fiberglass insulation. • Clean diffusers and associated ductwork. TOWN MANAGER OFFICES: ' Located adjacent to the meeting room an is open office conditioned p by four(4) linear diffusers located in the center of the area. Each 1 linear is flush to a four(4) foot light fixture and provides 75 CFM of heating and cooling. The diffusers are connected to a 5" O branch duct which is routed to the 9" 0 main then to a pressure reducing box. The box is manufactured by the Buensod Company (model type HS) and is fed from a 10" O high pressure duct that ' originates from the central shaft. The box is rated for 250 CFM and all the associated ductwork for the area is insulated with fiberglass insulation. A wall mounted thermostat controls zone along with area sensors to detect space temperature. The Honeywell Company ' is the manufacturer for the thermostats and Johnston controls for the sensors. The ductwork's insulation appeared to have ' deterioration in several areas and debris was found on the linears face. All the components appeared in fair condition and original to the building The two remaining offices have four(4) linear diffusers located over the existing windows on the perimeter wall. Each linear is ' flush to a four(4) foot light fixture and provides 50 CFM of heating and cooling. The diffusers are connected to a 5" O branch duct which is routed to the 9" 0 main then to the same pressure ' reducing box in the finance office. All the associated ductwork for the area is insulated with fiberglass insulation. A wall mounted thermostat controls the pressure reducing box along with area ' sensors to detect space temperature. The Honeywell Company is the manufacturer for the thermostats and sensors. All the components appeared in fair condition and original to the building. 82 South Windsor Town Hall ' Capital Needs Assessment Mechanical (HVAC) Recommendation: ' • Option of adding Terminal Re-heat, due to respective age of pressure box and existing conditions. • Remove and replace thermostats due to the respective age of ' the unit .: • Remove and replace faulty fiberglass insulation. t • Clean diffusers and associated ductwork. TOWN CLERK ' OFFICES: The open office area is conditioned by four(4) linear diffusers ' located in the areas center. Each linear is flush to a four(4) foot light fixture and provides 75 CFM of heating and cooling. The diffusers are connected to a 5" 0 branch duct which is routed to the 9" 0 main then to a pressure reducing box. The box is manufactured by the Buensod Company(model type HS) and is fed from a 10" O high pressure duct that originates from the central ' shaft. The box is rated for 250 CFM and all the associated ductwork for the area is insulated with fiberglass insulation. A wall mounted thermostat controls the zone along with area sensors to ' detect space temperature. The Honeywell Company is the manufacturer for the thermostats and sensors. All the components appeared in fair condition and original to the building The two rear offices have four(4) linear diffusers located over the ' existing windows and on the perimeter wall. Each linear located under a window provides 50 CFM and the single unit on the perimeter wall provides 70 CFM of heating and cooling. The diffusers are connected to a 5" O branch duct which is routed to ' the 9" O main then to a pressure reducing box. The box is manufactured by the Buensod Company(model type HS) and is ' fed from a 9" 0 high pressure duct that originates from the northeaster shaft. The boxes is rated for 250 CFM and all the associated ductwork for the area is insulated with fiberglass insulation. A wall mounted thermostat controls the pressure reducing box along with area sensors to detect space temperature. The Honeywell Company is the manufacturer for the thermostats ' and sensors. All the components appeared in fair condition and original to the building. ' Recommendation: • Option of adding Terminal Re-heat, due to respective age of pressure box and existing conditions. 83 ' South Windsor Town Hall Capital Needs Assessment ' Mechanical (HVAC) • Remove and replace thermostats due to the respective age of ' the unit • Remove and replace faulty fiberglass insulation. • Clean diffusers and associated ductwork. VAULT: Heating and cooling for the vault are provided through two (2) ceiling mounted fan coil units. The units are manufactured by the - ` Trane Company(model D, coil type Q. An integral coil is fed from two (2) insulated 1/4" supply and return lines. The coil is rated for both heating and cooling and is controlled by a valve located in the mechanical room. The control valve is installed between the hot/chilled water supply and return piping. Depending on the season the valve will open to the appropriate water supply. Condensate for the units is drained through a 1/4"pipe that is routed to the lower level. The integral fan is controlled by a wall mounted thermostat manufactured by the Honeywell Company. A second 1 thermostat was found underneath one of the units. The Dayton Company manufactured this unit and it appeared to be newer to the building. The units and thermostat appeared to be in fair condition with minor deterioration on the casing. The units also appeared to be original to the building. The estimated Energy Efficiency Ratio is 10 EER, current replacement units can range from 11-13 EER, thus creating energy savings. Recommendation.- Replacement of unit and associated accessories due to the estimated life span, deterioration level and current energy €` consumption. A current replacement can provide Higher efficiency, thus creating energy savings. • Heating Ventilation and Air Conditioning rebates are currently available from Connecticut Light and Power. Coordinate selection of equipment with CL&P prior to installation. • Remove and replace thermostat due to the respective age of the unit. Ventilation for the vault is provided by a ceiling mounted exhaust fan located above the drop ceiling. The fan is manufactured by the Penn Company (model REX 30W) and provides 730 CFM of ventilation to the area. Ductwork for the fan is mounted on each side of the unit at 24"x6". One side of duct is connected to a 24"x24"return grille rated for 720 CFM and is manufactured by 84 South Windsor Town Hall Capital Needs Assessment rMechanical (HVAC) the Titus Company(model ML3400). The remaining duct is routed to a 24"x12" supply diffuser rated for 720 CFM and is also manufactured by the Titus Company(model TMD-51).No insulation was found on the existing ductwork. Controls for the fan are located on a wall mounted switch located near the main entry. Debris was found on the grilles face and the remaining components appeared to be in fair condition and original to the building. Recommendation: • Replace existing exhaust fan and associated accessories due to the respective age of the unit. • Clean grille, diffuser and associated ductwork ASSESSORS OFFICES: Heating and cooling for the open office area is provided by four(4) linear diffusers. Each linear is flush to a four(4) foot light fixture and provides 50 CFM of heating and cooling. The diffusers are connected to a 5"0 branch duct which is routed to the 8"0 main then to a pressure reducing box. The box is manufactured by the Buensod Company(model type HS)rated for 200 CFM and is fed from a 5"0 high pressure duct that originates from the southeastern shaft. All the associated ductwork for the area is insulated with fiberglass insulation. A wall mounted thermostat controls the zone and it is manufactured by the Honeywell Company. All the components appeared in fair condition and original to the building. Recommendation: • Option of adding Terminal Re-heat, due to respective age of pressure box and existing conditions. • Remove and replace thermostats due to the respective age of the unit. • Clean diffusers and associated ductwork. 1 _ The two rear offices have four(4) linear diffusers located over the existing windows and on the perimeter wall. Each linear located under a window provides 50 CFM and the single unit on the perimeter wall provides 150 CFM of heating g and cooling. The diffusers are connected to a 5" O branch duct which is routed to the 9" 0 main then to a pressure reducing box. The box is manufactured by the Buensod Company(model type HS)rated for 250 CFM and is fed from a 7" D high pressure duct that originates from the eastern shaft. All the associated ductwork for the area is insulated with fiberglass insulation. A wall mounted thermostat 85 South Windsor Town Hall Capital Needs Assessment Mechanical(HVAC) controls the zone along with area sensors to detect space temperature. The Honeywell Company is the manufacturer for the thermostats and sensors. All the components appeared in fair condition and original to the building. Recommendation: • Option of adding Terminal Re-heat, due to respective age of pressure box and existing conditions. • Remove and replace thermostats due to the respective age of the unit • Clean diffusers and associated ductwork. TAX COLLECTOR OFFICES: The open area has three (3) two (2) foot linear diffusers (model ML 3500)that provide 125 CFM of heating and cooling to the area. One (1) of the linears is connected to a separate pressure reducing box that is manufactured by Buensod Company(model type HS)via a 5" O branch ducts which are connected to the 10" O main. The box is rated for 325 CFM and is fed from a 6" 0 high pressure duct that originates from the eastern shaft. The remaining two (2) diffusers are connected to 5" O branch ducts which are connected to the 10" 0 main routed to the pressure reducing box. The box is rated at 350 CFM and is manufactured by Buensod Company (model type HS). An 8"main high pressure duct is routed from the Southeastern shaft and is routed to the box. After the last linear diffuser the ductwork transitions to a I2"x5" duct to a stairwell diffuser. All the existing ductwork is insulated by fiberglass insulation throughout. During our offices site visit it was noted that the occupants indicated that the area did not provide a sufficient means of heat and no local controls where present. All the components appeared to be original to the building and in fair condition. Recommendation: • Option of adding Terminal Re-heat, due to respective age of pressure box and existing conditions. • Remove and replace thermostats due to the respective age of the unit • Additional components to introduce local control. • Clean diffusers and associated ductwork. The rear office is conditioned by three (3) four(4) foot linear diffusers (model ML 3400) that provide 50 CFM of heating and cooling. All the four(4) foot units are connected to 5" 0 branch ducts which are connected to the 8" 0 main routed to the pressure 86 South Windsor Town Hall Capital Needs Assessment Mechanical (HVAC) reducing box. The box is rated at 200 CFM and is manufactured by rt Buensod Company(model type HS). A 7"main high pressure duct is routed from the eastern shaft and is routed to the box. All the existing ductwork is insulated by fiberglass insulation throughout. During our offices site visit it was noted that the occupants indicated that the area did not provide a sufficient means of heat and no local controls where present. All the components appeared to be original to the building and in fair condition. Recommendation: • Option of adding Terminal Re-heat, due to respective age of pressure box and existing conditions. • Clean diffusers and associated ductwork. Heating and cooling for the rear supply closet is provided by one (1)two (2) foot linear diffuser(model ML 3400)that provides 100 CFM to the area. The linear is connected to 5" 0 branch duct which is connected to the 10" 0 main routed to the pressure reducing box. The box is rated at 350 CFM and is manufactured by Buensod Company(model type HS). A 6"main high pressure duct is routed from the southeastern shaft and is routed to the box. All the existing ductwork is insulated by fiberglass insulation throughout. All the components appeared to be original to the building and in fair condition. Recommendation: • Option of adding Terminal Re-heat, due to respective age of pressure box and existing conditions. • Clean diffusers and associated ductwork. UPPER LEVEL:V L. STAIRWELL B: Conditioning for the stairwell is provided by a 12"xl2" supply diffuser which is connected to a 12"x5"branch duct. The diffuser 1! provides 200 CFM and is manufactured by the Titus Company (Model TMD-51). The unit appeared to be original to the building - with minor deterioration(rust) and in fair condition. During our office's site visit it was noted that heating for this area appeared insufficient. Recommendation: • Clean diffuser and associated ductwork. • Option to add supplemental electric heat unit. 87 South Windsor Town Hall Capital Needs Assessment Mechanical (HVAC) ELEVATOR LOBBY: Located over the lobby's window a two (2) foot linear diffuser provides 150 CFM of heating and cooling to this area. The 3 `R diffuser is connected to a 6" O branch duct,then to a 10"O main. The diffuser is manufactured by the Titus Company(model ML 3500) and appeared to be original to the building. No deterioration was present and it was in fair condition. Recommendation: • Clean diffuser and associated ductwork. CONSOLE CHAMBER (ROOM ON MAIN FLOOR): Heating and cooling is provided by an air handling unit located in an adjacent mechanical room. The ductwork supplied from the unit is routed through two (2) 30"x14" ducts that are located at the room's perimeter. Each main then transitions down to a 28"xl2" and finishing at 18"x12". There are four(4) supply grilles mounted on each main duct providing 600 CFM each. The grilles are manufactured by the Titus Company(Model CS 274) and are connected to an 18"xl8"branch main. At the end of each main duct an 18"x18" supply grille (Model CS 274)provides 500 CFM of heating and cooling. All components appeared to be original to the building and in fair condition. Recommendation: • Clean diffusers and associated ductwork. Return air is provided through a twenty 20 foot return grille p g Y( ) manufactured by the Titus Company(Model RF-50). The grille is mounted six (6) inches below the high ceiling. The grille appeared to be original to the building d ng and in fair condition. Recommendation: • Clean grille and associated ductwork. MENS AND WOMEN'S TOILET ROOM: A Supply and exhaust are found in this area the supply diffuser is an 8"x8" 2-way diffuser manufactured by the Titus Company(Model MH-51). The diffuser provides 100 CFM and appears to be " original to the building. No deterioration was found and the 3 " diffuser is in good condition. 88 South Windsor Town Hall Capital Needs Assessment Mechanical (HVAC) Recommendation: • Clean diffusers and associated ductwork. The 8"x6"main is connected to a pressure reducing box _ manufactured by the Buensod Company(Model type HS) and is rated for 200 CFM. A 5" O high pressure duct is connected to the other side of the box and originates from the 0 12" 0 main riser in the central shaft. The ductwork is insulated by fiberglass insulation. All components appeared to be original to the building and in fair condition. Recommendation: • Option of adding variable air volume box with supplemental heat, due to respective age ofpressure box and existing conditions. • Clean linear diffuser and associated ductwork. Exhaust for each toilet room is provided through an 8"x8" exhaust € grille. Each grille provides 100 CFM of exhaust and is manufactured by the Titus Company(Model TMD-51). Each grille appeared to be original to the building and in fair condition. Recommendation: • Clean grille and associated ductwork. COMMON CORRIDOR/ UPPER LOBBY: R The upper ceilings interior perimeter has a full size linear duct with eight (8) four(4) foot linears rated for 100 CFM each. Manufactured by the Titus Company(Model ML 3400 1-A-1). Each diffuser is connected by a 5 0 duct back to the 12" 0 main. A pressure reducing box manufactured by the Buensod Company (Model type HS) and is rated for 800 CFM. The zone is controlled by a wall mounted thermostat by the Honeywell Company. An 8" 0 high pressure duct is connected to the other side of the box and originated from the 12" O main riser in the central shaft. All ductwork is insulated by fiberglass insulation. All the components appear to be in fair condition and original to the building. fy 89 South Wind sor Town Hall Capital Needs Assessment Mechanical (HVAC) Recommendation: • Option of adding Terminal Re-heat, due to respective age of pressure box and existing conditions. • Remove and replace thermostats due to the respective age of the unit. • Clean diffusers and associated ductwork. BUSINESS OFFICES: The office's main area has four 4 linear diffusers located along g an exterior wall. Each diffuser provides 150 CFM and is manufactured by the Titus Company(model ML 3500). All the diffusers are connected to a 5" 0 duct to the main 14" 0 main. The main duct is routed to a pressure reducing box rated for 950 CFM. The box is manufactured by the Buensod Company(model type HS) and is connected to the 9" O high pressure duct that originated from the northeast shaft. All the associated ductwork is insulated by fiberglass insulation. The zone is controlled by a local thermostat manufactured by the Honeywell Company. All the components appeared to be original to the building and in fair condition. Two (2)notes were taken during our office's site visit. Area appeared to have insufficient heating and one (1) diffuser is covered by duct tape due to excessive noise. Recommendation: • Option of adding Terminal Re-heat, due to respective age of pressure box and existing conditions. • Remove and replace thermostats due to the respective age of the unit. ' • Clean diffusers and associated ductwork. Five additional diffusers provide heating and cooling for areas located in front of the existing windows. Each diffuser is rated 50 CFM and is connected to a 5' O branch duct. A 11" O main is M a routed to a pressure reducing box rated for 475 CFM. All the ductwork is insulated by fiberglass insulation. The box is manufactured by the Buensod Company(model type HS) and is connected to a 7" 0 high pressure duct riser in the northwest shaft. The zone is controlled by a local thermostat manufactured by the Honeywell Company. All components appeared to be original to the building and in fair condition. 90 South Windsor Town Hall Capital Needs Assessment Mechanical (HVAC) Recommendation: • Option of adding Terminal Re-heat, due to respective age of pressure box and existing conditions. • Remove and replace thermostats due to the respective age of the unit • Clean diffusers and associated ductwork. PUBLIC WORKS OFFICE/ FIRE MARSHALL: ' Several different linear supply diffusers provide heating and cooling to these areas. Two (2) 360 CFM pressuring reducing boxes are routed from a 6" 0 high pressure duct. After each box a 10" O main serves the six (6) diffusers which are located parallel with the light fixtures in the main area provides 60 CFM each. All the ductwork is insulated by fiberglass insulation. Both boxes are manufactured by the Buensod Company (model type HS) and is controlled by a wall mounted thermostat. All components appeared to be original to the building and in fair condition. Recommendation: • Option of adding Terminal Re-heat, due to respective age of pressure box and existing conditions. • Remove and replace thermostats due to the respective age of the unit • Clean diffusers and associated ductwork. Three (3) supply diffusers are located in the central area providing 65 CFM each of heating and cooling. The diffusers are connected to an 8" 0 duct routed to a pressure reducing box rated for 195 .«t CFM. The box is manufactured by the Buensod Company and is connected to a 7" O high pressure duct originating from the buildings central shaft. Thezone is controlled by a wall mounted thermostat manufactured by the Honeywell Company. All the ductwork is insulated by fiberglass insulation. All components appeared to be original to the building and in fair condition. Recommendation.- 0 Option of adding Terminal Re-heat, due to respective age of pressure box and existing conditions. • Remove and replace thermostats due to the respective age of the unit • Remove and replace faulty fiberglass insulation. • Clean diffusers and associated ductwork. 91 South Windsor Town Hall Capital Needs Assessment Mechanical (HVAC) Perimeter heating and cooling is provided by six (6) linear diffusers rated at 95 CFM each. All the diffusers are manufactured f by the Titus Company(model ML 5400) and are connected to a 5" 0 branch duct. Each diffuser is connected to a pressure reducing box thorough a 11" 0 duct. The box is manufactured by the Buensod Company(model type HS) and is rated at 475 CFM. A wall mounted thermostat manufactured by the Honeywell Company controls the zone. The main 7" 0 high pressure duct feeds the box and is routed to the 9" 0 main riser located in the northern shaft. All the ductwork is insulated by fiberglass ductwork. All the components appeared to be original to the building and in good condition. Recommendation: • Option of adding Terminal Re-heat, due to respective age of pressure box and existing conditions. • Remove and replace thermostats due to the respective age of the unit • Clean diffusers and associated ductwork. ENGINEERING DEPARMENT: The open area for this department is conditioned by twelve (12) diffusers located on each side of the lighting fixtures. The linears are four feet long and provide 65-72 CFM. Each set of diffusers are connected to a 5" 0 branch duct which is routed to the 10" G main off the pressure reducing box. The box is manufactured by the Buensod Company(model type HS) and is fed from an 8" 0 high pressure duct that originates from the south eastern shaft. A wall mounted thermostat controls the zone and it is manufactured by the Honeywell Company. All the components appeared to be original to the building and in fair condition. Recommendation: • Option of adding Terminal Re-heat, due to respective age of pressure box and existing conditions. • Remove and replace thermostats due to the respective age of the unit • Clean diffusers and associated ductwork. 92 South Windsor Town Hall Capital Needs Assessment Mechanical (HVAC) Perimeter heating and cooling is provided by three different types of linear diffusers with black sections. All the units are manufactured by the Titus Company and are mainly located over the existing windows. The zone is controlled by wall mounted thermostats manufactured by the Honeywell Company. The northeastern perimeter has ten(10)two (2) foot units (model ML 3400)that provide 70 CFM. Five (5) of the units are connected to 5" 0 branch ducts which are connected to the 10" 0 main routed to the pressure reducing box. The box is rated at 445 CFM and is manufactured by Buensod Company(model type HS). A 9"main high pressure duct is routed from the northern shaft and is routed to the box. All the components appeared to be original to the building _ and in fair condition. The remaining five (5) units are also connected to 5" 0 branch ducts which are connected to the 10" 0 main routed to the pressure reducing box. The box is rated at 350 CFM and is manufactured by Buensod Company(model type HS). A 9"main high pressure duct is routed from the northern shaft and is routed to the box. All the components appeared to be original to the building and in fair condition. The Eastern perimeter has six 6 four 4 foot units model ML 3400)that provide 95 CFM and one (1)two (2) foot unit(model ML 3400)that provides 140 CFM. All of the units are connected to 5" 0 branch ducts which are connected to the 12" 0 main routed to the pressure reducing box. The box is rated at 640 CFM and is ,e manufactured by Buensod Company (model type HS). An 8"main high pressure duct is routed from the eastern shaft and is routed to the box. All the components appeared to be original to the building and in fair condition The Southern perimeter has four(4)two (2) foot units (model ML 3500)that provide 105 CFM and one (1) 12"x12 diffuser(model TMD-51)providing 200 CFM located in Stairwell B. All of the two (2) foot units are connected to 5" 0 branch ducts which are connected to the 12" 0 main routed to the pressure reducing box. The box is rated at 600 CFM and is manufactured by Buensod Company(model type HS). An 8"main high pressure duct is routed from the Southeastern shaft and is routed to the box. After the last linear diffuser the ductwork transitions to a 12"x5" duct to the stairwell diffuser. All the components appeared to be original to the building and in fair condition. 93 South Windsor Town Hall Capital Needs Assessment Mechanical (HVAC) Recommendation: • Option of adding Terminal Re-heat, due to respective age of pressure box and existing conditions. • Remove and replace thermostats due to the respective age of the unit • Remove and replace faulty fiberglass insulation. • Clean diffusers and associated ductwork. MECHANICAL ROOM: ! • Conditioning for the Chamber Console Room is provided by a central station air handling unit. The unit includes a fan section heating coil, cooling coil, mixing box and provides 5,800 CFM. The Carrier Company(model 39BA080D27) manufactured the unit and is currently controlled by the Honeywell control panel. A wall mounted sensor which provides space temperature is 4 located within the Console Chamber is also manufactured by the Honeywell Company. The air handling unit and associated control z components appeared to be original to the building and in fair condition. The estimated Energy Efficiency Ratio is 10 EER, current replacement units can range from 11-13 EER,thus creating energy savings. The heating coil in the unit is connected to a 1-1/2"hot water supply and return that originates in the boiler room. The piping is routed thought the central shaft, entering the room and routed to the coil. All the hot water piping appears to be insulated with fiberglass insulation. Existing control valves and pipe insulation appeared to have deterioration in several areas and original to the building. The coiling coil in the unit is connected to a 2-1/2 chilled water supply and return pipe that originates in the boiler room. The piping is also routed thought the central shaft, entering the room and routed to the coil. All the chilled water piping appears to be insulated with fiberglass insulation. Existing control valves and pipe insulation appeared to have deterioration in several areas and original to the building Fresh air for the unit is provided through a 35"x20" duct routed - through the central shaft up to the fan housing. Entering the room, the ductwork has a full-size motorized damper which controls the 94 South Windsor Town Hall Capital Needs Assessment Mechanical (HVAC) open/closed positions. The duct entering the room has indentations located on the top of the ductwork and appeared to be original to the building. Supply air is provided through a 54"x14"fiberglass insulated duct that is routed off the back of the unit to the space to which it serves. Once the duct enters the chamber room it splits into two (2) 30"x14"ducts. The ductwork's insulation appeared to have deterioration in several areas and original to the building. The return air system is provided through a open-ended 40"00" a: duct with a motorized damper. Filters for the air handling unit are located in the unit's rear module and appeared to have been recently replaced. The duct and damper appeared in fair condition and original to the building. Recommendation: • Replacement of unit and associated accessories due to the SF estimated life span, deterioration level and current energy consumption. A current replacement can provide Higher efficiency, thus creating energy savings. s • Heating Ventilation and Air Conditioning rebates are currently available from Connecticut Light and Power. Coordinate selection of equipment with CL&P prior to installation. • Clean associated ductwork. ROOF: The mechanical components on the main roof include: exhaust fan serving the general building exhaust, exhaust fan serving the toilet rooms and an air cooled condensing unit serving the indoor chiller. The general exhaust fan provides 3050 CFM of exhaust to the upper level. The unit is manufactured by the Penn Company -� (Model 33 LINEA) sits on a sonotrol roof curb and appeared to be original to the building. The units casing appeared to have extensive deterioration(rust) and a large stone for vibration support. Recommendation: • Replace exhaust fan, roof curb and associated accessories due to the respective age and deterioration. • Clean existing ductwork. 95 South Windsor Town Hall Capital Needs Assessment Mechanical (HVAC) Toilet exhaust is routed to the roof mushroom fan through an 14"x14"duct which has an open end to the duct chase. The toilet exhaust fan provides 865 CFM of exhaust for the toilet rooms. The unit is manufactured by the Penn Company(Model DXI6VSR) and sits on an existing roof curb with extension. The fan appeared to be newer to the site and in good condition. Recommendation: • Provide scheduled maintenance as required by manufacturer. • Clean fan and associated ductwork. Cooling for the indoor chiller is provided by a roof mounted air cooled condensing unit. The unit sits on a full size roof curb and is manufactured by the Carrier Company(Model 09DC044S30). The rating of the unit is forty(40)tons and is installed with R-22 refrigerant. The unit and associated piping appears to be original to the building with signs of deterioration and the fan guards and unit casing. The estimated Seasonal Energy Efficiency Ratio is 10 -` SEER, current replacement units can range from 11-13 SEER. Recommendation: `� • Replacement of unit and associated accessories due to the - estimated life span, deterioration level and current energy ., consumption. A current replacement can provide Higher jet t� efficiency, thus creating energy savings. • Heating Ventilation and Air Conditioning rebates are r currently available from Connecticut Light and Power. Coordinate selection of equipment with CL&P prior to installation. UPPER ROOF: Three components are located in the central area of the upper roof and they include: 40"x40" fresh air intake duct with fan body, console chamber's exhaust fan and gravity ventilation for the console chamber. 96 South Windsor To wn Hall Capital Needs Assessment Mechanical (HVAC) 'p A fresh air intake (with the fan housing) is connected to a 35"x20" duct which is routed to the air handling unit located on the upper floor. The unit sits on a 40"x40" roof curb and provides the required fresh air to the air handling unit. The unit appeared to be in fair condition and original to the building. Recommendation: • Replace Intake and associated accessories due to the components respective age. General exhaust for the console chambers is provided by a roof mounted exhaust fan manufactured by the Penn Company(Model REX 30W) the fan provides 1260 CFM of exhaust and sits on a roof curb. The unit is connected to a 20"x20" duct to an exhaust grille located in the ceiling. The fan appeared to be original to the building with a large stone for vibration issues. Recommendation: • Replace fan and associated accessories due to the components respective age. Ventilation for the console chamber is provided through a 40"x40"duct to a roof mounted ventilator. The unit is manufactured by the Penn Company and sits on a roof curb. The unit appeared to be in fair condition and original to the building, Recommendation: Replace Ventilator and associated accessories due to the components respective age. 97 South Windsor Town Hall Capital Needs Assessment Electrical CAPITAL NEEDS ASSESSMENT-ELECTRICAL Walkthroughs of the facility were executed on January 5th, 15th and 201h, 2009 to assess the electrical conditions of the existing facility. The electrical walkthroughs were carried out by Frank Berardi, Electrical Engineer, Salamone &Associates,P.C. General - Please note recommendations are based on continuation of Note maintenance as recommended by respective manufacturers. • Please note components and materials original to the building may contain hazardous materials and should be tested prior to implementation of any construction. This testing is beyond this reports scope of work. EXTERIOR Southern Exterior The lighting components observed on the Southern side of the building (front), consisted of the following fixtures. The walkway leading to the building steps is illuminated by six (6) t HID light fixtures with clear round spherical lens mounted on 15 feet high metal poles. The pole positioned closest to the western side also had two (2) HID floodlights connected to it in addition to the sphere. One (1) of these floodlights is directed s upward and appears to illuminate the flag at night. The other is positioned parallel to the ground and faces west. The luminaries seem to be in good overall condition,however appear to have been in place a number of years and due to their lens, do not have light cutoff. Steps and front courtyard lighting consisted of recessed lights mounted within the brick retaining walls. Two (2) of these fixtures illuminated the steps with one (1) being located on each OF side and five (5)were located along the perimeter of the courtyard area. These fixtures appeared to be in fair condition. Also observed were two (2) wall sconces utilizing compact fluorescent lamps mounted adjacent to the building entry doors with one (1) located on each side. The lenses of these fixtures are discoloring. Under the entry door overhang, four(4) ceiling recessed wall wash fixtures were observed. Two (2) baffle down-lights were observed recessed in the ceiling under both of the exterior balcony overhangs. 98 South Windsor Town Hall Capital Needs Assessment Electrical In addition, blank outlet cover plates were also observed. Due to their proximity to the ground, it would seem that these outlets may have been for receptacles that have since been removed or never installed. A telecommunications enclosure was observed on this side as well. The wiring seems to penetrate the exterior wall of the building via holes drilled through it. The openings do not appear to be sealed. An alarm beacon for the underground fuel storage tank located was also located at the southwest corner. Recommendation: q The pole mounted HID fixtures should be removed and replaced with new HID fixtures utilizing high power factor ballasts and light cutoff refractors. °z. The step and courtyard recessed lighting should also be removed and replaced. ■ The wall sconces as well as the wall washers and down lights should be removed and replaced with more efficient fixtures utilizing compact fluorescent limping. ■ Existing wiring and conduit penetrations through the exterior wall should be sealed it 99 South Windsor Town Hall Capital Needs Assessment Electrical Western Exterior Lighting on the Western side (side entry side) of the building consisted of two (2)baffle down-lights recessed in the second floor overhang above the side entry door. 2 S 3 Electrical components observed on this side were a Tork series 2001 photoelectric control and associated conduit as well as what appeared to be a keyed switch. A telecommunications enclosure was observed on this side of the building as well. Recommendation: ■ The down-lights should be removed and replaced with more energy efficient fixtures utilizing compact fluorescent lamping. a Wall sconce should be installed adjacent to doorway. No rthern Exterior The light fixtures observed on the Northern side of the building (main parking side) consisted of three (3) HID light fixtures i i with clear round spherical lens mounted on 10 feet high metal poles illuminating the walkway to the rear door. A wall sconce f was located adjacent to the door entry. The lens of the fixture I is discolored. The HID luminaries seem to be in good overall condition,however appear to have been in place a number of years and due to their lens, do not have light cutoff. Also located at the entry door was an ADA automatic door activation switch as well as a card reader for building entry after hours. In addition, this side of the building contained a condensing unit within a wooden fence enclosure. The electrical disconnect for the condenser was mounted to the unit. Wiring to the disconnect switch is routed in metallic conduit. Do to weathering, our office was unable to ascertain the actual ratings of the disconnect switch. However, based on the electrical nameplate ratings of the condensing unit, the disconnect switch is most likely rated at 60A, 240V, 3 phase. No receptacle was observed near this unit as is required by current code. 100 South Windsor Town Hall Capital Needs Assessment Electrical _ Recommendation: ■ The pole mounted HID fixtures should be removed and replaced with new HID fixtures utilizing high power factor ballasts and light cutoff refractors. The wall sconce should be removed and replaced. ■ Disconnect for condensing unit should be removed and replaced when unit is replaced. ■ Install GFCI receptacle within weatherproof enclosure on wall adjacent to condensing unit. Eastern Exterior The only electrical component observed on the eastern side of the building was an emergency generator situated on a concrete pad. The generator is a diesel unit manufactured by Cummins, which is housed within a weatherproof enclosure that sits upon V a sub-base fuel tank. It appears that the generator is rated at • '{ 60kW (75KVA) at 120/208 3-phase voltage. Conduit and wiring is routed down the exterior of the building and underground to the generator set. A duplex receptacle was also observed within the generator enclosure. Recommendation.- The generator and associated wiring and conduit appear to M _ be in good condition and should remain. Provided the generator is tested regularly and maintenance provided as per the manufacturer's maintenance schedule, the generator should not require replacement for an additional 15 to 20 years. Parking Areas Three (3) HID light fixtures with spherical lenses,mounted on 10 foot high metal poles illuminate the parking area adjacent to the front entry of the building. I ON The main parking area, located in the rear of the building, consisted of six (6) HID gooseneck type streetlights. These fixtures provide illumination for this parking area. The roadway on the eastern side of the building is illuminated via four(4) HID light fixtures with square heads. The fixtures appeared to be in good overall condition, however the parking area fixtures seem to have been in place a number of years. 101 South Windsor Town Hall Capital Needs Assessment Electrical Recommendation: `4't.'r ■ The parking area fixtures should be removed and replaced with new HID fixtures utilizing high power factor ballasts and light cutoff refractors. Roof Electrical components on the roof consisted of a GE 30Amp, 240V, 3-phase disconnect servicing the condensing unit. The disconnect is antiquated and in poor condition. Recommendation: ' The existing disconnect should be removed and replaced. GFCI receptacles should be installed within 25 feet of all mechanical equipment. INTERIOR Electrical Distribution Electrical power for the building is a 120/208V, 3 phase, 4 wire «� service provided via transformer(maintained by Connecticut Light and Power(CL&P)) situated in an electrical transformer vault located within the building on the lower level. The main distribution switchboard for the building is a two- section AN Line switchboard manufactured by General Electric (GE) and is located in the mechanical room on the lower level. One section of the switchboard contains the main service disconnect switch, which is rated at 800 Amps, and the CT compartment for metering. CL&P's meter is located adjacent to ` the switchboard in it's own enclosure. The second section is the main distribution section of the switchboard and provides overcurrent protection for electrical panelboards located within 102 South Windsor Town Hall Capital Needs Assessment Electrical the building as well as the elevator and mechanical equipment. This section is currently labeled with the number five (5) and is i rated at 800 Amps Also located adjacent to the main switchboard were five (5) panelboards/load centers. These panelboards/load centers were labeled generator panel#1, generator panel#2, generator panel #4,panel #3 and panel#6 (SL). Generator panel#1 and 42 are QO load centers manufactured by Square D. No ratings identification was observed on these load centers. Generator panel #1 is a 12-pole load center and utilizes twin single pole circuit breakers due to the limited spaces within. This panel provides power for the Veeder Root system, Metasys control panel, automatic door opener, oil burner, back entry heater and water pump as well as lighting and receptacles in the lower level mechanical rooms and hallway. Generator panel #2 is a 20- ole load cent er. This panel p provi des p s p p power for lighting and receptacles located in the stairwells, main and upper level hallways, town managers office, town clerks office, engineering office as well as the air compressor r and fire alarm system. Generator panel 44 is a 1 OOAmp, 3-phase, 4-wire, 20-pole, 120/208V, MLO panelboard manufactured by GE. This panel sub feeds panel #2 and provides power for the sub panels located in the IT room and maintenance room, and mechanical - equipment such as the AHU for the council chamber and �� mechanical room. Panel designated#3 is also manufactured by GE and is a 100Amp, 3-phase, 4-wire, 30-pole, 120/208V, MLO panelboard. This panelboard provides power for restroom lighting and exhaust fans, small office lighting and receptacles, 1 exit lights, fire alarm number 2, as well as mechanical equipment and controllers. The panel-designated#6 (SL) is manufactured by GE and is a 100Amp, 1-phase, 3-wire, 12-pole, MLO panelboard. This panel appears to provide power for the exterior lighting of the building including the main parking area. Also observed adjacent to these panels were a number J p of time clocks. These time clocks included a Tork model 1101 which 103 South Windsor Town Hall Capital Needs Assessment Electrical seems to control lower level hallway lighting, a Tork Digital time clock model DG100 for control of restroom exhaust fans, two (2) Intermatic time clocks models T174 and T101 and an AMF Paragon model 7008-00 which seems to control lighting on the main and upper levels. Power is provided for the remainder p d of the buildings electrical needs via four(4) panelboards. Panelboard P1 is located in the janitors closet on the lower level and provides power for the lower level. Panel P 1 is a GE 100Amp, 3-phase, 4-wire, . ` 120/208V, 24-pole, MLO panelboard. Panel boards P21eft and P2 right are located in the main level janitors closet. These panels are manufactured by GE and are rated at 225Amps, 3-phase, 4-wire, 120/208V, 24-pole, MLO. These panelboards provide power the main level. Panel LP3 is a 225Amp, 3-phase, 4-wire, 42-pole, MLO GE - panelboard. This panelboard is located in the upper level ffi janitors closet and provides power for said level lighting and receptacles, Two additional sub panels were also observed within the building. One sub panel was located in the closet of the IT w room. This panel was a 3-phase, 4-wire, 120/208V, 24-pole, MLO load center manufactured by GE. The amperage capacity of this sub panel was not stated. However, the overcurrent protection device (OCPD) for this sub panel was rated at 100 Amps. As such, it would seem that the load center has at least a y 100Amp rating. The second sub panel is a 4-pole circuit breaker enclosure, *�•■,,,�,� which is located in the maintenance office. These circuit breakers provide OCPD for outlets for video and phone equipment. All the panelboards are original to the building and are in good condition for their age, however they are nearing the end of their useful life expectancy. Recommendation: ■ Existing electrical switchboard and majority of panelboards should be replaced within the next 10 to fifteen years. 104 South Windsor Town Hall Capital Needs Assessment Electrical ■ Generator panel #1 should be replaced with a larger capacity panelboard thereby eliminating the need to utilize twin circuit breakers due to lack of space. ■ Server room load center should remain. ■ Maintenance office circuit breaker enclosure should be replaced with a panelboard. Emergency Power Emergency power for the building i provided g Y p gs p d by the Cummins generator located on the eastern side of the building. The generator provides emergency power via a Cummins automatic transfer switch(ATS) located in the Fire Alarm Equipment/ Phone/Generator Control room within the mechanical room on the lower level. It is rated at 225Amps. The ATS then feeds emergency panelboard labeled generator panel#4. This panelboard in turn provides power to emergency panelboards generator panel #1 & #2 as well as the sub panel load center in the IT room. The emergency panelboards provide power for emergency lighting and exit signs on each level as well as the fire alarm system and certain mechanical and HVAC equipment. Recommendation: ■ The ATS appeared to be in good condition and should remain in use. Elevator A single hydraulic elevator manufactured by General Elevator, serves all three levels of the building. The elevator machine room equipment appears to be original to the building and over forty years old, while the cab interior seems to have been updated in the past. Elevator capacity is labeled at 15001bs with a speed of 80 fps. The elevator cab interior was in good overall condition. However,the exhaust fan was not operating during the walkthroughs and the cab does not contain two-way hands free communications meeting today's requirements. Please also note that no elevator recall system was observed. Although the elevator is in good overall condition, it is reaching the end of its useful life expectancy. 105 South Windsor Town Hall Capital Needs Assessment Electrical I!� Recommendation: ■ The elevator should be modernized and an elevator recall system installed. Fire Alarm System The fire alarm system for the building is a conventional system. A Simplex Fire Alarm Control Panel (FACP) is located in the Fire Alarm Equipment/Phone/Generator Control room. This room is located within the mechanical room on the lower level. The FACP appears to be a Simplex model 4246-1. Also observed was the battery charger for the system. The FACP appears to be original to the building and in good condition for - it's age. However, it is antiquated and obsolete. Fire alarm detection devices consisted of smoke and heat detectors located in limited areas. Smoke detectors were located in the Probate Court vault, IT server room and Town Clerks vault. Two (2) smoke detectors were located on either side of �.� the upper level hallway doors for release of the magnetic door holders. Heat detectors were located in the mechanical rooms, restrooms,janitor closets, Probate Court vault, Town Clerks vault, elevator machine room, closet within Registrars office, maintenance office and maintenance storage room. Please note that the heat detector within the maintenance office is located above the suspended ceiling and just has the ceiling tile below it removed. Fire alarm initiation devices consisted of manual pull stations. These were located in the following corridor and stairwell areas. On the lower level a manual pull station is located outside the maintenance office entry doorway. The main level has manual pull stations adjacent to the interior main lobby entry doors, stairwell `A' main landing doors leading to the entry vestibule and adjacent to the men's restroom doorway. The upper level consists of manual pull stations located at outside the entry door to stairwell `A' and again adjacent to the men's restroom doorway. These devices appear to have been in place a number of years and seem to be in fair condition. However, they're mounting height is above the maximum allowed by current ADA requirements. i106 South Windsor Town Hall Capital Needs Assessment Electrical Notification devices consisted of horns located above each z manual pull station listed above with the exception of the pull a station located within stairwell `A' main landing. These devices also appear to have been in place a number of years and are in fair condition. A surface mounted fire department knox box was also observed adjacent to the main level entry doors and appeared to be in good condition. Recommendation: ■ The fire alarm system has been in place for a number of years and is obsolete. Detection devices provide minimal coverage in selected areas. Initiation devices are insufficient and not located as required per current codes. Notification devices are also insufficient. Current code would require different types of notification devices to be installed. As such the entire fire alarm system should be removed and replaced with additional detection, initiation and notification devices added to provide complete coverage for the buildings meeting current codes. Call-For-Aid No call-for-aid devices were observed within the building. Recommendation: ■ Provide call-for-aid devices were required by current codes. Emergency Lighting The majority of the emergency lighting throughout the building is provided via the existing light fixtures. The lighting circuits of some of the existing light fixtures are connected to the emergency panelboards served by the emergency generator. Dual head emergency light fixtures with battery back-up provide emergency lighting in the Sprenkel Room and the Madden room on the lower level. Both of these emergency fixtures appeared to be non-functional when tested. A dual head unit recessed in the ceiling of the hallway outside the Sprenkel and Madden rooms was also observed. This fixture also s A appeared to be non-functional when tested. Recommendation: Emergency lighting should remain connected to the emergency generator. 107 South Windsor Town Hall Capital Needs Assessment Electrical ■ Non-functional dual head emergency lighting units should be removed and replaced. ■ Emergency lighting should be provided in common area restrooms and employee lounge. Exit Signs Exit signage was located at the exit doorways and at most stairwell entry doorways. These fixtures are in fair condition and appear to have been in place a number of years. The lenses on some of these fixture r s are discoloring. Panelboard directories indicate that the exit signs are not on emergency generator power. However, the units did not appear to contain battery back-up and town staff indicated that they are connected to an emergency panelboard lighting circuit. Testing to verify would require temporary shutdown of normal power to the building, which was not feasible during the walkthroughs. Recommendation: ■ The existing exit signs should be removed and replaced - with units utilizing LEDs. ■ Additional exit signage should be installed to better indicate the path of egress in certain areas. Lower Level Rooms ' Mechanical Room Lighting in the lower level mechanical room consisted of eighteen (18) 4"x4' one(1) lamp strip lights utilizing T8 lamps. These fixtures appeared to be controlled by a wall mounted occupancy sensor with off/auto/on control located adjacent to the entry doors. They appeared to be in good condition, but no guards were observed on the light fixtures. .. . The main electrical switchboard as well as panelboards generator panel #1, #2, #4, panel #3,panel #6 (SL) and associated time clocks as previously discussed are also located t a within this room. Also observed were two 2 GE disconnects rated at 3hp, 240 3-phase and associated controls for the hot water pump and the j chilled water pump. Furnas controls were observed for the compressor. These devices appear to have been in service a number of years. Four(4) duplex receptacles were also observed. However, these e v receptacles were not GFCI. ' 108 South Windsor Town Hall Capital Needs Assessment Electrical Fire alarm components consisted of a heat detector. Emergency lighting i g y g g s provided via the emergency generator, ' Recommendation: ■ The existing lighting appears adequate and should remain. v 4 Wire guards should be added to the existing fixtures. i The wall mounted occupancy sensor is poorly positioned and will not pick up movement in most of the room due to blockage caused by mechanical equipment. Ceiling mounted occupancy sensors should be installed to provide p y r better coverage. Disconnects and associated controls for the pumps should be upgraded when the pumps are replaced. Existing receptacles should be replaced with GFCI receptacles. • Fire alarm should be upgraded when fire alarm system for building is upgraded Fire Alarm Equipment/ Phone/Generator Control Room Lighting in this room consisted of four (4) 4"x4' one (1) lamp strip lights utilizing T8 lamps. These fixtures appeared to be controlled by a single pole switch with a pilot light located on the exterior of the room. These fixtures also did not have guards. The automatic transfer switch (ATS) and fire alarm control panel (FACP) previously discussed are located within this room. In addition, this room also contained a telecommunications l~ punch down enclosure as well as security/entry system enclosures. Six (6) duplex receptacles were also observed. However, these receptacles were not GFCI. No fire alarm detection, initiation or notification devices were observed in this room, i109 South Windsor Town Hall Capital Needs Assessment ' Electrical This room did not appear to contain emergency lighting. Recommendation: The existing lighting appears adequate and should remain. Wire guards should be added to the existing fixtures. An occupancy sensor-should be installed within the room in lieu of the switch and pilot light on the exterior. ■ Existing receptacles should be replaced with GFCI receptacles. Fire alarm devices should be installed when fire alarm j1 system for building is upgraded. ■ Emergency lighting should be installed. Elevator Machine Room Elevator machine room lighting consisted of a single 12"x12" surface mounted light fixture, which was controlled by a single pole light switch with a pilot light located on the exterior of the room. ' This room contained the elevator controller and the hydraulic pump unit a previously discussed. A Westinghouse general duty ' 240V 3-phase disconnect was located adjacent to the doorway on the interior of the room, No receptacles were observed within the room. Fire alarm components consisted of a heat detector. This room did not appear to contain emergency lighting. Recommendation: ■ The existing lighting is inadequate. New light fixtures utilizing energy efficient ballasts and lamping should be installed. An occupancy sensor should be installed within the room in lieu of the switch and pilot light on the exterior. ■ Disconnect should be replaced when elevator is modernized. ■ A GFCI duplex receptacle should be installed. ■ Fire alarm should be upgraded when fire alarm system for building is upgraded ■ Emergency lighting should be installed. 110 South Windsor Town Hall Capital Needs Assessment Electrical Elevator Lobby Elevator lobby lighting consisted of three 3 2'x2' recessed lensed troffers utilizing two (2) T8 fluorescent lamps. The lobby also contained a black and white camera by Pro Video as well as a handicapped switch for the exterior exit ' doors automatic opener. The doors also contained magnetic door locks by Locknetics, A Locknetics emergency break glass door release is located adjacent to the exit door, while a door Ilock release is located on the ceiling. These devices appeared to be in good condition. No receptacles or fire alarm devices were observed, An exit sign was located at the exit doorway and emergency lighting seems to be provided by a lighting circuit connected to i the emergency generator. The lobby also contained a surface mounted electric unit heater. Wiring for the heater is routed from the unit to above the suspended ceiling via wiremold, ' Recommendation: ■ The existing lighting is adequate and should remain in use.. ■ A GFCI duplex receptacle should be installed. ' ■ Fire alarm devices should be installed when fire alarm system for building is upgraded r g.. a„ Y Men's Restroom Three (3) 4' wall mounted vanity lights provide illumination for the room. One (1) fixture is located above the sinks and the remaining two (2) are located above the water closets and r111 ' South Windsor Town Hall Capital Needs Assessment Electrical urinals. These fixtures utilize two (2) T12 fluorescent lamps and are controlled via a wall mounted occupancy sensor with off ' /auto control. Receptacles consisted of a single receptacle, which was integral with the vanity light above the sink. 1 Fire alarm components consisted of a heat detector. This room did not appear to contain emergency lighting, Recommendation. ■ The existing lighting should be removed and replaced with more energy efficient light fixtures. ' A GFCI duplex receptacle should be installed. ■ Fire alarm should be upgraded when fire alarm system for building is upgraded. Emergency lighting should be installed. Women's Restroom Three (3) 4' wall mounted vanity lights provide illumination for the room. One (1) fixture is located above the sinks and the remaining two (2) are located above the water closets and urinals. These fixtures utilize two (2) T12 fluorescent lamps and -- ---_ are controlled via a wall mounted occupancy sensor with off /auto control. Receptacles consisted of a single receptacle, which was integral with the vanity light above the sink. ' Fire alarm components consisted of a heat detector. This room did not appear to contain emergency lighting. Recommendation: • The existing lighting should be removed and replaced with more energy efficient light fixtures. ■ A GFCI duplex receptacle should be installed. ■ Fire alarm should be upgraded when fire alarm system for building is upgraded. ■ Emergency lighting should be installed. 112 South Windsor Town Hall Capital Needs Assessment ' Electrical Janitors Closet A single surface mounted incandescent light fixture utilizing a ' screw in type compact fluorescent lamp provided illumination for the closet. The fixture is controlled via a wall mounted occupancy sensor with off/auto/on control. Panelboard designated `P1' was observed within the closet as previously discussed. Also located within the closet was an ' AMF Paragon model #7007-00 time clock,which appears to control general lighting for stairwell `A'. No receptacles were observed within the closet. Fire alarm components consisted of a heat detector. ' This room did not to co ntain emergency gency lighting. Recommendation: ■ The existing light fixture should be removed and replaced with a more energy efficient fixture designed to utilize 1 { compact fluorescent lighting. ■ A GFCI duplex receptacle should be installed. ■ Fire alarm should be upgraded when fire alarm system for building is upgraded. Sprenkel Room Lighting in this room is provided by eight (8)recessed 2'x4' lensed troffers, which utilize four(4)T8 fluorescent lamps. A wall mounted occupancy sensor with off/auto controls these fixtures. Observed within the room were six (6) wall mounted duplex receptacles and one (1) ceiling mounted duplex receptacle located above the ceiling mounted television set. ' No fire alarm components were observed within the room. Emergency lighting for the room appeared to be provided by a wall mounted dual head emergency light fixture with battery backup, which is manufactured by Dual-Lite. This fixture appeared to be nonfunctional when tested. An Exit sign located ' above the door provides egress lighting. The faceplate is beginning to discolor. The units seem to have been in place a number of years and are at the end of their useful life expectancy. ' 113 South Windsor Town Hall Capital Needs Assessment ' Electrical .' Tele/data observed within the room consisted of one (1) wall mounted telephone, five (5)recessed single jack tele/data ' outlets, two (2) quad jack tele/data outlets as well as five (5) surface mounted jacks and a ceiling mounted AN jack for the x television. Also seen within the room is what appeared to be a recording system. The system seemed to consist of two (2) Marantz dual cassette deck components, a Shure SCM268 microphone mixer and a microphone protruding through a ceiling tile. Recommendation: ■ The existing lighting should remain. ■ Fire alarm should be upgraded when fire alarm system for ' building is upgraded 3 _ The existing emergency lighting and exit sign should be removed and replaced. s ' Madden Room Lighting in this room is provided by sixteen (16) recessed 2'x4' lensed troffers, which utilize four (4) T8 fluorescent lamps. Four(4) of these fixtures are situated over the seating area on ' the side and are controlled by a single pole switch. The remaining lights located over the table area of the room are controlled by two (20 sets of two (2) three way switches, which ' are located at each of the exit doors. An electrical junction box located above the suspended ceiling was missing it's cover. Also observed within the room were eleven (11) wall mounted duplex receptacles and one (1) ceiling mounted duplex receptacle located above the ceiling mounted television set. ' No fire alarm components were observed within the room. ' 114 South Windsor Town Hall Capital Needs Assessment Electrical Emergency lighting for the room appeared to be provided by a wall mounted dual head emergency light fixture with battery backup, which is manufactured by Sure-Lite. This fixture appeared to be nonfunctional when tested. Two (2) exit signs are located with this room. One is located above the door leading in from the Sprenkel room hallway and the other is wall mounted with directional chevron pointing to the other doorway. The faceplates are discoloring. The units seem to have been in place a number of years and are at the end of their useful life expectancy. ' Tele/data observed within the room consisted of one (1) wall mounted telephone, seventeen(17)recessed single jack tele/data outlets, two (2) dual jack tele/data outlets and a ceiling mounted AN jack for the television. Also seen within the room is what appeared to be a recording system. The system seemed to consist of two (2) Marantz dual cassette deck components, a Shure SCM268 microphone mixer and three (3) microphones protruding through ceiling tiles located around the room. Recommendation: rt0 The existing lighting should remain. ■ Fire alarm should be upgraded when fire alarm system for building is upgraded. 0 The existing emergency lighting and exit sign should be removed and replaced. ■ Exposed electrical junction box above suspended ceiling should have a cover installed. Employee Lounge Two (2) recessed 2'x2' lensed troffers utilizing two (2)u shape T-12 fluorescent lamps provide lighting for the room. A single pole light switch located in a surface mounted box adjacent to the door controls these fixtures. Also observed were six (6) one foot square recessed fixtures. These fixtures did not appear to be operational. Receptacles within the room consisted of one (1) duplex receptacle located in a surface mounted box and one (1) quad ' box housing two (2) duplex receptacles. A GFCI duplex receptacle was located behind the microwave on the shelf. 115 South Windsor Town Hall Capital Needs Assessment ' Electrical ;p No fire alarm components were observed within the room. ' No emergency lighting was observed within the room. Tele/data consisted of a wall-mounted telephone and a coaxial cable routed through the suspended ceiling to the television set. Recommendation: ' 0 The existing lighting should be upgraded to more energy efficient fixtures. ■ Fire alarm should be upgraded when fire alarm system for ' building is upgraded. ■ Emergency lighting should be installed. ■ A GFCI receptacle should be installed adjacent to the sink. Surface duplex receptacle behind coffee machine should be ' changed to a GFCI receptacle. A coaxial cable outlet should be installed so that the wiring ' is not routed from the ceiling to the Television. Registrars Lighting in the front room consisted of five (5) recessed 2'x4' lensed troffers utilizing four(4) T-8 fluorescent lamps. A wall- mounted occupancy sensor with off/auto/on controlled the lighting. Receptacles observed within the room consisted of five (5) ' duplex receptacles. . REGISTRAR S No fire alarm components were observed within the room. No emergency lighting was observed within the room. ' A single tele/data jack was observed. Also located within this room was a Design Controls model 12- 200 alarm panel, which controlled the key entry for the room. ' 116 ' South Windsor Town Hall Capital Needs Assessment Electrical Recommendation: �. The existing lighting should remain. ■ Fire alarm should be upgraded when fare alarm system for building is upgraded. Emergency lighting should be installed. ' Re _ 9 Registrars Interior office Lighting in this room consisted of five (5)recessed 2 x 49 lensed troffers utilizing four(4) T-8 fluorescent lamps. A wall- mounted occupancy sensor with off/auto/on controlled the lighting. Receptacles observed within the room consisted of four(4) duplex receptacle and one (1) quad box housing two (2) duplex ' receptacles. No fire alarm components were observed within the room. No emergency lighting was observed within the room. Tele/data consisted of four(4) recessed jacks and two (2) ' 1 wiremold surface raceway outlet boxes. One being a duplex and / the other a quad. ='f ' Recommendation. ■ The existing lighting should remain. ■ Fire alarm should be upgraded when fire alarm system for building is upgraded. ■ Emergency lighting should be installed. ' Registrars Interior Closet Lighting in the closet consisted of single surface mounted incandescent fixture, which is controlled by a wall-mounted ' occupancy sensor with off/auto/on. No receptacles were observed within the closet. ' Fire alarm components consisted of a heat detector. Recommendation: The existing light fixture should be removed and replaced with a more energy efficient fixture designed to utilize compact fluorescent lighting. • Fire alarm should be upgraded when fare alarm system for building is upgraded. 117 South Windsor Town Hall Capital Needs Assessment Electrical Registrars Interior Restroom Lighting in the closet consisted of single surface mounted incandescent fixture, which is controlled by a wall-mounted ' occupancy sensor with off/auto/on. x No receptacles were observed within the closet. No fire alarm components were observed. ' Recommendation. The existing light fixture should be removed and replaced } with a more energy efficient fixture designed to utilize ' compact fluorescent lighting. }% Fire alarm should be upgraded when fire alarm system for building is upgraded. Maintenance Office Lighting in the maintenance office consisted of one (1) 2'x4' ' f troffer utilizing four(4) T8 f;uorescent lamps. Fixture is missing its lens. Also observed were two (2) 1'x4' strip lights utilizing two (2) T8 fluorescent lamps and two (2)porcelain sockets ' which are utilizing screw in type compact fluorescent lamps. These fixtures are located above the suspended ceiling with the ceiling the removed for illumination. An occupancy sensor with off/auto/on controls all the fixtures. The sensor is wall-mounted adjacent to the entry door and is poorly positioned to sense movement in areas of the room. Receptacles observed consisted of a three (3) quad duplex ' receptacle surface mounted outlets as well as a 240V outlet. Also observed was a four (4)pole circuit breaker enclosure with three (3) 20Amp, single pole circuit breakers. Fire alarm components consisted of a heat detector located ' above the suspended ceiling. The ceiling panel has been removed below the heat detector. It appears as emergency lighting for this room is provided via k the emergency generator. ' Tele/data consisted of Telco punchdown block enclosure, punchdown blocks mounted to a plywood board as well as three (3) outlets. This room also housed the camera control and mo nitoring equipment. 118 ' South Windsor Town Hall Capital Needs Assessment Electrical Recommendation: ., 0 The existing light fixtures should be removed, replaced and relocated to provide better illumination for the room. ■ The occupancy sensor should also be relocated be better lighting control. ■ Fire alarm should be upgraded when fire alarm system for building is upgraded. ,m R• �3 �H ££ t t Maintenance Storage Lighting in the maintenance office storage room consisted of two (2) 6"'x4' strip lights utilizing two (2) T8 fluorescent lamps and two (2) porcelain sockets. One of the fixtures was utilizing screw in type compact fluorescent lamp and the other had no lamp. A wall-mounted occupancy sensor with off/auto/on controls the fixtures. ' Do to all the obstructions positioned along the walls; our office was unable to determine the receptacles within this room. ' A 60Amp, 3-phase, 240V disconnect manufacturered by GE and an electrical control reset panel manufactured by Square D were observed in this room. Fire alarm components consisted of a heat detector. r .It appears as emergency lighting for this room is provided via the emergency generator. Do to all the obstructions positioned along the walls; p g s, our office was unable to determine the tele/data components within this room. 119 ' South Windsor Town Hall Capital Needs Assessment rElectrical Recommendation: ■ The existing light fixtures should be removed, replaced and relocated to provide better illumination for the room. ■ Fire alarm should be upgraded when fire alarm system for r building is upgraded. Probate Court Admin Lighting in the Probate Court administration area consisted of six (6) 2'x4' recessed lensed troffers utilizing four (4) T8 fluorescent lamps and one (1) 1'x4' two (2) lensed troffer. A wall mounted occupancy sensor controls these fixtures with off/auto control. Four(4) duplex receptacles were observed. No fire alarm components were observed. ' No emergency lighting or exit signs were observed. x Tele/date appeared to consist of three (3) outlets. Also observed within this room as a security camera. f " Recommendation: ■ The existing light fixtures should remain. ' Fire alarm should be upgraded when fire alarm system for building is upgraded. ■ Emergency and exit lighting should be installed. rProbate Court Hearing Rm. Lighting in the Probate Court hearing room consisted of six (6) ' 2'x4' recessed lensed troffers utilizing four (4) T8 fluorescent lamps. A wall mounted occupancy sensor controls these fixtures with off/auto control. One (1) duplex receptacle was observed. No fire alarm components were observed. No emergency lighting or exit signs were observed. No tele/data was observed Recommendation: 120 ' South Windsor Town Hall Capital Needs Assessment Electrical ■ The existing light fixtures should remain. ■ Fire alarm should be upgraded when fire alarm system for building is upgraded. ■ Emergency and exit lighting should be installed Judge's Office Lighting in the judge's office consisted of two (2) 2'x4' recessed lensed troffers utilizing four(4) T8 fluorescent lamps. A wall mounted occupancy sensor controls these fixtures with of control. Three (3) duplex receptacles were observed. No fire alarm components were observed. No emergency lighting or exit signs were observed. Tele/date appeared to consist of one (1) outlet. r t Also observed within this room was a security camera. ' Recommendation: ■ The existing light fixtures should remain. ■ Fire alarm should be upgraded when fire alarm system for building is upgraded. Vault Lighting in the vault consisted of three (3)banks of seven (7) 2'x4' recessed lensed troffers utilizing four(4) T8 fluorescent lamps. Three (3) single pole switches controlled these fixtures. One (1) of the switches controlled three (3) of the lights within each bank while the other two (2) switches controlled two (2) lights per bank. No receptacles were observed within this room. Fire alarm components consisted of a heat detector and a smoke detector. No emergency lighting or exit signs were observed. No tele/date was observed . Recommendation.- The existing light fixtures should remain. ■ Fire alarm should be upgraded when f re alarm system for building is upgraded. Emergency lighting should be installed, j 121 South Windsor Town Hall Capital Needs Assessment Electrical IT Room Lighting in the IT room consisted of six (6) 2'x4' recessed lensed troffers utilizing four (4) T8 fluorescent lamps. A single pole light switch located at t he entry door controlled these fixtures. Eight (8) duplex receptacles were observed within the room. However, due to positioning of the desks an exact quantity could not be obtained. No fire alarm components were observed. f � No emergency lighting or exit signs were observed. Four(4) tele/data outlets were observed within the room. However, due to positioning of the desks an exact quantity {{ could not be obtained. Also observed within this room was a security camera. A card access reader located on the corridor side of the entry doorframe controls entry into the room. Recommendation: ■ The existing light fixtures should remain. ■ Fire alarm should be upgraded when fire alarm system for building is upgraded. ■ Emergency lighting should be installed IT Storage Lighting in the IT room storage closet consisted of one (1) 2'x4' recessed lensed troffers utilizing four (4) T8 fluorescent lamps. A wall mounted occupancy sensor with off/auto controls the r light fixture. ~— Located within the closet was a GE 120/208V, 3-phase, 4-wire, 24 pole, MLO load center as previously discussed, Also observed adjacent to the load center was a 2KVA 120/240V primary— 12/24V secondary transformer by General Signal. The room also contained a Tork model W220 time clock, which appears to control the HVAC equipment within the room. Receptacles consisted of a single duplex receptacle, which appeared to be nonfunctional. No fire alarm components were observed. 122 South Windsor Town Hall Capital Needs Assessment Electrical No emergency lightings was observed. No tele/data outlets were observed. Recommendation: ■ The existing light fixtures should remain. ■ Fire alarm should be upgraded when fire alarm system for building is upgraded. ■ Emergency lighting should be installed. IT Server Room Lighting in the server room consisted of two (2) 2'x4' recessed lensed troffers utilizing four(4) T8 fluorescent lamps. A wall mounted occupancy sensor with off/auto controlled the lighting. Receptacles observed within the room consisted of six (6) duplex receptacles, one (1) quad outlet, a nine (9) receptacle wiremold power strip and three (3) 240V outlets. Also located within the room were local disconnects for the HVAC equipment for the room. In addition an ADT Focus panel as well as Altronix enclosure were observed. Fire alarm components consisted of a smoke detector. No emergency lighting was observed. �+ Tele/data wiring is routed to the room via two (2) 4" conduits. Along with the data racks and associated equipment, five (5) tele/data outlets were observed along with a punchdown block. Recommendation: ■ The existing light fixtures should remain. ■ Fire alarm should be upgraded when fare alarm system for building is upgraded. ,; ` ■ Emergency lighting should be installed. Main Corridor Lighting in the main corridor consisted of fifteen (15) 19-inch square surface mounted fluorescent fixtures with acrylic diffusers utilizing FC 12T9 lamps. Light fixtures on the general lighting circuit are controlled by two (2) three way light switches, which are located at each end of the corridor. No receptacles were observed within the corridor. 123 South Windsor Town Hall Capital Needs Assessment Electrical F, Fire alarm components consisted of a manual pull station mounted at 55 inches and a horn mounted at 80 inches located outside the maintenance office. Emergency lighting is provided via general lighting light fixtures connected to an emergency generator panel. No exit signs were observed within the corridor. Recommendation: ■ The existing light fixtures should remain. ■ Fire alarm should be upgraded when fire alarm system for building is upgraded. ■ Exit lighting should be installed. ■ Provide additional emergency lighting as required. Sprenkel Room Hallway Lighting in the hallway leading to the Sprenkel room consisted of three (3) 11 inch round and one (1) 8 inch round surface mounted fluorescent fixtures with acrylic diffusers. A single pole light switch located at the hallway entry from the main corridor controls these fixtures. Three (3)recessed duplex receptacles were observed within the hallway. No fire alarm components were observed in this hallway. A ceiling mounted dual head emergency light fixture provides emergency lighting for this hallway. However, when tested the fixture appeared to be non-functional. An exit sign was located at the hallway entry from the main corridor. s 4 P Recommendation: ■ The existing light fixtures should remain. ■ Fire alarm should be upgraded when fire alarm system for building is upgraded. ■ Emergency and exit lighting should be removed and replaced. Lighting in the stairwells consisted of a combination of recessed down lighting and 15"round surface mounted fluorescent fixtures. These fixtures are directly connected to their respective panelboards with the fixtures used for emergency lighting 124 South Windsor Town Hall Capital Needs Assessment Electrical connected to an emergency panelboard. The general lighting seems to be controlled via time clocks. No receptacles were observed. No fire alarm components were observed. Exit signs were located at the doorways. Their faceplates are discoloring. Recommendation.- 0 The existing round fluorescent light fixtures should remain. The recessed light fixtures should be removed and replaced with compact fluorescent fixtures. ■ Fire alarm should be upgraded when fire alarm system for building is upgraded. ■ Exit signs should be removed and replaced. Main Level Rooms iCaucus Room Lighting in this room consisted of two (2) rows of three (3) 2'x4' recessed lensed troffers utilizing four(4) T8 fluorescent lamps. A wall mounted occupancy sensor with off/auto controls these fixtures. Six (6) duplex and one (1) single receptacle along with a ceiling mounted duplex for the television were observed within the room. No fire alarm components were observed. It appears as emergency lighting is provided via general lighting fixtures connected to an emergency panelboard. No exit signage was observed. Tele/data consisted of three (3) outlets and a ceiling mounted coaxial cable outlet for the television. Recommendation: ■ The existing lighting should remain. Fire alarm devices should be installed when fare alarm system for building is upgraded. 125 South Windsor Town Hall Capital Needs Assessment 1 Electrical ■ Exit signage should be provided. Caucus Interior Lobby Lighting in this area consisted of two 2'x4' recessed lensed troffers utilizing four(4) T8 fluorescent lamps. A wall mounted _ three way switch controlled these light fixtures as well as the light fixtures in the office and breakroom, r . Two (2) duplex receptacles were observed within this area. One receptacle was located through a hole made in the wall. No fire alarm components were observed. i It appears as emergency lighting is provided via general lighting fixtures connected to an emergency panelboard. No exit signage was observed. Tele/data consisted of two (2) outlets. Also observed in the corner were two (2) 4" conduits for tele/data wiring routed to server room. Recommendation: ■ The existing lighting should remain. i Fire alarm devices should be installed when fire alarm system for building is upgraded. ■ Exit signage should be provided. Caucus Interior Office Lighting in the office consisted of two 2'x4' recessed lensed troffers utilizing four (4) T8 fluorescent lamps. These lights are controlled by the three way switch located in the interior lobby area. Two (2) duplex receptacles were observed within the office. No fire alarm components were observed. Tele/data consisted of two (2) outlets. Recommendation.- The existing lighting should remain. A switch should be installed so that the office is switched separately. ■ Fire alarm devices should be installed when fire alarm system for building is upgraded. Caucus Break Room Lighting in the break room/filing consisted of two (2) 2'x4' recessed lensed troffers utilizing four (4) T8 fluorescent lamps. 126 South Windsor Town Hall Capital Needs Assessment Electrical These lights are controlled by the three way switch located in the interior lobby area. Due to obstructions along the walls only one (1) duplex receptacle was observed. No fire alarm components were observed. Further investigation would be required to determine if the light fixture(s)within this room are also connected to an emergency panelboard. Due to obstructions along the walls our office was unable to determine if any tele/data outlets are located within the room. Recommendation: ■ The existing lighting should remain. A switch should be installed so that the lighting is switched separately. ■ Fire alarm devices should be installed when fire alarm system for building is upgraded. ■ Emergency lighting should be installed as required. Copy Room Lighting in the copy room consisted of a single 2'x2' recessed lensed troffers utilizing two (2) U31 T8 fluorescent lamps. The other three way switch controlling the interior lobby, office and break room lighting is located within this room. Two (2) duplex receptacles was observed. No fire alarm components were observed. Tele/data consisted of two (2) outlets. Recommendation: The existing lighting should remain. ■ Fire alarm devices should be installed when fire alarm system for building is upgraded. Town Managers Office Administration Area Lighting in the administration area of the town managers office consisted of three (3) banks of three (3) 2'x4' recessed troffers utilizing four(4)T lensed 8 fluorescent lamps, A single pole wall mounted switch located adjacent to the entry door controls the light fixtures. 127 South Windsor Town Hall Capital Needs Assessment Electrical Five (5) duplex receptacles were observed within this area. However due to obstructions an exact count could not be obtained. No fire alarm components were observed. No emergency lighting was observed. No exit signage was observed. Due to obstructions, our office was unable to determine the quantity of tele/data outlets in this area. Also observed was a panic button installed under the front most desk, which send a signal directly to the police department. A security camera was also observed within this area. Recommendation:;. hon: ■ The existing lighting should remain. ■ Fire alarm devices should be installed when fire alarm system for building is upgraded. ■ Emergency lighting should be provided. ■ Exit signage should be provided. Office of the Clerk of the Council Lighting in the clerk of the councils office consisted of two (2) 2'x4' recessed lensed troffers utilizing four(4) T8 fluorescent lamps. A wall mounted occupancy sensor with off/auto controls these fixtures. Two (2) duplex receptacles were observed within this office. No fire alarm components were observed. Two (2)tele/data outlets were observed within this office. Recommendation: ■ The existing lighting should remain. ■ Fire alarm devices should be installed when fire alarm system for building is upgraded. i128 South Windsor Town Hall Capital Needs Assessment Electrical Town Managers Office Lighting in the town managers office consisted of two (2) 2'x4' recessed lensed troffers utilizing four(4) T8 fluorescent lamps. A wall mounted occupancy sensor with off/auto controls these ■ fixtures. Three(3) duplex receptacles were observed within this office. No fire alarm components were observed. Three 3 tele/data outlets were observed within O this office. Recommendation: ■ The existing lighting should remain. ■ Fire alarm devices should be installed when fire alarm system for building is upgraded. Town Clerks Office Lighting in the town clerks office consisted of three (3)banks of three (3) 2'x4' recessed lensed troffers utilizing four(4) T8 fluorescent lamps. A single pole wall mounted switch located adjacent to the entry door controls the light fixtures. Two (2) duplex and one (1) single receptacle were observed. Also observed was a surface mounted wiremold quad outlet. This office area also conatins four(4) workstations,which have receptacles. These workstations are feed via electrical whips. No fire alarm components were observed. ® No emergency lighting was observed. g Y g g Four(4)tele/data outlets were observed along with an outlet in wiremold located at the counter. A security camera was also observed within this area. Recommendation: ■ The existing lighting should remain. ■ Fire alarm devices should be installed when fare alarm system for building is upgraded. ■ Emergency lighting should be provided. ■ Exit lighting should be provided. ' Town Clerks Vault Lighting in the town clerks vault consisted of three (3)banks of six (6) 2'x4' recessed lensed troffers utilizing four(4) T8 fluorescent lamps. A three way wall mounted switch located 129 So uth Windsor Town Hall Capital Needs Assessment Electrical adjacent to the entry door controls the light fixtures as well as the surface mounted receptacle. The other three way switch is 1 located near the assessors office vault entry, Two (2) duplex receptacles were observed. One (1) recessed r within the wall and the other routed in wiremold. Fire alarm components observed consisted of a heat detector and a smoke detector. One (1) tele/data outlet routed in wiremold was also observed. Recommendation: - 0 The existing lighting should remain. Fire alarm devices should be upgraded when fare alarm system for building is upgraded. ■ Emergency lighting should be provided. Exit lighting should be provided. Town Clerks Copy/Supply Lighting in the town clerks copy/supply room consisted of two (2) 2'x4' recessed lensed troffers utilizing four(4) T8 fluorescent lamps. A wall mounted occupancy sensor with off/auto controls these fixtures. Two (2) duplex receptacles were observed. - No fire alarm components were observed. 4 One (1) tele/data outlet was observed. Recommendation: ■ The existing lighting should remain. ■ Fire alarm devices should be installed when fare alarm system for building is upgraded. Town Clerks Back Room Lighting in the town clerks back room consisted of two (2) 2'x4' recessed lensed troffers utilizing four(4) T8 fluorescent lamps. A wall mounted occupancy sensor with off/auto controls these fixtures. � One 1 duplex O receptacle was observed. t. ' 130 South Windsor Town Hall Capital Needs Assessment Electrical x No fire alarm components were observed. 1; No tele/data outlets were observed within the room. However, data cabling was routed from the computer station and through Aid the suspended ceiling. Recommendation: ■ The existing lighting should remain. ' ■ Fire alarm devices should be installed when fire alarm system for building is upgraded. ■ Data outlet within the room should be installed. Assessors Office Lighting in the Assessors office consisted of three (3) banks of three (3) 2'x4' recessed lensed troffers utilizing four(4) T8 fluorescent lamps. A single pole wall mounted switch located adjacent to the entry door controls the light fixtures. Three way switches were located near the entry door to the vault as discussed prior. Four (4) duplex receptacles were observed. Two (2) were recessed and the other two (2) installed in wiremold. The room also contained a power pole, which housed four (4) receptacles. No fire alarm components were observed. No emergency lighting was observed, Four(4)tele/data outlets were observed. The power pole also contained a data channel. Recommendation: The existing lighting should remain. ■ Fire alarm devices should be installed when fire alarm system for building is upgraded. Emergency lighting should be provided. ■ Exit lighting should be provided Assessors Individual Offices Lighting in the two (2) individual offices within the assessors office consisted of two (2) 2'x4' recessed lensed troffers utilizing four(4) T8 fluorescent lamps, A wall mounted ■' occupancy sensor with off/auto controls the fixtures. Four (4) duplex receptacles were observed within each office. No fire alarm components were observed. ' 131 South Windsor Town Hall Capital Needs Assessment Electrical Two (2)tele/data outlets were observed within one office and one (1) tele/data outlet was observed within the other. A security camera was also observed within this area. Recommendation: ■ The existing lighting should remain. ■ Fire alarm devices should be installed when fire alarm system for building is upgraded. Tax Collectors Office Lighting in the Assessors office consisted of three (3) banks of three (3) 2'x4' recessed lensed troffers utilizing four(4) T8 fluorescent lamps. A single pole wall mounted switch located adjacent to the entry door controls the light fixtures. Six (6) duplex receptacles were observed. F r No fire alarm components were observed. No emergency lighting was observed. �) Eight (8) tele/data outlets were observed. A panic switch was observed below the counter. 1 �'" A security camera was also observed. Recommendation: ■ The existing lighting should remain. ■ Fire alarm devices should be installed when fire alarm system for building is upgraded. ■ Emergency lighting should be provided. ■ Exit lighting should be provided. Tax Collector Individual Office Lighting in the office within the tax collectors office consisted of two (2) banks of(2) 2'x4' recessed lensed troffers utilizing four (4) T8 fluorescent lamps. A wall mounted occupancy sensor with off/auto controls the fixtures. Also observed was a 4 foot under-cabinet light with integral switch at the workstation . ' - desk. e Five (5) duplex receptacles and a quad in a wiremold box were observed within the office. r 132 South Windsor o Town Hall Capital Needs Assessment Electrical No fire alarm components were observed. Three (3)tele/data outlets were observed. Recommendation: ■ The existing lighting should remain. ■ Fire alarm devices should be installed when fire alarm system for building is upgraded. rTax Collector Storage Room Lighting in the storage room consisted of one (1) 12"xl2" a _ square incandescent light fixture. This fixture is controlled by a single pole light switch and pilot light located on the exterior of }' the room. The switch is partially obstructed by the workstation desk. No receptacles were observed. No fire alarm components were observed. No tele/data was observed. Recommendation: ■ The existing light fixture should be removed and replaced with a more energy efficient fixture designed to utilize compact fluorescent lighting. An occupancy sensor should be installed within the room in lieu of the switch and pilot light on the exterior. ■ Fire alarm devices should be installed when fire alarm system for building is upgraded. Council Chambers Lighting in the council chambers consisted of eleven(11)wall wash down lights located at the rear of the room, nine (9) 2'x2' surface mounted fluorescent fixtures in the center and eight (8) wall wash along with four(4) recessed down lights in the front. ss£' A bank of seven (7) single pole light switches located at the side entry doorway controls these fixtures. Two (2) of these switches seem to control the lighting at the rear of the room, while the center lighting is controlled by three (3) switches. Each switch controlling three (3) lights. The remaining two (2) switches control the wall wash and down lights in the front. t Nine (9) duplex receptacles were observed. 133 South Windsor Town Hall Capital Needs Assessment Electrical The room also contained four (4) floor boxes d' No fire alarm components were observed. No emergency lighting was observed. No exit signs were obs erved served Three (3) tele/data outlets were observed. A wiremold outlet housing connectors for two (2) headphones were also observed within the room, i. Also observed were three (3) cameras. ter. ° Two (2) large speakers were observed halfway down the sides bigof the room, while two (2) smaller speakers were located in the rear. The council bench also contained speakers. Recommendation: ■ The existing surface mounted fluorescent lighting should remain. The existing wall wash and down lights should be removed and replaced with a more energy efficient fixture designed to utilize compact fluorescent lighting. ■ Fire alarm devices should be installed when fare alarm I� system for building is upgraded. ■ Emergency lighting should be provided. ■ Exit lighting should be provided. k 134 South Windsor Town Hall Capital Needs Assessment iElectrical Men's R estroom Three (3)4' wall mounted vanity lights provide illumination for the room. One (1) fixture is located above the sinks and the remaining two (2) are located above the water closets and urinals. These fixtures utilize two (2) T12 fluorescent lamps and are controlled via a wall mounted occupancy sensor with off /auto control. Receptacles consisted of a single receptacle, which was integral with the vanity light above the sink. Fire alarm components consisted of a heat detector. This room did not appear to contain emergency lighting. Recommendation: ■ The existing lighting should be removed and replaced with more energy efficient light fixtures. ■ A GFCI duplex receptacle should be installed. ■ Fire alarm should be upgraded when fire alarm system for building is upgraded. ■ Emergency lighting should be installed. Women's Restroom Three (3) 4' wall mounted vanity lights provide illumination for the room. One (1) fixture is located above the sinks and the remaining two (2) are located above the water closets and urinals. These fixtures utilize two (2) T12 fluorescent lamps and are controlled via a wall mounted occupancy sensor with off /auto control. 1 Receptacles consisted of a single receptacle, which was integral with the vanity light above the sink. 135 South Winds or Town Hall Capital Needs Assessment Electrical Fire alarm components consisted of a heat detector. This room did not appear to contain emergency lighting, Recommendation: The existing lighting should be removed and replaced with T: more energy efficient light fixtures. ■ A GFCI duplex receptacle should be installed. ■ Fire alarm should be upgraded when fire alarm system for building is upgraded. ■ Emergency lighting should be installed. Janitors Closet A single surface mounted incandescent light fixture utilizing a screw in type compact fluorescent lamp provided illumination for the closet. The fixture is controlled via a wall mounted occupancy sensor with off/auto control. Panelboard designated `P2 left' and `P2 right' were observed within the closet as previously discussed. No receptacles were observed within the closet. Fire alarm components consisted of a heat detector. t A telco enclosure was also observed within the closet No emergency lighting was observed. Recommendation: The existing light fixture should be removed and replaced with a more energy efficient fixture designed to utilize r compact fluorescent lighting, A GFCI duplex receptacle should be installed. Y Fire alarm should be upgraded when fire alarm system for building is upgraded. Elevator Lobby Elevator lobby lighting consisted of two (2) 2'x2' recessed lensed troffers utilizing two (2) U31 T8 fluorescent lamps. It appears as emergency lighting is provided via general lighting fixtures connected to an emergency panelboard. No other electrical devices were observed in the lobby, 136 South Windsor Town Hall Capital Needs Assessment Electrical Recommendation: ■ The existing lighting should remain. ■ Fire alarm devices should be installed when fire alarm system for building is upgraded. ■ Provide additional emergency lighting as required. Main Corridor/Lobby Lighting in the main corridor consisted of fourteen (14) recessed fluorescent fixtures utilizing two (2) U31 T8 lamps. These light fixtures on the general lighting circuit appeared to be controlled by time clock. ' Lobby area illumination is provided by twelve (12) down lights. These fixtures seem to be controlled by two (2) switches located in the lobby at the corner of the janitor closet. One (1) duplex receptacle was observed across from the town >- managers office while another is mounted high on the wall in the lobby for the television set. Fire alarm components consisted of a manual pull station mounted at 57 inches and a horn mounted at 80 inches located outside the men's room and an additional pull station located at the main entry doors. This was also mounted at 57 inches above the finished floor. Emergency lighting is provided via general lighting light fixtures connected to an emergency generator panel. Exit signs were observed above the main entry doors and at the M doorway to stairwell `A'. The faceplates appeared to be discoloring. ' Tele/data observed consisted of a coaxial cable outlet mounted high on the wall in the lobby for the television set. Also observed was a camera mounted adjacent to the television in the lobby. ' The lobby also contained a ceiling fan, which is controlled by a switch that is located in the janitors closet on the upper level. IC9 ' 137 South Windsor Town Hall Capital Needs Assessment Electrical a Recommendation: ■ The existing corridor light fixtures should remain. The 1 existing lobby light fixtures should be removed and replaced with a more energy efficient fixture designed to utilize compact fluorescent lighting. ■ Fire alarm should be upgraded when fire alarm system for building is upgraded. ■ Exit lighting should be removed, replaced with additional ' provided as required. ■ Provide additional emergency lighting as required. ■ Receptacles should be replaced with GFCI receptacles. Upper Level Rooms Finance Office Lighting in the finance office consisted of two (2)rows of three (3) and five(5) separate 2'x4' recessed lensed troffers utilizing four(4) T8 fluorescent lamps. An additional bank of three(3) 2'x4' recessed lensed troffers is split between areas within the office. The majority of the lighting is controlled by one (1) single pole switch while a second single pole switch controls two (2) of the fixtures. Both switches are located adjacent to the - entry door. i In addition, each of the work desk stations contained a 4 foot task light with integral switch. These fixtures utilize a T12 fluorescent lamp. Receptacles observed were four(4) quad outlets and four(4) duplex outlets. No fire alarm components were observed. No emergency lighting was observed. No exit si na a was observed. g g Tele/data observed consisted of seven(7) outlets. A 4" conduit containing tele/data wiring was also observed within the room. ' Recommendation: ■ The existing lighting should remain. ■ Fire alarm devices should be installed when fire alarm ' system for building is upgraded. ■ Emergency lighting should be provided. 138 South Windsor Town Hall Capital Needs Assessment Electrical Finance Storage Lighting in the storage room consisted of a 2'x2' recessed lensed troffer utilizing two (2) U31 T8 fluorescent lamps. This 1 fixture is connected to and controlled by the lighting circuit in the main office. Due to obstructions, our office was unable to determine receptacles existence and/or quantities. No fire alarm components were observed. No emergency lighting was observed. Due to obstructions, our office was unable to determine tele/data outlet existence and/or quantities. Recommendation.- The existing lighting should remain. ■ Fire alarm devices should be installed when fare alarm system for building is upgraded. ' Finance Directors Office Lighting in this office consisted of a 2'x4' recessed lensed troffer utilizing four (4) T8 fluorescent lamps. A wall mounted occupancy sensor with off/auto controls this fixture. Receptacles observed were four (4) duplex outlets. 56�. No fire alarm components were observed. One (1) tele/data outlet was observed. Recommendation: The existing lighting should remain. Fire alarm devices should be installed when fire alarm system for building is upgraded. Fire Marshals Office Lighting in this office consisted of four (4) 2'x4' recessed lensed troffer utilizing four(4) T8 fluorescent lamps. A single ' pole switch controls these fixtures. Four (4) duplex receptacles were observed. ' No fire alarm components were observed. Four (4) tele/data outlet was observed. L ' 139 ' South Windsor Town Hall Capital Needs Assessment ' Recommendation: Electrical ■ The existing lighting should remain. An occupancy sensor should be installed in lieu of the single pole switch. ■ Fire alarm devices should be installed when fire alarm Public Works system for building is upgraded. Conference Room Lighting in this conference room consisted of four(4) 2'x4' recessed lensed troffer utilizing four(4) T8 fluorescent lamps. ' A wall mounted occupancy sensor with off/auto controls these fixtures. Due to obstructions, only two (2) duplex receptacles were observed. No fire alarm components were observed. No emergency lighting was observed. Two (2)tele/data outlets and one (1) coaxial cable outlet were observed. Recommendation: rhe; 0 The existing lighting should remain. ■ Fire alarm devices should be installed when fire alarm system for building is upgraded ■ Emergency lighting should be provided. ' Public Works Directors Office Lighting in the directors office consisted of two (2) 2'x4' recessed lensed troffer utilizing four (4) T8 fluorescent lamps. 1 A wall mounted occupancy sensor with off/auto controls these fixtures. ' Three (3) duplex receptacles were observed. No fire alarm components were observed. One (1) tele/data outlet and one (1)phone jack were observed. ' Recommendation: ■ The existing lighting should remain. ■ Fire alarm devices should be installed when fire alarm system for building is upgraded. ' 140 ' South Windsor Town Hall Capital Needs Assessment Water Pollution Electrical Control Authority Lighting above this area consisted of two (2) 2'x4' recessed lensed troffer utilizing four(4) T8 fluorescent lamps. A single pole light switch controls these lights. An additional single pole light switch is located within the switch box. This switch controls the light fixtures above the Public Works Dept. Two (2) duplex receptacles were observed. 1 �! g No fire alarm components were observed. f I One (1) tele/data outlet and two (2)phone jacks were observed. " k A security camera was observed in the corner of the area. Recommendation: The existing lighting should remain. ■ Fire alarm devices should be installed when fare alarm system for building is upgraded. Public Works Department Lighting above this area consisted of two (2) 2'x4' recessed lensed troffer utilizing four (4) T8 fluorescent lamps. A single pole light switch controls these lights located within the switch box containing the switch for water pollution department controls these light fixtures. Three (3) duplex receptacles were observed. No fire alarm components were observed. One (1) tele/data outlet and two (2)phone jacks were observed. Recommendation: ■ The existing lighting should remain. Fire alarm devices should be installed when fare alarm ' system for building is upgraded. Public Works General Office Lighting above the general office area of public works consisted X p of eleven (11) 2'x4' recessed lensed troffer utilizing four (4) T8 fluorescent lamps. A single pole light switch located adjacent to the entry door seems to control these fixtures. 1 141 ' South Windsor To wn Hall Capital Needs Assessment Electrical Receptacles observed consisted of duplex receptacles in power strips at bottom of walls in a wiremold surface raceway box, duplex receptacle in power pole, recessed duplex receptacle and quad outlet receptacle box in wiremold surface raceway. �= No fire alarm components were observed. No emergency lighting was observed No exit signs were observed Two (2) tele/data outlets and two (2)phone jacks were _ observed. ' Recommendation: ■ The existing lighting should remain. t' Fine alarm devices should be installed when fire alarm system for building is upgraded. ■ Emergency lighting should be provided. ' Exit signage should be provided. ■ Additional receptacles should be installed as required. Engineering Area Lighting above the engineering area consisted of three (3) banks of six (6) 2'x4' recessed lensed troffer utilizing four(4) T8 fluorescent lamps. These lights appear to be controlled by a bank of five (5) single pole light switches. Receptacles observed consisted of duplex receptacles installed within the four(4) work station desks as well as three (3) recessed duplex receptacles and two (2) floor box duplex -� receptacles, No fire alarm components were observed. "= No emergency lighting was observed No exit signs were observed Due to obstructions, only three (3) tele/data outlets were observed. An additional data outlet is no longer fastened to the ' 3 y backbox and is lying on the floor. Additional data wiring was seen being routed through walls. ;.: ' Recommendation: ■ The existing lighting should remain. 142 South Windsor Town Hall Capital Needs Assessment Electrical ■ Fire alarm devices should be installed when fare alarm system for building is upgraded. Emergency lighting should be provided. Exit signage should be provided. Additional receptacles should be installed as required. / Data outlets should be properly secured and installed. ' Engineering Area Individual office Lighting in the office is provided by the general lighting for the area as the walls are not full height. Two (2) duplex receptacles were observed. No fire alarm components were observed. One (1) tele/data outlet and two (2) phone jacks were observed. Recommendation: ' ■ The existing lighting should remain. ■ Fire alarm devices should be installed when fire alarm system for building is upgraded. ' 0 Additional receptacles should be installed as required. Building Department Area Lighting above the building department area consisted of ' twenty-four(24) 2'x4' recessed lensed troffer utilizing four(4) T8 fluorescent lamps. The majority of these lights appear to be controlled by a bank of four(4) switches located adjacent to the ' corridor entry door. One of these switches is a three way while the others appear to be single pole. The other three way is { s located adjacent to the doorway leading to the stairwell. The other lights are controlled by a single pole switch routed in wiremold raceway located adjacent to the assistant director of planning office. Receptacles observed consisted of duplex receptacles ins p p p taped power within pole and floor boxes. p No fire alarm components were observed. ' No emergency lighting was observed. One (1) exit sign was observed. AN Due to obstructions, only the tele/data outlets located on the power pole were observed. 143 ' South Windsor Town Hall Capital Needs Assessment Electrical Also observed was a security camera. Recommendation: fi The existing lighting should remain. } ■ ' Fire alarm devices should be installed when fire alarm system for building is upgraded. ■ Emergency lighting should be provided. ' Additional exit signage should be provided. ■ Additional receptacles should be installed as required. ■ Data outlets should be installed as required. 7,7­ Building Inspectors Office Lighting in this office consisted of two (2) 2'x4' recessed lensed troffer utilizing four(4) T8 fluorescent lamps. A single pole switch controlled these fixtures. Five (5) duplex receptacles were observed. 1 i No fire alarm components were observed. One (1) tele/data outlet and one (1) phone jack were observed, Recommendation: ' N The existing lighting should remain. ■ Fire alarm devices should be installed when fire alarm system for building is upgraded. 1 Assistant Director of Planning Lighting in this office consisted of four (4) 2'x4' recessed ' lensed troffer utilizing four(4) T8 fluorescent lamps. A wall mounted occupancy sensor with off/auto controls these fixtures. 1 Three (3) duplex receptacles were observed. No fire alarm components were observed. ' One (1)tele/data outlet and one (1) phone jack were observed. Recommendation: ■ The existing lighting should remain. ' 144 South Windsor Town Hall Capital Needs Assessment Electrical ■ Fire alarm devices should be installed when fire alarm system for building is upgraded. Mechanical Room Lighting in this mechanical room consisted of four incandescent surface mounted fixtures. A wall mounted occupancy sensor with off/auto controls these fixtures. Electrical components located within the room consisted of an Intermatic model T7401B timer, Honeywell controller, and a 30Amp, 3-phase, 240V disconnect and control reset. Both of ' rt these are manufactured by GE and appear to be original. No receptacles were observed. Fire alarm components consisted of a heat detector. Recommendation: ■ The existing light fixture should be removed and replaced with a more energy efficient fixture designed to utilize fluorescent lighting. ■ A GFCI duplex receptacle should be installed. ■ Fire alarm devices should be upgraded when fire alarm v system for building is upgraded. z2 Electrical components should be upgraded when mechanical equipment is upgraded. Men's Restroom Three (3) 4' wall mounted vanity lights provide illumination for the room. One (1) fixture is located above the sinks and the remaining two (2) are located above the water closets and ' urinals. These fixtures utilize two (2) T12 fluorescent lamps and are controlled via a wall mounted occupancy sensor with off /auto control. Receptacles consisted of a single receptacle, which was integral g p � g with the vanity light above the sink. Fire alarm components consisted of a heat detector. ' This room did not appear to contain emergency lighting. 145 South Windsor Town Hall Capital Needs Assessment Electrical Recommendation: ■ The existing lighting should be removed and replaced with more energy efficient light fixtures. A GFCI duplex receptacle should be installed ■ Fire alarm should be upgraded when fire alarm system for 'ter building is upgraded.vri ■ Emergency lighting should be installed. Women's Restroom Three (3) 4' wall mounted vanity lights hts provide illumination for the room. One (1) fixture is located above the sinks and the remaining two (2) are located above the water closets and urinals. These fixtures utilize two (2) T12 fluorescent lamps and are controlled via a wall mounted occupancy sensor with off ' /auto control. Receptacles consisted of a single receptacle, which was integral with the vanity light above the sink. Fire alarm components consisted of a heat detector. Th is room did not appear to contain emergency lighting. ' Recommendation: ■ The existing lighting should be removed and replaced with more energy efficient light fixtures. ' 0 A GFCI duplex receptacle should be installed ■ Fire alarm should be upgraded when fire alarm system for building is upgraded. ■ Emergency lighting should be installed Janitors Closet A single surface mounted incandescent light fixture (missing lens) utilizing an incandescent bulb provided illumination for the closet. The fixture is controlled via a wall mounted occupancy sensor with off/auto control. Panelboard designated `LP-3' was observed within the closet as previously discussed. y No receptacles were observed within the closet. ' Fire alarm components consisted of a heat detector. F= A telco enclosure was also observed within the closet. v� 146 South Windsor Town Hall Capital Needs Assessment Electrical The control for the lobby ceiling fans was also located within t u` the closet. �i Recommendation, f The existing light fixture should be removed and replaced with a more energy eff cient fixture designed to utilize compact fluorescent lighting. ' A GFCI duplex receptacle should be installed. ■ Fire alarm should be upgraded when fire alarm system for building is upgraded. ' Elevator Lobby Elevator lobo lighting consisted of four 4 12 inch round Y g g ( ) surface mounted fluorescent fixtures. The light fixtures on the ' general lighting circuit appeared to be controlled by time clock. It appears as emergency lighting is provided via general lighting fixtures connected to an emergency panelboard. No other electrical devices were observed in the lobby. Recommendation: ■ The existing lighting should remain. ' E Fire alarm devices should be installed when fire alarm system for building is upgraded. ■ Provide additional emergency lighting as required. Main Corridor The main corridor is divided by double doors located at the janitors closet. Magnetic door holders hold these doors open. Corridor lighting on the restroom side of the double doors consisted of six (6) 12 inch round surface mounted fluorescent fixtures. The light fixtures on the general lighting circuit appeared to be controlled by time clock. ' Corridor lighting on the opposite side of the double doors consisted of none (9) 12 inch round surface mounted fluorescent fixtures. The light fixtures on the general lighting circuit appeared to be controlled by time clock. � One (1) duplex receptacle was observed in the corridor sections on each side of the double doors. r Fire alarm components consisted of a manual pull station and a horn located outside the men's room and an additional manual £` pull station and horn located at the entry to stairwell `A'. Also ' 147 South Windsor Town Hall Capital Needs Assessment ' Electrical observed were two smoke detectors. These were located on Fz: each side of the double doors and control the release of the magnetic door holders under a fire alarm condition. Emergency lighting is provided via general lighting light ' fixtures connected to an emergency generator panel. Exit signs were observed at each stairwell door as well as an ' additional one located at the double doors on the lobby side. ' A tele/data was also observed within the lobby side corridor. Recommendation: ■ The existing corridor light fixtures should remain. ■ Fare alarm should be upgraded when fire alarm system for ' building is upgraded. ■ Exit lighting should be removed and replaced ■ Provide additional emergency lighting as required. ■ Receptacles should replaced with GFCI receptacles. 1 ' 148